F16 SPACE
F17 SPACE
TOTAL KVA 14.41 14.41 14.41 62 MAIN FEEDER: USE BUSDUCT COPPER 4000A, 3P+N+G INDOOR (IP42 MINIMUM)
PHASE "L1" CONNECTED LOAD (KVA) = 14.414 KVA CONNECTED LOAD (AMPS) = 62 AMPERES
PHASE "L2" CONNECTED LOAD (KVA) = 14.414 KVA DEMAND FACTOR = 0.80
PHASE "L3" CONNECTED LOAD (KVA) = 14.41 KVA FEEDER LOAD (AMPS) = 50 AMPERES
TOTAL CONNECTED LOAD (KVA) = 43.241 KVA
DEMAND LOAD 35 KVA
PANEL DESIGNATION: DB-GF MAIN PANEL BUS RATING: AMPERES
PANEL VOLTAGE: 400/230V, 3Ø, 4W MAIN PANEL CIRCUIT BREAKER RATING: 0
PANEL LOCATION: GF NEUTRAL BUS RATING (100% OF RATED CURRENT):
POWER SUPPLY ORIGIN: EPC Metering GROUND BUS RATING (25% OF RATED CURRENT):
MOUNTING TYPE: WALL MOUNTED REMARKS:
ENCLOSURE / PROTECTION: DATE PREPARED: FOR APPROVAL
INTERRUPTING CAPACITY
DISTRIBUTION PANEL LOAD SCHEDULE
TOTAL KVA 14.395 9.331 8.035 MAIN FEEDER: USE CU/XLPE/PVC 1x4C-50mm2 & G25mm² IN CABLE TRAY
PHASE "L1" CONNECTED LOAD (KVA) = 14.395 KVA CONNECTED LOAD (AMPS) = 45.843 AMPERES
PHASE "L2" CONNECTED LOAD (KVA) = 9.331 DEMAND FACTOR = 0.80
PHASE "L3" CONNECTED LOAD (KVA) = 8.035 FEEDER LOAD (AMPS) = 36.675 AMPERES
TOTAL CONNECTED LOAD (KVA) = 31.761 KVA DEMAND LOAD 25.41 KVA
25.409 KVA
PANEL DESIGNATION: DB-KC MAIN PANEL BUS RATING: AMPERES
PANEL VOLTAGE: 400/230V, 3Ø, 4W MAIN PANEL CIRCUIT BREAKER RATING: MCCB, 3P 0
PANEL LOCATION: GF NEUTRAL BUS RATING (100% OF RATED CURRENT): AMPERES
POWER SUPPLY ORIGIN: MDB GROUND BUS RATING (25% OF RATED CURRENT): AMPERES
MOUNTING TYPE: WALL MOUNTED REMARKS:
ENCLOSURE / PROTECTION: DATE PREPARED: FOR APPROVAL
INTERRUPTING CAPACITY
DISTRIBUTION PANEL LOAD SCHEDULE
9.184 KVA