Prepared by
Global Customer Service (UPS) Team
Delta Energy System
2
Summary of the commissioning report to be checked:-
Battery:
3
2.Accesories with UPS:
2.1 Default :
Quantity
Parallel Cable
RS232 Cable
Software/User Manual CD
Almex Connector for Dry Contacts
Door Key
User Manuals
2.2 Optional :
Hardware Software
SNMP Card Yes/No Insight Power Client Yes/No
Modbus Card Yes/No Three Phase UPSentry Yes/No
I/O Relay Card Yes/No Insight Power Manager Yes/No
SNMP+ 5 Port Switching Yes/No Shutdown Agent Yes/No
Environmental Sensor Box Yes/No Insight Power Panel Yes/No
4
3.2. Physical healthiness check of battery:
(**Note: All the batteries must be checked as per “Annexure II” and reading and
observation must be recorded)
5
5. Tightness of UPS components:-
6
6.3Short-Pin Position Table
(** Note:The short-pin position of the input current sensor circuit on PCB-C is
depend on UPS rating, as follow table)
6.3.1: 6-pulse rectifier 3/3, 3/1 Models
6.3.3:The short-pin position of the output current sensor circuit on PCB-A is depend
on UPS rating, as follow table:
3/3 Models:
JPA18 JPA38 JPA22 JPA23
Rated power
JPA34 JPA39 JPA24 JPA26
(KVA)
JPA35 JPA40 JPA25 JPA27
15、20 none none none none
30、40 Short-pin none none none
50、60、80 Short-pin Short-pin none none
100、120 Short-pin Short-pin Short-pin none
160、200 Short-pin Short-pin Short-pin Short-pin
7
3/1 Models:
Rated power
JPA18 JPA38 JPA22 JPA23
(KVA)
15、20 Short-pin Short-pin none none
30、40 Short-pin Short-pin Short-pin none
50、60 Short-pin Short-pin Short-pin Short-pin
6.3.4: The short-pin position of the over current protect circuit on inverter(PCB-A) is
depend on UPS rating, as follow table:
3/3 Models:
JPA41 JPA28 JPA29
Rated power
JPA42 JPA30 JPA32
(KVA)
JPA43 JPA31 JPA33
30、40 none none none
3/1 Models:
Rated power
JPA41 JPA28 JPA29
(KVA)
15、20 Short-pin none none
30、40 Short-pin Short-pin none
50、60 Short-pin Short-pin Short-pin
8
6.3.5Short-Pin Position Table
The short-pin position of the input current sensor circuit on PCB-C is depend on UPS
rating, as follow table:
(1) 6/12-pulse rectifier 3/3,
9
7.1: Display Parameter setting
10
7.2:Control Setting
11
8. Software/Firmware Check:
8.1: Firmware:
Inverter Control Rectifier/Static Display
20~200kVA
260~500kVA
9.1.2:
Bypass Input
LCD Reading DMM Reading
Voltage (L-N) Voltgae (L-L) Voltage (L-N) Voltgae (L-L)
R
S
T
Frequency (Hz)
9.1.3:
Inverter Output
LCD Reading DMM Reading
Voltage (L-N) Voltgae (L-L) Voltage (L-N) Voltgae (L-L)
U-V
V-W
W-U
Frequency (Hz)
12
9.1.4:
UPS Output
LCD Reading DMM Reading
Voltage (L-N) Voltgae (L-L) Voltage (L-N) Voltgae (L-L)
U-V
V-W
W-U
Frequency (Hz)
9.1.5:
UPS Outptu Lading (LCD Reading)
Laod% Laod (Amp)
R
S
T
9.1.6:
UPS Outptu Lading (LCD Reading)
Laod(kVA) Laod (kW)
R
S
T
9.1.7:
Battery
LCD Reading DMM Reading
Battery Float Voltage
Battery Current
Battery Status
Battery Capacity
9.1.8:
Temperature
LCD Reading DMM Reading
Rectifier/Static
Inverter
UPS
Transformer
13
9.2Power Measure with load:-
(** Note: if the threre is difference in measure value and displayed value more than 1%
then calibrate the display with the help of “Intamenu-Modbus.exe”
9.2.1:
Rectifier Input
LCD Reading DMM Reading
Voltage Current Voltage Current
U-V
V-W
W-U
Frequency (Hz)
9.2.2:
Bypass Input
LCD Reading DMM Reading
Voltage (L-N) Voltgae (L-L) Voltage (L-N) Voltgae (L-L)
R
S
T
Frequency (Hz)
9.2.3:
Inverter Output
LCD Reading DMM Reading
Voltage (L-N) Voltgae (L-L) Voltage (L-N) Voltgae (L-L)
U-V
V-W
W-U
Frequency (Hz)
9.2.4:
UPS Output
LCD Reading DMM Reading
Voltage (L-N) Voltgae (L-L) Voltage (L-N) Voltgae (L-L)
U-V
V-W
W-U
Frequency (Hz)
9.2.5:
UPS Outptu Lading (LCD Reading)
Laod% Laod (Amp)
R
S
T
14
9.2.6:
UPS Outptu Lading (LCD Reading)
Laod(kVA) Laod (kW)
R
S
T
9.2.7:
Battery
LCD Reading DMM Reading
Battery Float Voltage
Battery Current
Battery Status
Battery Capacity
9.2.8:
Temperature
LCD Reading DMM Reading
Rectifier/Static
Inverter
UPS
Transformer
15
12. Site condition:-
12.1. Adequate space is available to work for maintenance safely? (Yes/No)
16
Annexure II
Battery Healthyness Check:
(Reading taken with meter……………………Type…………………………………..)
1.Reading taken on individual battery/cell before connecting them into series
Battery Bank1UPS1 Battery Bank2UPS1 BatteryBank1UPS2 Battery Bank2UPS2
# Batch No. V # Batch No. V # Batch No. V # Batch No. V
1. 1. 1. 1.
2. 2. 2. 2.
3. 3. 3. 3.
4. 4. 4. 4.
5. 5. 5. 5.
6. 6. 6. 6.
7. 7. 7. 7.
8. 8. 8. 8.
9. 9. 9. 9.
10. 10. 10. 10.
11. 11. 11. 11.
12. 12. 12. 12.
13. 13. 13. 13.
14. 14. 14. 14.
15. 15. 15. 15.
16. 16. 16. 16.
17. 17. 17. 17.
18. 18. 18. 18.
19. 19. 19. 19.
20. 20. 20. 20.
21. 21. 21. 21.
22. 22. 22. 22.
23. 23. 23. 23.
24. 24. 24. 24.
25. 25. 25. 25.
26. 26. 26. 26.
27. 27. 27. 27.
28. 28. 28. 28.
29. 29. 29. 29.
**Faulty/Suspected battery to be encircled (Please check open circuit voltage of each
battery must be >12.6V)
17
changeover
Status after……min of
changeover
Individual Battery ckd Y/N Y/N Y/N Y/N Y/N Y/N Y/N Y/N
(** Faulty battery’s batch no must be recorded.)
Readings taken on individual battery during battery discharge test with actual load
UPS1
# Bank1 (Volt) Bank2 (Volt) # Bank3(Volt) Bank4 (Volt)
1. 1.
2. 2.
3. 3.
4. 4.
5. 5.
6. 6.
7. 7.
8. 8.
9. 9.
10. 10.
11. 11.
12. 12.
13. 13.
14. 14.
15. 15.
16. 16.
17. 17.
18. 18.
19. 19.
20. 20.
21. 21.
22. 22.
23. 23.
24. 24.
25. 25.
26. 26.
27. 27.
28. 28.
29. 29.
(**This test needs to be conducted to ensure the battery is supporting the power outage
and all terminals are tightened properly)