SITE ACCEPTANCE TEST FOR RET670 RELAY

CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

Table of Contents

1. Transformer Protection Relay-RET670........................................................2


1.1 Relay...............................................................................................2
1.2 Common checks...........................................................................2
1.3 Analog inputs................................................................................2
1.3.1 Measurements.................................................................3
1.3.2 Differential Measurements :...........................................4
1.4 Binary Inputs.................................................................................5
1.5 Binary Outputs..............................................................................7
1.6 LEDs...............................................................................................8
2. Protection functions...................................................................................9
2.1 Differential protection T2WPDIF (87T).........................................9
2.2 General Setting:-...........................................................................9
2.2.1 Settings:-........................................................................10
2.2.2 Id min measurements:..................................................11
2.2.3 Id unrestraint measurements:......................................12
2.2.4 BIAS characteristic.......................................................13
2.2.5 Stability Check:..............................................................13
2.2.6 Differential Negative Sequence Function Checked:...13
2.2.7 Harmonic restraint.........................................................14
3. Over excitation Protection (24)................................................................15
3.1 Measurement...............................................................................15
4. Thermal Overload Protection (49)...........................................................16
5. Operational checks...................................................................................17

6. Test Equipment.........................................................................................17

7. Remarks:...................................................................................................17

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 1 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

1. Transformer Protection Relay-RET670


Customer : Manufacturer :
Station : Feeder/Location :

1.1 Relay
-F87T Ordering No

Product Def / Firmware Version

Relay type Serial No

RET670 Frequency 50 I rated 1.00 A

1.2 Common checks


Description OK Remark

Inspect for no physical damage.

Verify the wiring connection as per approved drawing
Confirm that only ring type Lugs are used for all CT/VT ✓

Relay case connected to a local earth bar

Check that Serial no. of relay matching with serial no. of case

Check Relay IRF Contact

1.3 Analog inputs


Channel Description OK Remark
AI01 Current transformer 300___/_1_A_ CT_.R_HV ✓
AI02 Current transformer 300___/ _1_A_ CT_.Y_HV ✓
AI03 Current transformer 300___/ _1_A_ CT_.B_HV ✓
AI04 Current transformer _2000__/ 1_A__ CT_.R_LV ✓
AI05 Current transformer _2000__/ 1_A_ CT_.Y_LV ✓
AI06 Current transformer _2000__/ 1_A_ CT_.B_LV ✓
AI07 Spare --
AI08 Spare --
AI09 Spare --
AI10 Voltage transformer _132000 / 110_V VT_.R_LV ✓

AI11 Voltage transformer _132000 / 110_ V VT_.Y_LV ✓

AI12 Voltage transformer _132000 / 110_V VT_.B_LV ✓

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 2 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

1.3.1 Measurements
Indication on relay Indication on relay
Channel Secondary injection [A,V] Remarks
(sec. val.) [A/V] (prim. val.) [A/kV]
AI 1 1.0
AI 2 1.0
AI 3 1.0
AI 4 1.0
AI 5 1.0
AI 6 1.0
AI 7 Spare
AI 8 Spare
AI 9 Spare
AI 10 63.51
AI 11 63.51
AI 12 63.51
Measurement function accuracy as per manufacurer data
Current : ±0.8% of I at 0.1 x Ir< I < 0.2 x Ir
± 0.5% of I at 0.2 x Ir< I < 0.5 x Ir
±0.2% of I at 0.5 x Ir< I < 4.0 x Ir
Voltage : ±0.3% of U at U≤ 50 V
±0.2% of U at U> 50 V

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 3 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

1.3.2 Differential Measurements :


Rated Current Injected in HV side Rated Current Injected in LV side
Fault I Diff /
0.437[A] 0.840[A]
Type I Bias.
IL1 Diff IL2 Diff IL3 Diff Idns IL1 Diff IL2 Diff IL3 Diff Idns
I Diff.
R-E
I Bias

