You are on page 1of 63

Transformer Protection

Transformer -Basics

2 > Transformer Protection - 2007 2


Transformer - Components

Laminated
iron core

Insulated
copper wire

3 > Transformer Protection - 2007 3


Transformer – Basic Analysis
Flux

I I Load
Source E 1
1 N1 N2 E
2

Primary Secondary

X1 '
R1 I 2
R2 X2
N1 N2
Io
I1 I2

load
V1 E1 E2 V2
Ro Xo

4 > Transformer Protection - 2007 4


Transformer Fault Categories

1. Winding and terminal faults


2. Sustained or uncleared external faults
3. Abnormal operating conditions such as
overload, overvoltage and overfluxing
4. Core faults

5 > Transformer Protection - 2007 5


Transformers Connections
- “Clock Face” numbers refer to position of low voltage
phase-neutral vector with respect to high voltage phase
neutral vector
- Line connections made to highest numbered winding
terminal available
- Line phase designation is same as winding
Example 1 : Dy 11 Transformer
High Low
Voltage Voltage
Windings Windings

A Phase
Windings
A2 A1 a1 a2
B Phase
Windings
B2 B1 b1 b2
C Phase
Windings
C2 C1 c1 c2

6 > Transformer Protection - 2007 6


Transformer Vector Groups

Group 1 Yy0
Dd0
0 Phase displacement Zd0
Group 2 Yy6
Dd6
180 Phase displacement Dz6
Group 3 Yd1
Dy1
30 Lag phase displacement Yz1
Group 4 Yd11
Dy11
30 Lead phase displacement Yz11

7 > Transformer Protection - 2007 7


Overcurrent & Earthfault Protection

8 > Transformer Protection - 2007 8


11kV Distribution Transformers
Typical Fuse Ratings

Transformer rating Fuse

kVA Full load Rated Operating time at


current (A) current (A) 3 x rating(s)

100 5.25 16 3.0


200 10.5 25 3.0
300 15.8 36 10.0
500 26.2 50 20.0
1000 52.5 90 30.0

9 > Transformer Protection - 2007 9


Transformer Overcurrent Protection

Requirements

X Fast operation for primary short circuits


X Discrimination with downstream protections
X Operation within transformer withstand
X Non-operation for short or long term overloads
X Non-operation for magnetising inrush

10 > Transformer Protection - 2007 10


Use of Instantaneous Overcurrent Protection

HV
Source LV

50
51

50 set to 1.2 - 1.3 x through fault level

11 > Transformer Protection - 2007 11


Overcurrent Relay Setting > IF.L.

If as multiple
of IF.L.
1.0
0.9 Star Side
0.8
χ
IF 0.7
0.6
51 0.5
Overcurrent 0.4
Relay
Delta Side
0.3
0.2
0.1
χ p.u..
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

Overcurrent Relay Setting > IF.L.

12 > Transformer Protection - 2007 12


Star Winding REF

Protected
Zone

REF

Relay only operates for earthfaults within protected zone.


Uses high impedance principle.
Stability level : usually maximum through fault level of
transformer

13 > Transformer Protection - 2007 13


Restricted E/F Protection
Low Voltage Windings (1)

A B C N

LV restricted E/F
protection trips
both HV and LV breaker
Recommended setting : 10% rated

14 > Transformer Protection - 2007 14


Restricted E/F Protection
Low Voltage Windings (2)

A B C N

LV restricted E/F protection trips both HV and LV breaker


Recommended setting : 10% rated

15 > Transformer Protection - 2007 15


Delta Winding Restricted Earth Fault

Source

Protected zone
REF

X Delta winding cannot supply zero sequence


current to system
X Stability : Consider max LV fault level
X Recommended setting : less than 30% minimum
earth fault level

16 > Transformer Protection - 2007 16


Unrestricted Earthfault Protection (1)

51N 51 51 51

- Provides back-up protection for system


- Time delay required for co-ordination

17 > Transformer Protection - 2007 17


Differential Protection

18 > Transformer Protection - 2007 18


Differential Protection

Overall differential protection may be justified for larger


transformers (generally > 5MVA).
Provides fast operation on any winding
Measuring principle :
Based on the same circulating current principle as the
restricted earth fault protection
However, it employs the biasing technique, to
maintain stability for heavy thro’ fault current
Biasing allows mismatch between CT outputs.
It is essential for transformers with tap changing facility.
Another important requirement of transformer differential
protection is immunity to magnetising in rush current.

