You are on page 1of 11

Construction and Building Materials 54 (2014) 421–431

Contents lists available at ScienceDirect

Construction and Building Materials


journal homepage: www.elsevier.com/locate/conbuildmat

Determination of shear strength of historic masonries by moderately


destructive testing of masonry cores
Claudio Mazzotti a,c,1, Enrico Sassoni b,c,⇑, Giulia Pagliai a
a
Department of Civil, Chemical, Environmental and Materials Engineering, University of Bologna, via Risorgimento 2, 40136 Bologna, Italy
b
Department of Civil, Chemical, Environmental and Materials Engineering, University of Bologna, via Terracini 28, 40131 Bologna, Italy
c
Centro Interdipartimentale di Ricerca Industriale (CIRI) Edilizia e Costruzioni, Università di Bologna, via Lazzaretto 15/5, 40131 Bologna, Italy

h i g h l i g h t s

 Assessing the seismic vulnerability of historic masonry buildings is an urgent task.


 A novel method to determine masonry shear strength by using cores is here presented.
 Purposely constructed reference masonry panels were tested to shear–compression.
 Masonry cores were subjected to splitting test with various mortar layer rotations.
 Results found for reference masonry panels and cores exhibit very good agreement.

a r t i c l e i n f o a b s t r a c t

Article history: To determine masonry shear strength, which is a fundamental parameter for evaluating the seismic vul-
Received 15 July 2013 nerability of existing masonry buildings, several experimental techniques can be adopted. A promising
Received in revised form 12 December 2013 method is subjecting cores, easily core-drilled from masonry buildings, to splitting test with mortar layer
Accepted 16 December 2013
rotation, so that in the centre of the mortar joint a mixed compression–shear stress state is present. To
Available online 23 January 2014
investigate the actual suitability of testing cores for determining masonry shear strength, in this study
a systematic comparison between reference masonry panels, subjected to shear-compression test, and
Keywords:
cores, subjected to splitting test with different mortar layer inclinations, was performed. Ten masonry
Masonry
Seismic vulnerability
panels were constructed using fired-clay solid bricks and a mixed lime-cement mortar with poor
Shear strength mechanical properties, with the aim of resembling materials used in historic buildings. After curing for
Cylindrical cores 28 days, nine masonry panels were tested, compression stress being kept constant at a fixed value and
Mohr–Coulomb criterion shear stress being increased until failure. By plotting shear stress against compression stress and per-
forming linear regression, the initial shear strength and the angle of internal friction of the masonry were
obtained. The tenth masonry panel was core-drilled to obtain cylindrical cores (10 cm diameter, 25 cm
length) with a central diametric mortar joint. The cores were then subjected to splitting test with mortar
layer inclinations of 0°, 15°, 30°, 40°, 45° and 50° with respect to the horizontal. While cores tested at 15°
and 30° exhibited a splitting failure mode, cores tested at higher mortar layer inclinations exhibited a
sliding failure mode, which was considered as the most representative one for evaluating masonry shear
resistance. By plotting the shear stress against the compression stress for cores tested at 40°, 45° and 50°
and then performing a linear regression, the initial shear strength and the angle of internal friction were
derived. As results found for reference masonry panels and for cylindrical cores exhibit very good agree-
ment, the proposed methodology seems like a very promising technique, which has the advantage of
requiring only moderately destructive samples that can be easily core-drilled from existing buildings.
Ó 2013 Elsevier Ltd. All rights reserved.

1. Introduction

Recent earthquakes that in the last decades struck Southern


⇑ Corresponding author at: Department of Civil, Chemical, Environmental and Europe and Asia clearly showed the sensitivity of masonry build-
Materials Engineering, University of Bologna, via Terracini 28, 40131 Bologna, Italy. ings to this type of dynamic actions. In an effort to limit the dam-
Tel.: +39 051 2090363; fax: +39 051 2090322.
ages from future earthquakes, the definition of the structural
E-mail addresses: claudio.mazzotti@unibo.it (C. Mazzotti), enrico.sassoni2@
unibo.it (E. Sassoni), pagliai.giulia@gmail.com (G. Pagliai). capabilities of this type of buildings has become a really actual
1
Tel.: +39 051 2093251; fax: +39 051 2093236. and urgent task [1]. In this framework, evaluating the seismic

0950-0618/$ - see front matter Ó 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.conbuildmat.2013.12.039
422 C. Mazzotti et al. / Construction and Building Materials 54 (2014) 421–431

