You are on page 1of 53

ENGLISH РУССКИЙ ЯЗЫК УКРАÏНСЬКА

INSTALLATION MANUAL

AIR
CONDITIONER

Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it
thoroughly.

For Heat Pump / Heat Recovery system


Original instruction

MFL68124509 www.lg.com
Rev.04_022720 Copyright © 2017 - 2020 LG Electronics Inc. All Rights Reserved.
2
ENGLISH

Installation
TIPS FOR SAVING ENERGY • Have all electric work done by a licensed electrician according to
"Electric Facility Engineering Standard" and "Interior Wire
Here are some tips that will help you minimize the power consumption Regulations" and the instructions given in this manual and always
when you use the air conditioner. You can use your air conditioner use a special circuit.
more efficiently by referring to the instructions below: - If the power source capacity is inadequate or electric work is
performed improperly, electric shock or fire may result.
• Do not cool excessively indoors. This may be harmful for your health • Ask the dealer or an authorized technician to install the air
and may consume more electricity. conditioner.
• Block sunlight with blinds or curtains while you are operating the air - Improper installation by the user may result in water leakage,
electric shock, or fire.
conditioner.
• Keep doors or windows closed tightly while you are operating the air • Always ground the product.
- There is risk of fire or electric shock.
conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate • Always intstall a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period • For re-installation of the installed product, always contact a dealer
or an Authorized Service Center.
of time.
- There is risk of fire, electric shock, explosion, or injury.
• Open windows regularly for ventilation as the indoor air quality may
• Do not install, remove, or re-install the unit by yourself (customer).
deteriorate if the air conditioner is used for many hours.
- There is risk of fire, electric shock, explosion, or injury.
• Clean the air filter once every 2 weeks. Dust and impurities collected
• Do not store or use flammable gas or combustibles near the air
in the air filter may block the air flow or weaken the cooling /
conditioner.
dehumidifying functions. - There is risk of fire or failure of product.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
For your records • Prepare for strong wind or earthquake and install the unit at the
specified place.
Staple your receipt to this page in case you need it to prove the date of - Improper installation may cause the unit to topple and result in
purchase or for warranty purposes. Write the model number and the injury.
serial number here: • Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
Model number :
• Use a vacuum pump or Inert(nitrogen) gas when doing leakage test
Serial number : or air purge. Do not compress air or Oxygen and do not use
Flammable gases. Otherwise, it may cause fire or explosion.
You can find them on a label on the side of each unit. - There is the risk of death, injury, fire or explosion.
Dealer’s name : • When installing and moving the air conditioner to another site, do
not charge it with a different refrigerant from the refrigerant
Date of purchase : specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant,
the refrigerant cycle may malfunction and the unit may be
damaged.
• Do not reconstruct to change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device
is shorted and operated forcibly, or parts other than those
specified by LGE are used, fire or explosion may result.
• Ventilate before operating air conditioner when gas leaked out.
IMPORTANT SAFETY - It may cause explosion, fire, and burn.
• Securely install the cover of control box and the panel.
INSTRUCTIONS - If the cover and panel are not installed securely, dust or water may
enter the outdoor unit and fire or electric shock may result.
READ ALL INSTRUCTIONS BEFORE USING THE • If the air conditioner is installed in a small room, measures must be
APPLIANCE. taken to prevent the refrigerant concentration from exceeding the
safety limit when the refrigerant leaks.
Always comply with the following precautions to avoid dangerous - Consult the dealer regarding the appropriate measures to prevent
situations and ensure peak performance of your product. the safety limit from being exceeded. Should the refrigerant leak
and cause the safety limit to be exceeded, harzards due to lack of
! WARNING oxygen in the room could result.
It can result in serious injury or death when the directions are ignored.
Operation
! CAUTION • Do not damage or use an unspecified power cord.
- There is risk of fire, electric shock, explosion, or injury.
It can result in minor injury or product damage when the directions are
ignored. • Use a dedicated outlet for this appliance.
- There is risk of fire or electrical shock.
• Be cautious that water could not enter the product.
! WARNING - There is risk of fire, electric shock, or product damage.
• Do not touch the power switch with wet hands.
• Installation or repairs made by unqualified persons can result in
- There is risk of fire, electric shock, explosion, or injury.
hazards to you and others.
• When the product is soaked (flooded or submerged), contact an
• The information contained in the manual is intended for use by a
Authorized Service Center.
qualified service technician familiar with safety procedures and
- There is risk of fire or electric shock.
equipped with the proper tools and test instruments.
• Be cautious not to touch the sharp edges when installing.
• Failure to carefully read and follow all instructions in this manual can
- It may cause injury.
result in equipment malfunction, property damage, personal injury
and/or death. • Take care to ensure that nobody could step on or fall onto the
outdoor unit.
- This could result in personal injury and product damage.
3

ENGLISH
• Do not open the inlet grille of the product during operation. (Do not • Turn on the power at least 6 hours before starting operation.
touch the electrostatic filter, if the unit is so equipped.) - Starting operation immediately after turning on the main power
- There is risk of physical injury, electric shock, or product failure. switch can result in severe damage to internal parts. Keep the
power switch turned on during the operational season.
• Do not touch any of the refrigerant piping during and after
! CAUTION operation.
Installation - It can cause a burn or frostbite.
• Do not operate the air conditioner with the panels or guards
• Always check for gas (refrigerant) leakage after installation or repair
removed.
of product.
- Rotating, hot, or high-voltage parts can cause injuries.
- Low refrigerant levels may cause failure of product.
• Do not directly turn off the main power switch after stopping
• Do not install the product where the noise or hot air from the
operation.
outdoor unit could damage the neighborhoods.
- Wait at least 5 minutes before turning off the main power switch.
- It may cause a problem for your neighbors.
Otherwise it may result in water leakage or other problems.
• Keep level even when installing the product.
• Auto-addressing should be done in condition of connecting the
- To avoid vibration or water leakage.
power of all indoor and outdoour units. Auto-addressing should also
• Do not install the unit where combustible gas may leak. be done in case of changing the indoor unit PCB.
- If the gas leaks and accumulates around the unit, an explosion • Use a firm stool or ladder when cleaning or maintaining the air
may result. conditioner.
• Use power cables of sufficient current carrying capacity and rating. - Be careful and avoid personal injury.
- Cables that are too small may leak, generate heat, and cause a • Do not insert hands or other objects through the air inlet or outlet
fire. while the air conditioner is plugged in.
• Do not use the product for special purposes, such as preserving - There are sharp and moving parts that could cause personal injury.
foods, works of art, etc. It is a consumer air conditioner, not a
precision refrigeration system.
- There is risk of damage or loss of property.
• Keep the unit away from children. The heat exchanger is very
sharp.
- It can cause the injury, such as cutting the finger. Also the
damaged fin may result in degradation of capacity.
• When installting the unit in a hospital, communication station, or
similar place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency
medical equipment, or radio communication equipment may cause
the air conditioner to operate erroneously, or fail to operate. On
the other hand, the air conditioner may affect such equipment by
creating noise that disturbs medical treatment or image
broadcasting.
• Do not install the product where it is exposed to sea wind (salt
spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on
the condenser and evaporator fins, could cause product
malfunction or inefficient operation.
• Means for disconnection must be incorporated in the fixed wiring in
accordance with the wiring rules.

Operation
• Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the
performance of the air conditioner or damage its parts.
• Do not block the inlet or outlet.
- It may cause failure of appliance or accident.
• Make the connections securely so that the outside force of the
cable may not be applied to the terminals.
- Inadequate connection and fastening may generate heat and
cause a fire.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing
property damage, product failure, or personal injury.
• Install and insulate the drain hose to ensure that water is drained
away properly based on the installation manual.
- A bad connection may cause water leakage.
• Be very careful about product transportation.
- Only one person should not carry the product if it weighs more
than 20 kg.
- Some products use PP bands for packaging. Do not use any PP
bands for a means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your
fingers.
- When transporting the outdoor unit, suspending it at the specified
positions on the unit base. Also support the outdoor unit at four
points so that it cannot slip sideways.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts,
may cause stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children
may not play with them. If children play with a plastic bag which
was not torn apart, they face the risk of suffocation.
4
ENGLISH

TABLE OF CONTENTS 44
44
Snow removal & rapid defrost
Setting Capacity Up Airflow Adjusting for IDU (Heating)
2 TIPS FOR SAVING ENERGY 44
44
Target pressure adjusting
Low Ambient Kit
2 IMPORTANT SAFETY INSTRUCTIONS 45
45
High Efficiency Mode (Cooling Operation)
Auto Dust Removal Mode
5 INSTALLATION PROCESS 45 Compressor Max. Frequency Limit
45 ODU Fan Max. RPM Limit
5 OUTDOOR UNITS INFORMATION 46 SLC (Smart Load Control)
46 Humidity Reference
5 ALTERNATIVE REFRIGERANT R410A 46 Central Control Connection at Indoor Unit side
46 Compressor Input Current Limit
5 SELECT THE BEST LOCATION 47 Power Consumption Display on wired remote controller
47 Overall Defrost Operating in Low temperature (Heating)
7 INSTALLATION SPACE 47 Base pan Heater operation
7 Individual Installation 47 Comfort Cooling operation
48 Self-Diagnosis Function
7 LIFTING METHOD
51 CAUTION FOR REFRIGERANT LEAK
8 INSTALLATION 51 Introduction
8 The location of the Anchor bolts 51 Checking procedure of limiting concentration
8 Foundation for Installation
9 Preparation of Piping 52 INSTALLATION GUIDE AT THE SEASIDE
10 Plumbing materials and storage methods 52 Model Designation
52
11 REFRIGERANT PIPING INSTALLATION Airborne Noise Emission
[For Heat Pump System Installation]
11 Precautions on Pipe connection / Valve operation
11 Connection of Outdoor units

[For Heat Recovery System Installation]


13 Precautions on Pipe connection / Valve operation
13 Connection of Outdoor units
13 Installation procedure for HR unit
14 Installation of Outdoor Unit, HR Unit, Indoor Unit Refrigerant
Pipe
14 Type of HR Unit
14 Installation of Zoning Control

16 PIPE CONNECTIONS BETWEEN INDOOR


AND OUTDOOR UNIT
[For Heat Pump System Installation]
16 Preparation Work
16 Pipe Drawing Out during Single / Series connection
17 Refrigerant piping system
18 Pipe Connection Method between outdoor unit/indoor unit
21 Branch pipe Fitting
22 Distribution Method
23 Vacuum Mode
23 Leak Test and Vacuum drying
25 Refrigerant charging
26 Thermal insulation of refrigerant piping

[For Heat Recovery System Installation]


27 Preparation Work
27 Pipe Drawing Out during Single / Series connection
28 Refrigerant piping system

30 ELECTRICAL WIRING
32 Control box and connecting position of wiring
32 Communication and Power Cables
33 Wiring of main power supply and equipment capacity
33 Point for attention regarding quality of the public electric power
supply
33 Field Wiring
35 Checking the setting of outdoor units
36 Switch for setup of HR Unit
38 Automatic Addressing
38 The Procedure of Automatic Addressing
39 Flow chart of auto pipe detection process
40 Flow chart of manual addressing for pipe detection
40 Example of manual valve addressing (Non-Zoning setting)
40 Example of manual valve addressing (Zoning setting)
41 Example of checking valve address
41 Identification of Manual Valve ID (Address)
41 Method of checking the pipe detection result at outdoor unit
41 Setting method of Master indoor unit in zoning
41 Group Number setting
42 Cool & Heat selector
43 High Static Pressure Compensation mode
43 Night Low Noise Function
43 Overall defrost mode
43 Setting the ODU address
5

ENGLISH
INSTALLATION PROCESS OUTDOOR UNITS INFORMATION
Determination of division work Indicate clearly who will be responsible for switch setting.
! CAUTION
Preparation of contract drawings Make connection clearly between outdoor, indoor, Combination Ratio(50~200 %)
remote controller and option.
Outdoor Number Connection Ratio
Single outdoor units 200 %
Take account of gradient
Sleeve and insert work Outdoor unit foundation work Double outdoor units 160 %
of drain piping
The foundation must be level even Triple outdoor units 130 %
Over the triple unit 130 %
Check model name to
Installation of indoor unit make sure the fitting Installation of outdoor unit
is made correctly Notes : * We can guarantee the operation only within 130 %
Avoid short circuits and ensure combination. If you want to connect more than 130 %
sufficient space is allowed for service
combination, please contact us and discuss the
Refrigerant piping work
Special attention to dryness, requirement like below.
cleanness and tightness
• If the operation of indoor unit is more than 130 %, the airflow
is operated as low in the all indoor units.
Drain pipe work Adjust to downward gradient

Duct work Make sure airflow is sufficient

Heat insulation work


Make sure no gaps are left where
the insulating materials are joined
ALTERNATIVE REFRIGERANT
Electrical work
(connection circuits and drive circuits)
Multiple core cable must not be used.
(suitable cable should be selected)
R410A
The refrigerant R410A has the property of higher operating pressure in
Airtight test In the final check for 24 hours at 3.8 MPa (38.7 kgf/cm2)[551.1 psi] comparison with R22.
there must be no drop in pressure.
Therefore, all materials have the characteristics of higher resisting
The vacuum pump used must have a capacity of reaching at least pressure than R22 ones and this characteristic should also be
Vacuum drying
5 torr, more than 1 hour
considered during the installation.
Additional charge of refrigerant
Recharge correctly as calculated in this manual. and record the R410A is an azeotrope of R32 and R125 mixed at 50 : 50, so the ozone
amount of added refrigerant
depletion potential (ODP) of R410A is 0.
Make sure there are no gaps left between the facing materials
Fit facing panels
used on the ceiling

Automatic addressing of indoor unit Refer to automatic addressing flowchart


Preheat the crank case with the electrical heater for more than 6 hours.
! CAUTION
Test run adjustment Run each indoor unit in turn to make sure the pipe work • The wall thickness of the piping should comply with the relevant
has been fitted correctly local and national regulations for the designed pressure 3.8 MPa
Explain the use of the system as clearly as possible to your customer and [551.1 psi]
Transfer to customer with explanation
make sure all relevant documentation is in order • Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state.

! CAUTION If the refrigerant is charged in its gaseous state, its composition


changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of
• The above list indicates the order in which the individual work
the sun to prevent it from exploding.
operations are normally carried out but this order may be varied
where local conditions warrants such change. • For high-pressure refrigerant, any unapproved pipe must not be
used.
• The thickness of the piping should comply with the relevant
local and national regulations for the designed pressure 3.8 MPa • Do not heat pipes more than necessary to prevent them from
(551.1 psi). softening.
• Since R410A is a mixed refrigerant, the required additional • Be careful not to install wrongly to minimize economic loss
refrigerant must be charged in its liquid state.(If the refrigerant because it is expensive in comparison with R22.
is charged in its gaseous state, its composition changes and the
system will not work properly.)

SELECT THE BEST LOCATION


Select space for installing outdoor unit, which will meet the following
conditions:
• No direct thermal radiation from other heat sources
• No possibility of annoying neighbors due to noise of unit
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• Because of the possibility of fire, do not install unit to the space
where generation, inflow, stagnation, and leakage of combustible gas
is expected.
6
ENGLISH

• Avoid unit installation in a place where acidic solution and spray


(sulfur) are often used.
• Do not use unit under any special environment where oil, steam and More than 100 (3-15/16)
sulfuric gas exist. (Servicing space)

• It is recommended to fence round the outdoor unit in order to


prevent any person or animal from accessing the outdoor unit.
More than More than
• If installation site is area of heavy snowfall, then the following 300 (11-13/16) 300 (11-13/16)
directions should be observed.
- Make the foundation as high as possible. (Servicing space) (Servicing space)
- Fit a snow protection hood.
• Select installation location considering following conditions to avoid
bad condition when additionally performing defrost operation.
- Install the outdoor unit at a place well ventilated and having a lot of
sunshine in case of installing the product at a place With a high
More than 100 (3-15/16)
humidity in winter (near beach, coast, lake, etc.) (Servicing space)
(Ex : Rooftop where there is always sunshine.)

More than More than


For Heat Recovery Installation
300 (11-13/16) 450 (17-23/32)

Select installation location of the HR unit suitable for following (Servicing space) (Servicing space)
conditions
124 (4-7/8)
- Avoid a place where rain may enter since the HR unit is for indoor. 4 5

128 (5-1/32)
- Sufficient service space must be obtained.
- Refrigerant pipe must not exceed limited length.

(1-3/16) (2-3/8)
60
- Avoid a place subject to a strong radiation heat from other heat
source.

30
- Avoid a place where oil spattering, vapor spray or high frequency 61 419 (16-1/2) 137
electric noise is expected. 6 (2-13/32) (5-13/32)

- Install the unit at a place in which it is not affected by operation noise.


(Installation within cell such as meeting room etc. may disturb
business due to noise.) ■ Unit: mm(inch)
- Place where refrigerant piping, drain piping and electrical wiring
works are easy. Description
No. Part Name PRHR042, PRHR042A
PRHR022, PRHR022A
481 (18-15/16) PRHR032, PRHR032A
7 Low pressure Gas Ø 28.58 (1-1/8) Ø 22.2 (7/8) Brazing
1
pipe connection port Brazing connection connection
High pressure Gas Ø 22.2 (7/8) Brazing Ø 19.05 (3/4) Brazing
2
pipe connection port connection connection
345 (13-19/32)

Ø 15.88 (5/8) Brazing


connection (PRHR042,
Liquid pipe PRHR042A) Ø 9.52 (3/8) Brazing
1 3
connection port Ø 12.7 (1/2) Brazing connection
2
connection (PRHR032,
3 PRHR032A)
450 (17-23/32)

Indoor unit Gas pipe Ø 15.88 (5/8) Brazing Ø 15.88 (5/8) Brazing
4
connection port connection connection
Indoor unit Liquid Ø 9.52 (3/8) Brazing Ø 9.52 (3/8) Brazing
5
Inspection door pipe connection port connection connection
(servicing space)
6 Control box - -
450 (17-23/32)
7 Hanger metal M10 or M8 M10 or M8
218 (8-19/32)

! NOTE
(7-5/32)
182

• Be sure to install the inspection door at the control box side.


• If reducers are used, servicing space must be increased equal to
174 174 reducer's dimension.
(6-27/32) 453 (17-27/32) (6-27/32)

More than 100 (3-15/16)


(Servicing space)
7

ENGLISH
INSTALLATION SPACE Seasonal wind and cautions in winter
• Sufficient measures are required in a snow areas or severe cold
areas in winter so that product can be operated well.
Individual Installation • Get ready for seasonal wind or snow in winter even in other areas.
During the installation of the unit, consider service, inlet, and outlet • Install a suction and discharge duct not to let in snow or rain.
acquire the minimum space as shown in the figures below. • Install the outdoor unit In such a way that it should not come in
contact with snow directly. If snow piles up and freezes on the air
Case 1 Case 2 suction hole, the system may malfunction. If it is installed at snowy
Category Installation Space (10 mm(13/32 inch) ≤ Side (Side Space area, attach the hood to the system.
Space ≤ 49 mm(13/14 inch)) ≥ 49 mm(13/14 inch)) • Install the outdoor unit at the higher installation console by 50 cm
b A ≥ 10 (13/32) A ≥ 50 (1-31/32) (19.7 inch) than the average snowfall (annual average snowfall) if it is
a c B ≥ 300 (11-13/16) B ≥ 100 (3-15/16) installed at the area with much snowfall.
C ≥ 10 (13/32) C ≥ 50 (1-31/32) • Where snow accumulated on the upper part of the Outdoor Unit by
d Front D ≥ 500 (19-11/16) D ≥ 500(19-11/16) more than 10 cm (3.9 inch), always remove snow for operation.
b
A ≥ 10 (13/32) A ≥ 50 (1-31/32)
B ≥ 300 (11-13/16) B ≥ 100 (3-15/16)
a e e c
C ≥ 10 (13/32) C ≥ 50 (1-31/32) - The height of H frame must be more than 2 times the snowfall
d Front
D ≥ 500 (19-11/16) D ≥ 500 (19-11/16) and its width shall not exceed the width of the product. (If width
E ≥ 20 (25/32) E ≥ 100 (3-15/16) of the frame is wider than that of the product, snow may
b
accumulate)
4 sides A ≥ 10 (13/32) A ≥ 50 (1-31/32)
a e c B ≥ 300 (11-13/16) B ≥ 100 (3-15/16) - Don't install the suction hole and discharge hole of the Outdoor
are C ≥ 10 (13/32) C ≥ 50 (1-31/32) Unit facing the seasonal wind.
f Front Front
walls D ≥ 500 (19-11/16) D ≥ 500 (19-11/16)
E ≥ 20 (25/32) E ≥ 100 (3-15/16)
F ≥ 600 (23-5/8) F ≥ 500 (19-11/16) Remove the Rear Grille
d Front Front
• Remove the rear grille in snowy area.
b
A ≥ 10 (13/32) A ≥ 50 (1-31/32) • Make sure that heat exchanger should not be damaged.
a e c
B ≥ 300 (11-13/16) B ≥ 100 (3-15/16)
f Front Front C ≥ 10 (13/32) C ≥ 50 (1-31/32)
D ≥ 300 (11-13/16) D ≥ 100 (3-15/16)
UXA UXB
E ≥ 20 (25/32) E ≥ 100 (3-15/16)
d
F ≥ 500 (19-11/16) F ≥ 500 (19-11/16)

b Front
a c A ≥ 10 (13/32) A ≥ 50 (1-31/32)
B ≥ 500 (19-11/16) B ≥ 500 (19-11/16)
f C ≥ 10 (13/32) C ≥ 50 (1-31/32)
D ≥ 500 (19-11/16) D ≥ 500 (19-11/16)
F ≥ 900 (35-7/16) F ≥ 600 (23-5/8)
d Front Rear Grille

b Front Front
A ≥ 10 (13/32) A ≥ 50 (1-31/32)
Rear a e c
B ≥ 500 (19-11/16) B ≥ 500 (19-11/16)
to f C ≥ 10 (13/32) C ≥ 50 (1-31/32)
D ≥ 500 (19-11/16) D ≥ 500 (19-11/16)
Rear E ≥ 20 (25/32) E ≥ 100 (3-15/16)
F ≥ 1200 (47-1/4) F ≥ 900 (35-7/16)
d Front Front
LIFTING METHOD
b Front Front Front
A ≥ 10 (13/32) A ≥ 50 (1-31/32) • When carrying the suspended, unit pass the ropes under the unit and
a e e c
B ≥ 500 (19-11/16) B ≥ 500 (19-11/16) use the two suspension points each at the front and rear.
f C ≥ 10 (13/32) C ≥ 50 (1-31/32)
D ≥ 500 (19-11/16) D ≥ 500 (19-11/16) • Always lift the unit with ropes attached at four points so that impact
E ≥ 20 (25/32) E ≥ 100 (3-15/16) is not applied to the unit.
d Front Front Front F ≥ 1800 (70-7/8) F ≥ 1200 (47-1/4) • Attach the ropes to the unit at an angle of 40° or less.

a
No limit for the A ≥ 10 (13/32)
Only 2
height of wall B ≥ 300 (11-13/16)
Front
sides
are b No limit for the height of wall A ≥ 200 (7-7/8)
walls B ≥ 300 (11-13/16)
a e e
E ≥ 400 (15-3/4) Locking points for
Front transportation ropes
(19-11/16’’)
500

h1
• The height of the wall on the front side must
be 1 500 mm (59 inch) or less.
1 500 (59)

A
Limitati
h2 • The height of the wall on the inlet side must
B
be 500 mm (19-11/16’’) or less.
(19-11/16’’)

ons on
500
(19-11/16’’)
500 50050050050

• There is no limit to the wall on the side.