I Diff.
Y-E
I Bias

I Diff.
B-E
I Bias

I Diff.
R-Y
I Bias

I Diff.
Y-B
I Bias

I Diff.
B-R
I Bias

I Diff.
R-Y-B
I Bias

Diff MEASUREMENT:
1-Phase measurement @ delta side = HV SIDE RATED CURRENT/ √3 = 175 / √3 = A
1-Phase measurement @ Star side = LV SIDE RATED CURRENT / 1.5 = 175 / 1.5 = A
2-Phase measurement @ delta side = HV SIDE RATED CURRENT / (√3/2) = 175 / (√3/2) = A
2-Phase measurement @ Star side = LV SIDE RATED CURRENT / 1 = 175 / 1 = A
3-Phase measurement @ delta side = HV SIDE RATED CURRENT /1 = 175 / 1 = A
3-Phase measurement @ Star side = LV SIDE RATED CURRENT / 1 = 175 / 1 = A

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 4 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

1.4 Binary Inputs

Threshold valve Pickup value= Drop off value=

Channel
Description OK Remarks
-X31
BI.01 Not In Test Mode ✓

BI.02 BCU Faulty ✓

BI.03 Spare ✓

BI.04 Spare ✓

BI.05 Spare ✓

BI.06 Spare ✓

BI.07 Spare ✓

BI.08 Spare ✓

Channel
Description OK Remarks
-X32
BI.09 Control DC MCB Trip ✓

BI.10 Spare ✓

BI.11 Spare ✓

BI.12 Spare ✓

BI.13 Spare ✓

BI.14 TC In Progress ✓

BI.15 Spare ✓

BI.16 Spare

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 5 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

Threshold valve Pickup value= Drop off value=

Channel
Description OK Remarks
-X51
BI.01 Spare ✓

BI.02 Spare ✓

BI.03 Spare ✓

BI.04 Spare ✓

BI.05 Spare ✓

BI.06 Spare ✓

BI.07 Spare ✓

BI.08 Spare ✓

Channel
Description OK Remarks
-X52
BI.09 Spare ✓

BI.10 Spare ✓

BI.11 Spare ✓

BI.12 Spare ✓

BI.13 Spare ✓

BI.14 Spare ✓

BI.15 Spare ✓

BI.16 Spare

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 6 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

1.5 Binary Outputs


Channel
Description OK Remarks(Ω)
-X41
BO.01 87T-1 TRIP ✓

BO.02 Spare ✓

BO.03 87T-1 TRIP ✓

BO.04 87T-1 TRIP ✓

BO.05 87T-1 TRIP ✓

BO.06 87T-1 TRIP ✓

BO.07 87T-1 TRIP ✓

BO.08 87T-1 TRIP ✓

BO.09 87T-1 TRIP ✓

BO.10 87T-1 TRIP ✓

BO.11 Spare ✓

BO.12 Spare ✓

Channel
Description OK Remarks(Ω)
-X42
BO.13 Spare ✓

BO.14 Spare ✓

BO.15 Spare ✓

BO.16 Spare ✓

BO.17 Spare ✓

BO.18 Spare ✓

BO.19 Spare ✓

BO.20 Spare ✓

BO.21 Spare ✓

BO.22 Spare ✓

BO.23 50 TCB OLTC BLOCK ✓

BO.24 50 TCB OLTC RELEASE ✓

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 7 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

1.6 LEDs
Channel Description OK Remark
LED1 Differential Trip ✓

LED2 Diff un-restrain Trip ✓

LED3 Spare ✓

LED4 Spare ✓

LED5 Spare ✓

LED6 Spare ✓

LED7 nd
2 harmonic block ✓

LED8 5th harmonic block ✓

LED9 Diff R phase Pick up ✓

LED10 Diff Y phase Pick up ✓

LED11 Diff B phase Pick up ✓

LED12 Tap Changer Blocking ✓

LED13 THOL Alarm Stage-1 ✓

LED14 THOL Alarm Stage-2 ✓

LED15 Test Active ✓

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 8 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