vulnerability of historic masonry buildings, with the aim of pre- portion (about 90  180 cm2), disconnected from the rest of the
dicting the damage level for a certain earthquake intensity, is a masonry wall and loaded both horizontally and vertically by
challenging task that structural engineers are often asked to deal means of hydraulic jacks [6]. This method has the advantage of
with. For instance, recent studies have been aimed at evaluating allowing to evaluate shear resistance for different compression
the seismic vulnerability of masonry towers [2], masonry churches levels. Moreover, the evaluation of test results is quite straightfor-
[3], masonry monumental palaces [4] and monumental building in ward, as masonry shear resistance with or without vertical loads is
general [5]. In particular, in Italy, after the Emilia earthquake of directly measured. However, this method has the strong limitation
2012, an increasing number of existing buildings has been sub- of being highly destructive, so that its actual applicability is limited
jected to seismic vulnerability analysis. to a very few cases.
To assess the structural response of masonry buildings, ma- An alternative in situ testing procedure is subjecting a masonry
sonry mechanical properties need to be first determined. Several portion (larger than 120  120 cm2, according to ASTM E519/
methods have been reported in the literature for the assessment 519M-10 [17]) to a diagonal compression test [6,18]. This method,
of the load bearing capacity of existing masonry constructions, which is highly destructive as well, has also the limitation of not
including monumental buildings, towers, bridges, etc. [6–10]. As allowing compression stress to be applied independently from
far as resistance to seismic actions is concerned, masonry shear shear load. According to the standard interpretation, from in situ
strength is the most important parameter to be evaluated. Accord- diagonal test the masonry shear strength with zero compression
ing to Eurocode 6 [11], as well as Italian Code for constructions stress is obtained, since the centre of the panel is assumed to be
[12], the masonry characteristic shear strength (fvk) for new subjected to pure shear [17,18]. However, further interpretations
constructions can be defined following the well-known Mohr– have been proposed so far, based on masonry panel modeling as
Coulomb failure criterion fvk = fvk0 + 0.4 rn, where fvk0 is the an isotropic and homogeneous material. According to these inter-
characteristic shear strength with zero compression stress and pretations, the centre of the panel is not subjected to pure shear,
rn is the average compression stress owing to vertical loads. and different formulas for masonry shear strength calculation have
A number of methods and techniques have been proposed so far been alternatively proposed [18].
to define the characteristic shear strength fvk0 and they will be dis- A less invasive technique for estimating masonry shear strength
cussed in the next section. Among them, masonry shear strength is subjecting triplets (made of three brick courses and two mortar
determination by testing of cylindrical cores seems like a promis- joints in-between) to a shear test, as described in EN 1052-3:2007
ing technique, which has the advantage of causing limited damage [19]. This method requires relatively small test specimens, and has
to the building and allowing to obtain information on shear also the advantage that triplets can be tested by either applying or
strength for different compression values. Nonetheless, the studies not axial force to bricks, so that masonry shear strength with or
that have been carried out so far to evaluate the suitability of using without compression loads can be estimated. However, while in
masonry cores were based on either empirical formulas or experi- the case of new masonries testing triplets is a simple and straight-
mental data obtained from samples coming from actual historical forward method, in the case of existing masonries its applicability
buildings [13–15]. In the latter case, test results exhibit significant is rather limited [18,20].
dispersion, which can be attributed to the variability of both bricks A semi-destructive method that can be successfully performed
and mortars used in historical buildings. To the authors’ best in situ is measuring masonry mortar joint shear strength, according
knowledge, no experimental study for evaluating the suitability to ASTM C 1531-09 [21]. The idea is determining the horizontal
of testing cores, making use of purposely constructed and con- force required to produce the relative slip of a brick with respect
trolled masonry samples, has been carried out so far. to the rest of the panel. This is possible since adjacent bricks along
Therefore, in this study a systematic comparison between shear the same course have to be removed. This in situ testing technique
strength values obtained from reference masonry panels, subjected has the advantage of being less destructive, less time-consuming
to shear-compression test according to EN 1052-3 [16], and values and more economical than direct shear-compression or diagonal
obtained from cores, core-drilled from analogous panels and sub- compression tests on masonry portions. However, its suitability
jected to splitting test with various mortar layer inclinations, was is limited to those cases where masonry wall shear strength is gov-
performed. For interpreting the results of the splitting tests on erned by shear strength of the mortar joints rather than shear
cores, a novel methodology was used, which is here presented capacity of the bricks [21]. As pointed out in the cited standard,
and discussed. the proposed method for measuring mortar joint shear strength
tends to overestimate the actual masonry wall shear strength,
which can be derived from the former by making use of an empir-
2. Existing methods to define shear strength ical relationship [21].
An alternative technique, requiring only moderately destructive
When dealing with new masonry, Codes allow two possibilities samples that can be easily core-drilled from existing masonries
to be followed for the definition of shear strength without axial [6,8,10], consists of subjecting to splitting test masonry cores with
force fvk0: (a) direct experimental measurement by performing a rotated mortar joint [13,22,23]. The method is based on the idea
shear tests on masonry units with different axial load or (b) its that in a core (made of two bricks and a central diametrical mortar
indirect estimation by making use of tables or empirical expres- joint) subjected to a splitting test, with the mortar layer rotated by
sions contained inside those same Codes [11,12], correlating fvk0 45° with respect to horizontal, the stress state in the centre of the
with brick and mortar compressive strength. Only the second mortar joint will be a mixed compression–shear stress state, which
method can be applied also to existing masonry but with a resembles that of a masonry panel subjected to a diagonal com-
reduced reliability. For a more accurate estimation, in situ pression test [13,22]. Then, by projecting the failure pressure (ob-
direct measurement of masonry shear strength, either with tained by dividing the failure load by the mortar layer area) in the
or without compression stress, has to be preferred. To this two directions orthogonal and parallel to the mortar layer, the
purpose, several techniques can be adopted, differing for their respective stress states can be derived.
destructiveness, expensiveness, technical challenge and signifi- The first experimental studies, aimed at evaluating the suitabil-
cance of results. ity of using splitting test on cores with a rotated mortar layer for
The most direct technique for in situ shear strength determina- evaluating masonry shear strength, pointed out that the nominal
tion is performing a shear-compression test on a large masonry shear strength of cores was about 1.5–1.9 times the nominal shear
C. Mazzotti et al. / Construction and Building Materials 54 (2014) 421–431 423