(19-11/16’’)

the
(19-11/16’’)

Inlet Front
height side side • If the height of the walls on the front and the
(19-11/16’’)
(19-11/16’’)
500500
(19-11/16’’)

of the side are higher than the limit, there must be


45° or
wall more additional space on the front and the side. Forklift Carrying Hole
240
(Refer (9-1/2’’) - Additional Space on the front side by 1/2 of
to 4 or more
h1
side - Additional Space on the inlet side by 1/2 of
walls)
h2
- h1 = A(Actual height) - 1 500 (59 inch)
50 (2) or more - h2 = B(Actual height) - 500 (19-11/16’’) Forklift Carrying Guide
8

CAUTION
ENGLISH

! Foundation for Installation


• Fix the unit tightly with bolts as shown below so that unit will not fall
Be very careful while carrying the product.
down due to earthquake or gust.
• Do not have only one person carry product if it is more than 20
• Use the H-beam support as a base support
kg (44 lbs).
• Noise and vibration may occur from the floor or wall since vibration is
• PP bands are used to pack some products. Do not use them as
transferred through the installation part depending on installation
a mean for transportation because they are dangerous.
status. Thus, use anti-vibration materials (cushion pad) fully (The base
• Do not touch heat exchanger fins with your bare hands. pad shall be more than 200 mm (7-7/8 inch)).
Otherwise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot
play with it. Otherwise plastic packaging bag may suffocate
children to death.
• When carrying in Outdoor Unit, be sure to support it at four
points. Carrying in and lifting with 3-point support may make
Outdoor Unit unstable, resulting in a fall.
At least
• Use 2 belts of at least 8 m (26.2 ft) long. 200 (7.87)
• Place extra cloth or boards in the locations where the casing
comes in contact with the sling to prevent damage.
• Hoist the unit making sure it is being lifted at its center of gravity.

Ⓐ The corner part must be fixed firmly. Otherwise, the support for the
INSTALLATION installation may be bent.
Ⓑ Get and use M10 Anchor bolt.
• Install at places where it can endure the weight and vibration/noise Ⓒ Put Cushion Pad between the outdoor unit and ground support for
of the outdoor unit. the vibration protection in wide area.
• The outdoor unit support blocks at the bottom shall have width of at Ⓓ Space for pipes and wiring (Pipes and wirings for bottom side)
least 100 mm (3-15/16 inch) under the Unit’s legs before being fixed. Ⓔ H-beam support
• The outdoor unit support blocks should have minimum height of Ⓕ Concrete support
200 mm (7-7/8 inch).
Unit : mm (inch)
• Anchor bolts must be inserted at least 75 mm (2-15/16 inch).

75(2.95)
200(7.87)

200(7.87)
75(2.95)
100(3.94)

m
0m
least 10 ch)
Outdoor units At /16 in
WARNING
5
should not be (3-1
supported only by mm !
00
the corner supports. ast 1 h)
At le /16 inc 100 mm • Install where it can sufficiently support the weight of the
5 ast
(3-1 h) Center of the Unit
At le /16 inc outdoor unit.
5
(3 1
- If the support strength is not enough, the outdoor unit may drop
and hurt people.
• Install where the outdoor unit may not fall in strong wind or
earthquake.
If there is a fault in the supporting conditions, the outdoor unit
mm may fall and hurt people.
00
t least 1 inch) • Please take extra cautions on the supporting strength of the
A /16
5
(3-1 ground, water outlet treatment(treatment of the water flowing
mm out of the outdoor unit in operation), and the passages of the
00
ast 1 h) m pipe and wiring, when making the ground support.
At le /16 inc t 100m
5
(3-1 At leas 6 inch) Center of the Unit
• Do not use tube or pipe for water outlet in the Base panel. Use
5/1
(3-1 drainage instead for water outlet. The tube or pipe may freeze
and the water may not be drained.
The location of the Anchor bolts
Unit : mm (inch)
! CAUTION
• Be sure to remove the Pallet(Wood Support) of the bottom side
of the outdoor unit Base panel before fixing the bolt. It may
cause the unstable state of the outdoor settlement, and may
cause freezing of the heat exchanger resulting in abnormal
65
(2-9/16)

At least
65 (2-9/16) 65 (2-9/16)

760 (29-29/32)
731 (28-25/32)

operations.
• Be sure to remove the Pallet(Wood Support) of the bottom side
of the outdoor unit before welding. Not removing Pallet(Wood
(2-9/16)

Support) causes hazard of fire during welding.


At least
65

Chassis A [mm (inch)] B [mm (inch)]


Pallet(Wood Support)
UXA 930 (36-5/8) 730 (28-3/4) - Remove before Installation
UXB 1 240 (47-1/4) 1 040 (40-15/16)
9

ENGLISH
Preparation of Piping Pipe size Tightening Torque
A [mm (inch)] Flare shape
[mm (inch)] N.m (lbs.ft)
Main cause of gas leakage is defect in flaring work. Carry out correct
90° ±2
flaring work in the following procedure. Ø 9.52 (3/8) 38±4 (28±3.0) 12.8 (0.5)~13.2 (0.52)
45
° ±2
A
Ø 12.7 (1/2) 55±6 (41±4.4) 16.2 (0.64)~16.6 (0.65)
Cut the pipes and the cable R = 0.4~0.8

- Use the accessory piping kit or the pipes purchased locally. Ø 15.88 (5/8) 75±7 (55±5.2) 19.3 (0.76)~19.7(0.78)
- Measure the distance between the indoor and the outdoor unit.
- Cut the pipes a little longer than measured distance.
- Cut the cable 1.5 m (4.92 ft) longer than the pipe length.
! CAUTION
Pipe
• Always use a charge hose for service port connection.
Reamer
Copper • After tightening the cap, check that no refrigerant leaks are present.
tube 90° Slanted Uneven Rough
• When loosening a flare nut, always use two wrenches in
Point down combination, When connecting the piping,
always use a spanner and torque wrench
in combination to tighten the flare nut.
Union
• When connecting a flare nut, coat the
flare(inner and outer faces) with oil for
R410A(PVE) and hand tighten the nut
3 to 4 turns as the initial tightening.
Burrs removal
- Completely remove all burrs from the cut cross section of pipe/tube.
- Put the end of the copper tube/pipe to downward direction as you
remove burrs in order to avoid to let burrs drop in the tubing.
Opening shutoff valve
<Wing nut type> <Clutch type>
Bar 1 Remove the cap and turn the valve counter clockwise with the
"A" hexagon wrench.
2 Turn it until the shaft stops.
Do not apply excessive force to the shutoff valve. Doing so may
break the valve body, as the valve is not a backseat type. Always
Copper pipe use the special tool.
3 Make sure to tighten the cap securely.

Flaring work
- Carry out flaring work using flaring tool as shown below. Closing shutoff valve
Pipe diameter A inch (mm) 1 Remove the cap and turn the valve clockwise with the hexagon
inch (mm) Wing nut type Clutch type wrench.
Ø 1/4 (Ø 6.35) 0.04~0.05 (1.1~1.3) 2 Securely tighten the valve until the shaft contacts the main body seal.
Ø 3/8 (Ø 9.52) 0.06~0.07 (1.5~1.7)
0~0.02 3 Make sure to tighten the cap securely.
Ø 1/2 (Ø 12.7) 0.06~0.07 (1.6~1.8) * For the tightening torque, refer to the table on the below.
(0~0.5)
Ø 5/8 (Ø 15.88) 0.06~0.07 (1.6~1.8)
Ø 3/4 (Ø 19.05) 0.07~0.08 (1.9~2.1)
Firmly hold copper tube in a bar(or die) as indicated dimension in the Tightening torque
table above.
Shut Tightening torque N.m (lbs.ft) (Turn clockwise to close)
off Shaft
Check valve Gas line
(valve body) Cap Service piping
- Compare the flared work with figure below. size Flare nut attached
- If flare is noted to be defective, cut off the flared section and do (mm
Closed Opened Hexagonal (Valve lid) port
(inch)) wrench to unit
flaring work again.
Ø 6.35 16±2
Smooth all round (1/4) 6.0±0.6 17.6±2.0 (12±1.5)
Inside is shining without scratches.
Ø 9.52 (4.4±0.4) 4 mm (13.0±1.5) 38±4
(3/8) (0.16 inch) (28±3.0)
= Improper flaring =
Ø 12.7 10.0±1.0 20.0±2.0 55±6
(1/2) (7.4±0.7) (14.8±1.5) (41±4.4)
-
Inclined Surface Cracked Uneven Ø 15.88 12.0±1.2 5.0±0.0 12.7±2 75±7
damaged thickness
Even length (5/8) (8.9±0.9) (3.7±0.4) 5 mm (9.4±1.5) (55±5.1)
all round
Ø 19.05 14.0±1.4 (0.24 inch) 110±10
(3/4) (10.3±1.0) 25.0±2.5 (81.1±7.4)
Flare shape and flare nut tightening torque (18.4±1.8)
Ø 22.2
Precautions when connecting pipes (7/8) 30.0±3.0 8 mm -
- See the following table for flare part machining dimensions. Ø 25.4 (22.1±2.2) (0.31 inch) 25±3
- When connecting the flare nuts, apply refrigerant oil to the inside and (1) (18.5±2.2)
outside of the flares and turn them three or four times at first. (Use
ester oil or ether oil.)
- See the following table for tightening torque.(Applying too much torque may Insulation of shutoff valve
cause the flares to crack.)
- After all the piping has been connected, use nitrogen to perform a 1 Use the heat insulation material for the refrigerant piping which has
gas leak check. an excellent heat-resistance (over 120 °C [248 °F]).
10
ENGLISH

2 Precautions in high humidity circumstance: Nitrogen substitution method


This air conditioner has been tested according to the "ISO Welding, as when heating without nitrogen substitution a large amount
Conditions with Mist" and confirmed that there is not any default. of the oxide film is formed on the internal piping.
However, if it is operated for a long time in high humid atmosphere
(dew point temperature: More than 23 °C [73.4 °F]), water drops The oxide film is a caused by clogging EEV, Capillary, oil hole of
are liable to fall. In this case, add heat insulation material according accumulator and suction hole of oil pump in compressor.
to the following procedure: It prevents normal operation of the compressor.
- Heat insulation material to be prepared: In order to avoid this problem, Welding should be done after replacing
EPDM (Ethylene Propylene Diene Methylene)-over 120 °C [248 air by nitrogen gas.
°F] the heat-resistance temperature. When welding plumbing pipe, the work is required.
- Add the insulation over 10 mm [0.39 inch] thickness at high Regulator
humidity environment.
Welding Point
Nitrogen gas
Fastening band Pressure 0.02 MPa
(accessory) (2.9 psi) less

Nitrogen
Oxide scale
Note) should not block the outlet side. Auxiliary valve
Refrigerant piping When the internal pressure in pipe is abo
Taping
(Should not
ve the atmospheric pressure, pinhole is
Indoor unit contain air)
occurred and it is a leakage cause.
Thermal insulator
(accessory)

Plumbing materials and storage methods ! CAUTION


Pipe must be able to obtain the specified thickness and should be • Always use the nitrogen.(not use oxygen, carbon dioxide, and a Chevron
used with low impurities. gas): Please use the following nitrogen pressure 0.02 MPa (2.9 psi)
Also when handling storage, pipe must be careful to prevent a Oxygen - Promotes oxidative degradation of refrigerant oil. Because it is
fracture, deformity and wound. flammable, it is strictly prohibited to use Carbon dioxide - Degrade the
Should not be mixed with contaminations such as dust, moisture. drying characteristics of gas Chevron Gas - Toxic gas occurs when
exposed to direct flame.
• Always use a pressure reducing valve.
• Please do not use commercially available antioxidant.
The residual material seems to be the oxide scale is observed. In
fact, due to the organic acids generated by oxidation of the alcohol
contained in the anti-oxidants, ants nest corrosion occurs. (causes of
organic acid → alcohol + copper + water + temperature)

Refrigerant piping on three principles


Drying Cleanliness Airtight
Should be no moisture There is no refrigerant
No dust inside.
inside leakage

Moisture Dust Leakage


Items

- Significant hydrolysis - Degradation of - Gas shortages


of refrigerant oil refrigerant oil - Degradation of
- Degradation of - Poor insulation of refrigerant oil
refrigerant oil the compressor - Poor insulation of
Cause - Poor insula’tion of
- Do not cold and the compressor
failure the compressor
- Do not cold and warm - Do not cold and
warm - Clogging of EEV, warm
- Clogging of EEV, Capillary
Capillary

- No moisture in the pipe - No dust in the pipe. - Airtightness test


- Until the connection - Until the should be.
is completed, the connection is - Brazing operations
plumbing pipe completed, the to comply with
entrance should be plumbing pipe standards.
strictly controlled. entrance should be - Flare to comply
- Stop plumbing at strictly controlled. with standards.
rainy day. - Pipe entrance - Flange connections
Counter - Pipe entrance should be taken to comply with
measur should be taken side side or bottom. standards.
e or bottom. - When removal burr
- When removal burr after cutting pipe,
after cutting pipe, pipe pipe entrance
entrance should be should be taken
taken down. down.
- Pipe entrance - Pipe entrance
should be fitted cap should be fitted cap
when pass through when pass through
the walls. the walls.
11

ENGLISH
REFRIGERANT PIPING Connection of Outdoor units
When installing ODU series, refer below picture.
INSTALLATION
For Heat Pump System Installation A B C D
(Master) (Slave 1) (Slave 2) (Slave 3)
Precautions on Pipe connection / Valve operation
Pipe connection is done by connecting from the end of the pipe to the
branching pipes, and the refrigerant pipe coming out of the outdoor
unit is divided at the end to connect to each indoor unit. Flare
connection for the indoor unit, and welding connection for the outdoor
pipe and the branching parts.

- Use hexagonal wrench to open/close the valve.


h In case of the heat pump system installation, be sure to maintain to
close no use pipe like below picture. A≥B≥C≥D
① IDU side connection pipe
Service Port
② ODU to ODU connection pipe (1st branch)
③ ODU to ODU connection pipe (2st branch)
④ ODU to ODU connection pipe (3rd branch)

2, 3, 4 Outdoor Units
Liquid pipe
Outdoor units Model Liquid Pipe Gas Pipe

No Use (Keep closed) O.D 15.88 I.D 19.05 I.D 22.2 O.D 28.58 I.D 34.9
331
416
314
408
C
I.D 15.88 I.D 15.88
I.D 28.58 I.D 28.58

I.D 19.05 I.D 12.7 I.D 9.52 83


Gas pipe 2 Unit C ARCNN21 I.D 31.8 I.D 34.9
I.D 22.2 111

I.D 22.2 O.D 19.05 I.D 41.3 I.D 38.1 O.D 34.9
I.D 12.7 I.D 15.88
C I.D 28.58
O.D 12.7 I.D 9.52
70
130

O.D 15.88 I.D 19.05 I.D 22.2 O.D 28.58 I.D 34.9
C

I.D 41.3 O.D 34.9


O.D 34.9 I.D 28.58
O.D 19.05 I.D 12.7 O.D 19.05 I.D 22.2
I.D 15.88
125
334 341
281 298

ARCNN31
WARNING
3 Unit I.D 22.2 I.D 19.05 I.D 19.05 83 I.D 41.3 I.D 34.9 111

! C
I.D 15.88 I.D 12.7
I.D 53.98 I.D 44.5 O.D 41.3
I.D 28.58

I.D 28.58 O.D 22.2

• Always careful not to leak the refrigerant during welding. O.D 15.88 I.D 19.05
I.D 22.2 O.D 28.58 I.D 34.9

• The refrigerant generates poisonous gas harmful to human body O.D 19.05 I.D 22.2 I.D 28.58
O.D 41.3 I.D 44.5 I.D 53.98
334
if combusted. 281
415
375

A ARCNN41
• Do not perform welding in a closed space. 4 Unit
C
I.D 22.2 I.D 19.05 I.D 19.05 83
I.D 44.48 I.D 53.98 I.D 41.3 134

I.D 15.88 I.D 12.7


• Be sure to close the cap of the service port to prevent gas I.D 31.8 I.D 28.58 O.D 22.2
I.D 28.58

leakage after the work. O.D 15.88 I.D 19.05 I.D 22.2 O.D 28.58 I.D 34.9

For more information, refer accessory installation manual.


! CAUTION
Please block the pipe knock outs of the front and side panels after Y branch
installing the pipes. Within +/- 10°
A
(Animals or foreign objects may be brought in to damage wires.) B

A To outdoor unit Viewed from point A


in direction of arrow
B To branch piping or indoor unit

Facing Facing
downwards upwards

Within ±3°

! CAUTION
Outdoor unit Y-branches can only be installed in a horizontal or
vertical UP configuration.
12
ENGLISH

1 Use the following materials for refrigerant piping. 9 The Multi V will stop due to an abnormality like excessive or
- Material: Seamless phosphorous deoxidized copper pipe insufficient refrigerant. At such a time, always properly charge the
- Wall thickness : Comply with the relevant local and national unit. When servicing, always check the notes concerning both the
regulations for the designed pressure 3.8 MPa piping length and the amount of additional refrigerant.
(551 psi). We recommend the following table as 10 Never perform a pump down. This will not only damage the
the minimum wall thickness. compressor but also deteriorate the performance.
Outer diameter 6.35 9.52 12.7 15.88 19.05 22.2 25.4 28.58 31.8 34.9 38.1 41.3 44.45 53.98 11 Never use refrigerant to perform an air purge. Always evacuate air
[mm(inch)] (1/4) (3/8) (1/2) (5/8) (3/4) (7/8) (1) (1-1/8) (1-1/4) (1-3/8) (1-1/2) (1-5/8) (1-3/4) (2-1/8) by using a vacuum pump.
12 Always insulate the piping properly. Insufficient insulation will
Minimum 0.8 0.8 0.8 0.99 0.99 0.99 0.99 0.99 1.1 1.21 1.35 1.43 1.55 2.1 result in a decline in heating/cooling performance, drip of
thickness (0.03) (0.03) (0.03) (0.04) (0.04) (0.04) (0.04) (0.04) (0.04) (0.05) (0.05) (0.06) (0.06) (0.08) condensate and other such problems.
[mm(inch)]
13 When connecting the refrigerant piping, make sure the service
2 Commercially available piping often contains dust and other valves of the Outdoor Unit is completely closed (the factory
materials. Always blow it clean with a dry inert gas. setting) and do not operate it until the refrigerant piping for the
Outdoor and Indoor Units has been connected, a refrigerant
3 Use care to prevent dust, water or other contaminants from entering leakage test has been performed and the evacuation process has
the piping during installation.
been completed.
4 Reduce the number of bending portions as much as possible, and 14 Always use a non-oxidizing brazing material for brazing the parts
make bending radius as big as possible.
and do not use flux. If not, oxidized film can cause clogging or
5 Always use the branch piping set shown below, which are sold damage to the compressor unit and flux can harm the copper
separately. piping or refrigerant oil.

Header
Y branch
4 branches 7 branches 10 branches ! WARNING
ARBLB01621, ARBLB03321, ARBL054 ARBL057 ARBL1010 When installing and moving the air conditioner to another site, be
ARBLB07121, ARBLB14521, sure to make recharge refrigerant after perfect evacuation.
ARBLB23220 ARBL104 ARBL107 ARBL2010 • If a different refrigerant or air is mixed with the original
refrigerant, the refrigerant cycle may malfunction and the unit
may be damaged.
6 If the diameters of the branch piping of the designated refrigerant • After selecting diameter of the refrigerant pipe to suit total
piping differs, use a pipe cutter to cut the connecting section and capacity of the indoor unit connected after branching, use an
then use an adapter for connecting different diameters to connect appropriate branch pipe set according to the pipe diameter of the
the piping. indoor unit and the installation pipe drawing.
7 Always observe the restrictions on the refrigerant piping (such as
rated length, difference in height, and piping diameter).
Failure to do so can result in equipment failure or a decline in
heating/cooling performance.
8 A second branch cannot be made after a header. (These are shown
by .)

A To Outdoor Unit
B Sealed Piping

B
13

ENGLISH
For Heat Recovery System Installation 2, 3, 4 Outdoor Units
Outdoor units Model Low Pressure Gas Pipe Liquid Pipe High Pressure Gas Pipe
Precautions on Pipe connection / Valve operation
O.D 15.88 I.D 19.05 O.D 22.2 I.D 15.88
I.D 22.2 O.D 28.58 I.D 34.9 I.D 19.05
331
Pipe connection is done by connecting from the end of the pipe to the C
I.D 28.58
416
408
I.D 28.58
I.D 15.88
314
I.D 15.88
416
408
I.D 28.58 I.D 28.58
branching pipes, and the refrigerant pipe coming out of the outdoor I.D 19.05 I.D 12.7 I.D 9.52 83

2 Unit C ARCNB21 I.D 22.2 111 I.D 22.2 111

unit is divided at the end to connect to each indoor unit. Flare


I.D 31.8 I.D 34.9
I.D 31.8 I.D 34.9
I.D 22.2 O.D 19.05
C I.D 41.3 I.D 38.1 O.D 34.9 I.D 12.7 I.D 15.88

connection for the indoor unit, and welding connection for the outdoor 130
I.D 28.58

70
O.D 12.7 I.D 9.52
I.D 28.58

pipe and the branching parts. O.D 28.58


I.D 22.2
I.D 19.05

C I.D 22.2 O.D 28.58 I.D 34.9 O.D 15.88 I.D 19.05

I.D 41.3 O.D 34.9


O.D 34.9 I.D 28.58

- Use hexagonal wrench to open/close the valve. 341


125
O.D 19.05
I.D 15.88
I.D 12.7 O.D 19.05 I.D 22.2
I.D 22.2 O.D 28.58
416
408
I.D 34.9

298 334 I.D 28.58 I.D 28.58


281

C 111
Service Port 3 Unit ARCNB31 I.D 41.3 I.D 34.9 111
I.D 22.2 I.D 19.05 I.D 19.05 83
I.D 31.8 I.D 34.9
I.D 41.3 I.D 38.1 O.D 34.9
I.D 22.2

I.D 28.58
I.D 28.58 I.D 15.88 I.D 12.7 130
I.D 53.98 I.D 44.5 O.D 41.3
C O.D 190.05 I.D 22.2 I.D 28.58 I.D 34.9 O.D 28.58 I.D 22.2

I.D 22.2 O.D 28.58 I.D 34.9


O.D 15.88 I.D 19.05
I.D 53.98 I.D 44.5 O.D 41.3

O.D 41.3 I.D 44.5 I.D 53.98 O.D 19.05 I.D 22.2 I.D 28.58 O.D 34.9 I.D 41.3 I.D 44.5
415 334 341
375 281 298

4 Unit A ARCNB41 I.D 44.48 I.D 53.98 I.D 41.3 134


I.D 22.2 I.D 19.05 I.D 19.05 83
I.D 41.3 I.D 34.9 111

C
I.D 15.88 I.D 12.7
I.D 31.8 I.D 28.58 O.D 22.2
Liquid pipe I.D 28.58 I.D 53.98 I.D 44.5 O.D 41.3 I.D 28.58

I.D 22.2 O.D 28.58 I.D 34.9


O.D 15.88 I.D 19.05 I.D 34.9 O.D 28.58 I.D 22.2

Low Pressure Gas pipe


For more information, refer accessory installation manual.
High Pressure Gas pipe
Y branch
A Within +/- 10°
B

A To outdoor unit Viewed from point A


in direction of arrow
B To branch piping or indoor unit

! WARNING Facing Facing


• Always careful not to leak the refrigerant during welding. downwards upwards
• The refrigerant generates poisonous gas harmful to human body
if combusted.
• Do not perform welding in a closed space.
• Be sure to close the cap of the service port to prevent gas
leakage after the work.

! CAUTION
Please block the pipe knock outs of the front and side panels after
installing the pipes. Within ±3°
(Animals or foreign objects may be brought in to damage wires.)

! CAUTION
Outdoor unit Y-branches can only be installed in a horizontal or
Connection of Outdoor units vertical UP configuration.
When installing ODU series, refer below picture.