2. Protection functions

2.1 Differential protection T2WPDIF (87T)

2.2 General Setting:-


Parameter Setting Note
RatedVoltageW1 (kV) 132 KV
RatedVoltageW2 (kV) 11 KV
RatedVoltageW3 (kV) - Not valid for two winding transformers.
RatedCurrentW1 (A) 175 A
RatedCurrentW2 (A) 2099 A
RatedCurrentW3.(A) - Not valid for two winding transformers
ConnectTypeW1 Delta
ConnectTypeW2 Star
ConnectTypeW3 - Not valid for two winding transformers
ClockNumberW2 (deg) 1 (30 deg)
ClockNumberW3 (deg) - Not valid for two winding transformers
ZSCurrSubtrW1 OFF
ZSCurrSubtrW2 ON
ZSCurrSubtrW3 - Not valid for two winding transformers
TconfigForW1 NO
CT1RatingW1 (A) 400 A
CT2RatingW1 (A) 400 A
TconfigForW2 NO
CT1RatingW2 (A) 2500 A
CT2RatingW2 (A) 2500 A
TconfigForW3 NO Not valid for two winding transformers
CT1RatingW3 (A) - Not valid for two winding transformers
CT2RatingW3 (A) - Not valid for two winding transformers

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 9 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

2.2.1 Settings:-
Parameter Settings
Operation ON
SOTF mode OFF
I Diff Alarm 0.20
T Alarm Delay 10 Sec
Id Min 0.30 IB
EndSection1 0.75 IB
EndSection2 3.0 IB
SlopeSection2 (%) 40%
SlopeSection3 (%) 80%
Id unre (%) 7.48 IB
I2/I1ratio (%) 10%
I5/I1ratio (%) 25%
Op Cross Block ON
Op Neg Seq Dif ON
Imin Neg Seq (A) 0.04 IB
Neg Seq ROA (deg) 60 Deg
Open CT Enable OFF

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 10 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

2.2.2 Id min measurements:


AD Current Delay @ 2 x Id min
Phase Channel Pick-up val. [A] meas. val. [ms]
HV R AI1
HV Y AI2
HV B AI3
HV RY AI12
HV YB AI23
HV BR AI31
HV RYB AI1-3
LV R AI4
LV Y AI5
LV B AI6
LV RY AI45
LV YB AI56
LV BR AI64
LV RYB AI4-6
Accuracy as per manufacurer data
Idmin : ±1.0% of Ir
Operate time : Min.=25ms to Max.=35ms

Calculated Pickup value:


MLF_Pry = CTratio/Transformer rated Pry Current = 400/175 = 2.285
MLF_Sec = CTratio/Transformer rated Sec Current = 2500/2100 = 1.190
3-Phase Pick up value for Pry side: Idmin / MLF_Pry = 0.30/2.285 = 0.131 A
3-Phase Pick up value for Sec side: Idmin / MLF_Sec = 0.30/1.190 = 0.252 A
2-Phase Pick up value for Pry side = 3-Phase Pick up value for Pry side x √3/2 = 0.113 A
2-Phase Pick up value for Sec side = 3-Phase Pick up value for Sec side = 0.252 A
1-Phase Pick up value for Pry side: 3-ph Pickup value x √3 = 0.226 A
1-Phase Pick up value for Sec side: 3-ph Pickup value x 1.5 = 0.378 A

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 11 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