strength of reference masonry panels, tested by diagonal compres- planes parallel to the mortar layer and pure shear in the orthogonal
sion [22]. The difference between the cores and the panels was planes (shear and compression values varying as a function of mor-
found to vary as a function of the mortar type, the curing time tar layer inclination) [13,14]. However, along the direction perpen-
and the failure mode. This was explained considering that, even dicular to the joint, where pure shear is assumed, the confinement
if the load that first initiates the crisis is basically the same for exerted by the surrounding mortar is neglected. Consequently, for
cores and panels, the failure loads are different. In the panels, the a more accurate estimation, the mortar confining effect has
failure load is practically the same as the load initiating the crisis, recently been investigated [15]. By finite element modeling, the
while in the cores the peripheral zones of the mortar layer are confinement was estimated, for different inclinations of the mortar
characterized by a stress state that is far from the one leading to layer, as a function of Poisson’s ratio. As confinement reaches
failure. As significant reserves of resistance are present in these lat- remarkable values (about 20–30% of the compression stress,
eral parts of the cores, a significant load increase after crisis initia- depending on mortar layer inclination), the resulting Mohr’s circles
tion is possible before failure is reached [22,23]. are reduced in dimension and shifted in the direction of the max-
Further studies were aimed at generalizing the results that can imum compression stress, compared to Mohr’s circles neglecting
be obtained by performing the splitting test on cores with a rotated the confining effect [15]. However, what value of Poisson’s ratio,
mortar layer [14,15]. Indeed, by testing multiple cores with differ- that changes during compression test, should be used for assessing
ent mortar layer inclinations (e.g., 30°, 45° and 60°), different com- the confining effect of the mortar layer is still matter of
pression–shear stress states of the central mortar layer can be investigation.
defined. Once different compressions stress/shear stress coordi-
nates are available, the Mohr’s circles corresponding to the differ-
3. Materials and methods
ent inclinations can be defined and the interpolating failure
envelope can be determined [14]. In this way, it is in theory possi- In the present investigation, the following materials and methods were used.
ble to predict the masonry shear strength for each value of com-
pression stress, including the case when no compression stress is
present. 3.1. Bricks

When cores with the central mortar layer rotated by different Fired-clay solid bricks, having 25  12  5.5 cm3 nominal dimensions, were
inclinations are tested, the stress state in the center of the mortar used. The bricks were selected because of their relatively low mechanical proper-
layer is generally assumed as being shear-compression in the ties, suitably resembling the characteristics of bricks used in historical buildings.

Fig. 1. Masonry panels used for shear-compression test: (a) scheme of panel geometry and (b) photo of a panel at the end of construction.

Fig. 2. Masonry panel used for core-drilling: (a) scheme of panel geometry and core-drilling points and (b) photo of the panel at the end of construction.
424 C. Mazzotti et al. / Construction and Building Materials 54 (2014) 421–431

Fig. 3. Photos of (a) the masonry panel after rotation and (b, c) an example of cylindrical core.

Fig. 4. Shear-compression test: (a) scheme of the testing equipment; (b) photo of a panel ready for testing; (c) detail of the shear loading point and (d) detail of a LVDT used
for measuring horizontal displacement.

3.2. Mortar 3.3. Masonry samples

A ready-mixed lime-cement mortar (classified as M5 according to EN 998-2 In order to carry out a systematic comparison between masonry shear strength
[24]) was used. The mortar was selected because its binder/aggregate ratio (about measured with destructive techniques and from cores, nine masonry panels for
1:6 in weight) and the water/binder ratio recommended in the technical data sheet shear-compression test and one masonry panel for core-drilling were constructed,
(about 1.3 in weight) are such as to achieve poor mechanical properties, in agree- using bricks and mortar described above. All the panels were constructed on the
ment with mortar characteristics reported in the literature for historical buildings same day by expert workmanship, employing traditional construction techniques.
[25]. In particular, the bricks were immersed in water for 10 min before they were used

Fig. 5. Splitting test with mortar joint rotation: (a) core with 45° and (b) core with 15° rotation.
C. Mazzotti et al. / Construction and Building Materials 54 (2014) 421–431 425

for masonry construction, with the aim of avoiding that dry bricks absorb water
from the fresh mortar, thus significantly altering its water/binder ratio. After
10 min of immersion, the average brick water absorption was 13.9 wt%, which
was about 80% of the average water absorption after complete saturation, that is
17.9 wt%.

3.3.1. Masonry panels for direct-shear test


The nine panels had nominal dimensions 51.0  31.5  12.0 cm3
(length  height  thickness), corresponding to a two-brick length, five-brick
course height and one-leaf thickness, considering 10 mm thick nominal mortar
joints (Fig. 1a). The measured final thickness of the mortar joints actually ranged
between 10 and 15 mm. The dimensions of the panels were designed to fulfill the
requirements of EN 1052-3 [16]. For ensuring, during the tests, a good stress distri-
bution and a good contact between the panels and the platens of the loading ma-
chine used for applying compression load (cf. Section 3.4.2), two steel plates
(5 mm thickness) were placed under and above the masonry panels, a mortar layer
being inserted between the panel and the plates (Fig. 1b). The nine masonry panels
were cured under laboratory conditions (approximately 20 °C and 50% RH) for
28 days before testing.