Installation procedure for HR unit


A B C D 1 Using an insert-hole-in- anchor, hang the hanging bolt.
(Master) (Slave 1) (Slave 2) (Slave 3)
2 Install a hexagon nut and a flat washer (locally-procured)to the
hanging bolt as shown in the figure in the bottom, and fit the main
unit to hang on the hanger metal.
3 After checking with a level that the unit is level, tighten the hexagon
nut.
* The tilt of the unit should be within ±5° in front/back and left/right.
4 This unit should be installed suspended from ceiling and side A
should always be facing up.
5 Insulate not used pipes completely as shown in the figure.
A≥B≥C≥D
① IDU side connection pipe
② ODU to ODU connection pipe (1st branch)
Six-sided Nut
③ ODU to ODU connection pipe (2st branch) (M10 or M8)
④ ODU to ODU connection pipe (3rd brach) A
Hanger metal

Flat washer
(M10) Insulation

Hanging bolt
(M10 or M8)
14
ENGLISH

Installation of Outdoor Unit, HR Unit, Indoor Unit Joint Method of HR Unit (Big Duct : ARNU76GB8-,
Refrigerant Pipe ARNU763B8-, ARNU96GB8-, ARNU963B8-)
3 pipes are connected to the HR unit from the outdoor unit, classified Joint Method is required when the big duct chassis is installed. In Joint
into liquid pipe, low pressure gas pipe and high pressure gas pipe Method, two neighboring outlets of one HR unit are linked by Y branch
depending on status of refrigerant passing through the pipe. pipe and connected to one indoor unit.
You must connect 3 pipes from outdoor unit to HR unit.
For connection between indoor unit and HR unit, you must connect 1st HR Unit 2nd HR Unit
both liquid pipe and gas pipe from the HR unit to the indoor unit. In this
case, connect them to the indoor unit starting from No.1 connection
port of the HR unit (the port number is displayed on ports of the HR
unit). Use auxiliary flare as annexed parts in connection to the indoor
unit.
1 2 3 4 1 2 3 4

B8 BG BH B8
(96 k) (28 k) (21 k) (76 k)

Gas pipe
Liquid pipe

High HR Unit
Low pressure gas pipe 3 4
Pressure Liquid pipe 1 2
High pressure gas pipe
Gas Pipe
3 4
1 2
Gas pipe
Remove caps on Gas pipe Ø 15.88 (5/8)
The brazing part. Liquid pipe Ø 9.52 (3/8)
Liquid pipe Low Pressure Brazing Type
Gas Pipe
Liquid pipe

PRHR022 PRHR032 PRHR042


HR unit
PRHR022A PRHR032A PRHR042A
Pipe
connection Low pressure
Ø 22.2 (7/8) Ø 28.58 (1-1/8) Ø 28.58 (1-1/8)
From left gas pipe
side Pipe
connection High pressure
From right Ø 19.05 (3/4) Ø 22.2 (7/8) Ø 22.2 (7/8)
gas pipe
side
Liquid pipe Ø 9.52 (3/8) Ø 12.7 (1/2) Ø 15.88 (5/8)

Parallel Installation of Zoning Control


pipe
connection Some indoor unit can be connected to one port of HR unit.

! CAUTION
Whenever connecting the indoor units with the HR unit, install the
indoor units in numerical order from No.1. HR unit HR unit
Ex) In case of installing 3 indoor units : No. 1, 2, 3 (O), No. 1, 2, 4 (X),
No.1, 3, 4 (X), No.2, 3, 4 (X).
Zoning control group 1 sealing Zoning control group 2

(Max. 8 Indoor Units) (Max. 8 Indoor Units)

Type of HR Unit Changeover under control Auto changeover Changeover under control

Select an HR unit according to the number of the indoor units to be


installed. HR units are classified into 3 types by the number of
connectable indoor units. ! WARNING
Ex) Installation of 6 indoor units • A branch pipe of HR unit allows up to 14.1 kW (48 kBtu/h) based
Consists of HR unit for 4 branches and HR unit for 2 branches. on cooling capacity of the indoor unit.
(up to 14.1 kW (48 kBtu/h) for max installation)
• The maximum total capacity of indoor units connected to a
PRHR042 or PRHR042A HR unit is 56.4 kW (192 kBtu/h).
• The maximum number of indoor units connected to a PRHR042
2 3
1 1
2 or PRHR042A HR unit are 32 indoor units. (The Maximum indoor
units per a branch pipe of HR unit are 8 indoor units)
• There is not operate “Auto-changeover” & “Mode override”
PRHR022 or PRHR022A PRHR032 or PRHR032A function in the zoning group.
(2 branches) (3 branches) • When there are operating indoor units on cooling(heating) mode,
another indoor units aren’t changed on heating(cooling) mode in
the zoning group.

3 4
1 2

PRHR042 or PRHR042A
(4 branches)
15

ENGLISH
[Reducers for indoor unit and HR unit]
Unit : mm (inch) A
Gas pipe
Models Liquid pipe
High pressure Low pressure

Indoor unit –
reducer OD 9.52(3/8) Ø 6.35(1/4)
OD 15.88(5/8) Ø 12.7(1/2)

PRHR022 OD 19.05(3/4) Ø 15.88(5/8) Ø 12.7(1/2) OD 22.2(7/8) Ø 19.05(3/4) Ø 15.88(5/8) A To Outdoor Unit


PRHR022A OD 9.52(3/8) Ø 6.35(1/4) B Sealed Piping

OD 12.7(1/2) Ø 9.52(3/8) OD 15.88(5/8) Ø 12.7(1/2)

HR unit
reducer
A

PRHR032,
PRHR042 OD 22.2(7/8) Ø 19.05(3/4) Ø 15.88(5/8) OD 28.58(1-1/8) Ø 22.2(7/8) Ø 19.05(3/4) B
PRHR032A,
PRHR042A OD 15.88(5/8) Ø 12.7(1/2) Ø 9.52(3/8)

OD 15.88(5/8) Ø 12.7(1/2)
OD 19.05(3/4) Ø 15.88(5/8)

1 Use the following materials for refrigerant piping.


- Material: Seamless phosphorous deoxidized copper pipe 9 The Multi V will stop due to an abnormality like excessive or
- Wall thickness : Comply with the relevant local and national insufficient refrigerant. At such a time, always properly charge the
regulations for the designed pressure 3.8 MPa unit. When servicing, always check the notes concerning both the
(551 psi). We recommend the following table as piping length and the amount of additional refrigerant.
the minimum wall thickness. 10 Never perform a pump down. This will not only damage the
compressor but also deteriorate the performance.
Outer diameter 6.35 9.52 12.7 15.88 19.05 22.2 25.4 28.58 31.8 34.9 38.1 41.3 44.45 53.98
[mm(inch)] (1/4) (3/8) (1/2) (5/8) (3/4) (7/8) (1) (1-1/8) (1-1/4) (1-3/8) (1-1/2) (1-5/8) (1-3/4) (2-1/8) 11 Never use refrigerant to perform an air purge. Always evacuate air
by using a vacuum pump.
Minimum 12 Always insulate the piping properly. Insufficient insulation will
0.8 0.8 0.8 0.99 0.99 0.99 0.99 0.99 1.1 1.21 1.35 1.43 1.55 2.1
thickness result in a decline in heating/cooling performance, drip of
(0.03) (0.03) (0.03) (0.04) (0.04) (0.04) (0.04) (0.04) (0.04) (0.05) (0.05) (0.06) (0.06) (0.08)
[mm(inch)]
condensate and other such problems.
2 Commercially available piping often contains dust and other 13 When connecting the refrigerant piping, make sure the service
materials. Always blow it clean with a dry inert gas. valves of the Outdoor Unit is completely closed (the factory
3 Use care to prevent dust, water or other contaminants from entering setting) and do not operate it until the refrigerant piping for the
the piping during installation. Outdoor and Indoor Units has been connected, a refrigerant
leakage test has been performed and the evacuation process has
4 Reduce the number of bending portions as much as possible, and been completed.
make bending radius as big as possible.
14 Always use a non-oxidizing brazing material for brazing the parts
5 Always use the branch piping set shown below, which are sold and do not use flux. If not, oxidized film can cause clogging or
separately. damage to the compressor unit and flux can harm the copper
piping or refrigerant oil.
Header
Y branch
4 branches 7 branches 10 branches ! WARNING
ARBLB01621, ARBLB03321, ARBL054 ARBL057 ARBL1010 When installing and moving the air conditioner to another site, be
ARBLB07121, ARBLB14521, sure to make recharge refrigerant after perfect evacuation.
ARBLB23220 ARBL104 ARBL107 ARBL2010 • If a different refrigerant or air is mixed with the original
refrigerant, the refrigerant cycle may malfunction and the unit
6 If the diameters of the branch piping of the designated refrigerant may be damaged.
piping differs, use a pipe cutter to cut the connecting section and • After selecting diameter of the refrigerant pipe to suit total
then use an adapter for connecting different diameters to connect capacity of the indoor unit connected after branching, use an
the piping. appropriate branch pipe set according to the pipe diameter of the
7 Always observe the restrictions on the refrigerant piping (such as indoor unit and the installation pipe drawing.
rated length, difference in height, and piping diameter).
Failure to do so can result in equipment failure or a decline in
heating/cooling performance.
8 A second branch cannot be made after a header. (These are shown
by .)
16
ENGLISH

PIPE CONNECTIONS BETWEEN Remove leakage prevention cap


• Remove the leakage prevention cap attached to the outdoor unit
INDOOR AND OUTDOOR UNIT service valve before pipe work.
• Proceed the leakage prevention cap removal as follows:
- Pipe connections can be done on the front side or on the side - Verify whether all the pipes are locked.
according to the installation environments. - Extract remaining refrigerant or air inside using the service port.
- Remove the leakage prevention cap
- Be sure to let 0.2 kgf/cm2 (2.8 psi) Nitrogen flow in the pipe when
welding. Service Port

- If Nitrogen was not flown during welding, many oxidized membranes


may form inside the pipe and disturb the normal operations of valves
and condensers.

Liquid pipe
Not used
(keep closed)
Regulator
Refrigerant Pipe Gas pipe
Right
Side Pipe Nitrogen
Draw Out Direction
Taping Valve

Nitrogen
Left Side Leakage
Pipe Draw Prevention Cap
Out Front Pipe Draw Out

Pipe Drawing Out during Single / Series connection


For Heat Pump System Installation
Method of drawing out pipes on the front side
- Proceed with the pipe work as shown in the below figure for front
Preparation Work side pipe drawing out.
- Use Knock Outs of Base Pan of the outdoor unit for Left/Right or High Pressure
Liquid pipe
Bottom pipe drawing outs. Gas pipe

Knock Out for low


pressure gas pipe

Knock Out for high


Knock Out for pressure gas pipe
Liquid pipe
Liquid pipe
Gas pipe

Knock Out for


Removal area for pipes Knock Out for power supply cable Chassis UXA UXB
bottom side connections. communication cable

! CAUTION
• Do not give damage to the pipe/base during the Knock Out
work.
• Proceed to pipe work after removing burr after Knock Out work.
• Perform sleeve work to prevent damage to the wire when
connecting wires using Knock Outs. A

HP 8 10 12 14/16 18/20/22 24/26


A(mm) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)
28.58
C(mm) 19.05(3/4) 19.05(3/4) 19.05(3/4) 22.2(7/8) 22.2(7/8)
(1-1/8)
* Elbow is Field supplied
17

ENGLISH
Method of drawing out pipes on the bottom side Series Outdoor Units (2 Units ~ 4 Units)
- Drawing out common pipe through side panel
Y branch method Slave 3
ODU Capacity
Master ≥ Slave 1 ≥ Slave 2 ≥ Slave 3
Liquid pipe Low Pressure Gas pipe Slave 2

Ⓐ : Outdoor Unit
Slave 1 Indoor
Master Slave 3
10 m or Slave 2 Unit

Ⓑ : 1st branch (Y branch)


less Slave 1
Master
Ⓒ : Indoor Units
Ⓓ : Downward Indoor Unit
Ⓔ : Connection branch
High Pressure Gas pipe pipe between Outdoor L 150 m [492 ft] (200 m [656 ft])

H 110 m [361 ft]


units: ARCNN41 l 40 m [131 ft] (90 m [295 ft])

Ⓕ : Connection branch
pipe between Outdoor
units : ARCNN31 h 40 m (131 ft)

Ⓖ : Connection branch
h * : See Table 4
pipe between Outdoor
units : ARCNN21

Remove Knock Out for the pipes


Combination of Y branch/ ODU Capacity
Master ≥ Slave 1 ≥ Slave 2 ≥ Slave 3
Slave 3
h Please weld with the proper Low pressure Gas pipe included with header Method Slave 2 Slave 3
Slave 2
Slave 1
Master
Ⓐ : Outdoor Unit
Slave 1
product. 10 m or
less Master
Ⓑ : 1st branch(Y branch)
Ⓒ : Y branch
Ⓓ : Indoor Unit
Refrigerant piping system Ⓔ : Connection branch pipe

H 110 m [361 ft]


between Outdoor
units : ARCNN41 L 150 m [492 ft] (200 m [656 ft])
1 Outdoor Units

h 40 m (131 ft)
Ⓕ : Connection branch pipe l 40 m [131 ft] (90 m [295 ft]

between Outdoor
Y branch method units : ARCNN31
Indoor
Unit
Ⓖ : Connection branch pipe h * : See Table 4
Ⓐ : Outdoor Unit between Outdoor
Ⓑ : 1st branch (Y branch) units : ARCNN21
Ⓗ : Header
Ⓒ : Indoor Units
L 150 m [492 ft] (200 m [656 ft]) Ⓘ : Sealed piping
H 110 m [361 ft]

l 40 m [131 ft] (90 m [295 ft])

Header Method Slave 3 ODU Capacity


Slave 2 Master ≥ Slave 1 ≥ Slave 2 ≥ Slave 3
h 40 m [131 ft] Ⓐ : Outdoor Unit 10 m or
Slave 1
Master Slave 3

Ⓑ : Header branch
Slave 2
less Slave 1
h * : See Table 4 Master
Ⓒ : Indoor Units
Ⓓ : Sealed piping
Ⓔ : Connection branch pipe
Combination of Y between Outdoor
H 110 m [361 ft]

L 200 m [656 ft]


branch/header Method units : ARCNN41 l 40 m [131 ft]

Ⓕ : Connection branch pipe


Ⓐ : Outdoor Unit between Outdoor
Ⓑ : 1st branch (Y branch) units : ARCNN31 h 40 m (131 ft)

Ⓖ : Connection branch pipe


Ⓒ : Y branch
H 110 m [361 ft]

between Outdoor
Ⓓ : Indoor Unit L 150 m [492 ft] (200 m [656 ft]) units : ARCNN21
h 40 m(131 ft)

Ⓔ : Header l 40 m [131 ft] (90m [295 ft])

Ⓕ : Sealed piping

h * : See Table 4

Header Method
Ⓐ : Outdoor Unit
Ⓑ : 1st branch
Ⓒ : Indoor Units
L 200 m [656 ft]
Ⓓ : Sealed piping
H 110 m [361 ft]

l 40 m [131 ft]
Ⓔ : Header

h 40 m [131 ft]
18
ENGLISH

Pipe Connection Method between outdoor (Table 2) Refrigerant pipe diameter from outdoor unit to first branch. (A)
unit/indoor unit Pipe diameter when pipe Pipe diameter when pipe Pipe diameter when height
Slave 1 ODU length is < 90 m (295 ft) length is ≥ 90 m (295 ft) differential (ODU↔IDU) is > 50 m
Master capacity (Standard) (164 ft)
Slave 2 Slave 3
(hp) Liquid Pipe Gas Pipe Liquid Pipe Gas Pipe Liquid Pipe Gas Pipe
mm (inch) mm (inch) mm (inch) mm (inch) mm (inch) mm (inch)
H1 8 Ø 9.52 (3/8) Ø 19.05 (3/4) Ø 12.7 (1/2) Ø 22.2 (7/8) Ø 12.7 (1/2) Not increased
L2
10 Ø 9.52 (3/8) Ø 22.2 (7/8) Ø 12.7 (1/2) Ø 28.58 (1-1/8) Ø 12.7 (1/2) Not increased
L3

E F G 12~16 Ø 12.7 (1/2) Ø 28.58 (1-1/8) Ø 15.88 (5/8) Ø 34.9 (1-3/8) Ø 15.88 (5/8) Not increased
Indoor
Unit L1 18~22 Ø 15.88 (5/8) Ø 28.58 (1-1/8) Ø 19.05 (3/4) Ø 34.9 (1-3/8) Ø 19.05 (3/4) Not increased
1st branch 24 Ø 15.88 (5/8) Ø 34.9 (1-3/8) Ø 19.05 (3/4) Ø 41.3 (1-5/8) Ø 19.05 (3/4) Not increased
l 40 m (131 ft) Refrigerant pipe diameter from outdoor unit to first branch
26~34 Ø 19.05 (3/4) Ø 34.9 (1-3/8) Ø 22.2 (7/8) Ø 41.3 (1-5/8) Ø 22.2 (7/8) Not increased
36~60 Ø 19.05 (3/4) Ø 41.3 (1-5/8) Ø 22.2 (7/8) Ø 44.5 (1-3/4) Ø 22.2 (7/8) Not increased
62~64 Ø 22.2 (7/8) Ø 44.5 (1-3/4) Ø 25.4 (1) Ø 53.98 (2-1/8) Ø 25.4 (1) Not increased
h 40 m (131 ft)
66~96 Ø 22.2 (7/8) Ø 53.98 (2-1/8) Ø 25.4 (1) Ø 53.98 (2-1/8) Ø 25.4 (1) Not increased

h See Table 2
A : Refrigerant pipe diameter from outdoor unit to first branch (Table 3) Refrigerant pipe diameter from first branch to last branch (B,C,D)
E : Refrigerant pipe diameter for outdoor unit capacity Downward indoor unit Liquid pipe Gas pipe
(Slave 1+ Slave 2+ Slave 3) total capacity [kW(Btu/h)] [mm(inch)] [mm(inch)]
F : Refrigerant pipe diameter for outdoor unit capacity ≤ 5.6(19 100) Ø 6.35(1/4) Ø 12.7(1/2)
(Slave 2+ Slave 3)
< 16.0 (54 600) Ø 9.52(3/8) Ø 15.88(5/8)
G : Refrigerant pipe diameter for outdoor unit capacity(Slave 3)
≤ 22.4 (76 400) Ø 9.52(3/8) Ø 19.05(3/4)
< 33.6 (114 700) Ø 9.52(3/8) Ø 22.2(7/8)
Level Difference
5 m [16.4 ft] < 50.4 (172 000) Ø 12.7(1/2) Ø 28.58(1-1/8)
(Outdoor unit ↔ Outdoor unit)
Less than 10 m [32.8 ft] < 67.2 (229 400) Ø 15.88(5/8) Ø 28.58(1-1/8)
Max length from first branch to < 72.8(248 500) Ø 15.88(5/8) Ø 34.9(1-3/8)
(equivalent length of piping 13 m
each outdoor unit (L1, L2, L3)
[42.7 ft]) < 100.8(344 000) Ø 19.05(3/4) Ø 34.9(1-3/8)
< 173.6(592 500) Ø 19.05(3/4) Ø 41.3(1-5/8)
< 184.8(630 700) Ø 22.2(7/8) Ø 44.5(1-3/4)
(Table 1) Limit Pipe length ≤ 224.0(764 400) Ø 22.2(7/8) Ø 53.98(2-1/8)
Y branch Combination of Y Header
branch/header
Method Method Method (Table 4) Conditional Application
Longest A + B + C + D + e ≤ A + B + b ≤ 150 m [492 ft] • To satisfy below condition to make 40 m~90 m of pipe length after first branch.
150 m [492 ft] A + C + e ≤ 150 m [492 ft] A + f ≤ 200 m
pipe (200 m [656 ft] : (200 m [656 ft] : Conditional [656 ft] Condition Example
Outdoor Unit length(L) Conditional application)* application)*
Max pipe Diameter of pipes between Ø 6.35(1/4) ’ Ø 9.52(3/8), Ø 9.52(3/8) ’
↔ Equivalent 175 m [574 ft] 175 m [574 ft] 225 m Ø 12.7(1/2), Ø 12.7(1/2) ’ Ø 15.88(5/8),
length (225 m [738 ft] : (225 m [738 ft] : first branch and the last 40 m [131 ft] < B + C +
Indoor Unit pipe length Conditional application)* Conditional application)* [738 ft] Ø 15.88(5/8) ’ Ø 19.05(3/4), Ø 19.05(3/4)
branch should be increased D+e ’ Ø 22.2(7/8), Ø 22.2(7/8) ’ Ø 25.4(1), Ø
1
Total pipe 1 000 m by one step, except pipe 90 m [295 ft] ’ B, C, D 25.4(1) ’ Ø 28.58(1-1/8), Ø 28.58(1-1/8)
1 000 m [3281 ft] 1 000 m [3 281 ft] diameter B, C, D is same Change a diameter ’ Ø 31.8(1-1/4), Ø 31.8(1-1/4) ’ Ø
length [3 281 ft]
as Diameter A 34.9(1-3/8), Ø 34.9(1-3/8) ’ Ø 38.1(1-1/2)
Outdoor Unit Difference in
Max 110 m [361 ft] 110 m [361 ft] 110 m [361 ft]
↔ Indoor Unit height(H) While calculating whole
A+Bx2+Cx2+Dx2
difference refrigerant pipe length, pipe
in height Indoor Unit Difference in 2 +a+b+c+d+e≤
40 m [131 ft] 40 m [131 ft] 40 m [131 ft] B, C, D length should be
↔ Indoor Unit height(h) 1 000 m [3 281 ft]
calculated twice.
Indoor
Longest pipe Pipe 40 m [131 ft] 40 m [131 ft] Length of pipe from each
Unit

length after (90 m [295 ft] : (90 m [295 ft] : 40 m [131 ft] a, b, c, d, e ≤ 40
length(l) Conditional application)* Conditional application)* 3 indoor unit to the closest
1st branch m [131 ft]
branch L
h * : See Table 4
H 110 m [361 ft]

l
Length of pipe from
outdoor unit to the
! WARNING farthest indoor unit 5 (A + (A + B + C + D + e)-
4 B + C + D + e)] - [Length (A + a) ≤ 40 m [131 h 40 m [131 ft]

Increased Pipe Diameter(table 2) of pipe outdoor unit to the ft]


closest indoor unit 1 (A +
- When pipe length is 90 m [295 ft] or more from ODU to 1st a)] ≤ 40 m [131 ft]
branch
- When level difference is 50 m [164 ft] or more
19

WARNING CAUTION

ENGLISH
! !
• In case of pipe diameter B connected after first branch is bigger • Bending radius should be 500 mm [19.7 inch] 500 mm [19.7 inch]
than the main pipe diameter A, B should be of the same size at least twice the diameter or more or more

with A. of the pipe.


• Bend pipe after 500 mm
Ex) In case indoor unit combination ratio 120 % is connected to
[19.7 inch] or more from
24HP(67.2 kW) outdoor unit. branch(or header).
1) Outdoor unit main pipe diameter A : Ø 34.9(1-3/8)(Gas Do not bend U type. R

pipe), Ø 15.88(5/8)(liquid pipe) It may affect performance


2) Pipe diameter B after first branch according to 120 % or result in noise. If U type
indoor unit combination(80.6kW) : Ø 34.9(1-3/8)(gas pipe), bending is required the R
Ø 19.05(3/4)(liquid pipe) should be more than 200
Therefore, pipe diameter B connected after first branch mm [7.9 inch]
would be Ø 34.9(1-3/8)(gas pipe) / Ø 15.88(5/8)(liquid pipe)
which is same with main pipe diameter.