19 > Transformer Protection - 2007 19


Biased Differential Scheme

Differential
Current

I 1 - I2 OPERATE
I1 BIAS BIAS I
2

I1 - I2
OPERATE RESTRAIN

I1 + I2 Mean Thro
2 Current

Bias = Differential (or Spill) Current


Mean Through Current

20 > Transformer Protection - 2007 20


Differential Protection

PROTECTED ZONE
HV LV

Correct application of differential protection requires CT ratio


and winding connections to match those of transformer.
CT secondary circuit should be a “replica” of primary system.
Consider :
(1) Difference in current magnitude
(2) Phase shift
(3) Zero sequence currents

21 > Transformer Protection - 2007 21


Earthfault on Transformer Winding

χ
χ2
Ι =
3

I For relay operation, Ι > ΙS


χ2
e.g. If ΙS = 20%, then > 20% for operation
3
i.e. χ > 59%
Differential Thus 59% of windi ng is not protected
Relay
Setting = IS

Differential Relay Setting % of Star Winding Protected

10% 58%
20% 41%
30% 28%
40% 17%
50% 7%
22 > Transformer Protection - 2007 22
Differential Connections

P1 P2 A2 A1 a1 a2 P2 P1

A B C

23 > Transformer Protection - 2007 23


ICT’s

24 > Transformer Protection - 2007 24


Use of Interposing CT

P1 P2 A2 A1 a1 a2 P2 P1

S1 S2 S1 S2

S2 S1 P1 P2

R
R
R

Interposing CT provides :
X Vector correction
X Ratio correction
X Zero sequence compensation
25 > Transformer Protection - 2007 25
Combined Differential and Restricted Earthfault
Protection

A2 A1 a1 a2 P1 P2
S1 S2

P1 S1 P2
REF
S2 P1
P2
S1

S2
To differential relay

26 > Transformer Protection - 2007 26


Vector Group Correction

Dy1 (-30 )

KBCH

Yy0 Yd11
0 87 +30

HV VectorCor
Yy0, Yd1, Yd5, Yy6, Yd7, Yd11, Ydy0
LV1 VectorCor
LV2 VectorCor 0 , -30 , -150 , 180 , +150 , +30 , 0

27 > Transformer Protection - 2007 27


In Zone Earthing Transformer
a1 a2
P1 P2
A1 A2 P2 P1

S2 S1

S2 S1 T2 T1 P1 P2

28 > Transformer Protection - 2007 28


CT Ratio Mismatch Correction - Modern Approach

33kV : 11kV
200/1 IL = 175A 10 MVA I L = 525A 400/1

0.875A KBCH 1.31 Amps


1A 1A
1.14 0.76
87

HV Ratio Cor
LV1 Ratio Cor 0.05 to 2 in steps of 0.01
LV2 Ratio Cor

29 > Transformer Protection - 2007 29


Integral Vectorial and Ratio Compensation

Power transformer

Ratio
correction
KBCH Relay

Vectorial
correction
Differential
Virtual interposing CT element Virtual interposing CT

30 > Transformer Protection - 2007 30


Transformer Magnetising Characteristic

Twice
Normal
Flux

Normal
Flux

Normal
No Load
Current
No Load Current
at Twice Normal
Flux

31 > Transformer Protection - 2007 31


Typical Magnetising Inrush Waveforms

A
B
C

32 > Transformer Protection - 2007 32


Typical Magnetising Inrush Waveforms

33 > Transformer Protection - 2007 33


Transformer Differential Protection

Effect of magnetising current

X Appears on one side of transformer only

X Seen as fault by differential relay

X Normal steady state magnetising current is less than


relay setting

X Transient magnetising inrush could cause relay to


operate

34 > Transformer Protection - 2007 34


Transformer Differential Protection (2)

