Comment 2:
Grating is not required for this area as
per drawing L001-12000-
CS-2408-4944_R0. COOEC is to check
and revise. Handrail layout to be revised
accordingly.
Comment 1:
Clearance between grating
and toe plate of handrail is
6mm as per Section A in
drawing L001-00000-
CS-2408-1005. Current
clearance as model by
COOEC is more than 6mm.
COOEC is to check and
update.
Length of grating G1, G40 to G42,
G119, G120 to be revised considering
the detail of expansion joint see
comment 3 on previous page.