Pipe Connection Method/Precautions for


Series connections between Outdoor units
Outdoor unit Connection
- Separate Y branch joints are needed for series connections between

WARNING
outdoor units.
! - Please refer to the below connection examples to install pipe
• In case of pipe diameter B connected after first branch is bigger connections between outdoor units.
than the main pipe diameter A, B should be of the same size
with A.
Ex) In case indoor unit combination ratio 120 % is connected to Pipe connection between outdoor
70 kW outdoor unit. units (General Case)
1) Outdoor unit main pipe diameter A : Ø 34.9(1-3/8))(Low
pressure gas pipe), Ø 15.88(5/8)(liquid pipe), Ø 28.58(1- The maximum pipe
length after the first
1/8)(High Pressure liquid pipe) branching between the
2) Pipe diameter B after first branch according to 120 % outdoor units is 10 m
[32.8 ft] or less
indoor unit combination(84 kW) : Ø 34.9(1-3/8)(Low
pressure gas pipe), Ø 19.05(3/4)(liquid pipe), Ø 28.58(1-
1/8)(High Pressure liquid pipe)
Therefore, pipe diameter B connected after first branch Pipes between outdoor units
would be Ø 34.9(1-3/8)(Low pressure gas pipe), Ø are 2 m [6.6 ft] or less
15.88(5/8)(liquid pipe), Ø 28.58(1-1/8)(High Pressure liquid
pipe) which is same with main pipe diameter.

2 m [6.6 ft] or less


[Example]
Do not choose the main pipe diameter by downward indoor unit
total capacity but its outdoor unit model name.
Pipes between outdoor units
Do not let the connection pipe from branch to branch exceed the
main pipe diameter chosen by outdoor unit model name. are 2 m [6.6 ft] or longer
EX) Where connecting the indoor units to the 22 HP (61.5 kW) Oil Trap
outdoor unit to 120 % of its system capacity (73.8 kW) and 0.2 m [0.66 ft]
2 m [6.6 ft] or less
branching 7 k (2.1 kW) indoor unit at the 1st branch 2 m [6.6 ft] or longer
Main pipe diameter(22 HP outdoor unit): Ø 28.58(1-1/8)(Low
pressure gas pipe), Ø 15.88(5/8)(Liquid pipe), Ø 22.2(7/8)(High
pressure gas pipe)
Pipe diameter between 1st and 2nd branch (71.7 kW indoor Oil Trap Oil Trap
units): Ø 34.9(1-3/8)(Gas pipe) Ø 19.05(3/4)(Liquid pipe) in
2 m [6.6 ft] or less 2 m [6.6 ft] or less
conformity with Downward indoor units. 2 m [6.6 ft] or longer 2 m [6.6 ft] or longer
Since the main pipe diameter of 22HP outdoor unit is Ø 28.58(1-
1/8)(Low pressure gas pipe), Ø 15.88(5/8)(Liquid pipe), Ø 22.2(7/8)
- If the distance between the outdoor units becomes more than 2 m
(High pressure gas pipe) is used as the main pipe and the
connection pipe between 1st and 2nd branch. [6.6 ft], apply Oil Traps between the gas pipes.
- If the outdoor unit is located lower than the main pipe, apply Oil Trap.

Indoor Unit Connection

Indoor Unit connecting pipe from branch (a,b,c,d,e,f)

Indoor Unit capacity Liquid pipe


Gas pipe [mm(inch)]
[kW(Btu/h)] [mm(inch)]
≤ 5.6(19 100) Ø 6.35(1/4) Ø 12.7(1/2)
< 16.0(54 600) Ø 9.52(3/8) Ø 15.88(5/8)
< 22.4(76 400) Ø 9.52(3/8) Ø 19.05(3/4)
< 28.0(95 900) Ø 9.52(3/8) Ø 22.2(7/8)
20
ENGLISH

Examples of Wrong Pipe Connections - When connecting the pipes between the outdoor units, the
accumulation of oil in the slave outdoor unit should be avoided.
Otherwise, the unit may not operate properly.
If the main pipe is
higher than the (Example 1)
outdoor units, oil is Oil Trap
accumulated in the
outdoor unit.

Toward indoor unit Toward indoor unit

(Example 2)
If there are differences in the height
between the outdoor units, oil is
accumulated in the lower outdoor unit.

(Example 1)

Toward indoor unit Toward indoor unit


Toward indoor unit

(Example 2)
(Example 3)

Toward indoor unit Pipe inclination (2° or more)


Toward indoor unit
Oil Trap
(Example 3) h h

0.2 m [0.66 ft]


Toward indoor unit Toward indoor unit

Toward indoor unit

Toward indoor unit

- Apply Oil Trap as shown below when the length of the pipe between
the outdoor units is more than 2 m [6.6 ft]. Otherwise, the unit may
not operate properly.

(Example 1)

Toward indoor unit 2m

(Example 2)
0.2 m [0.66 ft]

Oil Trap

Toward indoor unit 2 m [6.6 ft]


2 m [6.6 ft]
21

ENGLISH
Branch pipe Fitting • Header should be insulated with the insulator in each kit.

Y branch
Insulate the header using

Ⓐ To Outdoor Unit
the insulation
material attached to the
B branch pipe kit

A
Ⓑ To Branch Piping or Indoor Unit as shown in the figure.

• Ensure that the branch pipes are attached horizontally or vertically


(see the diagram below.)

-3° +3° -3° +3°


Vertical DOWN
Straight-through Leg Branch Leg Configuration for
Indoor Unit
Y-Branches.
±5° • Joints between branch and pipe should be sealed with the tape
Horizontal included in each kit.
Plane Vertical UP
Configuration for Tape
±5° Indoor Unit
Y-Branches.
Y-branch Inlet

Insulator
Outdoor Unit is Permitted. Outdoor Unit is Not Permitted.

Outdoor unit Y-branches can only be installed in a horizontal or vertical Insulator of field pipe

UP configuration.
The vertical DOWN configuration is not permitted.
• Any cap pipe should be insulated using the insulator provided with
• There is no limitation on the joint mounting configuration.
each kit and then taped as described above.
• If the diameter of the refrigerant piping selected by the procedures
described is different from the size of the joint, the connecting
Insulator for cap pipe
section should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulator in each kit.
Tape
Cap pipe
(field supply) Tape

Liquid and gas Insulator for


Y branch pipe [Unit:mm(inch)]
Insulator pipe joints field piping
(included with kit)
Models Gas pipe Liquid pipe
I.D 12.7(1/2)
Header I.D 15.88(5/8)
I.D 12.7(1/2)
I.D 15.88(5/8)
I.D 9.52(3/8)
I.D 6.35(1/4)
I.D 6.35(1/4)
I.D 9.52(3/8)

Ⓐ To Outdoor Unit 1 1
A I.D 15.88(5/8) 74 I.D 6.35(1/4) 74

Ⓑ To Indoor Unit ARBLN01621


I.D 12.7(1/2) (2-29/32) I.D 9.52(3/8) (2-29/32)

281(11-1/16) 281(11-1/16)
292(11-1/2) 292(11-1/2)

• The indoor unit having larger I.D 19.05(3/4) I.D 12.7(1/2)


1 O.D 9.52(3/8)
capacity must be installed closer 1
70(2-3/4)
O.D 15.88(5/8)
70(2-3/4)

to Ⓐ than smaller one.


B
• If the diameter of the refrigerant I.D 22.2(7/8) I.D 19.05(3/4)

piping selected by the I.D 25.4(1) I.D 19.05(3/4) I.D 15.88(5/8) I.D 12.7(1/2)
2
I.D 12.7(1/2)
1 I.D 9.52(3/8) I.D 6.35(1/4)
procedures described is I.D 19.05(3/4) I.D 12.7
I.D 15.88(5/8)
83
(1/2) (3-9/32)
I.D 9.52(3/8)

different from the size of the I.D 12.7(1/2) 74


ARBLN03321 390(15-11/32)
413(16-1/4)
3 I.D 12.7(1/2) I.D 9.52(3/8) I.D 6.35(1/4) (2-29/32)

C joint, the connecting section I.D 22.2(7/8) I.D 28.58(1-1/8) I.D 22.2(7/8) 321(12-5/8)
should be cut with a pipe cutter. O.D 19.05(3/4) O.D 25.4(1) O.D 19.05(3/4)
I.D 25.4(1)
332(13-1/16)

3 1 2

ⓒ Pipe cutter
70(2-3/4) 80(3-5/32) 110(4-11/32)

I.D 19.05(3/4) I.D 15.88(5/8) I.D 19.05(3/4)


• When the number of pipes to be I.D 28.58(1-1/8) I.D 22.2(7/8) I.D 15.88(5/8)
2
I.D 12.7(1/2) I.D 15.88(5/8) I.D 12.7(1/2)
2
connected is smaller than the 1
I.D 15.88(5/8) I.D 12.7 96
I.D 19.05(3/4)
I.D 15.88(5/8) I.D 12.7(1/2)
I.D 19.05(3/4)
83
I.D 31.8(1-1/4) (3-9/32)
number of header branches, I.D 19.05(3/4) (1/2) (3-25/32)

3
376(14-13/16) 371(14-19/32)
install a cap to the unconnected ARBLN07121 404(15-29/32)
3
394(15-1/2)

branches. I.D 28.58(1-1/8)


I.D 34.9(1-3/8)
O.D 19.05(3/4)
I.D 22.2(7/8)
O.D 12.7(1/2)
I.D 9.52(3/8)
I.D 9.52(3/8)
O.D 22.2(7/8) I.D 31.8(1-1/4) O.D 31.8(1-1/4) I.D 28.58(1-1/8) I.D 6.35(1/4) O.D 12.7(1/2)
2 1 3 3 2

120(4-23/32) 90(3-17/32) 120(4-23/32) 110(4-11/32) 70(2-3/4)


• When the number of indoor units to be connected to the branch
pipes is less than the number of branch pipes available for I.D 34.9(1-3/8)
I.D 41.3(1-5/8)
I.D 34.9(1-3/8)
I.D 38.1(1-1/2) I.D 28.58(1-1/8)

connection then cap pipes should be fitted to the surplus branches. 2 I.D 15.88(5/8)
I.D 19.05(3/4)
I.D 19.05(3/4)
I.D 22.2(7/8) I.D 15.88(5/8)
2
I.D 28.58(1-1/8) I.D 22.2 1
I.D 38.1(1-1/2) I.D 34.9(1-3/8) (7/8) 125
(4-29/32) I.D 15.88(5/8) I.D 12.7 96
I.D 22.2(7/8) I.D 19.05(3/4) (1/2)
(3-25/32)
471(18-17/32) 3
517(20-11/32)
41616-3/8) 3
ARBLN14521 I.D 19.05(3/4) I.D 41.3(1-5/8)
444(17-15/32)
O.D 22.2(7/8) I.D 15.88(5/8)
O.D 38.1(1-1/2) O.D 34.9(1-3/8) I.D 38.1(1-1/2) I.D 9.52(3/8)
I.D 12.7(1/2) O.D 19.05(3/4)
3 2 3 I.D 41.3 O.D 15.88(5/8) I.D 9.52(3/8) I.D 22.2(7/8) O.D 12.7(1/2) I.D 6.35(1/4)
(1-5/8)
120(4-23/32) 90(3-17/32) 130(5-1/8) 2 3 3
I.D 12.7(1/2)
O.D 28.58(1-1/8) I.D 22.2(7/8) 110(4-11/32) 80(3-5/32) 110(4-11/32)
3
B O.D 15.88(5/8)
2 I.D 19.05(3/4)

70(2-3/4) 120(4-23/32)

Pinched pipe
I.D 44.48(1-3/4)
I.D 53.98(2-1/4) I.D 41.3(1-5/8) I.D 38.1(1-1/2) I.D 25.4(1)
I.D 25.4(1) I.D 22.2(7/8) I.D 22.2(7/8) I.D 19.05(3/4)
2
1 2
I.D 44.48(1-3/4)
• Fit branch pipe lie in a horizontal plane. I.D 44.48(1-3/4) I.D 41.3(1-5/8) I.D 38.1(1-1/2) 134 I.D 25.4(1)
I.D 22.2(7/8) I.D 19.05(3/4) 96(3-25/32)
420(16-17/32) 3
490(19-9/32) 346(13-5/8) 3
ARBLN23220 I.D 34.9(1-3/8)
I.D 31.8(1-1/4) I.D 53.98(2-1/4) I.D 25.4(1)
379(14-29/32)
O.D 38.1(1-1/2) I.D 28.58(1-1/8) O.D 44.48(1-3/4) I.D 22.2(7/8)
O.D 28.58(1-1/8)
Horizontal plane 2 3 X2 2 3 X2 3 I.D 15.88(5/8) I.D 9.52(3/8)
O.D 19.05(3/4) O.12.7(1/2) O.12.7(1/2) I.D 6.35(1/4)
175(6-7/8) 100(4-11/32) 115(4-17/32)
I.D 12.7(1/2) I.D 19.05(3/4) 2 3 X2 3
I.D 15.88(5/8)
3 3
O.D 15.88(5/8) O.D 22.2(7/8) 110(4-11/32) 110(4-11/32)
70(2-3/4) 120(4-23/32)

View from point B in the direction of the arrow


22
ENGLISH

Header Distribution Method


[Unit:mm(inch)]
Horizontal Distribution
Models Gas pipe Liquid pipe
Slave
360 360(14-5/32) Master
120 ID 9.52(3/8)
ID 9.52(3/8) 120(4-23/32)
ID 12.7 ID 9.52(3/8) ID 6.35(1/4)
ID 9.52(3/8)
ID 6.35(1/4)
4 branch ID 12.7
IDID9.52(3/8)
ID9.52(3/8)
9.52(3/8) 9.52(3/8) ID 9.52(3/8) 150
ID 15.88 150 IDID9.52(3/8) ID
ID 9.52(3/8)
9.52(3/8) 120
120 ID 9.52(3/8) (5-29/32)
ARBL054 ID 15.88 (4-23/32)

Slave 3rd main pipe distribution


ID 19.05 ID 15.88 ID 12.7(1/2) ID 9.52(3/8)
1st 2nd Master
540 540(21-1/4)
120 120(4-23/32)
ID 12.7 ID 6.35(1/4)

7 branch ID 12.7
ID 15.88 150 ID 9.52(3/8) 150
ARBL057
ID 15.88 120 120
(4-23/32)
(5-29/32) Slave
Master 1st 2nd 3rd
ID 19.05 ID 15.88 ID 12.7(1/2) ID 9.52(3/8)

400 360(14-5/32)
160 ID 9.52(3/8)
ID 9.52(3/8)
120(4-23/32)
ID 15.88 ID 6.35(1/4)
ID 9.52(3/8)
ID 6.35(1/4)ID 9.52(3/8)
ID 12.7
4 branch ID 19.05 ID 9.52(3/8) 150 1st 2nd 3rd
150 IDID9.52(3/8)
ID9.52(3/8)
9.52(3/8) 9.52(3/8) 120
120 IDID9.52(3/8) ID
ID 9.52(3/8)
ID 9.52(3/8)9.52(3/8)
ID 15.88 (4-23/32) (5-29/32)
ARBL104 1st
Main pipe
ID 28.58 ID 25.4 ID 22.2 ID 12.7(1/2) ID 9.52(3/8) Distribution

ID 12.7 ID 12.7 ID 6.35(1/4)


ID 6.35(1/4) 700(27-9/16)
3rd
580
ID 12.7 ID 6.35(1/4) ID 6.35(1/4) 120(4-23/32)
Main pipe
ID 12.7 160
ID 15.88ID 15.88 ID 15.88 ID 9.52(3/8) ID 9.52(3/8) ID 6.35(1/4) Distribution
7 branch ID 15.88
ID12.7
12.7 ID
IDID12.7
ID12.7
ID
ID 12.7ID
12.7
15.88
ID 12.7
12.7
ID 9.52(3/8)
IDID6.35(1/4)
IDID6.35(1/4)
ID6.35(1/4)
6.35(1/4)
ID
6.35(1/4)
ID 9.52(3/8)
ID 6.35(1/4)
ID 6.35(1/4)6.35(1/4)
150
ID 19.05 150 ID 9.52(3/8) ID 9.52(3/8) 120
15.88IDID15.88
ID15.88 15.88 IDID9.52(3/8)
9.52(3/8) (5-29/32)
ARBL107
IDID15.88 ID
ID 15.88ID 15.88
15.88
120 ID 9.52(3/8)
ID 9.52(3/8)ID
ID 9.52(3/8)
9.52(3/8)
ID 9.52(3/8) (4-23/32)

ID 28.58 ID 25.4 ID 22.2 ID 12.7(1/2) ID 9.52(3/8) Vertical Distribution


760 720(28-11/32) - Ensure that the branch pipes are attached vertically.
160 120(4-23/32)
ID 15.88 ID 6.35(1/4) ID 6.35(1/4)
10 branch ID 12.7

ID 19.05 150
ID 9.52 ID 9.52
ID(3/8)
9.52 (3/8) ID 9.52
120
150
(5-29/32)
Slave
ARBL1010 ID 15.88 120
(3/8) (3/8)
(4-23/32)
Master
9.52 IDID9.52
ID9.52 9.52
IDID9.52 ID
ID
ID 9.52(3/8)9.52
9.52
(3/8) ID 9.52(3/8) ID 9.52(3/8)
(3/8)
(3/8)
(3/8) (3/8) (3/8)
(3/8) ID 12.7(1/2)
ID 28.58 ID 25.4 ID 22.2

700(27-9/16)
775 107
182 60*9 = 540(21-1/2) (4-7/32)
ID 15.88 ID 6.35(1/4)
10 branch ID 12.7
ID 6.35 ID 6.35
ID(1/4)
6.35 (1/4) ID 6.35
150
(1/4) 120
ID 19.05 150 (1/4)
(4-23/32) (5-29/32)
ARBL2010 ID 15.88 120 ID 9.52 ID 9.52
IDID ID6.35
(3/8)
ID
9.52
6.35ID 6.35
IDID6.35
6.35(3/8)
ID
6.35
ID 6.35
6.35
ID
(1/4) 9.52
(1/4)
(1/4)
(3/8) (1/4)
(1/4) (1/4) (1/4)
(1/4)
(3/8)
ID 9.52(3/8)
9.52 IDID9.52
ID9.52 9.52 ID 19.05(3/4)
ID 31.8 ID 34.9 ID 28.58 IDID9.52 ID
ID
ID 9.52(3/8)9.52
9.52
(3/8)
(3/8)
(3/8) ID 15.88(5/8)
(3/8) (3/8) (3/8)
(3/8)

Slave
Master

The others

Slave
Master

Slave
Master

Header
23

ENGLISH
Vacuum Mode Leak Test and Vacuum drying
This function is used for creating vacuum in the system after Leak test
compressor replacement, ODU parts replacement or IDU Leak test should be made by pressurizing nitrogen gas to 3.8 MPa(38.7
addition/replacement. kgf/cm2). If the pressure does not drop for 24 hours, the system
passes the test. If the pressure drops, check where the nitrogen leaks.
For the test method, refer to the following figure. (Make a test with
Vacuum mode setting method the service valves closed. Be also sure to pressurize liquid pipe, gas
pipe and high pressure gas pipe)
DIP-SW01
The test result can be judged good if the pressure has not be reduced
7-Segment after leaving for about one day after completion of nitrogen gas
SW04C (X : cancel) pressurization.
SW03C (ȯ: forward)
SW02C (ȭ: backward) Series Installation (Heat Recovery)
SW01C (Ɨ: Confirm /
Automatic Addressing)
Slave 1 outdoor unit Master outdoor unit
SW01D (reset)

Close
When inserting nitrogen
gas of high pressure, it
Close
Close
Close Close Close must be used with
Nitrogen Gas
Master unit PCB DIP switch on : No.5 Cylinder regulator.

High Pressure

High Pressure
Low Pressure

Low Pressure
Liquid Pipe

Liquid Pipe
Gas Pipe

Gas Pipe

Gas Pipe

Gas Pipe
Select the mode using ‘▶’, ‘◀’ Button :
Liquid Pipe
“SVC” Push the ‘●’ button Nitrogen Gas
HR unit Indoor
Unit
Cylinder

Gas Pipe

Select the Function using ‘▶’, ‘◀’ Button :


“Se3” Push the ‘●’ button

Series Installation (Heat Pump)


Start the vacuum mode : “VACC”
Slave 1 outdoor unit Master outdoor unit
ODU Valve open
ODU EEV open When inserting nitrogen
Close
gas of high pressure, it
IDU EEV open Close
Close must be used with
Close Close
Close
HR unit valve open, SC EEV open regulator.
No use (closed)

No use (closed)
Liquid Pipe

Liquid Pipe
Gas Pipe

Gas Pipe
Vacuum mode off method Nitrogen Gas Liquid Pipe
Cylinder Indoor
Unit
DIP switch off and push the reset button on Master unit PCB
Gas Pipe

! CAUTION
ODU operation stops during vacuum mode. Compressor can't
operate. ! WARNING
Use a vacuum pump or Inert(nitrogen) gas when doing leakage test
or air purge. Do not compress air or Oxygen and do not use
Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
24
ENGLISH

NOTE Series Installation (Heat Pump)


!
If the ambient temperature differs between the time when pressure is
applied and when the pressure drop is checked, apply the following Slave 1 outdoor unit Master outdoor unit

correction factor
There is a pressure change of approximately 0.01 MPa(1.5 psi) for each Close

33.8 °F (1 °C) of temperature difference.


Close
Correction= (Temp. at the time of pressurization – Temp. at the time of Close
Close
Close
Close
check) X 0.1
For example: Temperature at the time of pressurization 3.8

No use (closed)

No use (closed)
MPa(551 psi) is 80.6 °F (27 °C)

Liquid pipe
Liquid pipe

Gas pipe

Gas pipe
24 hour later: 3.73 MPa(541 psi), 68 °F (20 °C)
In this case the pressure drop of 0.07 MPa Liquid side
Indoor unit
(10 psi) is because of temperature drop
And hence there is no leakage in pipe Scale
Use a graviometer. (One that can measure Gas side
occurred. down to 0.1 kg (0.22 lbs)). If you are
unable to prepare such a high-precision
gravimeter you may use a charge cylinder.

! CAUTION
WARNING
To prevent the nitrogen from entering the refrigeration system in
the liquid state, the top of the cylinder must be at higher position !
than the bottom when you pressurize the system.
Use a vacuum pump or Inert(nitrogen) gas when doing leakage test
Usually the cylinder is used in a vertical standing position. or air purge. Do not compress air or Oxygen and do not use
Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
Vacuum
Vacuum drying should be made from the service port provided on the outdoor
unit’s service valve to the vacuum pump commonly used for liquid pipe, gas ! NOTE
pipe and high/low pressure common pipe. (Make Vacuum from liquid pipe, gas
pipe and high/low pressure common pipe with the service valve closed.) Always add an appropriate amount of refrigerant. (For the refrigerant
* Never perform air purging using refrigerant. additional charge)
Too much or too little refrigerant will cause trouble.
• Vacuum drying: Use a vacuum pump that can evacuate to -100.7 kPa To use the Vacuum Mode (If the Vacuum mode is set, all valves of Indoor
(-14.6 psi, 5 Torr, -755 mmHg). units and Outdoor units will be opened.)
- Evacuate the system from the liquid and gas pipes with a vacuum
pump for over 2 hrs and bring the system to -100.7 kPa(-14.6 psi).

WARNING
After maintaining system under that condition for over 1 hr, confirm
the vacuum gauge rises. The system may contain moisture or leak. !
- Following should be executed if there is a possibility of moisture When installing and moving the air conditioner to another site,
remaining inside the pipe. recharge after perfect evacuation.
(Rainwater may enter the pipe during work in the rainy season or
over a long period of time) - If a different refrigerant or air is mixed with the original
After evacuating the system for 2 hrs, give pressure to the system refrigerant, the refrigerant cycle may malfunction and the unit
to 0.05 MPa(7.3 psi) (vacuum break) with nitrogen gas and then may be damaged.
evacuate it again with the vacuum pump for 1hr to -100.7 kPa(-14.6
psi)(vacuum drying). If the system cannot be evacuated to -100.7
kPa(-14.6 psi) within 2 hrs, repeat the steps of vacuum break and its
drying. Finally, check if the vacuum gauge does not rise or not, after
maintaining the system in vacuum for 1 hr.