3.3.2. Masonry panel for core-drilling


The tenth masonry panel was purposely constructed for core-drilling. The panel
had nominal dimensions 103  129  25 cm3 (length  height  thickness), corre-
sponding to a four-brick length, twenty-brick course height and two-leaf thickness,
considering 10 mm thick nominal mortar joints; it was constructed according to the
Ancient bond (Fig. 2a). Also in this case, the measured final thickness of the mortar
joint was between 10 and 15 mm. To facilitate the core-drilling operation, it was
planned to rotate the masonry panel by 90° before proceeding with the extraction
of cores. To avoid cracking, a pre-compression stress was applied to the panel be-
fore rotation. Once in the horizontal position (Fig. 3a), the wall was core-drilled
according to the scheme reported in Fig. 2a. Thirty-six identical cores (10 cm diam-
eter, 25 cm length), having a central diametric mortar layer only, were core-drilled
(Fig. 3b); in particular, each core was composed by a continuous element on one
side of the horizontal mortar layer and by two half elements on the opposite side
of the same layer, mutually facing a thin vertical mortar layer (Fig. 3c). The curing
conditions of the masonry panel, before core-drilling, and those of the cores, after
core-drilling, were exactly the same as those of the panel described in the previous
section. All the cores were tested 28 days after the construction of the original
panel.

3.4. Testing procedures

3.4.1. Bricks and mortar


The brick compressive strength (fbc) was measured according to European Stan-
dard EN 772-1 [26] on 6 cubic samples (50 mm side), obtained from 3 bricks by
sawing. The specimens were tested using an Amsler universal machine (load capac-
ity 120 kN), by loading them along the same direction as bricks are loaded inside
the walls.
The mortar flexural strength (fmf) and compressive strength (fmc) were mea-
sured according to EN 1015-11 [27] on 6 prismatic samples (40  40  160 mm3
– width  height  length), prepared during the construction of the masonry

Table 1
Results of brick and mortar mechanical characterization (fbc = brick compressive
strength; fmf = mortar flexural strength; fmc = mortar compressive strength;
C.o.V. = coefficient of variation). The values are averages for 6 samples.

Bricks Mortars Fig. 6. Graphs illustrating shear load against horizontal displacement of the nine
masonry panels, tested for different nominal compressive stress values: (a) 0.2 MPa,
fbc (MPa) C.o.V. (%) fmf (MPa) C.o.V. (%) fmc (MPa) C.o.V. (%) (b) 0.6 MPa and (c) 1.0 MPa.
19.3 6.1 2.8 6.7 7.8 5.1
panels. After curing for 28 days in a climatic chamber (20 °C and 98% RH), mortar
prisms were tested in flexure (three point bending) and compression using an Ams-
ler universal machine (load capacity 100 kN).
Table 2
Results of the shear-compression tests on the nine masonry panels (Fc = compression
load; Fv = shear load; A = cross section; rc = compressive stress; fv = shear stress). 3.4.2. Masonry panels
The nine masonry panels were subjected to shear-compression test according
2
Panel name Fc (kN) Fv (kN) A (mm ) rc (MPa) fv (MPa) to EN 1052-3 [16]. Compression axial load was applied and kept constant using a
P1 12.9 36.0 58812 0.22 0.31 Metrocom loading machine (maximum load 4000 kN); three specimens were tested
P2 16.1 49.4 58140 0.28 0.42 for each of the following compression axial stress values: 0.2 MPa, 0.6 MPa, 1.0 MPa,
P3 11.1 35.6 58928 0.19 0.30 according to cited standard. Shear load was applied by means of a purposely
P4 36.9 79.5 59787 0.62 0.66 designed loading equipment (Fig. 4a), composed of a ribbed steel plate (20 mm
P5 38.5 80.6 59160 0.65 0.68 thick) at one side of the specimen, two steel plates (20 mm thick) at the other side
P6 37.8 84.2 58075 0.65 0.73 of the specimen, four threaded steel rods (20 mm diameter) connecting the plates at
P7 61.0 115.9 58650 1.04 0.99 the two sides of the specimen and a hydraulic ram between the ribbed plate and the
P8 61.0 111.9 58650 1.04 0.95 masonry panel (Fig. 4b–c). The hydraulic ram was positioned so as to load exclu-
P9 59.9 95.6 58650 1.02 0.82 sively the central brick course, a 30 mm thick steel plate being inserted between
the ram and the brick to properly distribute the load (Fig. 4c). The two plates at
426 C. Mazzotti et al. / Construction and Building Materials 54 (2014) 421–431

the other side of the panel acted as contrasts, being anchored to the upper and low-
er brick courses and leaving the central course free to slip horizontally. The horizon-
tal displacement of the central brick course, with respect to the lower one, was
measured by means of two displacement transducers, one at each side of the panel
(Fig. 4d). The shear-compression test was articulated as follow: in the first phase
the compression axial stress was applied and kept constant at the prescribed level
then, in the second phase, the shear load was increased at a prescribed rate of
2 kN/s up to failure, due to relative slip of a brick course with respect to the others
(above and below).

