PANEL DESIGNATION: MDB MAIN PANEL BUS RATING: AMPERES

PANEL VOLTAGE: 400/230V, 3Ø, 4W MAIN PANEL CIRCUIT BREAKER RATING:


PANEL LOCATION: NEUTRAL BUS RATING: AMPERES
POWER SUPPLY ORIGIN: GROUND BUS RATING: AMPERES
MOUNTING TYPE: REMARKS:
ENCLOSURE / PROTECTION: DATE PREPARED: FOR APPROVAL
INTERRUPTING CAPACITY
LOW VOLTAGE SWITCHGEAR LOAD SCHEDULE

CIRCUIT LOAD CONSUMPTION CONNECTED LOAD (KVA) CIRCUIT BREAKER


DESCRIPTION AMPS CONDUCTOR TYPE AND SIZE REMARKS
NUMBER WATT KVA L1 L2 L3 TYPE FRAME TRIP kAIC POLE
10.587
F1 DB-GF 25,408.800 31.761 10.587 45.844
10.587
3.827
F2 DB-KC 9,184.000 11.480 3.827 16.570
3.827

F16 SPACE

F17 SPACE

TOTAL KVA 14.41 14.41 14.41 62 MAIN FEEDER: USE BUSDUCT COPPER 4000A, 3P+N+G INDOOR (IP42 MINIMUM)
PHASE "L1" CONNECTED LOAD (KVA) = 14.414 KVA CONNECTED LOAD (AMPS) = 62 AMPERES
PHASE "L2" CONNECTED LOAD (KVA) = 14.414 KVA DEMAND FACTOR = 0.80
PHASE "L3" CONNECTED LOAD (KVA) = 14.41 KVA FEEDER LOAD (AMPS) = 50 AMPERES
TOTAL CONNECTED LOAD (KVA) = 43.241 KVA
DEMAND LOAD 35 KVA
PANEL DESIGNATION: DB-GF MAIN PANEL BUS RATING: AMPERES
PANEL VOLTAGE: 400/230V, 3Ø, 4W MAIN PANEL CIRCUIT BREAKER RATING: 0
PANEL LOCATION: GF NEUTRAL BUS RATING (100% OF RATED CURRENT):
POWER SUPPLY ORIGIN: EPC Metering GROUND BUS RATING (25% OF RATED CURRENT):
MOUNTING TYPE: WALL MOUNTED REMARKS:
ENCLOSURE / PROTECTION: DATE PREPARED: FOR APPROVAL
INTERRUPTING CAPACITY
DISTRIBUTION PANEL LOAD SCHEDULE

CIRCUIT LOAD CONSUMPTION CONNECTED LOAD (KVA) CIRCUIT BREAKER


DESCRIPTION AMPS CONTACTOR CONDUCTOR TYPE AND SIZE REMARKS
NUMBER WATT KVA L1 L2 L3 TYPE RCBO FRAME TRIP kAIC POLE
L1 DL-1-20Nos + WL-1-12Nos+HL-1-7Nos 525 0.656 0.656 2.853 TEST, TIMER & EMERGENCY LIGHTS
L2 SL-1-10meter + HL-2-6Nos 720 0.900 0.900 3.913
L3 DL-1-9Nos+EF-50Wx2 208 0.260 0.260 1.130
L4 DL-1-8Nos+WL-1-5Nos 171 0.214 0.214 0.929
L5 HL-1-10Nos+WL-1-3Nos 195 0.244 0.244 1.060
L6 Landscape (200W) Estimate 200 0.250 0.250 1.087
L7 Façade (100W) Estimate 100 0.125 0.125 0.543
L8 Water Fourtain (100W) Estimate 100 0.125 0.125 0.543
L9 Spare 0.000 0.000 0.000
L10 Spare 0.000 0.000 0.000
L11 Spare 0.000 0.000 0.000
L12 Space 0.000 0.000 0.000
L13 Space 0.000 0.000 0.000
P1 S.S.O 13A (Service) -8Nos 400 0.500 0.500 2.174
P2 Coffee Machine 5.15KW 5150 6.438 6.438 27.989
P3 S.S.O 13A (Service) -2Nos 100 0.125 0.125 0.543
P4 Computer & Printer 400W 400 0.500 0.500 2.174
P5 S.S.O 13A (Service) -2Nos 100 0.125 0.125 0.543
P6 S.S.O 13A (Service) -5Nos 250 0.313 0.313 1.359
P7 Cool Drink 250W 250 0.313 0.313 1.359
P8 S.S.O 13A (Service) -10Nos 500 0.625 0.625 2.717
P9 FCU-1 3600 4.500 4.500 19.565
P10 FCU-2 3600 4.500 4.500 19.565
P11 FCU-3 3600 4.500 4.500 19.565
P12 FCU-4 2500 3.125 3.125 13.587
P13 FCU-5 1370 1.713 1.713 7.446
P14 FCU-6 1370 1.713 1.713 7.446
P15 Spare 0.000 0.000 0.000
P16 Spare 0 0.000 0.000 0.000
P17 Spare 0 0.000 0.000
P18 Space 0 0.000 0.000

