You are on page 1of 1

Project : Doc. No.

:
Owner : Rev. : A
Contractor : HAP WO No. :
PO No. : Report No. : QC519
Date : Saturday, 16 September 2023 Page No : 01 of 01
Item : BE SILO Grounding Test

BE SILO 1 AND 2 EARTH RESISTANCE TEST


ACCEPTANCE
VALUE RESULT
No DESCRIPTION LOCATION CRITERIA REMARKS
(ohm) (as per NEC) ACC / NOT
Earth Resistance 1 on BE SILO 1
1 BE SILO 1 (TK-BE-01) 0,02 < 5 ohm ACC
Structure
Earth Resistance 2 on BE SILO 1
2 BE SILO 1 (TK-BE-01) 0,02 < 5 ohm ACC
Structure
Earth Resistance 1 on BE SILO 2
3 BE SILO 2 (TK-BE-02) 0,01 < 5 ohm ACC
Structure
Earth Resistance 2 on BE SILO 2
4 BE SILO 2 (TK-BE-02) 0,01 < 5 ohm ACC
Structure
Earth Resistance on LocalPanel
5 Inside Refinery Building 0,00 < 5 ohm ACC
BE SILO

Reference : National Electrical Code

NOTES :

Prepared By Witness By, Witness By,


Contractor Owner Owner