3.4.3. Masonry cores


The masonry cores were subjected to splitting test using an Amsler universal
machine (load capacity 120 kN, adopted loading rate 0.2 kN/s). To apply the load
along two opposite longitudinal lines and prevent possible irregularities on core lat-
eral surface from causing stress accumulation, two wood stripes (5 mm thick,
15 mm width) were inserted between the loading platens and the cores (Fig. 5).
Twenty-two cores were tested in total. The cores were rotated so that the mortar
joint was inclined by the following angles, with respect to the horizontal reference:
0° (3 specimens), 15° (5 specimens), 30° (5 specimens), 40° (2 specimens), 45° (5
specimens), 50° (2 specimens).
Fig. 8. Graph illustrating shear strength against compressive stress of the nine
masonry panels: by linear regression, the masonry initial shear strength (fv0) and
4. Results and discussion the angle of internal friction (u) were obtained.

4.1. Bricks and mortar


have medium compressive strength (fbc = 19.3 MPa), which is
The results of brick and mortar mechanical characterization (at however significantly higher than that of mortar (fmc = 7.8 MPa).
the time of masonry panels testing) are reported in Table 1. Bricks Materials used for masonry panels construction hence proved to

Fig. 7. Photos of four representative masonry panels after shear-compression test at different nominal compressive stress: (P1 and P2) 0.2 MPa; (P4) 0.6 MPa and (P9)
1.0 MPa.
C. Mazzotti et al. / Construction and Building Materials 54 (2014) 421–431 427

be suitable for resembling bricks and mortar used in historical


buildings, where masonry shear strength is usually limited by shear
strength of mortar, which is the weakest constitutive material.

4.2. Masonry panels

The results of the shear-compression tests of the nine masonry


panels (labeled P1 to P9) are reported in Table 2; while the com-
pressive axial stress (rc) was computed according to the conven-
tional approach, the shear strength (fv) was calculated according
Fig. 9. Scheme illustrating how the compressive stress (fc) and shear stress (fv) have
to the formula:
been calculated, for different angles of mortar layer inclination (a), by dividing the
failure load (F) by the mortar layer area (A) and projecting along the directions
fv ¼ F v =2A ð1Þ
parallel and perpendicular to the mortar layer.
where Fv is the shear load and A is the cross section of the specimen;
introduction of twice the cross-section is necessary since the sliding According to the method described in EN 1052-4 [16] and by
brick course is supposed to have relative displacement with respect considering a Mohr–Coulomb failure criterion, from the results of
to both the lower and upper courses. The graphs showing the shear the shear-compression tests of the nine masonry panels the shear
load against the horizontal relative displacement are reported in strength without axial force (fvo) and the angle of internal friction
Fig. 6a–c, respectively for the three axial stress levels considered (u) of the masonry were derived. In particular, by plotting the
(in growing order). shear capacity fv of each panel as a function of the prescribed axial
In all the cases, failure occurred at the brick–mortar interface, as stress rc (Fig. 8) and then performing a linear regression of the
bricks slid over the mortar layer, while no horizontal cracking corresponding points, the following results were obtained:
within the mortar layer or in the bricks occurred. In most cases, fvo = 0.20 MPa and u = 36°. The correlation index R2 = 0.95 is very
the central brick course slid horizontally with respect to the adja- high, confirming the good quality and repeatability of results.
cent mortar layers (P1 in Fig. 7), but in some cases the mortar lay-
ers slid together with the central brick course (P2 in Fig. 7). In 4.3. Masonry cores
almost all the cases, independently of the compression level, the
mortar joints adjacent to the central brick course were affected The results of the splitting tests on cores with different mortar
by vertical cracks that crossed the mortar layer, so that the loss layer inclinations are reported in Table 3, where the axial stress at
of adhesion between bricks and mortar started at one interface failure rc and the shear capacity fv have been calculated according
of the mortar layer (e.g. the lower interface), then a vertical crack to the formulas:
formed across the mortar and the loss of adhesion continued on rc ¼ ðF=AÞ  cos a ð2Þ
the other interface of the mortar layer (e.g. the upper interface)
(P1, P4 and P9 in Fig. 7).
fv ¼ ðF=AÞ  sin a; ð3Þ
In the case of P1, after the first horizontal displacement of the
central brick course, an increase of the compression load was reg- where F is the failure load, A is the area of the mortar layer and a is
istered, which caused a corresponding increase of the shear load. the mortar layer inclination, with respect to the horizontal reference
However, for evaluating the shear resistance of the panel, the com- (Fig. 9). The proposed approach derives from some simple hypothe-
pression and shear loads corresponding to the first horizontal dis- ses: (a) the failure mode is supposed to be a sliding movement at
placement only were considered (Table 2). the brick-mortar interface, (b) the applied concentrated force F can

Table 3
Results of splitting tests on cores with different mortar layer inclination (F = failure load; A = mortar layer area; rc = compressive stress; fv = shear stress).