Series Installation (Heat Recovery)


Slave 1 outdoor unit Master outdoor unit

Vacuum
pump
Close

Close
Close Close
Close
Close
Low Pressure

Low Pressure
High Pressure

High Pressure
Liquid pipe

Liquid pipe
Gas pipe

Gas pipe
Gas pipe

Gas pipe

Vacuum
pump

Liquid side
HR unit Indoor unit

Gas side
Scale
Use a graviometer. (One that can measure
down to 0.1 kg (0.22 lbs)). If you are
unable to prepare such a high-precision
gravimeter you may use a charge cylinder.
25

ENGLISH
Refrigerant charging The amount of Refrigerant
For Heat Recovery System Installation
The calculation of the additional charge should take into account the
Ⓐ Manifold Gauge length of pipe and CF(correction Factor) value of indoor unit.
Ⓑ Low pressure side Handle
Ⓒ High pressure side Handle Additional charge(kg) = Total liquid pipe : Ø 25.4 mm (1.0 inch) × 0.480 kg/m (0.323 lbs/ft)

+ Total liquid pipe : Ø 22.2 mm (7/8 inch) × 0.354 kg/m (0.238 lbs/ft)

+ Total liquid pipe : Ø 19.05 mm (3/4 inch) × 0.266 kg/m (0.179 lbs/ft)

+ Total liquid pipe : Ø 15.88 mm (5/8 inch) × 0.173 kg/m (0.116 lbs/ft)

+ Total liquid pipe : Ø 12.7 mm (1/2 inch) × 0.118 kg/m (0.079 lbs/ft)

+ Total liquid pipe : Ø 9.52 mm (3/8 inch) × 0.061 kg/m (0.041 lbs/ft)

+ Total liquid pipe : Ø 6.35 mm (1/4 inch) × 0.022 kg/m (0.015 lbs/ft)
Include only for
Heat Recovery + Number of installed HR units × 0.5 kg/EA (1.1 lbs/EA)
Liquid Pipe system
CF value of indoor unit
Low Pressure
Gas Pipe
High Pressure Amount refrigerant of Indoor units
Gas Pipe Example) 4 Way Ceiling Cassette 14.5 kW -1 ea, Ceiling concealed Duct
7.3 kW-2 ea,
Wall Mounted 2.3 kW-4 ea
CF = [0.64 kg (1.411 lbs) × 1 EA] + [0.26 kg (0.573 lbs) × 2 EA]
+ [0.26 kg (0.529 lbs) × 4 EA]
= 2.12 kg (4.67 lbs)
For Heat Pump System Installation
Ⓐ Manifold Gauge
Ⓑ Low Pressure Side Handle Attach the additional refrigerant table of IDU.
Ⓒ High Pressure Side Handle

Liquid Pipe

Not used
(keep closed) ! WARNING
• Regulation for refrigerant leakage
Gas Pipe : the amount of refrigerant leakage should satisfy the following
equation for human safety.

Total amount of refrigerant in the system


≤ 0.44 kg/m3
Volume of the room at which Indoor Unit of (0.028 lbs/ft3)
! WARNING the least capacity is installed

• Pipe to be vacuumed : gas pipe, liquid pipe If the above equation can not be satisfied, then follow the
(In case of Heat Recovery system, pipe to be vacuumed : High following steps.
pressure gas pipe, Low pressure gas pipe, Liquid pipe) • Selection of air conditioning system: select one of the next
• If the refrigerant amount is not exact, it may not operate - Installation of effective opening part
properly. - Reconfirmation of Outdoor Unit capacity and piping length
- Reduction of the amount of refrigerant
• If additionally bottled refrigerant amount is over 10 %, - Installation of 2 or more security device (alarm for gas leakage)
condenser burst or insufficient indoor unit performance may be • Change Indoor Unit type
caused. : installation position should be over 2 m (6.6 ft) from the floor (Wall
mounted type ’ Cassette type)
• Adoption of ventilation system
: choose ordinary ventilation system or building ventilation
system
• Limitation in piping work
: Prepare for earthquake and thermal stress
26
ENGLISH

Thermal insulation of refrigerant piping Penetrations


Inner wall (concealed) Outer wall Outer wall (exposed)
Be sure to give insulation work to refrigerant piping by covering liquid D
pipe and gas pipe separately with enough thickness heat-resistant C E
A B B
polyethylene, so that no gap is observed in the joint between indoor A B
unit and insulating material, and insulating materials themselves. When
insulation work is insufficient, there is a possibility of condensation
drip, etc. Pay special attention to insulation work to ceiling plenum. I

Heat insulation Adhesive + Heat - resistant Floor (fireproofing) Penetrating portion on fire Roof pipe shaft
material polyethylene foam + Adhesive tape
limit and boundary wall
Indoor Vinyl tape D
I
J
Outer Floor Water-proof hemp cloth + F G
exposed Bronze asphalt D
covering
Outdoor Zinc plate +hemp
Water-proof cloth + B
Oily paint
G H A
1m 1m
Ⓐ Heat insulation material B F (3.28 ft) (3.28 ft)

Ⓑ Pipe
Ⓒ Outer covering(Wind the connection part and cutting part of heat Ⓐ Sleeve
insulation material with a finishing tape.) Ⓑ Heat insulating material
Ⓒ Lagging
Ⓓ Caulking material
! NOTE Ⓔ Band
Ⓕ Waterproofing layer
When using polyethylene cover as covering material, asphalt Ⓖ Sleeve with edge
roofing shall not be required. Ⓗ Lagging material
Ⓘ Mortar or other incombustible caulking
Ⓙ Incombustible heat insulation material

Bad example When filling a gap with mortar, cover the penetration part with steel plate so
that the insulation material will not be caved in. For this part, use
• Do not insulate gas or low pressure pipe and liquid or incombustible materials for both insulation and covering. (Vinyl covering
highpressure pipe together. should not be used.)
B Ⓐ Liquid pipe
A F Ⓑ Gas pipe
ⓒ Power lines
C ⓓ Finishing tape
ⓔ Insulating material
D
E ⓕ Communication lines

• Be sure to fully insulate connecting portion.


A

Ⓐ These parts are not insulated.

Good example

C
Power lines Communication lines
D
D
A
Ⓐ Liquid pipe
B
Ⓑ Gas pipe
ⓒ Power lines
E ⓓ Insulating material
Separation
ⓔ Communication lines
27

ENGLISH
For Heat Recovery System Installation Pipe Drawing Out during Single / Series connection
Method of drawing out pipes on the front side
Preparation Work - Proceed with the pipe work as shown in the below figure for front
side pipe drawing out.
- Use Knock Outs of Base Pan of the outdoor unit for Left/Right or
Bottom pipe drawing outs.
High Pressure
Liquid pipe
Gas pipe

Knock Out for low


pressure gas pipe

Knock Out for high


Knock Out for pressure gas pipe
Low Pressure Gas pipe
Liquid pipe

Liquid pipe
High Pressure Gas pipe

Low Pressure Gas pipe

Knock Out for


Removal area for pipes Knock Out for power supply cable
bottom side connections. communication cable
Chassis UXA UXB
! CAUTION
• Do not give damage to the pipe/base during the Knock Out
work.
• Proceed to pipe work after removing burr after Knock Out work.
• Perform sleeve work to prevent damage to the wire when
connecting wires using Knock Outs.

A
Remove leakage prevention cap
• Remove the leakage prevention cap attached to the outdoor unit
service valve before pipe work. B
• Proceed the leakage prevention cap removal as follows:
- Verify whether the liquid/gas pipes are locked.
- Extract remaining refrigerant or air inside using the service port. C
- Remove the leakage prevention cap
HP 8 10 12 14/16 18/20/22 24/26
Service Port
A(mm) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)
28.58 28.58 28.58 34.9
B(mm) 19.05(3/4) 22.2(7/8)
(1-1/8) (1-1/8) (1-1/8) (1-3/8)
28.58
C(mm) 19.05(3/4) 19.05(3/4) 19.05(3/4) 22.2(7/8) 22.2(7/8)
(1-1/8)
Liquid pipe
High Pressure
Low Pressure Gas pipe * Elbow is Field supplied
Gas pipe

Method of drawing out pipes on the bottom side


- Drawing out common pipe through side panel

Liquid pipe Low Pressure Gas pipe


Leakage
Prevention Cap

High Pressure Gas pipe

Remove Knock Out for the bottom side of Liquid / Gas pipe
28
ENGLISH

Refrigerant piping system Refrigerant pipe diameter from branch to branch (B, C,
D)
4 Outdoor Units
Example : 12 Indoor Units connected ! WARNING
Ⓐ : Outdoor Unit
* : Serial connection of HR units : Capacity sum of indoor units ≤
Ⓑ : Y branch 192.4 kBtu/hr
Ⓓ : Indoor Unit • Refer to the HR unit PCB part for the valve group control setting.
Ⓔ : Connection branch pipe between Outdoor units : ARCNB41 • It is recommended that difference in pipe lengths between an HR
Ⓕ : Connection branch pipe between Outdoor units : ARCNB31 unit and indoor units, for example difference in length of a, b, c,
Ⓖ : Connection branch pipe between Outdoor units : ARCNB21 and d, be minimized. The larger difference in pipe lengths, the
more different performance between indoor units.
Ⓗ : Header
• Piping length from outdoor branch to outdoor unit ≤ 10 m (33 ft),
Ⓘ : HR Unit
equivalent length : max 13 m (43 ft)
* If the large capacity indoor units (Over 5 HP; using over Ø 15.88
Slave 3 (5/8) / Ø 9.52 (3/8)), are installed, it should be used the Valve
A4
Slave 2 Group setting
A3 Slave 1
A2
Master
A1

Refrigerant pipe diameter from branch to branch (B, C)


ODU Capacity
G Master ≥ Slave 1 ≥ Slave 2 ≥ Slave 3
10 F Downward indoor Gas pipe [mm(inch)]
mo
r le E Liquid pipe
ss unit total capacity
[mm(inch)] Low pressure High pressure
A [kW(Btu/h)]
1
≤ 5.6(19 100)
D

a
B1
Ø 6.35(1/4) Ø 12.7(1/2) Ø 9.52(3/8)
D
2
b B < 16.0 (54 600) Ø 9.52(3/8) Ø 15.88(5/8) Ø 12.7(1/2)
I1 C1 < 22.4 (76 400) Ø 9.52(3/8) Ø 19.05(3/4) Ø 15.88(5/8)
*
c B2
< 33.6(114 700) Ø 9.52(3/8) Ø 22.2(7/8) Ø 19.05(3/4)
H 3 D

d
"a" C3
I3
< 50.4(229 000) Ø 12.7(1/2) Ø 28.58(1 1/8) Ø 22.2(7/8)
C2
h g i "b" < 61.6(210 600) Ø 15.88(5/8) Ø 28.58(1 1/8) Ø 22.2(7/8)
D
I2 D 7
I4 < 72.8(210 600) Ø 15.88(5/8) Ø 34.9(1 3/8) Ø 28.58(1 1/8)
4 k
j
f H < 100.8(344 000) Ø 19.05(3/4) Ø 34.9(1 3/8) Ø 28.58(1 1/8)
x sealing
e 8 D
l m n
< 173.6(592 500) Ø 19.05(3/4) Ø 41.3(1 5/8) Ø 34.9(1 3/8)
9 D 10 D 11 D 12 D < 184.8(630 700) Ø 22.2(7/8) Ø 44.5(1 3/4) Ø 41.3(1 5/8)
6 D

5 D
≤ 224.0(764 400) Ø 22.2(7/8) Ø 53.98(2 1/8) Ø 44.5(1 3/4)

- Case 1 ("a") : Maximum height is 15 m (49.2 ft) if you install with Y


branch. Total pipe length = A + B + C1 + C2 + C3 + a + b + c + d
- Case 2 ("b") : Maximum height is 5 m (16.4 ft) in serial connection of + e + f + g + i + j + k + l + m + n ≤ 1 000 m (3 280 ft)
HR units. Longest pipe length * Equivalent pipe length
L
A + B + C3 + D + k ≤ 150 m (200 m**) [(492 ft(656 ft**)] A + B + C3 + D + k ≤ 175 m (225 m**) [(574 ft(738 ft**)]
(**) Conditional Application (In case of D12 is the farthest in door) Longest pipe length after 1st branch
Below condition must be satisfied for 40~90 m (131~295 ft) piping length l
B + C3 + D + k ≤ 40 m(90 m**) [131 ft (295 ft)]
after first branch.
Difference in height(Outdoor Unit ↔ Indoor Unit)
1 Diameter of pipes between first branch and the last branch should be H
increased by one step, except if the pipe diameter B, C3 is same as H ≤ 110 m (361 ft)
diameter A (main pipe diameter) Difference in height (Indoor Unit ↔ Indoor Unit)
Ø 6.35 (1/4), Ø 9.52 (3/8), Ø 12.7 (1/2), Ø 15.88 (5/8), Ø 19.05 (3/4),Ø 22.2 h
h ≤ 40 m (131 ft)
(7/8), Ø 25.4* (1), Ø 28.58 (1-1/8), Ø 31.8* (1-1/4), Ø 34.9 (1-3/8), Ø 38.1*
(1-1/2) Difference in height (Outdoor Unit ↔ Outdoor Unit)
h1
* : If available on site, select this pipe size. h1 ≤ 5 m (16.4 ft)
Otherwise it doesn’t need to be increased Difference in height(HR unit ↔ HR unit)
2 While calculating total refrigerant piping length, pipe B, C3 length should "a", "b"
a ≤ 15 m (49 ft), b ≤ 5 m (16 ft)
be calculated twice.
A + B x 2 + C3 x 2 + C1 + C2 + a + b + c + d + e + f + g + i + j + k + l - * : Assume equivalent pipe length of Y branch to be 0.5 m (1.64 ft),
+ m + n ≤ 1 000 m (3281 ft) that of header to be 1 m (3.3 ft), calculation purpose
3 Length of pipe from each indoor unit to the closest HR unit - It is recommended that indoor unit is installed at lower position than
(a, b, c, d, e, f, g, i, j, k, l, m, n) ≤ 40 m (131 ft) the header.
4 [Length of pipe from outdoor unit to the farthest indoor unit D12 (B + - ** : To apply conditional application.
C3 + K)
- [Length of pipe from outdoor unit to the closest indoor unit D1 (C1 +
a)] ≤ 40 m (131 ft) ! WARNING
When the equivalent length between a outdoor and the farthest
indoor unit is 90 m (295 ft) or more, main pipe(A) must be increased
one grade.
29

ENGLISH
Refrigerant pipe diameter from outdoor unit to first Pattern 3
branch. (A)
Pipe diameter when pipe length is ≥ 90
Standard Pipe Diameter m (295 ft) or when height differential
ODU. (ODU↔IDU) is > 50 m (164 ft)
Capacity
Liquid Pipe Low
(hp) pressure High pressure Liquid Pipe Low pressure High pressure HR1
gas pipe gas pipe gas pipe gas pipe
mm (inch) mm mm (inch)
(inch) mm (inch) mm (inch) mm (inch)
8 Ø 9.52 (3/8) Ø 19.05 (3/4) Ø 15.88 (5/8) Ø 12.7 (1/2) Not increased Not increased 1 2 3 4

10 Ø 9.52 (3/8) Ø 22.2 (7/8) Ø 19.05 (3/4) Ø 12.7 (1/2) Not increased Not increased 48 k 48 k 48 k 48 k
• The maximum total capacity of indoor
12 Ø 12.7 (1/2) Ø 28.58 (1-1/8) Ø 19.05 (3/4) Ø 15.88 (5/8) Not increased Not increased units is 56.4 kW(192 kBtu/h).

14~16 Ø 12.7 (1/2) Ø 28.58 (1-1/8) Ø 22.2 (7/8) Ø 15.88 (5/8) Not increased Not increased
Pattern 4
18~20 Ø 15.88 (5/8) Ø 28.58 (1-1/8) Ø 22.2 (7/8) Ø 19.05 (3/4) Not increased Not increased
22 Ø 15.88 (5/8) Ø 28.58 (1-1/8) Ø 28.58 (1-1/8) Ø 19.05 (3/4) Not increased Not increased
24 Ø 15.88 (5/8) Ø 34.9 (1-3/8) Ø 28.58 (1-1/8) Ø 19.05 (3/4) Not increased Not increased
HR1
26~34 Ø 19.05 (3/4) Ø 34.9 (1-3/8) Ø 28.58 (1-1/8) Ø 22.2 (7/8) Not increased Not increased
36 Ø 19.05 (3/4) Ø 41.3 (1-5/8) Ø 28.58 (1-1/8) Ø 22.2 (7/8) Not increased Not increased B

38~60 Ø 19.05 (3/4) Ø 41.3 (1-5/8) Ø 34.9 (1-3/8) Ø 22.2 (7/8) Not increased Not increased
1 2 3 4
62~64 Ø 22.2 (7/8) Ø 44.5 (1-3/4) Ø 41.3 (1-5/8) Ø 25.4 (1) Not increased Not increased
12 k 12 k 12 k 12 k
66~96 Ø 22.2 (7/8) Ø 53.98 (2-1/8) Ø 44.5 (1-3/4) Ø 25.4 (1) Not increased Not increased • The maximum total capacity of a branch
pipe of HR unit is 14.1 kW(48 kBtu/h).
* If available on site, select pipe size according to upper table.
Otherwise it doesn’t need to be increased.
Pattern 5

Y branch, Header and HR unit connection pattern

Pattern 1
A

HR1 HR2

1 2 3 4

48 k 48 k 48 k 48 k
B

Pattern 6
HR1 HR2

1 2 3 4

48 k 48 k 48 k 48 k
• Impossible installation : Head branch pipe HR unit HR1

A A
A
B
Pattern 2

1 2 3 4 5

24 k 24 k 12 k 12 k 24 k

HR1

A
B

1 2 3 4 5 6 7

7k 7k 7k 7k 7k 24 k 24 k

• Impossible installation : HR unit Head branch


pipe Y and Head branch pipe.
30
ENGLISH

Pattern 7
ELECTRICAL WIRING
* - Follow ordinance of your governmental organization for technical
standard related to electrical equipment, wiring regulations and
HR2 HR3
A guidance of each electric power company.
HR1
3 4 5 6
! WARNING
48 k 48 k 48 k 48 k
1 2 Be sure to have authorized electrical engineers do the electric
48 k 48 k
work using special circuits in accordance with regulations and this
installation manual.
• * : Serial connection of HR units : Capacity sum of indoor units ≤ 56.4 kW (192 kBtu/h) If power supply circuit has a lack of capacity or electric work
deficiency, it may cause an electric shock or fire.
Pattern 8

- Install the Outdoor Unit communication cable away from the power
* source wiring so that it is not affected by electric noise from the power
A
HR2 source. (Do not run it through the same conduit.)
A
HR1 - Be sure to provide designated grounding work to Outdoor Unit.
B

1 2
! CAUTION
3 4 5 6 7 8
48 k 48 k Be sure to correct the outdoor unit to earth. Do not connect ground
12 k 12 k 12 k 12 k 24 k 24 k
wire to any gas pipe, liquid pipe, lightening rod or telephone earth
• * : Maximum indoor units per a branch are 8 indoor units line. If earth is incomplete, it may cause an electric shock.

Indoor Unit Y Branch pipe Head Branch pipe


- Give some allowance to wiring for electrical part box of Indoor and
1 A B
Outdoor Units, because the box is sometimes removed at the time of
service work.
Low pressure Gas pipe Gas pipe
Outdoor High pressure Gas pipe Indoor
HR1
Unit Liquid pipe Liquid pipe Unit - Never connect the main power source to terminal block of
communication cable. If connected, electrical parts will be burnt out.
• Pipe installation from outdoor units to HR units
: 3 pipes(Low pressure Gas pipe, High pressure Gas pipe, Liquid pipe) - Use the 2-core shielded wires for communication cable.( mark in
• Pipe installation from HR units to indoor units the figure below) If communication cable of different systems are
: 2 pipes(Gas pipe, Liquid pipe)
wired with the same multiplecore cable, the resultant poor
transmitting and receiving will cause erroneous operations. ( mark
in the figure below)
Keep the 40 m (131 ft) distance from the first branch to the farthest
indoor. - Only the communication cable specified should be connected to the
terminal block for Outdoor Unit communication.
5 m(16 ft)

1) under 40 m (131 ft) 2-core shielded cables


15 m(49 ft)

Y branch Indoor Indoor Indoor Indoor 1 Unit 2 Unit 3 Unit 4 Unit


Unit Unit Unit Unit
Master Slave 1 Slave 2 Slave 3
Keep the sum of indoor capacity under 56.4 kW(192 kBtu/h).
1) under 40 m (131 ft) Indoor Indoor
Unit Unit

Remote Remote
Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor control control
Unit Unit Unit Unit Unit Unit Unit Unit
Master Slave 1 Slave 2 Slave 3
Keep the sum of indoor capacity under 56.4 kW(192 kBtu/h).

Indoor Indoor
Unit Unit

Remote Remote
control control
31

ENGLISH
Master Slave Master Slave 1 Slave 2
Indoor Indoor Indoor Indoor
Unit Unit Unit Unit

Remote Remote Remote Remote


control control control control
Master Slave 1 Slave 2
Master Slave
Indoor Indoor Indoor Indoor
Unit Unit
Unit Unit
Remote Remote
Remote Remote control control
control control

Master Slave 1 Slave 2 ! CAUTION


Indoor Indoor • Use the 2-core shielded wires for communication cables. Never use
Unit Unit them together with power cables.
• The conductive shielding layer of cable should be grounded to the
Remote Remote metal part of both units.
control control • Never use multi-core cable
Master Slave 1 Slave 2 • As this unit is equipped with an inverter, to install a phase leading
capacitor not only will deteriorate power factor improvement effect,
Indoor Indoor but also may cause capacitor abnormal heating. Therefore, never
Unit Unit install a phase leading capacitor.
• Make sure that the power unbalance ratio is not greater than 2 %.
Remote Remote If it is greater the units lifespan will be reduced.
control control

Multi-Core Cable
Precautions when laying power wiring
Master Slave 1 Slave 2 Slave 3 Use round pressure terminals for connections to the power terminal
Indoor Indoor block.
Unit Unit
Power cable
Round pressure terminal
Remote Remote
control control
Master Slave 1 Slave 2 Slave 3
Indoor Indoor
Unit Unit When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal
Remote Remote block. (Slack in the power wiring may cause abnormal heat.)
control control - When connecting cable which is the same thickness, do as shown in
the figure below.

Master Slave
Indoor Indoor
Unit Unit

Remote Remote
control control - For wiring, use the designated power cable and connect firmly, then
Master Slave secure to prevent outside pressure being exerted on the terminal
Indoor Indoor block.
Unit Unit - Use an appropriate screwdriver for tightening the terinal screws. A
screwdriver with a small head will strip the head and make proper
Remote Remote tighterning impossible.
control control - Over-tightening the terminal screws may break them.

