EDWARDS SYSTEMS TECHNOLOGY

TM INTERNATIONAL NOTIFICATION APPLIANCES

Genesis Speakers and Strobes


Genesis G4 Series

Features Multi-
la!
„ Unique low-profile design Cande
*
– The most compact UL/ULC listed speaker-strobe available
– Ultra-slim, protrudes a mere one inch from the wall
– Attractive appearance, no visible mounting screws
„ Field configurable – no need to remove the device!
– Select ¼, ½, 1, or 2 watt operation and 15, 30, 75, or 110 *
MEA
candela output with convenient switches that remain
visible even after the unit is installed
„ Unparalleled performance
– loud 90 dBA output ensures clear, crisp audio Patents pending
– Exclusive FullLight™ strobe technology produces the industry’s * Pending
most even light distribution
– Precision timing electronics meet tough new synchronizing
standards for strobes when used with compatibile modules STROBES: Thanks to patented breakthrough technology, Genesis
– Low current draw minimizes system overhead strobes do not require bulky specular reflectors. Instead, an
– Highly regulated in-rush current allows the maximum exclusive mask-and-cavity design channels and conditions light to
number of strobes on a circuit produce a highly controllable distribution pattern. Intensive
– Industry's first temporal strobe output development efforts employing this new technology have given
– 25 VRMS and 70 VRMS models available, all supplied with a DC rise to a new benchmark in strobe performance – FullLight™
blocking capacitor for audio circuit supervision technology.

„ Easy to install FullLight strobe technology produces a smooth light distribution


– Fits all standard 4" square electrical boxes with plenty of pattern without the spikes and voids characteristic of specular
room behind the signal for extra wire – no extension ring or reflectors. This ensures the entire coverage area receives consis-
trim plate needed tent illumination from the strobe flash.
– Simple jumper snips set strobe flash rates All Genesis strobes self-synchronize when installed with the
– #18 - #12 AWG terminals – ideal for long runs, existing wiring Genesis Signal Master or SIGA-CC1S module. Strobe flashes from
„ Approved for public and private mode applications devices on the same circuit synchronize to within 10 milliseconds
UL 1971-listed as signaling devices for the hearing impaired and of each other indefinitely. This exceeds the revised UL standards in
UL 1638-listed as protective visual signaling appliances effect as of November, 2000, which specify this level of synchroni-
zation over only two hours.
Speaker-strobes feature 15, 30, 75 or 110 candela output,
Description selectable with a conveniently-located switch on the bottom of the
The Genesis line of signals are the smallest, most compact device. The candela setting remains clearly visible even after final
audible-visible emergency signaling devices in the world. Protrud- installation.
ing no more than one inch from the wall, Genesis speakers and SPEAKERS: All Genesis speakers include a DC
speaker-strobes blend with any decor. blocking capacitor to allow electrical supervision
Signals feature textured housings in architecturally neutral white or of the audio distribution circuit. Models for 25
traditional fire alarm red. An ingenious iconographic symbol VRMS and 70 VRMS circuits are available. The mylar
indicates the purpose of the device. This universal symbol is code- speaker with its sealed back construction pro-
compliant and is easily recognized by all building occupants vides extra durability and improved audibility.
regardless of what language they speak. Speaker-only ¼ W to 2 W operation is selectable with a
unit conveniently-located switch on the bottom of the
Genesis devices are fully compatible with Enhanced Integrity device. The wattage tap setting remains clearly
signals. The two product lines may be mixed on the same circuit. visible even after final installation.

EST I NTERNATIONAL
201 CITY CENTRE DRIVE SUITE 500, MISSISSAUGA, ONTARIO, CANADA L5B 2T4
PHONE : (001) 905-270-1711 • FAX: (001) 905-270-9553 • WORLD WIDE WEB: WWW.ESTINTERNATIONAL .COM
U.S. SALES: SARASOTA, FL 941-739-4638; FAX 941-727-1214 • CANADA SALES: OWEN SOUND, ON; PHONE 519-376-2430; FAX 519-376-7258
Issue 3 Literature Sheet #85001-0549 Page 1 of 4
Not to be used for installation purposes.
Speaker Application Non-Sleeping Rooms and Corridors: Genesis strobes rated at less
than 110 cd per UL 1971 are intended for use in non-sleeping areas
The suggested sound pressure level for each signaling zone used only. Install with the bottom of the device at least 80 inches (2.0 m)
with alert or alarm signals is a minimum of 15 dB above the and no more than 96 inches (2.4 m) above the finished floor. No point
average ambient sound level or 5 dB above the maximum sound in any space (including corridors) required to have strobes should
level having a duration of at least 60 seconds, whichever is greater. be more than 50 feet (15.2 m) from the signal (in the horizontal
This is measured 5 feet (1.5 m) above the floor. The average plane).
ambient sound level is the
RMS, A-weighted sound Typical Sound Output In large rooms or spaces (such as auditoriums) that exceed
Distribution dBA 100 feet (30.4 m) across and without obstructions more than 72
pressure measured over a
Measured in anechoic chamber inches (1.8 m) above the finished floor, strobes may be placed
24-hour period. at two watts
around the perimeter, spaced a maximum of 100 feet (30.4 m)
Doubling the distance from apart. This is an alternative to suspending strobes from the ceiling.
the signal to the ear will 96 90 0°