Mortar layer rotation Core name F (kN) A (mm2) rc (MPa) fv (MPa) Failure mode
0° C1 41.0 23,655 – – Splitting
C2 48.0 23,406 – – Splitting
C3 55.6 23,250 – – Splitting
15° C4 50.0 23,688 2.04 0.55 Splitting (+sliding)
C5 48.8 23,406 2.01 0.54 Splitting
C6 47.5 23,250 1.97 0.53 Splitting
C7 40.0 23,312 1.66 0.44 Splitting
C8 48.5 23,312 2.01 0.54 Splitting
30° C9 44.0 23,312 1.63 0.94 Sliding
C10 45.0 23,312 1.67 0.97 Splitting (+sliding)
C11 41.5 23,655 1.52 0.88 Splitting (+sliding)
C12 34.5 23,406 1.28 0.74 Splitting (+sliding)
C13 53.5 23,064 2.01 1.16 Splitting (+sliding)
40° C14 50.7 23,360 1.66 1.40 Sliding (+splitting)
C15 47.3 22,506 1.61 1.35 Sliding (+splitting)
45° C16 31.8 23,406 0.96 0.96 Splitting
C17 23.8 23,218 0.72 0.72 Sliding (+splitting)
C18 33.0 23,500 0.99 0.99 Sliding
C19 35.0 23,406 1.06 1.06 Sliding
C20 27.0 23,406 0.82 0.82 Sliding (+splitting)
50° C21 12.7 23,406 0.35 0.42 Sliding
C22 11.5 23,406 0.32 0.38 Sliding
428 C. Mazzotti et al. / Construction and Building Materials 54 (2014) 421–431

Fig. 10. Photos of six representative cores (one for each mortar layer inclination), where different failure modes can be observed: splitting is the essential failure
mechanism for cores tested with mortar layer inclinations of 0°, 15° and 30°, while sliding becomes significant and progressively predominant for cores tested at 40°, 45°
and 50°.
C. Mazzotti et al. / Construction and Building Materials 54 (2014) 421–431 429

be uniformly distributed along the whole interface, (c) the obtained


stresses do not describe the internal state of stress of the mortar but
they are strictly related and applied to the interface.
As reported in Table 3 and shown in Fig. 10 (where a represen-
tative case for each mortar layer inclination is illustrated), cores
tested with increasing inclination exhibited a progressive decrease
in the failure load and a modification in the failure mode. In partic-
ular, as far cores tested at 0°, 15° and 30° are concerned, a reduc-
tion of the average failure load from 48.2 kN to 43.7 kN was
observed. As a consequence of the increasing mortar layer rotation,
compressive and shear stress components at failure were modified
as well: shear stress, which is absent in the case of 0° rotation, in-
creased to 0.52 MPa and 0.94 MPa for inclinations of 15° and 30°;
correspondingly, compressive stress decreased from 2.06 MPa for
0° rotation to 1.94 MPa and 1.62 MPa for 15° and 30° rotations.
All the cores tested with the horizontal mortar layer exhibited a
typical splitting failure mode (vertical crack), as expected in the Fig. 12. Graph illustrating the mean values of shear strength and compressive
case of a standard tensile splitting test (Fig. 10). Because of the stress of cores tested with mortar layer inclinations of 40°, 45° and 50°: by linear
increasing mortar layer rotation, cores tested with a = 15° and regression, the masonry initial shear strength (fv0) and the angle of internal friction
30° exhibited a progressive modification of the failure mode to- (u) were obtained.

wards sliding, even though splitting remained the main failure


mechanism. As illustrated in Fig. 10, cores tested at 15° and, to a masonry panels. Since the stress components in this case are not
larger extent, at 30° exhibited, on the one side of the core, a partial independent but come from the projection of a unique force onto
sliding at the brick-mortar interface, and, at the opposite side of an inclined plane and onto its normal, all data coming from speci-
the core, a semi-vertical crack, typical of the splitting failure mode. mens tested according to the same inclination of the mortar layer
This type of failure has been classified as mix-mode failure. belong to the same straight line (dashed lines in Fig. 11); this
As mortar layer inclination increases to 40°, 45° and 50°, the means that the ratio s/r would be constant for all these points
shear stress component becomes progressively predominant over and it also represents the angle of rotation of the mortar layer.
the compression one (Table 3). It is noteworthy that the average The data points corresponding to cores tested according to an
failure load at 40° (49.0 kN) is higher than that at 30° (43.7 kN), inclination of 50°, 45° and 40° exhibit a progressive increase of
so that also the resulting compressive and shear stress components both shear and compression components, while cores tested at
are higher at 40° (1.64 and 1.37 MPa, respectively) than at 30° 30° and 15° layer inclination exhibit only a slight increase in com-
(1.62 and 0.94 MPa, respectively). This is due to the different fail- pression stress, together with a decrease in shear stress. This is the
ure mechanisms leading to crisis in the two cases: while for mortar direct consequence of the different failure mode (splitting instead
layer rotation of 30° the failure mode is mainly splitting, which in- of sliding). Because of the different failure mechanism, cores tested
volves tensile strength of materials, for cores tested at 40° sliding at 30° and 15° layer inclination were considered as not fully signif-
at the interface level is predominant (Fig. 10). As mortar layer is icant for evaluating masonry shear resistance. Indeed, since failure
further rotated, the failure load progressively decreases, while occurs because of brick and mortar splitting, as a consequence of
the shear component equals the compression one at 45° and then the tensile stresses that arise in the materials, no significant infor-
becomes predominant at 50° (Table 3). All these cases presented a mation can be obtained about the shear strength of the brick-mor-
failure mode characterized by the sliding of most of the brick-mor- tar interface or of the mortar layer itself. For this reason, to
tar interface, as observed during the shear-compression tests on determine masonry shear strength, in the present work only cores
masonry panels. tested with 40°, 45° and 50° mortar layer inclination were taken
For every test, the corresponding axial and shear stresses at fail- into account. In particular, the mean value for every considered
ure were reported in the r–s plane (Fig. 11), as already done for angle was reported in Fig. 12 and a best fit procedure allowed to