! CAUTION
When the 400 volt power supply is applied to “N” phase by mistake,
check damaged parts in control box and replace them.
32
ENGLISH

Control box and connecting position of wiring Communication and Power Cables
- Remove all of the screws at front panel and remove the panel by Communication cable
pulling it forward. - Types : shielded wires
- Connect communication cable between main and sub outdoor unit - Cross section : 1.0 ~ 1.5 mm2 (1.55 × 10-3 ~ 2.32 × 10-3 in2)
through the terminal block.
- Maximum allowable temperature: 60 °C (140 °F)
- Connect communication cables between outdoor unit and indoor
units through the terminal block. - Maximum allowable cable length: under 1 000 m (3 281 ft)
- When the central control system is connected to the outdoor unit, a
dedicated PCB must be connected between them. Remote control cable
- When connecting communication cable between outdoor unit and - Types : 3-core cables
indoor units with shielded cable, connect the shield ground to the
earth screw. Central control cable

Product type Cable type Diameter


1.0 ~ 1.5 mm2
ACP&AC Manager 2-core wires (shielded) (1.55 × 10-3 ~
2.32 × 10-3 in2)

1.0 ~ 1.5 mm2


AC Smart 2-core wires (shielded) (1.55 × 10-3 ~
2.32 × 10-3 in2)

1.0 ~ 1.5 mm2


Simple central controller 4-core wires (shielded) (1.55 × 10-3 ~
2.32 × 10-3 in2)

1.0 ~ 1.5 mm2


Front Panel AC Ez 4-core wires (shielded) (1.55 × 10-3 ~
2.32 × 10-3 in2)

! WARNING ! CAUTION
In case of using the shielded wires, it should be grounded.
The temperature sensor for outdoor air should not be exposed to
direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
Separation of communication and power cables
- If communication and power cables are installed alongside each other
UXB UXA then there is a strong likelihood of operational faults developing due
to interference in the signal wiring caused by electrostatic and
electromagnetic coupling.
The tables below indicates our recommendation as to appropriate
spacing of communication and power cables where these are to be
Main Board run side by side

External Board Current capacity of power cable Spacing


Main power line 10 A 300 mm (11-13/16 inch)
terminal block 50 A 500 mm (19-11/16 inch)
100 V or more
(Take care of the phase 100 A 1 000 mm (39-3/8 inch)
sequence of 3-phases Exceed 100 A 1 500 mm (59-1/16 inch)
4-wires power system)

! NOTE
• The figures are based on assumed length of parallel cabling up to
100 m [328 ft]. For length in excess of 100 m [328 ft] the figures
will have to be recalculated in direct proportion to the additional
length of cable involved.
• If the power supply waveform continues to exhibit some distortion
the recommended spacing in the table should be increased.
- If the cable are laid inside conduits then the following point must
also be taken into account when grouping various cable together
for introduction into the conduits
- Power cable(including power supply to air conditioner) and
communication cables must not be laid inside the same
- In the same way, when grouping the power wires and
communication cables should not be bunched together.

! CAUTION
If apparatus is not properly earthed then there is always a risk of
electric shock, the grounding of the apparatus must be carried out
by a qualified person.
33

ENGLISH
Wiring of main power supply and equipment Point for attention regarding quality of the
capacity public electric power supply
- Use a separate power supply for the Outdoor Unit and Indoor Unit. This equipment complies with respectively:
- Bear in mind ambient conditions (ambient temperature,direct - EN/IEC 61000-3-11 (1) provided that the system impedance Zsys is
sunlight, rain water,etc.) when proceeding with the wiring and less than or equal to Zmax and
connections. - EN/IEC 61000-3-12 (2) provided that the short-circuit power Ssc is
- The cable size is the minimum value for metal conduit wiring. The greater than or equal to the minimum Ssc alue at the interface point
power cord size should be 1 rank thicker taking into account the line between the user's supply and the public system. It is the
voltage drops. Make sure the power-supply voltage does not drop responsibility of the installer or user of the equipment to ensure, by
more than 10 %. consultation with the distribution network operator if necessary, that
- Specific wiring requirements should adhere to the wiring regulations the equipment is connected only to a supply with respectively:
of the region. - Zsys less than or equal to Zmax and
- Power supply cords of parts of appliances for outdoor use should not - Ssc greater than or equal to the minimum Ssc value.
be lighter than polychloroprene sheathed flexible cord.
- Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply. Standard combination of Minimum Ssc Value
Zmax (Ω)
outdoor units (kVA)
The thickness of Minimum wire (mm2 [ inch2])
Leakage ARUM080LTE5 - 2 776
Main power circuit breaker ARUM100LTE5 - 3 828
Branch wire Ground wire (4P ELCB)
wire ARUM120LTE5 - 3 828
2.5~16 2.5~4 ARUM140LTE5 - 6 339
Below 20~60 A
1 Unit [3.875 × 10-3 - [3.875 × 10-3
100 mA 0.1 s ARUM160LTE5 - 6 339
~2.48 × 10-2] ~6.2 × 10-3]
ARUM180LTE5 - 6 339
16~50 4~10
Below 75~150 A ARUM200LTE5 - 6 339
2 Unit [2.48 × 10-2 - [6.2 × 10-3
100 mA 0.1 s
~7.75 × 10-2] ~1.55 × 10-2] ARUM220LTE5 - 6 339
50~95 ARUM240LTE5 - 8 144
10 Below 150~200 A
3 Unit [7.75 × 10-2 -
[1.55 × 10-2] 100 mA 0.1 s ARUM260LTE5 - 8 144
~1.4725 × 10-1]

95~120 10~16 (1) European / International Technical Standard setting the limits for
Below 200~250 A
4 Unit [1.4725 × 10-1 - [1.55 × 10-2 voltage changes, voltage fluctuations and flicker in public low-
100 mA 0.1 s
~1.86 × 10-1] ~2.48 × 10-2] voltage supply systems for equipment with rated current ≤75 A.
(2) European / International Technical Standard setting the limits for
Ground wire harmonic currents produced by equipment connected to public low-
voltage systems with input current >16 A and ≤75 A per phase.
1 The power wire Between the master outdoor unit and slave1
outdoor unit - minimum : 6 mm2 [9.3 × 10-3 inch2]
2 The power wire Between the slave1 outdoor unit and slave2
outdoor unit - minimum : 4 mm2 [6.2 × 10-3 inch2] Field Wiring
3 The power wire Between the slave2 outdoor unit and slave3
outdoor unit - minimum : 2.5 mm2 [3.875 × 10-3 inch2]
Single outdoor unit
h The above standard is CV wire standard.
h Please use the 3-phases 4-wires quadrupole Leakage circuit breaker Outdoor Voltage range(V)
of circuit breaker. Power supply
Frequency
Outdoor Indoor
(3 Ø 4 wires)
[Outdoor Unit] 60 Hz 380 V 220 V

WARNING
(Main Switch)
50 Hz 380-415 V 220-240 V
! Switch
R S T N

• Follow ordinance of your governmental organization for Fuse


Indoor
technical standard related to electrical equipment, wiring Power supply
regulations and guidance of each electric power company. (1 Ø 2 wires)

• Make sure to use specified cables for connections so that no L N


Power Line
external force is imparted to terminal connections. If (4 Wires Cable)
Power Line
connections are not fixed firmly, it may cause heating or fire. (2 Wires Cable)
Communication Line
(2 Wires Cable)
• Make sure to use the appropriate type of overcurrent protection
switch. Note that generated overcurrent may include some Pull Box Pull Box Pull Box Pull Box

amount of direct current. (Installer option) (Installer option) (Installer option) (Installer option)

! CAUTION HR unit

Power Line Power Line Power Line Power Line


• All installation site must require attachment of an earth leakage (2 Wires Cable) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable)

breaker. If no earth leakage breaker is installed, it may cause an In case of Heat


Recovery System
electric shock. Communication Line
(3 Wires Cable)
• Do not use anything other than breaker and fuse with correct [Indoor Units]
capacity. Using fuse and wire or copper wire with too large capacity
may cause a malfunction of unit or fire.
34

WARNING WARNING
ENGLISH

! !
• Indoor Unit ground wires are required for preventing electrical • Indoor Unit ground wires are required for preventing electrical shock
shock accident during current leakage, Communication disorder by accident during current leakage, Communication disorder by noise
noise effect and motor current leakage (without connection to effect and motor current leakage (without connection to pipe).
pipe). • Don't install an individual switch or electrical outlet to disconnect each
• Don't install an individual switch or electrical outlet to disconnect of indoor unit separately from the power supply.
each of indoor unit separately from the power supply. • Install the main switch that can interrupt all the power sources in an
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment
integrated manner because this system consists of the equipment utilizing the multiple power sources.
utilizing the multiple power sources. • If there exists the possibility of reversed phase, lose phase,
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product
momentary blackout or the power goes on and off while the is operating, attach a reversed phase protection circuit locally.
product is operating, attach a reversed phase protection circuit Running the product in reversed phase may break the compressor
locally. Running the product in reversed phase may break the and other parts.
compressor and other parts.

Between Indoor and Master Outdoor unit Between Indoor and Master Outdoor unit
The communication cables between indoor unit and master outdoor
Master unit are possible to connect with BUS type or STAR type.
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12 V
Outdoor Unit
Master
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12 V
Outdoor Unit SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12 V Master
Outdoor unit
The GND terminal at the
main PCB is a ‘-’ terminal
3 4 3 4 3 4
HR unit
for dry contact, it is not 3 4
HR unit
3 4 3 4 SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12 V
Slave 1
Outdoor Unit
the point to make ground
connection. In case of Heat Recovery System
In case of Heat Recovery System
Slave 2
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12 V
Outdoor Unit

Series outdoor units


Voltage range(V)
When the power source is connected Frequency SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12 V
Slave 3
Outdoor Unit
In series between the units. Outdoor Indoor
60 Hz 380 V 220 V
Outdoor
50 Hz 380-415 V 220-240 V The GND terminal at the main PCB is a ‘-’ terminal for dry contact.
Power supply
(3 Ø 4 wires) It is not the point to make ground connection.
[Master] [Slave 1] [Slave 2] [Slave 3]
(Main Switch)
R S T N
- Make sure that terminal number of master and slave outdoor units
Switch
are matched.(A-A, B-B)
Fuse
Indoor
Power supply
(1 Ø 2 wires) Example) Connection of transmission wire
L N
Power Line

Power Line
(4 Wires Cable)
[BUS type] [STAR type]
(2 Wires Cable)
Communication Line
(2 Wires Cable)
- Connection of communication - Abnormal operation can be
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
cable must be installed like caused by communication
below figure between indoor defect, when connection of
unit to outdoor unit. communication cable is installed
HR unit
like below figure(STAR type).
Power Line Power Line Power Line Power Line
(2 Wires Cable) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable)
In case of Heat
Recovery System
Communication Line
(3 Wires Cable)

[Indoor Units]

! WARNING
When the total capacity is over than as follow, the power source
do not use in series between the units.
The First terminal block could be burnt out.

When the power source is supplied to Each outdoor unit individually.


Outdoor
Power supply
(3 Ø 4 wires)
[Master] [Slave 1] [Slave 2] [Slave 3]
(Main Switch)
R S T N R S T N R S T N R S T N

Switch Switch Switch Switch

Fuse Fuse Fuse Fuse


Indoor
Power supply
(1 Ø 2 wires)
L N

Power Line
(2 Wires Cable)
Power Line Communication Line
(4 Wires Cable) (2 Wires Cable)

Pull Box Pull Box Pull Box Pull Box


(Installer option) (Installer option) (Installer option) (Installer option)

HR unit

Power Line Power Line Power Line Power Line


(2 Wires Cable) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable)
In case of Heat
Recovery System
Communication Line
(3 Wires Cable)

Voltage range(V) [Indoor Units]


Frequency
Outdoor Indoor
60 Hz 380 V 220 V
50 Hz 380-415 V 220-240 V
35

ENGLISH
Example) Connection of power and communication cable (UXA) Front Side
Bottom Side
Main power
terminal block

Main power Ground wire


terminal block When connecting
When connecting Communication wires
Ground wire / Ground wire from
Main power lines
/ Ground wire from left side front guide panel

Gap : Over Gap : Over


50 mm(1.97’’) 50 mm(1.97’’)
Fix firmly with cable tie When connecting
When connecting
Communication wires or clamp cord not to be Main power lines
/ Ground wire from
/ Ground wire from left side
displaced front guide panel

Front Side
Main power line Communication/Ground
Main power connection wire connection
terminal block

Ground wire

When connecting
Communication wires
/ Ground wire from ODU-IDU
front guide panel Main power Communication
terminal block cable
Gap : Over ODU-ODU
50 mm(1.97’’) Insulation sleeves
attachments Communication
Fix firmly with cable tie or cable
When connecting
Main power lines clamp cord not to be displaced
/ Ground wire from
front guide panel

Ground wire Ground wire

Main power line Communication/Ground


wire connection
connection
! CAUTION
It should be wiring power cables or communication cables to avoid
interference with the oil level sensor. Otherwise, That oil level sensor
Ground wire would be operated abnormally.
Main power ODU-IDU
terminal block Communication
cable
Insulation sleeves
attachments ODU-ODU
Communication
cable

Checking the setting of outdoor units


Ground wire
Checking according to DIP switch setting

! CAUTION - You can check the setting values of the Master outdoor unit from the
7 segment LED.
The DIP switch setting should be changed when the power is OFF.
It should be wiring power cables or communication cables to
avoid interference with the oil level sensor. Otherwise, That oil
level sensor would be operated abnormally. Checking the initial display
The number is sequentially appeared at the 7 segment in 5 seconds
after applying the power. This number represents the setting condition.
Example) Connection of power and communication cable (UXB)
[Main Board]
Bottom Side

DIP switch
Main power
terminal block

7 segment
Ground wire

When connecting
Main power lines
/ Ground wire from left side

Gap : Over
50 mm(1.97’’)
SW01C
When connecting
Communication wires (Automatic Addressing Setting)
/ Ground wire from left side
36
ENGLISH

Quick control Setting Setting For Heat Recovery Unit (Refer Only Heat Recovery Installation)
In the factory setting, main PCB DIP switch setting is all “OFF”. [Heat Recovery (HR) Unit Board]
- Check and make sure that all the indoor unit model name are
#4 valve housing
ARNU******4.
- Change the main PCB DIP switch No. 3 “OFF → ON” like below
picture. #1 valve housing

- Push the reset button.


DIP Switch 7 segment

7-SEG

Reset button SW05M

SW01M
SW02M
SW01M/SW03M/SW04M
(DIP switch for setup of
(Switch for manual valve
The function of HR unit)
addressing)

SW03M SW04M

• Initial display order Switch for setup of HR Unit


Order No Mean Main function of SW02M
① 8~24 Master unit capacity
ON
② 10~24 Slave 1 unit capacity Selection
S/W
③ 10~24 Slave 2 unit capacity Method for addressing valves of an HR
④ 10~24 Slave 3 unit capacity No.1
unit (Auto/Manual)
⑤ 8~96 Total capacity No.2 Model of HR unit
⑥ 3 Heat Pump (Factory Setting)
No.3 Model of HR unit
38 380 V model
⑦ 46 460 V model No.4 Model of HR unit
22 220 V model No.5 Valve group setting
SW02M
⑧ 40 Full function No.6 Valve group setting
Use only in factory
No.7
• Example) ARUM620LTE5 production (preset to “OFF”) Zoning
62 hp 380 V Heat Pump System (Master unit: 18 hp, Slave setting
Use only in factory (“ON”)
1: 16 hp, Slave 2: 14 hp, Slave 3: 14 hp) No.8
production (preset to “OFF”)
① ② ③ ④ ⑤ ⑥ ⑦ ⑧
18 16 14 14 62 3 38 40 1 Selection of the method for addressing valves of an HR unit
(Auto/Manual)

Switch No.1 Off Switch No.1 On


Master/Slave DIP switch setting
Auto Manual
• Master Unit • Slave Unit
DIP switch DIP switch
ODU Setting ODU Setting
setting setting

Heat Pump System


Slave 1
(Factory Setting) 2 Setting the zoning control
DIP Switch setting
Slave 2
Normal
control
Slave 3 SW01M

Turn the DIP switch of


h Heat Recovery installation Zoning the zoning branch on.
control Ex) Branch 1, 2 are
① Turn on the DIP s/w No 4. SW01M
zoning control.
DIP switch
ODU Setting
setting

Setting Heat pump system or Heat Recovery system


(Installer Setting)

② The factory setting display is appeared “HP”.


③ Change “HP” into “HR” display pushing ▶ button and then push
confirm button.
④ Turn off the DIP s/w No 4. and Push reset button to restart the
system. (If you turn on the DIP s/w No 4, you can make sure “HR”
or “HP” display later.)
37

ENGLISH
3 Selection of the model of HR unit Y branch pipe (Unit: mm [inch])
Models Low pressure Gas pipe Liquid pipe High pressure Gas pipe
I.D 22.2(7/8) I.D 19.05(3/4)
I.D 19.05(3/4)
I.D 19.05(3/4) I.D 22.2(7/8) I.D 22.2(7/8)
I.D 25.4(1) I.D 19.05(3/4) I.D 15.88(5/8) I.D 12.7(1/2) I.D 12.7(1/2) I.D 15.88(5/8)

2 3 3 4 2 I.D 9.52(3/8) I.D 9.52(3/8) I.D 6.35(1/4)


1 1
2 1 2 1
I.D 19.05(3/4) I.D 12.7 83 I.D 19.05(3/4)
2
I.D 15.88 96
I.D 25.4(1) I.D 22.2(7/8)
I.D 15.88(5/8) (1/2) (3-9/32) (5/8) (3-25/32)
I.D 12.7(1/2) 74
I.D 12.7(1/2) I.D 9.52(3/8) I.D 6.35(1/4) (2-29/32) 421(16-9/16) 3
ARBLB03321 390(15-11/32)
413(16-1/4)
3 444(17-15/32)

321(12-5/8) O.D 15.88(5/8)


(For 2 branches) (For 3 branches) (For 4 branches) I.D 22.2(7/8)
O.D 19.05(3/4)
I.D 28.58(1-1/8)
O.D 25.4(1) O.D 19.05(3/4)
I.D 22.2(7/8)

I.D 25.4(1)
332(13-1/16)
I.D 12.7(1/2)
O.D 15.88(5/8) I.D 9.52(3/8) I.D 12.7(1/2)
3 2
PRHR022 PRHR032 PRHR042 3

70(2-3/4) 80(3-5/32)
1 2

110(4-11/32) 110(4-11/32)
70(2-3/4)

PRHR022A PRHR032A PRHR042A

Initial
Setting
SW05M (Rotary S/W for addressing HR unit)
1 branches Must be set to '0' when installing only one HR unit.
Connected When installing multiple HR units, address the HR units with
sequentially increasing numbers starting from '0'.
2 branches
Connected Ex) Installation of 3 HR units

3 branches
Connected A B A B A B

4 branches 3 4 3 4 3 4
1 2 1 2 1 2
Connected

* Each model is shipped with the switches No.2 and No.3 pre-adjusted
as above in the factory.

! WARNING
• If you want to use a PRHR032 or PRHR032A for 2 branches HR SW01M/SW03M/SW04M (DIP S/W and tact S/W for
unit after closing the 3rd pipes, set the DIP switch for 2
branches HR unit. manual valve addressing)
• If you want to use a PRHR042 or PRHR042A for 3 branches HR 1 Normal setting (Non-Zoning setting)
unit after closing the 4th pipes, set the DIP switch for 3 - Set the address of the valve of the HR unit to the central control
branches HR unit. address of the connected indoor unit.
• If you want to use a PRHR042 or PRHR042A for 2 branches HR - SW01M: selection of the valve to address
unit after closing the 3rd and 4th pipes, set the DIP switch for 2 SW03M: increase in the digit of 10 of valve address
branches HR unit. SW04M: increase in the last digit of valve address
• The unused port must be closed with a copper cap, not with a - Prerequisite for manual valve addressing : central control address
plastic cap. of each indoor unit must be preset differently at its wired remote
control.
S/W No. Setup
4 Setting the Valve Group. No.1 Manual addressing of valve #1
DIP S/W setting Example
No.2 Manual addressing of valve #2
SW01M
No.3 Manual addressing of valve #3
4 Indoor Unit No.4 Manual addressing of valve #4
Not control
3 Indoor Unit
2
1 Indoor Unit Increase in the digit of 10 of valve
Indoor Unit SW03M SW03M
address
Increase in the last digit of valve
SW04M SW04M
No.1, 2 Valve
4
3
Indoor Unit address
Indoor Unit
2
Control 1 Large capacity indoor unit

2 Zoning setting
- Set the address of the valve of the HR unit to the central control
No.2, 3 Valve 4
3
Indoor Unit address of the connected indoor unit.
Control 2 Large capacity indoor unit
1 Indoor Unit - SW01M : selection of the valve to address
SW03M : increase in the digit of 10 of valve address
SW04M : increase in the last digit of valve address
SW05M :Rotary S/W
4 Large capacity indoor unit
No.3, 4 Valve 3 - Prerequisite for manual valve addressing : central control address
2 Indoor Unit
Control 1 Indoor Unit of each indoor unit must be preset
differently at its wired remote control.
No.1, 2 Valve
4 Large capacity indoor unit
/ 3
2 Large capacity indoor unit
1
No.3, 4 Valve
Control

! NOTE
If the large capacity indoor units are installed, below Y branch pipe should be
used.

I.D 6.35(1/4)
38
ENGLISH

S/W No. Setup The Procedure of Automatic Addressing


No.1 Manual addressing of valve #1
No.2 Manual addressing of valve #2 Power On

No.3 Manual addressing of valve #3


SW01M
No.4 Manual addressing of valve #4 Waiting 3 minutes

Increase in the digit of 10 of valve


SW03M SW03M Press RED Button for 5 s.
address (SW01C)

SW04M SW04M Increase in the last digit of valve address Automatic Addressing process start
7-segment LED = 88

SW05M SW05M Manual addressing of zoning indoor units


Don’t press RED Button
(SW01C)

Automatic Addressing Waiting about 2~7 minutes


• Automatic addressing process end Numbers of indoor
unit connected are indicated for 30 seconds on
7-segment LED after completing process
The address of indoor units would be set by Automatic
Addressing 7-segment LED NO Check the connections
of communication cable
- Wait for 3 minutes after supplying power. = 88
(Master and Slave outdoor units, indoor units)
YES
Indoor address number is displayed on wired remote controller or
- Press RED button of the outdoor units for 5 seconds. (SW01C) indoor unit display window. It is not an error message, will
- A “88” is indicated on 7-segment LED of the outdoor unit PCB. disappeared when on/off button is pressed on remote controller
ex) Display of 01, 02, ..., 15 means connection of 15 indoor units
- For completing addressing, 2~7 minutes are required depending on OK and Automatic addressing is completed normally.
numbers of connected indoor units
- Numbers of connected indoor units whose addressing is completed are
indicated for 30 seconds on 7-segment LED of the outdoor unit PCB
- After completing addressing, address of each indoor unit is indicated
! CAUTION
on the wired remote control display window. (CH01, CH02, CH03, … • In replacement of the indoor unit PCB, always perform Automatic
…, CH06 : Indicated as numbers of connected indoor units) addressing setting again (At that time, please check about using
Independent power module to any indoor unit.)
[Main Board] • If power supply is not applied to the indoor unit, operation error
occur.
• Automatic Addressing has to be performed after more than 3
minutes to improve indoor unit communition when initial power is
DIP switch supplied.
• Please be sure that all the DIP switch (1~7) of master outdoor unit is
7 segment OFF before Automatic Addressing setting

SW01C
(Automatic Addressing Setting)
39

ENGLISH
Setting For Heat Recovery Unit Manual pipe detection
(Refer Only Heat Recovery Installation) 1 Enter the central control address into each indoor unit using its
wired remote controller.
Automatic pipe detection 2 Turn No.1 of DIP s/w SW02M of HR unit PCB on.
1 Turn No.1 of DIP s/w SW02M of HR unit PCB off. 3 Reset the power of HR unit PCB.
2 Confirm that the setting of No.2, 3 of SW02M corresponds with the 4 On the HR unit PCB, manually set address of each valve of the HR
Type of the valve connection. unit to the central control address of the indoor unit connected to
3 Reset the power of HR unit PCB the valve.
4 Master Out door unit PCB DIP switch on : No.5 5 Reset the power of outdoor unit PCB.
5 Select the mode using ‘▶’, ‘◀’ Button : “Idu” Push the ‘●’ button 6 The number of the indoor unit installed is displayed after about 5
minutes.
6 Select the “Id 5” function using ‘▶’, ‘◀’ Button :“Ath” or “”Atc” Ex) HR ‡ The number of the indoor
Push the ‘●’ button.
Outdoor temperature is over 15 °C(59 °F) : “Ath” Using (If it fail, use 7 Reset the power of outdoor unit PCB, HR unit.
“Atc”) 8 Manual pipe detection is completed
Outdoor temperature is below 15 °C(59 °F) : “Atc” Using (If it fail,
use “Ath”)
7 Select the mode using ‘▶’, ‘◀’ Button : “Idu” Push the ‘●’ button ! WARNING
8 Select the “Id 6” function using ‘▶’, ‘◀’ Button :“StA” Push the ‘●
• In case that central controller is not installed, firstly set up central
’ button
controller’s setting to make address setting of indoor units.
9 System is operated after “88” is displayed on 7-SEG of the outdoor
• In case that central controller is installed, please set central control
unit main PCB.
address in wired remote control of indoor unit.
10 Pipe detection process is proceeded.
• HR unit’s manual pipe address is set by the central control adress of
11 5~30 minutes are required depending on the number of the indoor indoor units.
units and outdoor temperature.
• Address of valve which is not connected with indoor unit should be
12 The number of the indoor units connected is displayed on7- set differently with the address of a valve which is indoor unit
Segment of the outdoor unit main PCB for about 1 minute connected(If address is overlapped valve will not work preperly)
- For a HR unit, the number of the indoor units connected to each • If there occurs some error during pipe detection process,it means
HR unit is displayed. pipe detection process is not properly finished.
- '200' is displayed in case of auto pipe detecting error, and auto • If an error occurred, it means that manual pipe setting is not
pipe detection process is completed after '88' is disappeared. completed.
* Auto pipe detection function : the function that sets connection • During 5 minutes after pipe detection process is completed, do not
relationship automatically between the indoor unit and HR unit. turn off the main outdoor unit’s PCB to save the result of pipe
detection automatically.