theoretically cause a 6dB 5ft (1.5m) For detailed spacing requirements, consult The Handbook of
reduction in the received Radius Visible Notification Appliances for Fire Alarm Applications
sound pressure level. The published by EST Press, or contact your local EST representative.
10ft (3.05m)
actual effect depends on the 93 Radius
Sleeping rooms: Genesis 110 cd strobes are intended for use in
acoustic properties of 90
sleeping rooms and should be installed along with a smoke
89
88
materials in the space. detector. It must be wall mounted at least 80" (2.03m) above floor
Doubling the power output level, but no closer than 24" (610mm) to the ceiling. The distance
87
of a device (e.g.: a speaker from the strobe to the pillow must not exceed 16' (4.8m).
from 1W to 2W) will increase 84
the sound pressure level by Sleeping Rooms EST wall mounted strobe
83
3dBA. A 3dBA difference 82
90° 75° 60° 45° Any size 110 cd within 16 feet of pillow
represents a barely notice- Genesis Series Cone Speaker/strobe
able change in volume.
Application Notes - USA
Audible signals in the public mode should never have a sound level
Strobe Application less than 75 dBA at 10' (3 m) per NFPA 72. Signals cannot exceed 120
dBA per ADA (130 dBA per NFPA 72) at the minimum hearing
Genesis strobes are UL 1971-listed for use indoors as wall-
distance to audible appliance.
mounted public-mode notification appliances for the hearing
impaired. Prevailing codes require strobes to be used where Strobe and combination speaker/strobe devices should be installed
ambient noise conditions exceed 105 dBA (87dBA in Canada), with the bottom of the device at least 80 inches (2.0 m) and no more
where occupants use hearing protection, and in areas of public than 96 inches (2.4 m) above the finished floor. Speakers should be
accommodation as defined in the Americans with Disabilities Act installed with their tops not less than 6 inches (152 mm) below the
(see application notes – USA). ceiling and not less than 90 inches (2.3 m) above the finished floor.
Genesis strobes are synchronized and UL-listed for use in both Strobes must be used to supplement audible signals wherever the
sleeping and non-sleeping areas. They are intended for indoor average ambient sound level exceeds 105 dBA. Combination
wall-mount applications only. Combination speaker-strobe signals audible/visual signals must be installed in accordance with NFPA
must be installed in accordance with guidelines established for guidelines established for strobes.
strobe devices.
ADA requires visible signals in the following areas:
Strobe Spacing • rest rooms, meeting rooms, and other common use areas.
The following guidelines are based on ANSI/NFPA 72 National Fire • sleeping rooms intended for use by persons with hearing
Alarm Code (1999). When applied and installed in accordance with impairment (in accordance with Title 1 of ADA).
that code, Genesis strobes meet or exceed the illumination • work areas used by a person with a hearing impairment (per
produced by the ADA-specified 75 candela (cd) strobe at 50 feet.* Title 1 of ADA).

Non-Sleeping Rooms EST wall mounted strobes*


Application Notes - Canada
Up to 20' x 20' (6.1 m x 6.1 m) One 15 cd strobe
(Based in part on 1995 Canada National Building Code)
Up to 30' x 30' (9.1 m x 9.1 m) One 30 cd or two 15 cd strobes
The fire alarm signal sound pressure level shall not exceed
Up to 40' x 40' (12.2 m x 12.2 m) One 75 cd or two 30 cd strobes 110 dBA in any normally occupied area. The sound pressure
Up to 50' x 50' (15.2 m x 15.2 m) One 110 cd or two 75 cd strobes level from an audible signal in a floor area used for occupancies
other than residential occupancies shall not be less than 10 dBA
Corridors
above ambient levels, and never less than 65 dBA. In sleeping
15 cd strobes spaced at 100' rooms the sound pressure level from an audible signal shall not
Any length. (30.5 m) max. Strobes must be be less than 75dBA when any intervening doors between the
Maximum width: 20' (6.1m). placed within 15' (4.5m) of each device and the sleeping room are closed. Audible signal devices
end of the corridor. shall be installed not less than 1.8 m to the center of the device
* ADA suggests using 75 cd strobes throughout an area, with spacing that never above the floor (per CAN/ULC S524).
exceeds 50ft from the strobe to any point in the protected space.