Fig. 11. Graph illustrating shear strength against compressive stress of the twenty-
two cores: points corresponding to different mortar layer inclinations a are aligned Fig. 13. Graph illustrating the match between results obtained from reference
along straight lines, whose slope corresponds to the tangent of a. panels and cores.
430 C. Mazzotti et al. / Construction and Building Materials 54 (2014) 421–431

From the experience gained from the present experimental


campaign, some important remarks can be done, to be carefully
considered for further applications:

(i) Since all the cores tested for a given mortar layer rotation a
are aligned along a straight line (on the r–s plane), that has
a slope corresponding to tan a and crosses the origin, at least
three different mortar layer inclinations should be consid-
ered and tested, so that the corresponding points on the
r–s plane cover a sufficient range of compression and shear
stress;
(ii) In order to ensure that results are statistically significant,
several cores should be tested for each mortar layer rotation,
so that the natural scattering of results could be controlled;
moreover, only the mean values for each inclination should
be used.
Fig. 14. Scheme and detail photo illustrating the possible failure mode, character- (iii) Since masonries subjected to shear loads may exhibit differ-
ized by brick wedge detachment, occurring for 60° rotation. ent failure modes (i.e., sliding at the brick-mortar interface,
cracking and sliding within the mortar layer or cracking of
the bricks), further experimental studies in laboratory condi-
obtain the governing parameters of the Mohr–Coulomb failure tions seem necessary to evaluate whether different failure
criterion, namely fv0 = 0.18 MPa and u = 37°. The obtained mechanisms may influence the capability of the proposed
values exhibit a very good agreement with those determined from methodology to suitably predict masonry shear resistance.
the masonry panels through direct compression–shear tests
(Fig. 13). 5. Conclusions
In the light of the results coming from the best fit process, the
suitability of taking into account only cores tested at 50°, 45° and In the present study, the suitability of using results obtained
40° is confirmed and circumstantiated by the following consider- from splitting tests on cores with an inclined mortar layer for
ations. For each mortar layer inclination a, the points in the r–s determining masonry shear strength was evaluated. In this frame-
plot are aligned along a straight line r, whose slope corresponds work, the Mohr–Coulomb failure criterion was considered as a cri-
to the tangent of a (Fig. 11). This line r intersects the Mohr–Cou- terion able to describe the shear failure of the masonry, which
lomb failure criterion calibrated with data coming from direct would be then characterized by the initial shear strength without
shear-compression tests on masonry panels (taken as reference) axial stress fv0 and by the angle of internal friction u. Reference
in one point, near which the data points corresponding to cores values of these parameters were obtained by subjecting reference
tested for that mortar layer inclination a are expected to be found masonry panels to shear-compression test, according to EN 1052-
(Fig. 13). As the mortar layer inclination a decreases, the intersec- 4 [16]; at the same time, a number of masonry cores were tested
tion point has r–s coordinates that become higher and higher, un- with mortar layer inclinations of 40°, 45° and 50°. By plotting shear
til the limit angle of mortar layer inclination a0 = u is reached. For stress against compression stress for each tested core and then per-
this limit case, no intersection point exists, since the mortar layer forming a linear regression, the initial shear strength and the angle
inclination line and the Mohr–Coulomb failure criterion line com- of internal friction of the masonry were derived. A very good agree-
ing from the panels are parallel. In the present study, the angle of ment between results obtained from the reference masonry walls
internal friction found by shear-compression tests on masonry and those obtained from the cores was found, which suggests that
panels is u = 36° (Fig. 8). Therefore, no cores tested with a mortar the proposed methodology is a very promising technique for
layer inclination a lower than 36° can be useful for evaluating ma- assessing masonry shear strength by means of moderately destruc-
sonry shear resistance, as the corresponding r–s coordinates do tive testing.
not intersect the failure line of the panels. In the light of the above As masonries subjected to shear loads may experience different
reported considerations, the opportunity of not taking into account failure modes, depending on the mechanical characteristics of the
results obtained for cores tested at 30° and 15° layer inclination, bricks and mortar, as well as on the adhesion at the brick-mortar
after the failure mode remarks (splitting in place of sliding), is con- interface, further experimental studies employing different consti-
firmed also in terms of mechanical aspects. As a general remark, tuting materials seem necessary, to evaluate whether different fail-
based also on other similar on-site experiences not reported here, ure mechanisms may influence the suitability of the proposed
a minimum mortar layer inclination of 40° is always suggested. As methodology. Such work is currently in progress.
for the upper limit, tests with a mortar layer inclination larger than
60° exhibited a failure mode driven by the detachment of a brick Acknowledgements
wedge just below the strip where the force was applied, more than
due to sliding (Fig. 14). With so large inclination, in fact, forces are The financial support of Emilia-Romagna Region (POR-FESR
applied very near to the edges of the bricks portions, producing funds) is gratefully acknowledged. The technicians of the Labora-
strong localization of stresses. tory of Structural and Geotechnical Engineering (LISG), especially
More complex, and out of the scope of the present paper, is the Mr. Davide Betti, are gratefully acknowledged for collaboration.
definition of a suitable range of mortar layer inclinations for those
methods [13–15] that propose using force values obtained from References
cores tested at various inclinations (including mortar compressive
strength, i.e. 0°) to define shear/axial compression stresses inside [1] Grasso S, Maugeri M. The road map for seismic risk analysis in a mediterranean
the mortar layer along different orientations; in those cases, the city. Soil Dyn Earthq Eng 2009;29(6):1034–45.
[2] Casolo S, Miliani G, Uva G, Alessandrini C. Comparative seismic vulnerability
corresponding Mohr’s circles can then be used to derive a general analysis on ten masonry towers in the coastal po valley in Italy. Eng Struct
linear or non-linear failure envelope. 2013;49:465–90.
C. Mazzotti et al. / Construction and Building Materials 54 (2014) 421–431 431