! WARNING
• Execute auto addressing and auto pipe detection again whenever the
indoor PCB and HR unit PCB is replaced. Flow chart of auto pipe detection process
- Operation error occurs unless power is supplied to the indoor and
HR units.
• Error No.200 occurs if the number of connected indoor units and that Confirm indoor unit’s address setting
Outdoor unit is operated for 5~60 minues.
of scanned indoor units are different.
Turn No.1 of DIP s/w SW02M of HR unit
• If auto pipe detection process fails, complete it with manual pipe PCB off.
detection (see Manual pipe detection part).
Dose the setting
NO
• If auto pipe detection process is completed normally, manual pipe Confirm that the setting of No.2, 3 of status satisfy indoor unit’s
configuration properly
SW02M corresponds with the valve
detection is not required. connecion type. during operation?
Display error on outdoor unit PCB
Display error on HR unit PCB
• If you want to do auto pipe detection again after auto pipe detection YES
fails, do after reset of outdoor unit by all means. Reset the power of HR unit PCB
Outdoor unit PCB : HR ơ HR unit
number ơ Valve number
• During 5 minutes after pipe detection is completed, do not turn off HR unit : '200'
Master Outdoor unit’s PCB DIP switch on :
the main unit PCB to save the result of pipe detection automatically. No.5 The number of indoor units detected is
displayed for 30 seconds on the outdoor
Check the HR unit and indoor unit
unit PCB after outdoor unit stopped
Select the mode using ‘ȯ’, ‘ȭ’ Button :
“Idu” Push the ‘Ɨ’ button
Is the number of
indoor units connected NO
Select the “Id 5” function using ‘ȯ’, ‘ȭ’ and displayed
Button :“Ath” or ”Atc” Push the ‘Ɨ’ button. one equal?
Outdoor temperature is over 15 °C(59 °F) : Pipe detection error occurs for 30
Select “Atc” (If fails, use “Ath”) YES seconds.
Outdoor temperature is below 15 °C(59 °F) :
Select “Ath”(If it fail, use “Atc”)

Check the installation of status of


Completion of auto pipe detection process outdoor, indoor, HR unit
Select the mode using ‘ȯ’, ‘ȭ’ Button :
“Idu” Push the ‘Ɨ’ button
Retry auto pipe detection process
after Fixing wrong installation
Select the “Id 6” function using ‘ȯ’, ‘ȭ’
Button :“StA” Push the ‘Ɨ’ button
Incompletion of auto detection
process
88' is displayed on 7-SEG of the outdoor
unit main PCB

* It is possible to be generated mode changing noise of


heating and cooling which is normal.
There is no mode changing noise at normal operation.
40
ENGLISH

DIP-SW01 Example of manual valve addressing (Zoning


7-Segment setting)
SW04C (X : cancel) (In case that an indoor unit of central control address "11" is connected
SW03C (ȯ: forward) to a valve #1 of an HR unit)
SW02C (ȭ: backward)
Zoning control is connecting 2 or more indoor units at one pipe of HR
SW01C (Ɨ: Confirm / unit. In case of Zoning control, in order to set controls with multiple
Automatic Addressing)
indoor units connection uses the rotary switch. Namely, only the rotary
SW01D (reset)
switch changes from same valve set condition and set indoor units
connection.
1 On DIP switch of the corresponding valves and sets the rotary
Flow chart of manual addressing for pipe switch at 0.
2 Setting the number with tact switch.
detection
3 In case of addition of indoor units to same port, increases 1 with the
Execute in case of Auto pipe detection rotary switch and sets number with tact switch.
failure
Wait for about 5 minutes.
4 In case of checking the number which the corresponding valve is
stored, turn on DIP switch and set the number of rotary switch.
Turn No.1 of SW02M of HR unit PCB on.
The number of the indoor units connected 5 Indoor units set available 7 per a port(rotary switch 0~6), in case of
is displayed.
Ex) HR रThe number of connected
setting above of 7 with rotary switch, it will display error.
Reset the power of HR unit PCB.
indoor units
6 Setting the rotary switch on original condition(HR unit number set
conditions) after all finishing a piping setting.
Input the central control address at each
indoor unit using wired remote controller.
Is the number
7 The rotary switch set value of above number of indoor units which
of indoor units connected with the NO
is connected with FF and prevents a malfunction.
outdoor unit and displayed
Set the address of each valve manually number equal? (Example: The case where 3 indoor units is connected in piping 1,
by referring indoor unit’s central control Check the central control address of
address connected with.
YES
indoor and HR unit. sets from rotary switch 0, 1, 2 and 3, 4, 5 with FF set)
- Prerequisite for manual valve addressing: central control address of
Reset the power of outdoor unit PCB. Completion of manual pipe detection
each indoor unit must be preset differently at its wired remote
Make sure that reset the outdoor
process Unit’s power after setting central control.
control address of indoor unit’s

No. Display and setup Setup and Contents


0
- Operation: None
Example of manual valve addressing (Non- 1 7-SEG SW01M SW03M SW04M SW05M
- Display: None
Zoning setting)
- Operation : Turn DIP S/W No.1 on to
(In case that an indoor unit of central control address "11" is connected 0 address valve #1
to a valve #1 of an HR unit) 2 7-SEG SW01M SW03M SW04M SW05M
- Display : Existing value saved in
- Prerequisite for manual valve addressing: central control address of EEPROM is displayed in 7-SEG.
each indoor unit must be preset differently at its wired remote
control. - Operation : Set the digit of 10(1) to the
number in Group High data of the wired
No. Display and setup Setup and Contents remote control connected to the
- Operation: None
0 corresponding indoor unit to the valve
1 3 #1 by pressing left tack S/W.
7-SEG SW01M SW03M SW04M - Display: None 7-SEG SW01M SW03M SW04M SW05M
- Display : Digit increasing with the times
- Operation: Turn DIP S/W No.1 on to of pressing tack S/W is displayed in left
address valve #1 7-SEG.
2
- Display: Existing value saved in
7-SEG SW01M SW03M SW04M
1 - Operation : SW05M : 1
EEPROM is displayed in 7-SEG. 4
7-SEG SW01M SW03M SW04M SW05M - Display : Display former value.
- Operation: Set the digit of 10 to the
number in Group High data of the wired 1
- Operation : Setting No. using SW03M
remote control connected to the 5 and SW04M, SW05M : 1
corresponding indoor unit to the valve 7-SEG SW01M SW03M SW04M SW05M
- Display : Display setting value.
3 #1 by pressing left tack S/W.
7-SEG SW01M SW03M SW04M - Operation : Turn DIP S/W No.1 off to
- Display: Digit increasing with the times 1 save the address of valve #1
of pressing tack S/W is displayed in left 6
7-SEG 7-SEG SW01M SW03M SW04M SW05M - Display : "11" displayed in 7-SEG
disappears.
- Operation: Set the digit of 1 to the
number in Group Low data of the wired - Operation : Return valve of addressing
0
remote control connected to the 7 HR unit.
corresponding indoor unit to the valve 7-SEG SW01M SW03M SW04M SW05M
- Display : None
4 #1 by pressing right tack S/W.
7-SEG SW01M SW03M SW04M
- Display: Digit increasing with the times
of pressing tack S/W is displayed in - Above setup must be done for all HR unit valves.
right 7-SEG - The valve that is not connected with any indoor unit should be
addressed with any other number than used address numbers of the
- Operation: Turn DIP S/W No.1 off to valves connected with indoor units.
save the address of valve #1 (The valves does not work if the address numbers are same.)
5
7-SEG SW01M SW03M SW04M - Display: "11" displayed in 7-SEG
disappears

- Above setup must be done for all HR unit valves.


- The valve that is not connected with any indoor unit should be
addressed with any other number than used address numbers of the
valves connected with indoor units.
(The valves does not work if the address numbers are same.)
41

ENGLISH
Example of checking valve address Group Number setting
(In case that an indoor unit of central control address "11" is connected Group Number setting for Indoor Units
to a valve #1 of an HR unit) - Confirm the power of whole system(Indoor Unit, Outdoor Unit) is
OFF, otherwise turn off.
No. Display and setup Setup and Contents
- The communication cables connected to CEN.A and CEN.B terminal
- Operation: Turn DIP S/W No.1 on. should be connected to central control of Outdoor Unit with care for
1 their polarity (A-A, B-B).
7-SEG SW01M - Display: "11" is displayed in 7-SEG
- Turn the whole system on.
- Operation: Turn DIP S/W No.1 off. - Set the group and Indoor Unit number with a wired remote control.
2
7-SEG SW01M - 7-SEG disappeared - To control several sets of Indoor Units into a group, set the group ID
from 0 to F for this purpose.

Identification of Manual Valve ID (Address) Outdoor Units (External PCB)

No. Display and setup Setup and Contents


SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
- Operation: more than 2 DIP switches
1 turned on.
7-SEG SW01M - Display: "Er" is displayed in 7-SEG

B(D) A(C)

Method of checking the pipe detection result


Example) Group number setting
at outdoor unit
1 F
1 Wait for 5 minutes, after Pipe detection is completed.
Group Indoor unit
2 Turn on the No.10, 14, 16 DIP S/W of SUB PCB at master unit
3 Check the data on 7- segment, switching rotary 01, 02. 1st number indicate the group number
2nd number point out indoor unit number
ROTARY 01 ROTARY 02
0

Group recognizing the central controller


The connected port number of HR No.0 group (00~0F)
unit No.1 group (10~1F)
No.2 group (20~2F)
The connected HR unit number
No.3 group (30~3F)
The auto addressing number of
No.4 group (40~4F)
indoor unit (digit of 1)
No.5 group (50~5F)
The auto addressing number of No.6 group (60~6F)
indoor unit (digit of 10)
No.7 group (70~7F)
No.8 group (80~8F)
No.9 group (90~9F)
Setting method of Master indoor unit in zoning No. A group (A0~AF)
1 Turn DIP switch 5, 6, 10 on at system off. No. B group (B0~BF)
2 Set the left Ratary switch for HR unit.(Rotary switch No. "0" ‘ HR No. C group (C0~CF)
unit No. "1") No. D group (D0~DF)
3 Set the right Ratary switch for IDU unit.(Rotary switch No. "0" ‘ HR No. E group (E0~EF)
unit branch No. "1") No. F group (F0~FF)
4 Display the Master IDU No. of the HR unit on 7segment.(Default
display is "00" on 7segment)
5 Press the black button.(The IDU No. increase every 1 second in the
zoning )
! WARNING
6 Set the Master IDU(Press the red button during 1.5 seconds stop • Valve address and central control address of its corresponding
twinkling) indoor unit should be set identical in manual addressing.

ROTARY 01 ROTARY 02 7 segment


EX)
0

Valve (04) Indoor unit (04)


Valve (03) Indoor unit (03)
HR unit
No. of Indoor unit. Valve (02) Indoor unit (02)
No. of HR unit branch. Valve (01) Indoor unit (01)

No. of HR unit.
Central control address

! CAUTION Setting the optional function


• Waiting for 80 seconds after power on. Select the mode/function/option/value using ‘▶’, ‘◀’ Button and
confirm that using the ‘●’ button after DIP switch No.5 is turned on.
• The zoning information and Master IDU information remove from
EEPROM after Auto-addressing. DIP-SW01
• If there is installed the central control, it is impossible setting of 7-Segment
Master IDU in zoning. SW04C (X : cancel)
SW03C (ȯ: forward)
SW02C (ȭ: backward)
SW01C (Ɨ: Confirm /
Automatic Addressing)
SW01D (reset)
42

CAUTION
ENGLISH

Optional Mode Selection Function Selection Option Selection !


Display Optional Remarks
Content Display (◎) Content Default • To perform the otional funtion should be sure that All the IDU is off
(◀, ▶ ’ ◎) (◀, ▶ ’ ◎)
mode, unless the function will not be performed.
Automatic Refrigerant
Fd 1 - -
Charging (Cooling)
Automatic Refrigerant
Fd 2 - -
Charging (Heating)
Refrigerant Amount
Fd 3 - -
Cool & Heat selector
* Refer FDD
Check (Cooling)
guidance Mode setting method
Refrigerant Amount
Fd 4 - -
FDD Fdd Check (Heating) Master unit PCB DIP switch on : No.5
Automatic system
check mode(cooling Fd 7 - -
or heating)
Select the mode using ‘▶’, ‘◀’ Button :
All IDU operation “Func” Push the ‘●’ button
Fd 8 - - Compulsory
(Cooling)
Operation for
All IDU operation 1 hour
Fd 9 - -
(Heating)
Select the Function using ‘▶’, ‘◀’ Button :
Cool & Heat oFF,
Selector
Fn 1 oFF
oP1~oP2 “Fn1” Push the ‘●’ button
High Static Pressure
oFF,
Compensation Fn 2 oFF
oP1~oP7
mode Select the Option using ‘▶’, ‘◀’ Button :
Night Low Noise oFF, “oFF”,“op1”,“op2” Push the ‘●’ button
Fn 3 oFF
mode oP1~oP12
North
Overall Defrost America: oFF
Fn 4 on, oFF Cool & Heat Selection mode is set
mode Europe: oFF
Tropical: oN
ODU address
Fn 5 0 254
setting Function setting
Snow Removal & oFF,
Fn 6 oFF
Rapid Defrost oP1~oP3 Switch Control Function
Airflow Adjusting
Switch Switch
for IDU (Heating Fn 7 oFF on, oFF oFF op1(mode) op2(mode)
capacity up) (Up) (Down)
Target Pressure
Fn 8 oFF
oFF, Right side Left side
Adjusting oP1~oP6 Not operate Cooling Cooling
(On) (On)
Low Ambient Kit Fn 9 oFF on, oFF Right side Right side
Not operate Heating Heating
High Efficiency
(On) (On)
Mode (Cooling Fn 10 oFF on, oFF Left side
Operation) - Not operate Fan mode Off
Saving in (Off)
Installation Func Auto Dust Removal oFF,
Fn 11 oFF EEPROM
Mode oP1~oP5
Compressor Max. oFF,
Fn 12 oFF Left side Right side
Frequency Limit oP1~oP9
ODU Fan Max.
oFF,
RPM Limit Mode Fn 13 oFF
oP1~oP7 Switch (Up)
settting
Smart Load Control oFF,
Fn 14 oFF
Mode setting oP1~oP3
Switch (Down)
Humidity Reference
Fn 16 on on, oFF
Mode setting
Central Control
Connection at Fn 19 oFF oFF, on
Indoor Unit side
Compressor Input
Current Limit mode
Fn 20 oFF
oFF,
oP1~oP10
! CAUTION
Power • Ask an authorized technician to setting a function.
Consumption SPL0, SPL1
Fn 21 SPL0 • If do not use a function, set an off-mode.
Display on wired [Pd10~Pd11]
remote controller • If use a function, first install a Cool & Heat selector.
Overall Defrost
Operating in Low
Fn 22 oFF on, oFF
temperature
(Heating)
Optional Base panel
Fn 23 oFF on, oFF
Heater
* Refer
Comfort Cooling Comfort Saving in
User Idu Id 10 EAch
Mode setting Cooling EEPROM
guidance
1time / 1
Service SvC Vaccum Mode SE 3 vACC -
Selection

* Functions save in EEPROM will be maintained continuously, though


the system power was reset.
43

ENGLISH
High Static Pressure Compensation mode Time Settings

This function secures the air flow rate of ODU, in case static pressure Step Judgment Time(Hr) Operation Time(Hr)
has been applied like using duct at fan discharge of ODU. op1 8 9
op2 6.5 10.5
Static pressure compensation mode setting method op3 5 12
op4 8 9
Master unit PCB DIP switch on : No.5 op5 6.5 10.5
op6 5 12
op7 8 9
Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button op8 6.5 10
op9 5 12
op10 Continuous operation
Select the Function using ‘▶’, ‘◀’ Button : op11 Continuous operation
“Fn2” Push the ‘●’ button op12 Continuous operation
Noise
Select the Option using ‘▶’, ‘◀’ Button : Chassis UXA UXB
“op1~op7” Push the ‘●’ button Capacity 8~12 hp 14~20 hp 22~26 hp
Step Noise(dBA)
op1~op3, op10 55 59 60
Start the Static pressure compensation mode : op4~op6, op11 52 56 57
Save the selected option value in EEPROM op7~op9, op12 49 53 55

FAN Maximum RPM of each step ! CAUTION


• Request installer to set the function during installation.
Chassis UXA UXB
Standard 880 1 000 • If ODU RPM changes, cooling capacity may go down.
Overload / Low
Temperature 1 000 1 150
op1 860 950 Overall defrost mode
op2 840 900
Max. RPM Mode setting method
op3 820 850
op4 800 800 Master unit PCB DIP switch on : No.5
op5 780 750
op6 760 700 Select the mode using ‘▶’, ‘◀’ Button :
op7 740 650 “Func” Push the ‘●’ button

Select the Function using ‘▶’, ‘◀’ Button :


“Fn4” Push the ‘●’ button
Night Low Noise Function
In cooling mode, this function makes the ODU fan operate at low RPM Select the Option using ‘▶’, ‘◀’ Button :
to reduce the fan noise of ODU at night which has low cooling load. “on”~“oFF” Push the ‘●’ button

Night low noise function setting method


Overall defrost mode is set
Master unit PCB DIP switch on : No.5
Mode setting
- on: Operate overall defrost
Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button - off: Operate partial defrost

! CAUTION
Select the Function using ‘▶’, ‘◀’ Button :
“Fn3” Push the ‘●’ button • Ask an authorized technician to setting a function.

Select the Option using ‘▶’, ‘◀’ Button : Setting the ODU address
“op1~op12” Push the ‘●’ button
Mode setting method
Master unit PCB DIP switch on : No.5
Start the Night low noise function :
Save the selected option value in EEPROM
Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button

Select the Function using ‘▶’, ‘◀’ Button :


“Fn5” Push the ‘●’ button

Select the Option using ‘▶’, ‘◀’ Button :


“0”~“255” Push the ‘●’ button

ODU address is set


44

CAUTION
ENGLISH

! Target pressure adjusting


Mode setting method
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller. Master unit PCB DIP switch on : No.5

Select the mode using ‘▶’, ‘◀’ Button :


“Func” Push the ‘●’ button
Snow removal & rapid defrost
Mode setting method Select the Function using ‘▶’, ‘◀’ Button :
“Fn8” Push the ‘●’ button
Master unit PCB DIP switch on : No.5

Select the Option using ‘▶’, ‘◀’ Button :


Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button “HEAT”, “COOL” Push the ‘●’ button

Select the Option using ‘▶’, ‘◀’ Button :


Select the Function using ‘▶’, ‘◀’ Button :
“Fn6” Push the ‘●’ button “op1”~“op4” Push the ‘●’ button

Select the Option using ‘▶’, ‘◀’ Button : Target pressure is set
“oFF”,“op1”~“op3” Push the ‘●’ button
Setting

Mode is set Purpose Condensing Evaporating


Mode temperature temperature
Heat Cool variation variation
Mode setting +2 °C -3 °C
op1 Increase capacity Increase capacity
(35.6 °F) (37.4 °F)
setting Mode
Decrease power +2 °C -1.5 °C
oFF Not setting op2 Increase capacity
consumption (35.6 °F) (-34.7 °F)
op1 Snow removal mode Decrease power Decrease power -4 °C +2.5 °C
op3
op2 Rapid defrost mode consumption consumption (-39.2 °F) (36.5 °F)
Decrease power Decrease power -6 °C -4.5 °C
op3 Snow removal mode. + Rapid defrost mode. op4
consumption consumption (-42.8 °F) (-40.1 °F)

! CAUTION ! CAUTION
• Ask an authorized technician to setting a function.
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.

Setting Capacity Up Airflow Adjusting for IDU


(Heating) Low Ambient Kit
If the operation of indoor unit is more than 130 %, the air flow is Mode setting method
operated as low in the all indoor units.
Master unit PCB DIP switch on : No.5
Mode setting method
Master unit PCB DIP switch on : No.5 Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button
Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button Select the Function using ‘▶’, ‘◀’ Button :
“Fn9” Push the ‘●’ button
Select the Function using ‘▶’, ‘◀’ Button :
“Fn7” Push the ‘●’ button Select the Option using ‘▶’, ‘◀’ Button :
“on”,“oFF” Push the ‘●’ button
Select the Option using ‘▶’, ‘◀’ Button :
“on”~“oFF” Push the ‘●’ button Low Ambient Kit Mode is set

IDU capacity adjusting is set h Reference for functional logic of I/O Module

Step Mode
OFF Not setting
ON Low capacity mode

! CAUTION
• Ask an authorized technician to setting a function.
45

ENGLISH
High Efficiency Mode (Cooling Operation) Compressor Max. Frequency Limit
Target low pressure will change according to ODU temperature during Mode setting method
the cooling operation.
Master unit PCB DIP switch on : No.5
Mode setting method

Master unit PCB DIP switch on : No.5


Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button
Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button
Select the Function using ‘▶’, ‘◀’ Button :
“Fn 12” Push the ‘●’ button
Select the Function using ‘▶’, ‘◀’ Button :
“Fn10” Push the ‘●’ button
Select the Option using ‘▶’, ‘◀’ Button :
“oFF”,“op1”,“op9” Push the ‘●’ button
Select the Option using ‘▶’, ‘◀’ Button :
“on”,“oFF” Push the ‘●’ button

Cool & Heat Selection mode is set


High Efficiency Mode is set

Function setting
Auto Dust Removal Mode
Setting Inverter (Hz)
The ability to set reverse run outdoor fan to remove dust, heat oFF -
exchanger.
op1 143 Hz
Mode setting method
op2 135 Hz
Master unit PCB DIP switch on : No.5 op3 128 Hz
op4 120 Hz
Select the mode using ‘▶’, ‘◀’ Button : op5 113 Hz
“Func” Push the ‘●’ button op6 105 Hz
op7 98 Hz
Select the Function using ‘▶’, ‘◀’ Button : op8 90 Hz
“Fn11” Push the ‘●’ button op9 83 Hz

Select the Option using ‘▶’, ‘◀’ Button :


“oFF”,“op1”~“op5” Push the ‘●’ button
! CAUTION
• Ask an authorized technician to setting a function.
Auto Dust Removal Mode is set • If use a function, first install a Central controller.