EST I NTERNATIONAL
Page 2 of 4 Literature Sheet #85001-0549 Issue 3
Not to be used for installation purposes.
The fire alarm audible signal shall be supplemented by fire alarm occupancies in which music and other sounds associated with
strobes in any floor area where the ambient noise level exceeds 87 performances could exceed 100 dBA. Strobes shall be installed in a
dBA, or where the occupants of the floor area use ear protective building so that the flash from one device is visible throughout the
devices, are located within an audiometric booth, or are located floor area or portion thereof in which they are installed. For
within sound insulating enclosures. This also applies to assembly maximum safety, EST recommends that strobes be installed as per
the guidelines shown here under Strobe Spacing.

Specifications
Genesis Speakers and Speaker-Strobes
Red or white textured UV stabilized, color impregnated engineered plastic.
Housing
Exceeds 94V-0 UL flammability rating.
Dimensions Height: 6.5" (165 mm). Width: 5" (127 mm). Depth to wall: 1" (25 mm).
Mounting Flush: North-American 4" square box, 2 1/8" (54 mm) deep.
(indoor wall mount only) Surface: model G4B (white) or G4RB (red) surface mount box.
Screw terminals: separate polarized inputs for speaker and strobe,
Wire Connections
#18 to #12 AWG (0.75 mm² to 2.5 mm²) wire size
Operating environment 32-120° F (0-49° C) ambient temperature; 0-93% relative humidity.
UL 1971, UL 1638, UL 1480, ULC S526, ULC S541, CSFM, (FM and MEA pending)
Agency Listings
(All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule.)

Speakers
Input/Operating Volts 25 VRMS or 70 VRMS. See ordering information.
Speaker Taps/Output* 2 W = 90 dBA; 1 W = 87 dBA; ½ W = 84 dBA; ¼ W = 81 dBA
Speaker frequency response: 250 to 5,000 Hz. Optimized for voice intelligibility.
Speaker Cone 4-inch (102mm) mylar cone, sealed back construction, rated for 8 watts, 8 ohm voice coil.

Strobes
Strobe output rating UL 1971, UL 1638, ULC S526: 15 cd, 30 cd, 60 cd, 75 cd or 110 cd
Strobe Operating Voltage 20 to 31 Vdc (continuous). 20 - 27 Vdc FWR (full wave rectified).
Strobe Flash Rate One flash per second.
All strobes: one flash per second (fps) within 200 milliseconds over 30 minutes on common circuit.
Strobe Flash Synchronization With optional synchronization module: one fps within 10 milliseconds indefinitely (exceeds UL 1971).
Temporal setting (private mode only): synchronized to temporal output on the same circuit.
Compatible Synchronization
G1M-RM, SIGA-CC1S, SIGA-MCC1S
Modules
Flash tube enclosure Clear polycarbonate
* Measured in reverberation room using 400-4,000 Hz band limited pink noise per UL 1480.

Strobe Operating Current Light output


Mean (rms) (per cent of UL rating versus angle)
Candela
15 30 75 110 % Of Candela H Spec.
rating % Of Candela V Spec.
0
20 Vdc 65 (78) 93 (101) 182 (188) 238 (245) -20
-15 -10
-5 5 10 15
20
-25 25
24 Vdc 55 (65) 78 (86) 153 (159) 196 (203) -35
-30 30
35
-40 40
31 Vdc 45 (53) 63 (69) 120 (124) 151 (157) -45 45
-50 50
20 Vfwr 56 (106) 79 (147) 147 (264) 197 (342) -55 55
-60 60
24 Vfwr 50 (95) 68 (130) 121 (225) 155 (283) -65 65