[3] Lourenço PB, Roque JA. Simplified indexes for the seismic vulnerability of [16] EN 1052-4, Methods of test for masonry – Part 4: determination of shear
ancient masonry buildings. Const Build Mater 2006;20:200–8. strength including damp proof course; 2001.
[4] Mallardo V, Malvezzi R, Milani E, Milani G. Seismic vulnerability of historical [17] ASTM E519/519M-10, Standard test method for diagonal tension (shear) in
masonry buildings: a case study in Ferrara. Eng Struct 2008;30:2223–41. masonry assemblages; 2010.
[5] Augusti G, Ciompoli M, Giovenale P. Seismic vulnerability of monumental [18] Alecci V, Fagone M, Rotunno T, De Stefano M. Shear strength of brick masonry
buildings. Struct Saf 2001;23:253–74. walls assembled with different types of mortar. Const Build Mater
[6] Binda L, Saisi A, Tiraboschi C. Investigation procedures for the diagnosis of 2013;40:1038–45.
historic masonries. Const Build Mater 2000;14:199–233. [19] EN 1052-3, Methods of test for masonry – Part 3: determination of initial shear
[7] Corradi M, Borri A, Vignoli A. Experimental study on the determination of strength; 2007.
strength of masonry walls. Const Build Mater 2003;17:325–37. [20] Gentilini C, Franzoni E, Bandini S, Nobile L. Effect of salt crystallization on the
[8] Brencich A, Sabia D. Experimental identification of a multi-span masonry shear behaviour of masonry walls: an experimental study. Const Build Mater
bridge: the tanaro bridge. Const Build Mater 2008;22:2087–99. 2012;37:181–9.
[9] Sassoni E, Mazzotti C. The use of small diameter cores for assessing the [21] ASTM C1531-09, Standard test method for in situ measurement of masonry
compressive strength of clay brick masonries. J Cult Herit 2013;14S:e95–e101. mortar shear strength index; 2009.
[10] Sassoni E, Mazzotti C, Pagliai G, Comparison between experimental methods [22] Braga F, Dolce M, Masi A. Interpretazione statistica di prove sperimentali per
for evaluating the compressive strength of existing masonry buildings, l’accertamento della resistenza a taglio della muratura di edifici esistenti, 6°
submitted to Materials and Structures. Convegno Nazionale ‘‘L’ingegneria sismica in Italia’’; Perugia (Italy); 13–15
[11] Eurocode 6, UNI ENV 1996-1-1, Design of masonry structures – Part 1-1: Ottobre 1993 [in Italian].
General rules for buildings – rules for reinforced and unreinforced masonry; [23] Filardi B, Liberatore D. Una nuova prova di carico per determinare la resistenza
1998. a taglio della muratura: modellazione e analisi parametrica, Atti del Convegno
[12] D.M. 14/01/2008 (Decreto del Ministero delle Infrastrutture 14 gennaio 2008), Nazionale ‘‘La meccanica della muratura tra teoria e progetto’’, Messina (Italy);
Approvazione delle nuove norme tecniche per le costruzioni; 2008 [in Italian]. 18–20 Settembre 1996 [in Italian].
[13] Benedetti A, Pelà L, Aprile A. Masonry properties determination via splitting [24] EN 998-2, Specification for mortar for masonry – Part 2: masonry mortar;
tests on cores with a rotated mortar layer. In: Proceedings of ‘‘8th international 2010.
seminar on structural masonry’’, Istanbul (Turkey); 5–7 November 2008. [25] Augenti N. Il calcolo sismico degli edifici in muratura, UTET, Torino; 2004 [in
[14] Benedetti A, Pelà L. Experimental characterization of mortar by testing on Italian].
small specimens. In: Proceedings of ‘‘15th international brick and block [26] EN 772-1, Methods of test for masonry units - determination of compressive
masonry conference’’, Florianòpolis (Brazil); 13–16 May 2012. strength; 2002.
[15] Pelà L, Benedetti A, Marastoni D. Interpretation of experimental tests on small [27] EN 1015-11, Methods of test for mortar for masonry – Part 11: determination
specimens of historical mortars. In: Proceedings of 8th international of flexural and compressive strength of hardened mortar; 2007.
conference on structural analysis of historical construction, Wroclaw
(Poland); 15–17 October 2012.

You might also like