Solution 1 : 2nd (and 5th) harmonic restraint

X Makes relay immune to magnetising inrush

X Slow operation may result for genuine transformer


faults if CT saturation occurs

35 > Transformer Protection - 2007 35


Transformer Differential Protection (3)

Effect of magnetising inrush

Solution 2 : Gap measurement technique

X Inhibits relay operation during magnetising inrush

X Operate speed for genuine transformer faults


unaffected by significant CT saturation

36 > Transformer Protection - 2007 36


Protection of Auto-Transformer by High
Impedance Differential Relays (1)

(a) Earth Fault Scheme

87 High impedance
relay

37 > Transformer Protection - 2007 37


Protection of Auto-Transformer by High
Impedance Differential Relays (2)

(b) Phase and Earth Fault Scheme

A
B
C
a
b
c

87 87 87

n
38 > Transformer Protection - 2007 38
Additional Protection

39 > Transformer Protection - 2007 39


Transformer REF Protection

40 > Transformer Protection - 2007 40


Application:
HV & LV REF

41 > Transformer Protection - 2007 41


Earthfault on Transformer Winding

Differential
Relay
Setting = IS

Differential Relay Setting % of Star Winding Protected

10% 58%
20% 41%
30% 28%
40% 17%
50% 7%
42 > Transformer Protection - 2007 42
High Impedance Principle

Based on Merz-Price circulating current principle

X Requires matched current transformers of low


reactance design, typically class X or equivalent
X Equal CT ratios
X Typically current operated relay with an external
stabilising resistor
X Non-linear resistor may be required to limit
voltage across relay circuit during internal faults
X Suitable for zones up to 200 - 300 metres
(typically)

43 > Transformer Protection - 2007 43


Star Winding REF

Protected
Zone

REF

Relay only operates for earthfaults within protected zone.


Uses high impedance principle.
Stability level : usually maximum through fault level of
transformer

44 > Transformer Protection - 2007 44


HIGH IMPEDANCE PRINCIPLE RESTRICTED EARTH FAULT

X High impedance schemes are used where one CT is completely


saturated and the other CTs are healthy.

Healthy CT Saturated CT
Protected
circuit

Zm1 R Zm2
R IF CT2 A-G
CT1

R R
L L
VS R ST
R R
L R L

X Voltage across relay circuit VS = IF (RCT + 2RL )


Where, If : Maximum secondary external fault current
X Stabilising resistor RST limits spill current to IS (relay setting)
Š RST = (VS / Ir )- RR (RR = very low relay burden)
45 > Transformer Protection - 2007 45
Stabilising Resistor

Use of stabilising resistor:

X Where relay impedance alone is too low to


ensure stability then the relay circuit
impedance can be increased through the
addition of an external resistor connected in
series with the relay
X Required circuit impedance > Vs/Is
X RSTAB > (Vs/Is) - Rrelay

46 > Transformer Protection - 2007 46


Non-Linear Resistors (Metrosils)
During internal faults the high impedance relay circuit constitutes an
excessive burden to the CT’s.
A very high voltage develops across the relay circuit and the CT’s which
can damage the insulation of CT’s, secondary wiring and relay.
Magnitude of peak voltage VP is given by an approximate formula (based
on experimental results)

VP = 2 √2(VK (VF - VK))


Where VF = If (RCT + 2RL + RSTAB + Rrelay)
Metrosil required if VP > 3kV

Vk = (VA x ALF) / In + (RCT . ALF. In)


where,

Vk = Required knee point voltage


VA = Rated burden in volts-amps,
In = Rated secondary current CT.
ALF = Accuracy limit Factor = 15
47 > Transformer Protection - 2007 47
High Impedance Circuit Arrangement
I

RST
VM VS

RR

Metrosil Characteristic
V = CIβ
Suitable values of C & β chosen based on :
(1) Max secondary current under fault conditions
(2) Relay setting voltage
48 > Transformer Protection - 2007 48
Inter-Turn Fault

CT
E
Load
Shorted
turn

Nominal turns ratio - 11,000 / 240


Fault turns ratio - 11,000 / 1
Current ratio - 1 / 11,000

Requires Buchholz relay

49 > Transformer Protection - 2007 49


Buchholz Relay Installation

3 x internal pipe
Conservator
diameter (minimum)
5 x internal pipe
diameter (minimum)

Oil conservator
3 minimum

Transformer

50 > Transformer Protection - 2007 50


Overfluxing

- Generator transformers
- Grid transformers

Usually only a problem during run-up or shut down, but can be caused
by loss of load / load shedding etc.