27 Vfwr 44 (84) 60 (115) 107 (200) 137 (251) -70 70

-75 75

-80 80

-85 85

-90 90
0
0
90

90
80

50

50

80
70

40

30

20

10

10

20

30

40

70
100

100
60

60
95

85

75

65

55

45

35

25

15

15

25

35

45

55

65

75

85

95

Minium UL required candela light output

EST I NTERNATIONAL
Issue 3 Literature Sheet #85001-0549 Page 3 of 4
Not to be used for installation purposes.
Installation and Mounting Wiring
All models are intended for indoor wall mounted applications only. Field wiring is connected to Genesis signals with terminals that
Speakers and speaker-strobes are flush mounted to a North- accommodate #18 to #12 AWG (0.75 mm² to 2.5 mm²) wiring.
American 4" square electrical box, 21/8" (54 mm) deep or a Euro- Speaker-only Wiriing
pean 100 mm square box. Signals may be surface mounted to a To listed fire alarm control panel
(supervised amplifier signal circuit
Genesis surface-mount box (see ordering information for details). – 25.2 or 70.7V rms) + +
Two tabs at the top of the signal unlock the cover to facilitate
mounting. The shallow depth of Genesis devices leaves ample
room behind the signal for extra wiring. Once installed with the Polarity shown in To next device
cover in place, no mounting screws are visible. alarm condition or end of line
device

SPKR
C
S+
S-
SPKR
C
S+
S-
Standard electric box
S S
2.
(54 125"
mm
m) )
Speaker-Strobe Wiring
7m
(12
5"
To listed fire alarm control panel
(supervised amplifier signal circuit
– 25.2 or 70.7V rms) + +
To listed fire alarm control panel
(supervised signal circuit
– 20-24 Vdc) + +
Grounding plate
Polarity shown in To next device
alarm condition or end of line
6.5" (165 mm)

device

SPKR
C
S+
S-

SPKR
C
S+
S-
S S
Optional Color-matched
Surface mount box

EST recommends that these fire alarm speaker-strobes always be Ordering Information
installed in accordance with the latest recognized edition of national
and local fire alarm codes. Catalog Number Ship Wt.
Description
White Red lbs (kg)

Field Configuration Speakers and Speaker-Strobes


Genesis speakers may be set for ¼, ½, 1, or 2 watt operation. The G4-S2 G4R-S225 Volt Speaker
wattage setting is visible through a small window on the bottom of
25 Volt Speaker-strobe with
the device and is changed by simply sliding the switch until the
G4-S2VM G4R-S2VM selectable 15, 30, 75, or
desired setting appears in the window. The speaker does not have
110 cd output 1.5
to be removed to change the wattage.
G4-S7 G4R-S7 70 Volt Speaker (0.68)
Genesis speaker-strobes may be set for 15, 30, 75, or 110 candela 70 Volt Speaker with
output. The output setting is visible through a small window on the G4-S7VM G4R-S7VM selectable 15, 30, 75, or
bottom of the device and is changed by simply sliding the switch 110 cd output
until the desired setting appears in the window. The speaker-
strobe does not have to be removed to change the output. Accessories
Synchronization Output 0.1
Use the Candela Switch and the To change strobe to temporal G1M-RM
Wattage switch to set desired operation. (private mode) cut JP1 Module (1-gang) (0.5)
Intelligent Synchronization 0.5
SIGA-CC1S
Output Module (2-gang) (0.23)
JP1

Synchronization Output 0.18


SIGA-MCC1S
15

Module (Plug-in UIO) (0.08)


Bottom View
Candela switch Wattage switch 0.7
G4B G4RB Surface mount box
(0.32)

Genesis speaker-strobes may also be configured for temporal


flash. This battery-saving feature is intended for private mode Housings available with “FIRE” markings
signaling only. To set the device for temporal flash, snip the circuit To specify housings with “FIRE” markings,
board as shown in the Jumper Locations diagram above. insert an “F” before the hyphen in the model
WARNING: These devices will not operate without electrical power. As fires frequently cause number.
power interruptions, we suggest you discuss further safeguards with your local fire protec-
tion specialist. Research indicates that the intensity of strobe needed to awaken 90% of Add an “F” here
sleeping persons is approximately 100 cd. EST recommends that strobes in sleeping rooms
be set to 110 cd minimum. G4 F -S2
Genesis and FullLight Strobe Technology are trademarks of Edwards Systems G4R F -S7VM
Technology, Inc.

EST I NTERNATIONAL
It is our intention to keep the product information current and accurate. We can not cover specific applications or anticipate all requirements.
All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact EST International.
Printed in Canada
© 2002 EST
Page 4 of 4 Literature Sheet #85001-0549 Issue 3
Not to be used for installation purposes.