Professional Documents
Culture Documents
Transformer -Basics
Laminated
iron core
Insulated
copper wire
I I Load
Source E 1
1 N1 N2 E
2
Primary Secondary
X1 '
R1 I 2
R2 X2
N1 N2
Io
I1 I2
load
V1 E1 E2 V2
Ro Xo
A Phase
Windings
A2 A1 a1 a2
B Phase
Windings
B2 B1 b1 b2
C Phase
Windings
C2 C1 c1 c2
Group 1 Yy0
Dd0
0 Phase displacement Zd0
Group 2 Yy6
Dd6
180 Phase displacement Dz6
Group 3 Yd1
Dy1
30 Lag phase displacement Yz1
Group 4 Yd11
Dy11
30 Lead phase displacement Yz11
Requirements
HV
Source LV
50
51
If as multiple
of IF.L.
1.0
0.9 Star Side
0.8
χ
IF 0.7
0.6
51 0.5
Overcurrent 0.4
Relay
Delta Side
0.3
0.2
0.1
χ p.u..
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Protected
Zone
REF
A B C N
LV restricted E/F
protection trips
both HV and LV breaker
Recommended setting : 10% rated
A B C N
Source
Protected zone
REF
51N 51 51 51
Differential
Current
I 1 - I2 OPERATE
I1 BIAS BIAS I
2
I1 - I2
OPERATE RESTRAIN
I1 + I2 Mean Thro
2 Current
PROTECTED ZONE
HV LV
χ
χ2
Ι =
3
10% 58%
20% 41%
30% 28%
40% 17%
50% 7%
22 > Transformer Protection - 2007 22
Differential Connections
P1 P2 A2 A1 a1 a2 P2 P1
A B C
P1 P2 A2 A1 a1 a2 P2 P1
S1 S2 S1 S2
S2 S1 P1 P2
R
R
R
Interposing CT provides :
X Vector correction
X Ratio correction
X Zero sequence compensation
25 > Transformer Protection - 2007 25
Combined Differential and Restricted Earthfault
Protection
A2 A1 a1 a2 P1 P2
S1 S2
P1 S1 P2
REF
S2 P1
P2
S1
S2
To differential relay
Dy1 (-30 )
KBCH
Yy0 Yd11
0 87 +30
HV VectorCor
Yy0, Yd1, Yd5, Yy6, Yd7, Yd11, Ydy0
LV1 VectorCor
LV2 VectorCor 0 , -30 , -150 , 180 , +150 , +30 , 0
S2 S1
S2 S1 T2 T1 P1 P2
33kV : 11kV
200/1 IL = 175A 10 MVA I L = 525A 400/1
HV Ratio Cor
LV1 Ratio Cor 0.05 to 2 in steps of 0.01
LV2 Ratio Cor
Power transformer
Ratio
correction
KBCH Relay
Vectorial
correction
Differential
Virtual interposing CT element Virtual interposing CT
Twice
Normal
Flux
Normal
Flux
Normal
No Load
Current
No Load Current
at Twice Normal
Flux
A
B
C
87 High impedance
relay
A
B
C
a
b
c
87 87 87
n
38 > Transformer Protection - 2007 38
Additional Protection
Differential
Relay
Setting = IS
10% 58%
20% 41%
30% 28%
40% 17%
50% 7%
42 > Transformer Protection - 2007 42
High Impedance Principle
Protected
Zone
REF
Healthy CT Saturated CT
Protected
circuit
Zm1 R Zm2
R IF CT2 A-G
CT1
R R
L L
VS R ST
R R
L R L
RST
VM VS
RR
Metrosil Characteristic
V = CIβ
Suitable values of C & β chosen based on :
(1) Max secondary current under fault conditions
(2) Relay setting voltage
48 > Transformer Protection - 2007 48
Inter-Turn Fault
CT
E
Load
Shorted
turn
3 x internal pipe
Conservator
diameter (minimum)
5 x internal pipe
diameter (minimum)
Oil conservator
3 minimum
Transformer
- Generator transformers
- Grid transformers
Usually only a problem during run-up or shut down, but can be caused
by loss of load / load shedding etc.
Flux O ∝ V
f
Effects of overfluxing :
- Increase in mag. Current
- increase in winding temperature
- increase in noise and vibration
- overheating of laminations and metal parts (caused by stray flux)
Tripping Characteristic
t
100
V/f>>
10
V/f>>>
... ...
1
100
With ambient of 20 C.
Hot spot rise of 78 is
design normal.
A further rise of 6 C
Relative 10 doubles rate of
rate using life.
of using
life
1.0
98
0.1
80 90 100 110 120 130 140
Hot spot temp C
53 > Transformer Protection - 2007 53
Typical Schemes
3.3kV
51 50 P121
200/5 51 50 N N
1MVA
1500/5
3.3/0.44kV
51
P120 N
64 1500/5
MCAG14
11kV
51 50 P121
64 MCAG14
5MVA
1000/5
11/3.3kV
51
P120 N
64 1000/5
MCAG14
3.3kV
56 > Transformer Protection - 2007 56
Above 5MVA
33KV
51 50 P141
200/5
P120
10MVA
51
33/11KV N
87
600/5
P631
64 MCAG14
600/5
5/5A
1600/1
1MVA RCT = 4.9Ω
(5%)
11000V 415V Vk =330V
Calculate :
1) Setting voltage (VS)
80MVA
2) Value of stabilising
resistor required
3) Peak voltage
1600/1 RS developed by CT’s
RCT = 4.8Ω MCAG14
IS = 0.1 Amp for internal fault