You are on page 1of 2

MFM376-230V Multifunction Meter

Features:
! 3 Ø (True rms) Voltage
! 3 Ø (True rms) Current
! 3 Ø Power Factor
! 3 Ø Power (Active, Reactive, Apparent)
! Energy (Active, Reactive, Apparent)
! Frequency
! Programmable CT/PT Primary/Secondary
! Single Pulse Output
Size: 96mm x 96mm (1/4 DIN)

Technical Specifications

Display Supply Specifications

Display 3 rows, 7 segment LED Auxiliary Supply 240V AC (±20%), 50-60Hz


Digit 4 VA Rating <8VA

Resettable Parameters
Input Specifications
C.T Primary 1A/5A to 10,000A (Programmable for
Electrical Connection 3Ø-3/4 wire, 1Ø-2 wire, 2Ø-3 wire
any value)
Input Voltage Range 11 to 300V AC, (Phase to Neutral)
C.T Secondary 1A/5A programmable
19 to 519V AC, (Phase to Phase)
P.T Primary 100V to 500kV (Programmable for any value)
Input Current Range Nominal 5A AC (Min-14mA, Max-6A)
P.T Secondary 100V to 500V (Programmable for any
Frequency 45Hz - 65Hz
value)
Power Consumption <8VA
Display Reset Programmable
(for energy, Auxiliary interrupt, Run hour) Environmental Specifications

Temperature Operating: -100 to +550C


Resolution For energy: 0.01k, 0.1k, 1k, 0.01M, 0.1M, 1M Storage: -200 to +750C
(depending upon CT ratio X PT ratio) Humidity (non-condensing) Upto 85% RH
For Power, Voltage,
Current: Auto resolution
For Power factor: 0.001 Mechanical Specifications
Accuracy Voltage (L-N / L-L), Current: ±0.5% of F.S
Power factor: ±0.01 Mounting Panel mount
Frequency: ±0.1% for L-N voltage > 20V
for L-L voltage > 35V Dimensions
Power (Active , Reactive & Apparent): 1%
Energy (Active , Reactive & Apparent): Class 1
Memory Retention 10 years (for energy)
Measuring Parameters Voltage (L-L / L-N) (Individual / Average) 90.5 90.5
99
Current (I1, I2, I3) (Individual / Average)
Frequency, Power Factor (Individual / Average)
Active, Reactive & Apparent power (Individual / 99 49 90.5
Total), Active, Reactive & Apparent Energy
3
Front bezel Side view Panel cutout
(Total), Phase Angle, CT polarity error, Run hour,
Auxiliary interrupt, Max/min power demand

Output Specifications

Pulse Output Voltage Range: External 24V DC max.


Current Capacity: 100mA max
Pulse Width: 100 ms ±5 ms

www.selec.com 1
MFM376-230V Multifunction Meter

Terminal Connections Ordering Information

N
Supply Voltage Output
L
Product
240V AC Pulse Output
+

PULSE O/P
MFM376-230V

L1 L
L2 O
L3 A
N D

S1 S2 S1 S2 S1 S2 N V1 V2 V3
I1 I2 I3

www.selec.com 2

You might also like