2.2.3 Id unrestraint measurements:


AD Current Delay @ 2 x Id min
Phase Channel Pick-up val. [A] meas. val. [ms]
HV R AI1
HV Y AI2
HV B AI3
HV RY AI12
HV YB AI23
HV BR AI31
HV RYB AI1-3
LV R AI4
LV Y AI5
LV B AI6
LV RY AI45
LV YB AI56
LV BR AI64
LV RYB AI4-6
Accuracy as per manufacurer data
Idmin High : ±1.0% of Set value
Operate time : Min.=5ms to Max.=15ms
Calculated Pickup value:
MLF_Pry = CT ratio/Transformer rated Pry Current = 400/175 = 2.285
MLF_Sec= CT ratio/Transformer rated Sec Current= 2500/2100 = 1.190
3-Phase Pick up value for Pry side: (Idmin / MLF_Pry) = 7.48/2.285 = 3.273A
3-Phase Pick up value for Sec side: (Idmin / MLF_Sec) = 7.48/1.190 = 6.28 A
2-Phase Pick up value for Pry side = 3-Phase Pick up value for Pry side x √3/2 = 2.834A
2-Phase Pick up value for Sec side = 3-Phase Pick up value for Sec side = 6.28 A
1-Phase Pick up value for Pry side: (3-ph Pickup value*√3) = 5.668 A
1-Phase Pick up value for Sec side: (3-ph Pickup value*1.5) = 9.42 A

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 12 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

2.2.4 BIAS characteristic


Test results from OMICRON test module attached as separate (Annex-1)

2.2.5 Stability Check:

Current is injected in both Side-1 and Side-2 simultaneously.


The Differential and Restraining currents are observed in both the sides __150___deg phase shift between the two
currents being injected in both the sides.

Current Injected
Fault Differential Restraining Relay
Phase Phase
Type Side-1 Side-2 Current Current Action
angle angle
NO TRIP

R-Y-B NO TRIP

NO TRIP

Current is injected in both Side-1 and Side-2 simultaneously.


The Differential and Restraining currents are observed in both the sides __-30____deg phase shift between the two
currents being injected in both the sides.

Current Injected
Differential Restraining Relay
Fault Type Phase Phase
Side-1 Side-2 Current Current Action
angle angle
TRIP

R-Y-B TRIP

TRIP

2.2.6 Differential Negative Sequence Function Checked:

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 13 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

2.2.7 Harmonic restraint


2nd harmonic restraint Setting of Harmonic Content in I-DIFF = 10 %

Current injected 2nd Current injected 2nd Harmonic


(A) Harmonic (A) Content
Phase
Nominal Harmonic Content Nominal Harmonic (%)
Freq Freq (%) Block Freq Freq Trip
R-E 1.0

Y-E 1.0

B-E 1.0

R-Y-B 1.0
Accuracy as per manufacurer data
Second Harmonic Blocking : ±1.0% of Ir

Cross Blocking Verified: OK

5th harmonic restraint Setting of Harmonic Content in I-DIFF = 25 %

Current injected 5th Current injected 5th Harmonic


(A) Harmonic (A) Content
Phase
Nominal Harmonic Content Nominal Harmonic (%)
Freq Freq (%) Block Freq Freq Trip
R-E 1.0

Y-E 1.0

B-E 1.0

R-Y-B 1.0
Accuracy as per manufacurer data
Fifth Harmonic Blocking : ±5.0% of Ir

Cross Blocking Verified: OK

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 14 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

3. Over excitation Protection (24)


As per approved final setting document, Over Excitation Protection function is kept off after testing.
Final Settings: OEXPVPH
Parameters Set Range
Operation Off On/Off
V/Hz> 115.0 100.0..180.0%UB/f
V/Hz>> 160.0 100.0..200.0%UB/f
tMin 5.000 0.000..60.000s
tMax 2500 0.00..9000.00s
Curve type Tailor made Inverse IEEE/Tailor made
t1Tailor 400 0.00..9000.00s
t2Tailor 30 0.00..9000.00s
t3Tailor 25 0.00..9000.00s
t4Tailor 20 0.00..9000.00s
t5Tailor 12 0.00..9000.00s
T6Tailor 12 0.00..9000.00s
Alarm Level 110 50.0…120.0 %
tAlarm 5.0 0.00..9000.00s

