Earth Resistance Test Report 1

The document is a site test report on earth pit resistance measurements conducted for a transformer neutral at the ARLA FOODS Blue at BIIP factory site in HIDD. The earth pits were found to be in good physical condition with clean connections, and testing on 26-10-2020 using the three wire method found a resistance of 0.56 ohms, below the acceptable criteria of less than 1 ohm. Continuity from the earth pits to the transformer was also confirmed to be satisfactory. The earth pits were determined to meet requirements based on the test results.

Uploaded by

prabhumanoc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
88% found this document useful (17 votes)
49K views1 page

Earth Resistance Test Report 1

The document is a site test report on earth pit resistance measurements conducted for a transformer neutral at the ARLA FOODS Blue at BIIP factory site in HIDD. The earth pits were found to be in good physical condition with clean connections, and testing on 26-10-2020 using the three wire method found a resistance of 0.56 ohms, below the acceptable criteria of less than 1 ohm. Continuity from the earth pits to the transformer was also confirmed to be satisfactory. The earth pits were determined to meet requirements based on the test results.

Uploaded by

prabhumanoc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

SITE TEST REPORT : EARTH PIT RESISTANCE MEASUREMENT

Client ARLA FOODS


Consultant BILFINGER TEBODIN
Contractor POULLAIDES CONSTRUCTION COMPANY
Project BLUE at BIIP, HIDD (ARLA FOOD FACTORY)

1. EARTH PIT DETAIL

LOCATION Room No 6

DESCRIPTION Earth pit for Transformer Neutral

EARTH PIT 1&2

2. MECHANICAL CHECK AND VISUAL INSPECTION

ITEM DESCRIPTION CHECKED


2.1 Inspect for physical damage / defects. OK
2.2 Check tightness of all connections. OK
2.3 Check for cleanliness and external contamination OK

3. ELECTRICAL CHECK:

ACCEPTABLE
DATE TEST RANGE TEST METHOD TEST RESULTS
CRATERIA
26-10-2020 20Ω 3 Wire Method 0.56 Ω <1Ω

4. CONTINUITY CHECK

CONTINUITY REMARKS
FROM: EARTH PIT NO TO: EQUIPMENT
CHECKED
1&2 Transformer OK PASS

5. REMARKS: The tested Earth Pit found satisfactory result.

Prepared by Witnessed by Approved by


Representative Castillo PCC
Name
Date
Signature
Test Equipment Used: Earth Resistance Tester