Mode Setting
Operation Operating Repeat
Setting Detail of function
time time cycle
Stop After product stopped 2 hour, fan operating 5
ODU Fan Max. RPM Limit
op1 5 minutes 2 hour
+2 hour min(Repeated every 2 hours) Mode setting method
after product stopped 5 minutes, fan Master unit PCB DIP switch on : No.5
stop Twice in
op2 3 minutes operating 3 min (Limited to two times within
+5 minutes 2 hour
2 hours)
Select the mode using ‘▶’, ‘◀’ Button :
stop after product stopped 2 hour, fan operating 5
op3 3 minutes 1 time “Func” Push the ‘●’ button
+5 minutes min(Repeated every 2 hours)
after product stopped 5 minutes, fan
Stop Select the Function using ‘▶’, ‘◀’ Button :
op4 1 minutes 1 time operating 3 min(when io module
+1 minutes “Fn13” Push the ‘●’ button
connection/one-time operation)
Stop Low after product stopped 1 minutes, fan
op5 1 minutes
+1 minutes speed operating 1 min(every time the product stops)
Select the Option using ‘▶’, ‘◀’ Button :
“oFF”,“op1”~“op7” Push the ‘●’ button

ODU Fan Max. RPM Limit Mode is set


46
ENGLISH

MAX. RPM Limit Setting Mode setting


- on:using humidity sensor
Chassis UXA UXB - oFF:not setting
oFF 880 1 000
oP1 -20 -50
<Using of humidity sensor>
oP2 -40 -100
- When used cooling operation of SLC function,it will improve energy
Fan MAX. RPM oP3 -60 -150 effcience because evaporation temperature wll be decreased
Limit (RPM) oP4 -80 -200 - When used heating operation in case of high humidity condition,
oP5 -100 -250 deforest will be delayed because target high/low pressure will be
oP6 -120 -300 changed.
oP7 -140 -350

SLC (Smart Load Control) Central Control Connection at Indoor Unit side
Function for set the variable target pressure which for the high Mode setting method
efficiency and comport operation depend on ODU load. Master unit PCB DIP switch on : No.5
Mode setting method

Master unit PCB DIP switch on : No.5 Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button

Select the mode using ‘▶’, ‘◀’ Button :


“Func” Push the ‘●’ button Select the Function using ‘▶’, ‘◀’ Button :
“Fn16” Push the ‘●’ button

Select the Function using ‘▶’, ‘◀’ Button :


“Fn14” Push the ‘●’ button Select the Option using ‘▶’, ‘◀’ Button :
“Fn19” Push the ‘●’ button

Select the Option using ‘▶’, ‘◀’ Button :


“oFF”,“op1”~“op3” Push the ‘●’ button Select the Option using ‘▶’, ‘◀’ Button :
“on”,“oFF” Push the ‘●’ button

SLC(Smare Lode Control) Mode is set


Central Control Connection at Indoor
Unit side Mode is set
SLC(Smare Lode Control) Mode

Setting Mode Detail of function


oFF Not Setting - Compressor Input Current Limit
oP1 Smooth Mode Slowly control, a target pressure value System Input Current Control
oP2 Normal Mode Normal control, a target pressure value Mode setting method
oP3 Peak Mode Fast control, a target pressure value
Master unit PCB DIP switch on : No.5

Select the mode using ‘▶’, ‘◀’ Button :


“Func” Push the ‘●’ button
Humidity Reference
Mode setting method Select the Function using ‘▶’, ‘◀’ Button :
“Fn20” Push the ‘●’ button
Master unit PCB DIP switch on : No.5

Select the mode using ‘▶’, ‘◀’ Button : Select the Option using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button “oFF”,“op1”~”op10” Push the ‘●’ button

Select the Function using ‘▶’, ‘◀’ Button : Compressor Input Current Limit mode is set
“Fn16” Push the ‘●’ button

Compressor Input Current Limit


Select the Option using ‘▶’, ‘◀’ Button :
“oFF”,“on” Push the ‘●’ button Mode Compressor Input Current Limit
op1 95 %
op2 90 %
Humidity Reference Control mode is set op3 85 %
op4 80 %
op5 75 %
op6 70 %
op7 65 %
op8 60 %
op9 55 %
op10 50 %
47

CAUTION

ENGLISH
! Base pan Heater operation
• Ask an authorized technician to setting a function. Master unit PCB DIP switch on : No.5
• If do not use a function, set an off-mode.
• If use a function, capacity may go down.
Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button

Power Consumption Display on wired remote


Select the Function using ‘▶’, ‘◀’ Button :
controller “Fn23” Push the ‘●’ button
Mode setting method
Master unit PCB DIP switch on : No.5 Select the Option using ‘▶’, ‘◀’ Button :
“oFF”,“on” Push the ‘●’ button

Select the mode using ‘▶’, ‘◀’ Button :


“Func” Push the ‘●’ button
Base pan Heater operation mode is set

Select the Function using ‘▶’, ‘◀’ Button :


“Fn21” Push the ‘●’ button
! CAUTION
• Function to prevent freezing of ODU base pan in a cold area.
Select the Option using ‘▶’, ‘◀’ Button :
“SPL0”,“SPL1”,”Pd10”,”Pd11”Push the ‘●’ • Heater is accesory.(Sold separately)
button

Power Consumption Display on wired remote


controller Mode is set Comfort Cooling operation
It is function to reduce the ODU energy consumption by the continuou
s operation without thermo off.
Setting Detail of function Mode setting method
SPL0 Not used Smart plug logic
Master unit PCB DIP switch on : No.5
SPL1 Using smart plug logic
Pd10 Not installation Select the mode using ‘▶’, ‘◀’ Button :
“Idu” Push the ‘●’ button
Pd11 PDI was installed

Select the Function using ‘▶’, ‘◀’ Button :


“Id10” Push the ‘●’ button
Overall Defrost Operating in Low temperature
(Heating)
EEV pulse appearing
Mode setting method (seg1, seg2:Idu No./seg3, seg4:Mode)
Master unit PCB DIP switch on : No.5 Select the Function using ‘▶’, ‘◀’ Button :
Idu No. setting and Push the ‘●’ button
Select the Function using ‘▶’, ‘◀’ Button :
Mode setting and Push the ‘●’ button
Select the mode using ‘▶’, ‘◀’ Button :
*Mode can be set 0~3 (”0” is no setting)
“Func” Push the ‘●’ button

Select the Function using ‘▶’, ‘◀’ Button : Setting of continous cooling operation
“Fn21” Push the ‘●’ button

Select the Function using ‘▶’, ‘◀’ Button : Setting of continous cooling operation
“Fn22” Push the ‘●’ button
Mode setting Effect
0 No setting
Overall Defrost Operating in Low Mode is set 1 Cooling capacity low,Power consumption low
2 Cooling capacity mid,Power consumption mid
3 Cooling capacity high,Power consumption high
Setting Detail of function
Defualt OFF
Setting ON/OFF Control
48
ENGLISH

Self-Diagnosis Function
Error Indicator
- This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
- Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit control board as
shown in the table.
- If more than two troubles occur simultaneously, lower number of error code is first displayed.
- After error occurrence, if error is released, error LED is also released simultaneously.

Error Display
1st, 2nd, 3rd LED of 7-segment indicates error number, 4th LED indicates unit number.(* = 1: Master, 2: Slave 1, 3: Slave 2, 4: Slave 3)
Ex) 1051 : Error occurrence with error number 105 at No. 1 outdoor unit (=Master unit) Repeat
In case of indoor unit error occurrence, the error number is only shown at remote controller
without 7 segment LED of outdoor unit. Error No. of Unit
Error No. of Compressor
Ex) CH → 01 : Error occurrence with error number 01 (at remote controller) Error No.
In case of compressor error occurrence, 7 segment LED of outdoor unit control board
will display its error number alternately with compressor number.
Ex) 213 → C23 : It means that compressor error occurred with Error No. 21 at No. 3 Outdoor unit (=Slave 2)

* Refer to the DX-Venitilation manual for DX-Venitilation error code.

Display Title Cause of Error


0 1 - Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short
0 2 - Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short
Communication error : wired remote controller ↔
0 3 - Failing to receive wired remote controller signal in indoor unit PCB
indoor unit
0 4 - Drain pump Malfunction of drain pump
0 5 - Communication error : outdoor unit ↔ indoor unit Failing to receive outdoor unit signal in indoor unit PCB
0 6 - Outlet pipe temperature sensor of indoor unit Outlet pipe temperature sensor of indoor unit is open or short

Hydro Kit Hot water storage tank Temperature


0 8 - Pipe temperature sensor is open or short
sensor

In case when the serial number marked on EEPROM of


0 9 - Indoor EEPROM Error
Indoor unit is 0 or FFFFFF
Indoor unit related error

Disconnecting the fan motor connector / Failure of indoor


1 0 - Poor fan motor operation
fan motor lock

Communication error : Hydro Kit Indoor unit ↔


1 1 - Failing to receive Inv. PCB signal in indoor unit
Inv.PCB

1 2 - Hydro Kit Inv.PCB error Hydro Kit Inv.PCB error

Hydro Kit Solar heat piping temperature sensor


1 3 - Pipe temperature sensor is open or short
error

1 4 - Hydro Kit Indoor unit Flow switch error Flow switch flow detection error
1 5 - Hydro Kit Liquid pipe Strange overheat Error Temperature sensor defective or hot water inflow

Hydro KitIndoor unit Inlet and Outlet pipe


1 6 - Pipe temperature sensor is open or short
Temperature sensor Error

Hydro Kit Indoor unit Inlet pipe Temperature


sensor Error
1 7 - Pipe temperature sensor is open or short
Outside air Introduction duct Inlet pipe
Temperature sensor Error
Hydro Kit Indoor unit Outlet pipe Temperature
1 8 - Pipe temperature sensor is open or short
sensor Error
2 1 * Outdoor Unit Inverter Compressor IPM Fault Outdoor Unit Inverter Compressor Drive IPM Fault
Outdoor unit related error

Inverter PCB Input Over Current(RMS) of Master


2 2 * Outdoor Unit Inverter PCB Input Current excess (RMS)
Outdoor Unit
Outdoor Unit Inverter Compressor DC Link Low or System is turned off by Master Outdoor Unit DC Link Low/High
2 3 *
High Voltage Voltage.
2 4 * Outdoor Unit High Pressure Switch System is turned off by Master Outdoor Unit high pressure switch.
Over 537 V or below 247 V (ARUM***LTE5)
2 5 * Outdoor Unit Input Voltage High/ Low Voltage Over 310 V or below 143 V (ARUM***BTE5)
Over 598 V or below 320 V (ARUM***DTE5)

• 1 : Master outdoor unit error, 2 : salve 1 outdoor unit error


• 3 : slave 2 outdoor unit error, 4 : slave 3 outdoor unit error
49

ENGLISH
Display Title Cause of Error
The first start failure by Outdoor Unit Inverter Compressor
2 6 * Outdoor Unit Inverter Compressor Start Failure
abnormality or Compressor locked

2 9 * Outdoor Unit Inverter Compressor Over Current Outdoor Unit Inverter Compressor Fault OR Drive Fault

Outdoor Unit Inverter Compressor1 High


3 2 * Outdoor Unit Inverter Compressor1 High Discharge Temperature
Discharge Temperature
Outdoor Unit Inverter Compressor2 High
3 3 * Outdoor Unit Inverter Compressor2 High Discharge Temperature
Discharge Temperature
3 4 * High Pressure of Outdoor Unit High Pressure of Outdoor Unit
3 5 * Low Pressure of Outdoor Unit Low Pressure of Outdoor Unit

4 0 * Outdoor Unit Inverter Compressor CT Sensor Fault Outdoor Unit Inverter Compressor CT Sensor open or short

Outdoor Unit Inverter Compressor1 Discharge Outdoor Unit Inverter Compressor Discharge Temperature
4 1 *
Temperature Sensor Fault Sensor open or short
4 2 * Outdoor Unit Low Pressure Sensor Fault Outdoor Unit Low Pressure Sensor open or short
4 3 * Outdoor Unit High Pressure Sensor Fault Outdoor Unit High Pressure Sensor open or short
4 4 * Outdoor Unit Air Temperature Sensor Fault Outdoor Unit Air Temperature Sensor open or short
Outdoor Unit Heat Exchanger Temperature Sensor Outdoor Unit Heat Exchanger Temperature Sensor(Front side)
4 5 *
(Front side) Fault open or short

4 6 * Outdoor Unit Suction Temperature Sensor Fault Outdoor Unit Suction Temperature Sensor open or short

Outdoor Unit Inverter Compressor2 Discharge Outdoor Unit Inverter Compressor2 Discharge Temperature
4 7 *
Temperature Sensor Fault Sensor open or short
Outdoor unit related error

4 9 * Outdoor Unit Faulty IPM Temperature Sensor Outdoor Unit IPM Temperature Sensor short/open

Omitting connection of R, S, T power of Outdoor


5 0 * Omitting connection of outdoor unit
Unit
Excessive connection of indoor units compared to capacity of
5 1 * Excessive capacity of indoor units
Outdoor Unit
5 2 * Communication error : inverter PCB ’ Main PCB Failing to receive inverter signal at main PCB of Outdoor Unit
Communication error : indoor unit ’ Main PCB of
5 3 * Failing to receive indoor unit signal at main PCB of Outdoor Unit.
Outdoor Unit
5 7 * Communication error : Main PCB ’ inverter PCB Failing to receive signal main PCB at inverter PCB of Outdoor Unit
6 0 * Inverter PCB EEPROM Error of Master Outdoor Unit Access Error of Inverter PCB of Outdoor Unit
System is turned off by Outdoor Unit Inverter Heatsink High
6 2 * Outdoor Unit Inverter Heatsink High Temperature
Temperature
Outdoor Unit Inverter Heatsink Temperature Outdoor Unit Inverter Heatsink Temperature Sensor open or
6 5 *
Sensor Fault short
6 7 * Outdoor Unit Fan Lock Restriction of Outdoor Unit
7 1 * Inverter CT Sensor Error of Master Outdoor Unit Inverter CT Sensor open or short of Outdoor Unit
7 5 * Outdoor Unit Fan CT Sensor Error Outdoor Unit Fan CT Sensor open or short
7 7 * Outdoor Unit Fan Over Current Error Outdoor Unit Fan Current is over 6 A

The first start failure by Outdoor Unit Fan abnormality or Fan


7 9 * Outdoor Unit Fan Start Failure Error
locked

Communication Fail Between Outdoor Unit Main MICOM and


8 6 * Outdoor Unit Main PCB EEPROM Error
EEPROM or omitting EEPROM
Communication Fail Between Outdoor Unit Fan MICOM and
8 7 * Outdoor Unit Fan PCB EEPROM Error
EEPROM or omitting EEPROM
Communication Error Between Outdoor Unit and
1 0 4 * Failing to receive Slave Unit signal at main PCB of Outdoor Unit
Other Outdoor Unit
1 0 5 * Outdoor Unit Fan PCB Communication Error Failing to receive fan signal at main PCB of Outdoor unit
1 0 6 * Outdoor Unit Fan IPM Fault Error Instant Over Current at Outdoor Unit Fan IPM
50
ENGLISH

Display Title Cause of Error

1 0 7 * Outdoor Unit Fan DC Link Low Voltage Error Outdoor Unit Fan DC Link Input Voltage is under 380 V
1 1 3 * Outdoor Unit Liquid pipe Temperature Sensor Error Liquid pipe temperature sensor of Outdoor Unit is open or short
Outdoor Unit Subcooling Inlet Temperature
1 1 4 * Outdoor Unit Subcooling Inlet Temperature Sensor Error
Sensor Error
Outdoor Unit Subcooling Outlet Temperature
1 1 5 * Outdoor Unit Subcooling Outlet Temperature Sensor Error
Sensor Error
1 1 6 * Outdoor Unit Oil Level Sensor Error Oil Level Sensor of Outdoor Unit is open or short
Outdoor unit Main Board - External Board
1 4 5 * Outdoor unit Main Board - External Board communication Error
Outdoor unit related error

communication Error
Outdoor Unit Compressor Discharge Superheat not satisfied
1 5 0 * Outdoor Unit Discharge Superheat not satisfied
during 5 Min.
Failure of operation mode conversion at Outdoor
1 5 1 * Failure of operation mode conversion at Outdoor Unit
Unit
Outdoor Unit Heat Exchanger Temperature Outdoor Unit Heat Exchanger Temperature Sensor (upper part)
1 5 3 *
Sensor (upper part) Fault Fault
Outdoor Unit Heat Exchanger Temperature Outdoor Unit Heat Exchanger Temperature Sensor(lower part)
1 5 4 *
Sensor (lower part) Fault open or short
Outdoor unit External Board Main-Sub Micom Outdoor Unit Main Board Main-Sub Micom communication
1 8 2 *
communication Error failed
Inlet water temperature is below 5 degree or water temperature
1 8 7 * Hydro - Kit P, HEX bursting error
error during defrosting operation.
System is turned off by Outdoor Unit Fan Heatsink High
1 9 3 * Outdoor Unit Fan Heatsink High Temperature
Temperature
Outdoor Unit Fan Heatsink Temperature Sensor
1 9 4 * Outdoor Unit Fan Heatsink Temperature Sensor open or short
Fault
Network error HR Unit related error

2 0 0 1 Searching pipe Error Failure of automatic addressing of valves


2 0 1 C + #HR HR unit1 Liqiud sensor error Liquid pipe sensor of HR unit open or short
2 0 2 C + #HR HR unit1 Sub Cooling Pipe sensor error Sub Cooling Pipe In sensor of HR unit open or short
2 0 3 C + #HR HR unit1 Sub Cooling Pipe Out sensor error Sub Cooling Pipe Out sensor of HR unit. open or short
2 0 4 C + #HR Communication error Failing to receive HR unit signal at outdoor unit

2 4 2 * Network error of cntral controller Communication wiring defect

C: HR unit
#: HR unit Number
51

ENGLISH
CAUTION FOR REFRIGERANT LEAK Calculate refrigerant concentration

The installer and system specialist shall secure safety against leakage Total amount of replenishedrefrigerant
according to local regulations or standards. in refrigerant facility [kg(lbs)]
= Maximum concentration limit
The following standards may be applicable if local regulations are not Volume of smallest room whereindoor [kg/m3 (lbs/ft3)]
available. 3 3
unit is installed [m (ft )]
(R410A)
Introduction
Though the R410A refrigerant is harmless and incombustible itself , - In case the result of calculation exceeds the Concentration limit, perform the
the room to equip the air conditioner should be large to such an extent same calculations by shifting to the second smallest, and the third smallest
that the refrigerant gas will not exceed the Concentration limit even if rooms until at last the result is below the Concentration limit.
the refrigerant gas leaks in the room.

In case the concentration exceeds the limit


Concentration limit When the concentration exceeds the limit, change original plan or take
one of the countermeasures shown below:
Concentration limit is the limit of Freon gas concentration where • Countermeasure 1
immediate measures can be taken without hurting human body Provide opening for ventilation.
when refrigerant leaks in the air. The Concentration limit shall be Provide 0.15 % or More size of opening to floor space both above
described in the unit of [kg/m3 (lbs/ft3)] (Freon gas weight per unit and below door, or provide opening without door.
air volume) for facilitating calculation.
• Countermeasure 2
Concentration limit : 0.44 kg/m3 (0.028 lbs/ft3) (R410A) Provide gas leak alarm linked with mechanical ventilator.
• Countermeasure 3
Reducing the outdoor refrigerant qty. by deviding into smaller
Outdoor unit separate system.
Flow of
(No.1 system) refrigerant
Gas leak alarm
Countermeasure 2
Mechanical ventilator
Indoor unit Room where refrigerant leaks
(Refrigerant of the whole No.1
system flows out.)

Indoor unit

Checking procedure of limiting concentration


Check Concentration limit along following steps and take appropriate
measure depending on the situation.
Calculate amount of all the replenished refrigerant [kg (lbs)] per each
refrigerant system.
Amount of pre charged Amount of additional = Total amount of
refrigerant per single unit + replenished refrigerant refrigerant in the system
system [kg (lbs)]
Countermeasure 1 Opening effective to ventilation
Amount of replenished Amount of additionally Note : In case one refrigerant facility is
refrigerant at factory shipment replenished refrigerant divided into 2 or more refrigerant
depending on piping systems and each system is
length or piping independent, amount of replenished
diameter by customer refrigerant of each system shall be
adopted. Pay a special attention to the place, such as a basement, etc.
where refrigerant can stay, since refrigerant is heavier than air.

Calculate minimum room capacity


Calculate room capacity by regarding a portion as one room or the
smaller room.
- Without partition - With partition and with opening
which serve as passage of air to
adjoining room
Outdoor unit Outdoor unit

Indoor unit Indoor unit In the case of opening


without door , or 0.15
Opening % or more openings
(to floor space) both
Partition above and below door)

- With partition and without opening which serve as passage of air to


adjoining room
Outdoor unit

Indoor unit

Smallest
room
52
ENGLISH

INSTALLATION GUIDE AT THE Model Designation


SEASIDE Product information

! CAUTION • Product Name : Air conditioner


• Model Name :
• Air conditioners should not be installed in areas where corrosive
gases, such as acid or alkaline gas, are produced. Product Sales Name Model Factory Name
• Do not install the product where it could be exposed to sea wind
(salty wind) directly. It can result corrosion on the product. ARUx***LTy5 series
Corrosion, particularly on the condenser and evaporator fins, x = N (Heat Pump), V (Cooling Only), M (Heat Recovery / Heat Pump)
could cause product malfunction or inefficient operation.
y = S (Basic function),
• If outdoor unit is installed close to the seaside, should avoid E (Additional function related to performance)
direct exposure to the sea wind.
*** = Numeric; (Cooling capacity)

Selecting the location(Outdoor Unit) • Additional information : Serial number is refer to the bar code on the
product.
If the outdoor unit is to be installed close to the seaside, direct
exposure to the sea wind should be avoided. Install the outdoor unit on
the opposite side of the sea wind direction.

Airborne Noise Emission


Sea wind The A-weighted sound pressure emitted by this product is below 70
dB.
** The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe
working levels.
Whilst there is a correlation between the emission and exposure
levels, this cannot be used reliably to determine whether or not further
precautions are required.
Factor that influence the actual level of exposure of the workforce
include the characteristics of the work room and the other sources of
Sea wind noise, i.e. the number of equipment and other adjacent processes and
the length of time for which an operator exposed to the noise. Also,
the permissible exposure level can vary from country to country.
This information, however, will enable the user of the equipment to
make a better evaluation of the hazard and risk.

In case, to install the outdoor unit on the seaside, set up a windbreak


not to be exposed to the sea wind.

Windbreak

Sea wind

- It should be strong enough like concrete to prevent the sea wind


from the sea.
- The height and width should be more than 150 % of the outdoor unit.
- It should be kept more than 70 cm (2.3 ft) of distance between
outdoor unit and the windbreak for smooth air flow.

Select a well-drained place.

• Periodic (1 times per 6 month) cleaning of the dust or salt


particles stuck on the heat exchanger is necessary by using clean
water.
ООО «ЛГ Электроникс РУС» 143160, РФ, Московская область, Рузский район, СП
Дороховское, 86-й км. Минское шоссе, д.9.
[Manufacturer] LG Electronics Inc. Changwon 2nd factory
84, Wanam-ro, Seongsan-gu, Changwon-si, Gyeongsangnam-do, KOREA

You might also like