TOTAL KVA 14.395 9.331 8.035 MAIN FEEDER: USE CU/XLPE/PVC 1x4C-50mm2 & G25mm² IN CABLE TRAY
PHASE "L1" CONNECTED LOAD (KVA) = 14.395 KVA CONNECTED LOAD (AMPS) = 45.843 AMPERES
PHASE "L2" CONNECTED LOAD (KVA) = 9.331 DEMAND FACTOR = 0.80
PHASE "L3" CONNECTED LOAD (KVA) = 8.035 FEEDER LOAD (AMPS) = 36.675 AMPERES
TOTAL CONNECTED LOAD (KVA) = 31.761 KVA DEMAND LOAD 25.41 KVA

25.409 KVA
PANEL DESIGNATION: DB-KC MAIN PANEL BUS RATING: AMPERES
PANEL VOLTAGE: 400/230V, 3Ø, 4W MAIN PANEL CIRCUIT BREAKER RATING: MCCB, 3P 0
PANEL LOCATION: GF NEUTRAL BUS RATING (100% OF RATED CURRENT): AMPERES
POWER SUPPLY ORIGIN: MDB GROUND BUS RATING (25% OF RATED CURRENT): AMPERES
MOUNTING TYPE: WALL MOUNTED REMARKS:
ENCLOSURE / PROTECTION: DATE PREPARED: FOR APPROVAL
INTERRUPTING CAPACITY
DISTRIBUTION PANEL LOAD SCHEDULE

CIRCUIT LOAD CONSUMPTION CONNECTED LOAD (KVA) CIRCUIT BREAKER


DESCRIPTION AMPS CONDUCTOR TYPE AND SIZE REMARKS
NUMBER WATT KVA L1 L2 L3
L1 FL-1 -8Nos +FF-1+EF-4+EF-3 774 0.968 0.968 4.207
L2 FL-1 -3Nos 60 0.075 0.075 0.326
L3 Spare 0 0.000 0.000 0.000
L4 Spare 0 0.000 0.000 0.000
L5 Spare 0 0.000 0.000 0.000
L6 Space 0 0.000 0.000 0.000
L7 Space 0 0.000 0.000 0.000
P1 S.S.O 13A -1Nos (Freezer)400W 400 0.500 0.500 2.174
P2 S.S.O 13A -1Nos (Refrigerator)300W 300 0.375 0.375 1.630
P3 S.S.O 13A -1Nos (Coffee Baker)6000W 6000 7.500 7.500 32.609
P4 S.S.O 13A -1Nos ( Baker)300W 300 0.375 0.375 1.630
P5 S.S.O 13A (Service) -2Nos 100 0.125 0.125 0.543
P6 S.S.O 13A (Service) -1Nos 50 0.063 0.063 0.272
P7 Transfer Pump 1 400 0.500 0.500 2.174
P8 Transfer Pump 2 400 0.500 0.500 2.174
P9 Pressure Pump 400 0.500 0.500 2.174
P10 Spare 0 0.000 0.000 0.000
P11 Spare 0 0.000 0.000 0.000
P12 Spare 0 0.000 0.000 0.000
P13 Space 0 0.000 0.000 0.000
P14 Space 0 0.000 0.000 0.000

TOTAL KVA 1.968 8.138 1.375


PHASE "L1" CONNECTED LOAD (KVA) = 1.968 KVA CONNECTED LOAD (AMPS) = 16.570 AMPERES
PHASE "L2" CONNECTED LOAD (KVA) = 8.138 DEMAND FACTOR = 0.80
PHASE "L3" CONNECTED LOAD (KVA) = 1.375 FEEDER LOAD (AMPS) = 13.256 AMPERES
TOTAL CONNECTED LOAD (KVA) = 11.480 KVA DEMAND LOAD 9.18 KVA

9.184 KVA