Flux O ∝ V
f

Effects of overfluxing :
- Increase in mag. Current
- increase in winding temperature
- increase in noise and vibration
- overheating of laminations and metal parts (caused by stray flux)

Protective relay responds to V/f ratio


Stage 1 - lower A.V.R.
Stage 2 - Trip field
51 > Transformer Protection - 2007 51
Overfluxing Protection

Tripping Characteristic

t
100
V/f>>

10
V/f>>>
... ...
1

1.00 1.10 1.20 1.30 1.40 1.50 1.60 V/f


Vnom/fnom

52 > Transformer Protection - 2007 52


Effect of Overload on Transformer Insulation Life

100
With ambient of 20 C.
Hot spot rise of 78 is
design normal.
A further rise of 6 C
Relative 10 doubles rate of
rate using life.
of using
life
1.0

98
0.1
80 90 100 110 120 130 140
Hot spot temp C
53 > Transformer Protection - 2007 53
Typical Schemes

54 > Transformer Protection - 2007 54


Up to 1MVA

3.3kV

51 50 P121
200/5 51 50 N N

1MVA
1500/5
3.3/0.44kV

51
P120 N

64 1500/5
MCAG14

55 > Transformer Protection - 2007 55


1 - 5MVA

11kV

51 50 P121

64 MCAG14

5MVA
1000/5
11/3.3kV

51
P120 N

64 1000/5
MCAG14
3.3kV
56 > Transformer Protection - 2007 56
Above 5MVA

33KV

51 50 P141
200/5

P120
10MVA
51
33/11KV N
87
600/5
P631

64 MCAG14

600/5
5/5A

57 > Transformer Protection - 2007 57


Worked Examples

58 > Transformer Protection - 2007 58


REF Calculations

59 > Transformer Protection - 2007 59


Restricted Earth Fault Protection

1600/1
1MVA RCT = 4.9Ω
(5%)
11000V 415V Vk =330V
Calculate :
1) Setting voltage (VS)
80MVA
2) Value of stabilising
resistor required
3) Peak voltage
1600/1 RS developed by CT’s
RCT = 4.8Ω MCAG14
IS = 0.1 Amp for internal fault

2 Core 7/0.67mm (7.41Ω/km)


100m Long

60 > Transformer Protection - 2007 60


Solution :

Earth fault calculation :-


Using 80MVA base
Source impedance = 1 p.u.
Transformer impedance = 0.05 x 80 = 4 p.u.
1
1 P.U. Total impedance = 14 p.u.
1 4
I1
∴ I1 = 1 = 0.0714 p.u.
14
4 Base current = 80 x 106
I2 √3 x 415
= 111296 Amps
4
∴ IF = 3 x 0.0714 x 111296
I0
= 23840 Amps (primary)
= 14.9 Amps (secondary)
Sequence Diagram
61 > Transformer Protection - 2007 61
Solution :
(1) Setting voltage
VS = IF (RCT + 2RL)
Assuming “earth” CT saturates,
RCT = 4.8 ohms
2RL = 2 x 100 x 7.41 x 10-3 = 1.482 ohms
∴ Setting voltage = 1.49 (4.8 + 1.482)
= 93.6 Volts
(2) Stabilising Resistor (RS)
RS = VS - 1
IS IS2 Where IS = relay current setting
∴ RS = 93.6 - 1 = 836 ohms
0.1 0.22
62 > Transformer Protection - 2007 62
Solution :

3) Peak voltage = 2√2 √VK (VF - VK)


VF = 14.9 x VS = 14.9 x 936 = 13946 Volts
IS
For ‘Earth’ CT, VK = 330V
∴ VPEAK = 2√2 √330 (13946 - 330)
= 6kV
Thus, metrosil voltage limiter will be required.

63 > Transformer Protection - 2007 63

You might also like