Blueprint Reading

JS - 21

Load Calculations

General Lights @ 100 W = 700 W

Applying Diversity @ 66% = 462 W

Total Current = 462 / 110 = 4.2A

Load per Phase = 2.1A / ph

General Plugs @ 15A

First 1 @ 100% of 20A = 20A

Rem. 8 @ 40% of 20A = 64A

Total Current = 84A

Amps per Phase = 42A / ph

GFCI Plugs @ 20A

All at 100% =20A

Amps per Phase =10A / ph


AC

1st AC

4 KW @ 125% = 4000 * 1.25 = 5000 W

P.F. = 90%

VA = P/ P.F.

= 5000 W / 0.9

= 5,555.56 VA

Amperage = VA / 220 V

= 25.25A

Total AC Current = 25.25 A

L1 L2
General Lights 6.9 A 6.9 A
Plugs 56 A 56 A
AC 35.35 A 35.35 A
Total 155.92 155.92 A
A

Given that the Ampacity of the installation is 155.92 A, use a figure of 200 A at 220 V. the main circuit breaker will be 200 A, DP, 220 V
Calculating Sub-circuits

Lighting

For 23 lights the number of lighting circuits will be 4 circuits

1 cct with 6 lights

2 ccts with 5 lights

1 cct with 7 lights

Receptacle Outlet

For the plugs

1st cct @ 20 A

Remainder ccts @ 40% of 20 A = 8 A

Kitchen – 2 ccts

General – 11 ccts.

Load Summary

Connected Current Poles per Number of Number of Conductor Circuit


Load Rating circuit circuits Poles Size Breaker
Size
Lights 6.9 A 1 4 4 2.5 mm2 15A SP
General 8A 1 11 11 2.5 mm2 20A SP
Plugs
Kitchen 8A 1 2 2 2.5 mm2 20A SP
Plugs
Range 36.36 A 2 1 2 6 mm2 40A DP
Aircon 35.35 A 2 2 4 6 mm2 40A DP
Water 11.36 A 2 1 2 2.5 mm2 20A DP
Heater
Washing 5.68 A 2 1 2 2.5 mm2 15A DP
Machine
Dish 9.09 A 1 1 1 2.5 mm2 15A SP
Washer
Service 175 A 2 2 70 mm2 175A DP
Main
Total 30 + main

Electrical Blueprint of Household


TYPE: Plus main, Plug-in VOLTS: 220 V
BUS AMPS:
MTG: Cuttler Hammer 200 A
MAIN CIRCUIT BREAKER: 200 A, DP, 220 V CB A.I.C. RMS. Sym. 35 kA

AMPS PER AMPS PER


CCT. CB WIRE PHASE BUS PHASE WIRE CB CCT.
No. SERVICE SIZE SIZE L1 L2 L1 L2 SIZE SIZE SERVICE No.
40A
1 AC Unit #2 40A DP 25 50 25 AC Unit #1 2
6 mm2 6 mm2 DP
40A
3 AC Unit #2 40A DP 25 50 25 AC Unit #1 4
6 mm2 6 mm2 DP
15A
5 Light cct. #1 15A SP 6.9 13.8 6.9 Light cct. #3 6
2.5 mm2 2.5 mm2 SP
15A
7 6.9 6.9 Light cct. #4 8
2.5 mm2 SP
20A
9 Kitchen plug #1 20A SP 8 16 8 Kitchen Plug #2 10
2.5 mm2 2.5 mm2 SP
20A
11 General plug #1 20A SP 8 16 8 General Plug #6 12
2.5 mm2 2.5 mm2 SP
20A
13 General Plug #2 20A SP 8 16 8 General Plug #7 14
2.5 mm2 2.5 mm2 SP
20A
15 General Plug #3 20A SP 8 16 8 General Plug #8 16
2.5mm2 2.5mm2 SP
20A
17 General Plug #4 20A SP 8 16 8 General Plug #9 18
2.5mm2 2.5mm2 SP
20A
19 General Plug #5 20A SP 8 16 8 General Plug #10 20
2.5mm2 2.5mm2 SP
47.7 20A
21 Range 40A DP 36.36 11.36 Water Heater 22
6 mm2 2 2.5mm2 DP
47.7 11.3 20A
Range 40A DP
23 6 mm2 36.36 2 6 2.5mm2 DP Water Heater 24
14.2
25 Washing Machine 15A DP 2.5mm2 14.21 1 26
15A
27 Washing Machine 15A DP 2.5mm2 14.21 23.3 9.09 2.5mm2 SP Dish Washer 28
29 Light cct. #2 15A SP 2.5 mm2 6.9 6.9 30
31 General Plug #11 20A SP 2.5mm 2
8 8 32
33 34
35 36
37 38
39 40

TOTAL LOAD PER PHASE


A B
180.63 183.92

NEC Calculations
Watt Per Square Metre Method

1
(1) 56 Ft. = 56.125 * 12 = 673.5 * 25.4
8

= 17,106.9 mm

= 17.1069 m

7
(2) 31 Ft. = 31.875 * 12 = 382.5 * 25.4
8

= 9,715.5 mm

= 9.7155 m

(3) Area = 17.1069 * 9.7155

= 166.202 m2

(4) Loading = 32.29 * 166.202 m2

= 5,366.66 W

3 Small Appliances @ 1500 W = 4500 W

Loading Current = 1500 W

Total General Lighting Load = 11,366.66 W

Applying Diversity

3000 W @ 100% = 3000 W


11,366.66 W – 3000 W = 8,366.66 W

8,366.66 W @ 35% = 2,928.331 W

Power Loads

1- 2.5kW, 220V Water Heater @ 100% = 2500W

1 – 8kW, 220V Electric Range = 8000W

2 – First-one 4kW, 220V AC @ 125% = 5000W

Second one 4KW,220AC@100% =4000W

=5000+4000=9000W

1 – 2.5kw, 220V Washing Machine @ 125% = 3125W

1 – 1000W, 110V Dish Washer @ 125% = 1250W

Total Wattage = 26,778.3093W

Ampacity = total wattage = 26,778.3093W

System Voltage 220V

= 121.72A
The total Ampacity of the Installation is 121.72A.

Main Circuit Breaker – 200A, DP

Main Conductor Size – 70 mm2

42 – Way Distribution Panel