Professional Documents
Culture Documents
Telephone Number:
Postcode:
Telephone Number:
Postcode:
INSPECTION
AND TESTING Trading Title: Same as Above
Address:
Registration Number:
Telephone Number:
Postcode:
Nominal frequency, f:
TN-C-S N/A (2 wire):
2-phase
(3 wire): N/A 2 pole: N/A
Prospective fault
50 Hz BS(EN): 1361
TNC N/A (3 wire): N/A 3 pole: N/A current, lpf: 1.28 kA Type: 2
3-phase 3-phase External earth fault
TT N/A (3 wire): N/A (4 wire): N/A Other: N/A 0.17 Rated current: 60 A
loop impedance, Ze:
Short-circuit
IT N/A Other: N/A Number of supplies: 1 capacity: 33 kA
Maximum Demand (Load): 60 Amps Protective measure(s) against electric shock: ADS
Main Switch or Circuit-Breaker Earthing and Protective Bonding Conductors
Type Earthing conductor
BS(EN): 60947-2 MCCB Voltage rating: 400 V Conductor Conductor Continuity
Number of Rated material: Copper csa: 16 mm2
check:
poles: 2 current, ln: 125 A Main protective bonding conductors
Supply Conductor Conductor Continuity
conductors Copper
RCD operating
N/A mA
material: Copper csa: 10 mm2 check:
current: Bonding of extraneous-conductive parts
material:
Lightning
Supply
conductors 25
RCD operating
mm2 time: N/A ms
Water service: Oil service: protection:
N/A
csa: Gas service: N/A Structural Steel: N/A Other services: N/A
10. COMMENTS ON EXISTING INSTALLATION
Note: Enter 'NONE' or, where appropriate, the page number(s) of additional page(s) of comments on the
existing installation. None
11. NEXT INSPECTION
I/We, the designer(s), RECOMMEND that this installation is further inspected and tested after an
interval of not more than: 5 Years
This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 0039291 Page: 2 of 5
12. SCHEDULE OF ITEMS INSPECTED Prevention of mutual detrimental influence
Methods of protection against electric shock N/A (a) Proximity of non-electrical services and other
influences
Basic and fault protection:
N/A (b) Segregation of Band I and Band II circuits or use of
Band II insulation
N/A (i) SELV N/A (ii) PELV
(ii) Non-conducting location ** Presence of fire barriers, suitable seals and protection
N/A against thermal effects
Absence of protective conductors General
Presence and correct location of appropriate devices for
(iii) Earth-free local equipotential bonding ** isolation and switching
Adequacy of access to switchgear and other equipment
N/A Presence of earth-free local equipotential bonding
(iv) Electrical Separation Particular protective measures for special installations
N/A and locations
N/A Provided for one item of current-using equipment Connection of single-pole devices for protection or
Provided for more than one item of current-using
switching in line conductors only
equipment ** N/A Correct connection of accessories and equipment
Additional protection:
N/A Presence of residual current device(s) Presence of undervoltage protective devices
Selection of equipment and protective measures
N/A Presence of supplementary bonding conductors appropriate to external influences
** For use in controlled supervised/conditions only N/A Selection of appropriate functional switching devices
13. SCHEDULE OF ITEMS TESTED Protection against direct contact by barrier or enclosure
N/A provided during erection
External earth fault loop impedance, Ze
Insulation of non-conducting floors or walls
N/A Installation earth electrode resistance, RA
N/A Polarity
This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 0039291 Page: 3 of 5
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
TO BE COMPLETED IN EVERY CASE
DIRECTLY TO THE ORIGIN OF THE INSTALLATION
Location of distribution board: Supply to distribution No of Nominal
N/A phases: N/A Voltage: N/A V
Dining Room Cupboard board is from:
Overcurrent protective device for the Associated RCD
distribution circuit: (if any) BS(EN): N/A
Distribution board designation:
Type RCD No
D.B. 1 BS(EN): N/A Rating: N/A A of poles: N/A RCD ln: N/A mA
permitted by BS7671
permitted by BS7671
Overcurrent protective
Reference Method
Maximum Zs
Short-circuit
Circuit number
Type of wiring
points served
Circuit designation
Operating
Capacity
Type No
Number of
and phase
current
Live cpc BS(EN)
Rating
mm2 mm2 s A kA mA
1 Ground Floor Lights A 1 --- 1 1 5 60898 B 6 6 --- ---
2 1st Floor Lights A 1 --- 1 1 5 60898 B 6 6 --- ---
3 2nd Floor Lights A 1 --- 1 1 5 60898 B 6 6 --- ---
4 Fire Alarm A 1 --- 1.5 1 5 60898 B 16 6 --- ---
5 Old Immersion A 1 --- 2.5 1 5 60898 B 16 6 --- ---
6 1st and Ground Floor Sockets A 1 --- 2.5 1 0.4 60898 B 32 6 20 10
7 Kitchen Sockets A 1 --- 2.5 1 0.4 60898 B 16 6 19 9
8 2nd Floor Sockets A 1 --- 2.5 1 0.4 60898 B 32 6 18 9
This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 0039291 Page: 4 of 5
17. CHARACTERISTICS AT THIS D.B. 18. DETAILS OF TEST INSTRUMENTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT Test Instruments (serial numbers) used:
CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION Earth fault loop
7654321 RCD: 1234567
Confirmation of supply polarity impedance:
Insulation
Zs: N/A Operating times At ln: N/A ms Resistance: 1234567 Other: N/A
of associated RCD
lpf: N/A kA (if any) At 5ln: N/A ms Continuity: 1234567 Other: N/A
19. TEST RESULTS
Insulation resistance RCD Operating
Circuit impedances (Ohms) Maximum
(record lower or lowest value) times
measured
All circuits earth fault
Ring final circuits only
Circuit number
20. TESTED BY
Name: JOE ENGINEER Position: Electrician
Date of
Signature: 01/11/2005
testing:
This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 0039291 Page: 5 of 5
ELECTRICAL INSTALLATION CERTIFICATE
This safety Certificate has been issued to confirm that the electrical installation work to which it
relates has been designed, constructed and inspected and tested in accordance with British Standard
7671 (as amended) (The IEE Wiring Regulations).
You should have received an original Certificate and the contractor should have retained a duplicate
Certificate. If you were the person ordering the work, but not the user of the installation, you should
pass this Certificate, or a full copy of it including the schedules, immediately to the user.
The 'original' Certificate should be retained in a safe place and be shown to any person inspecting or
undertaking further work on the electrical installation in the future. If you later vacate the property,
this Certificate will demonstrate to the new owner that the electrical installation complied with the
requirements of British Standard 7671 at the time the certificate was issued. The Construction
(Design and Management) Regulations require that for a project covered by those regulations, a copy
of this Certificate, together with schedules is included in the project health and safety documentation.
For safety reasons, the electrical installation will need to be inspected at appropriate intervals by a
competent person. The maximum time interval recommended before the next inspection it stated on
Page 1 under 'Next Inspection'.
This Certificate is intended to be issued only for a new electrical installation or new new work
associated with an alteration or addition to an existing installation. It should not have been issued for
the inspection of an existing electrical installation. A 'Periodic Inspection Report' should be issued for
such a periodic inspection.
This Certificate is only valid if a Schedule of Inspections and Schedule of Test Results are appended.