3.1 Measurement
Setting Pick-up Drop-Off
Phase Remarks
[%UB/f] [V] [Hz] [%UB/f] [V] [Hz] [%UB/f]
R-Y 115%
Formula for Applied Voltage =2.2* (Set value / 100 )*Applied Frequency
Time delay:
Injected voltage Delay
Phase Remarks
[%UB/f] [V] [Hz] Expected(s) Measured(s)
R-Y
R-Y
R-Y
R-Y
R-Y
R-Y
R-Y
Accuracy as per manufacurer data
Operate Value: ±0.5% of U Operate time : ±1.0% or ±45ms whichever is greater

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 15 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

4. Thermal Overload Protection (49)


As per approved final setting document, Thermal Overload Protection function is kept off after testing.
.
Final Settings:TRPTTR
Parameter Setting Range Unit
Operation : Off Off, On ---
I Reference (IRef) : 0.90 10.0-1000.0 %
IRef Multiplication (IRefMult) : 1 0.01–1.00 -
Base Currnet - 1 (IBase1) : 100 1.0–100.0 %IB
IBase1 Time constant (Tau1) : 30 0.10-500.00 min
Steady Operate Current
: 110 1.0-110.0 %IB
(ITrip)
First Alarm Level (Alarm1) : 80 1.0-80.0 %Itr
Second Alarm Level (Alarm2) : 90 1.0-90.0 %Itr

Measurements

Operation Time in Sec (Without Pre load Condition)


Current Injected
Phase Alarm1 Stage Alarm2 Stage
in Amp
Expected(s) Actual(s) Expected(s) Actual(s)

R 1.56

Y 1.56 35.15

B 1.56

Accuracy as per manufacurer data


Operate time : ±5.0% or ±200ms whichever is greater

Formula for operating time

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 16 of 17
SITE ACCEPTANCE TEST FOR RET670 RELAY
CLIENT: CONSULTANT: MAIN CONTRACTOR:

NEW 132 KV RAF-1 SUBSTATION AND ASSOCIATED WORKS FOR THE Contract No. : GTC/917/2018
REPLACEMENT OF RAF-A 132KV SWITCHYARD Date :
Name of Substation : COMMON FOR ALL S/S Bay Number :
Name of Equipment : RET670 RELAY F87T Manufacturer :

5. Operational checks
Functional Check:
SL. No. Function Description Tested Remarks
3.1 Tripping of CB on Differential Protn. Trip to 132kV side ✓

3.2 Tripping of CB on Differential Protn. Trip to 11kV side ✓

3.3 Differential Protn. Trip to Lockout Relay K86.1 ✓

3.4 Test Block Operation checked for CT Shorting ✓

3.5 Test Block Operation checked for VT Isolation ✓

3.6 Test Switch Operation checked for tripping isolation ✓

3.7 Final Settings downloaded to Relay after Test ✓

3.8 Relay found healthy ✓

Fault Recorder Signal check: (Minimum Requirement As Per KM Standard) Configured Remark
✓ s
1 DIFF Start L1

2 DIFF Start L2

3 DIFF Start L3

4 DIFF Trip

5 DIFF Restrain Trip

6 DIFF Unrestraint trip
7 nd ✓
DIFF 2 Harmonic Block R phase
8 nd ✓
DIFF 2 Harmonic Block Y phase
nd ✓
9 DIFF 2 Harmonic Block B phase
th ✓
10 DIFF 5 Harmonic Block R phase
th ✓
11 DIFF 5 Harmonic Block Y phase
th ✓
12 DIFF 5 Harmonic Block B phase

13 Test Active

6. Test Equipment
Type Serial Number Calibration due date
Secondary Injection Kit (OMICRON CMC-356)
Multimeter(Flike-87V)

7. Remarks:

L&T/ABB LAHMEYER INTERNATIONAL/ KAHRAMAA


Signature Signature

Name Name
Date Date
Doc.No. RAF-917-10-36-P217 Rev. 0 Page No. 17 of 17