Mini-shelter installed on a concrete floor foundation Mini-shelter installed on the rooftop steel structure
(1) Mini-shelter (2) Concrete floor foundation (3) Steel structure beam
Minishelter concrete foundation design drawing
2.Hardware introduce
Product Description-minishelter cabinet
Maximum
2420 mm x 905 mm x 1135
external
mm (95.28 in. x 35.63 in. x
dimensions (H
44.69 in.)
x W x D)
9
Product Description-ETP48200
10
Monitor system---EMUA
Function An EMUA collects and uploads environment alarms for the site. An EMUA can upgrade alarm signals
only through Huawei main equipment.
Weight 3.5 kg
Environment parameter Smoke sensor, door sensor, water sensor, temperature and Sensor selection
humidity sensor
Alarm input port 32 output branches
Parameter Index
- 48 V DC input and nine-48 V DC outputs, which power the BBU and DC RRU. To be used with the
Function DBS3900. Core diameter of the DC power cable from the DCDU to customers: 16 mm^2 (-48 V blue,
GND black)
Power distribution 6x20 A + 3x12 A; 6 20-A air circuit breakers are used to power the RRU; one 12 A air circuit breaker
specification® powers the BBU and the other two are reserved.
Outline dimensions (height x
43.6 mm (height, 1U) x 442 mm (width, 19 inches) x 200 mm (depth)
width x depth)
12
Review the packing list
MATERIAL CTNNO. PART NUMBER DESCRIPTION QTY UOM
RTN
Space
battery1
battery2
Installation ETP48200B
Installation DCDU
Installation EMUA-Setting the switches in EMUA
off
on
on
on
SW_ADDR出厂默认拨码设置
Installation EMUA
Installation temperature and humidity sensor
Installation smoke sensor
Installation water sensor
Installation outdoor grounding bar
4.Power and alarm Cable
connection
Powee and alarm System layout
4.1 Power Cable layout
DC Power distribute
F9 20A MCB Lamp
Load Low Voltage F8 100A MCB
Disconnection
F7 100A MCB DCDU
F6 16A MCB EMUA
ETP48200 F5 16A MCB PC500D
Battery Low
F4 16A MCB AH1500
Voltage
F3 32A MCB
Disconnection
F2 32A MCB BBU
F1 32A MCB RTN
LOAD8 12A MCB
LOAD7 12A MCB
LOAD6 12A MCB
LOAD5 20A MCB RRU1
DCDU LOAD4 20A MCB RRU2
LOAD3 20A MCB RRU3
LOAD2 20A MCB RRU4
LOAD1 20A MCB RRU5
LOAD0 20A MCB RRU6
32
AC Power distribute
33
Set some parameter in ETP48200
Password: 0#
34
Cable connection battery
Cable connection AH1500
Cable connection PC500D
Installation and connection lamp
Installation and connection socket
Grounding Cable connection
Seal Cable hole
4.2 Alarm Cable layout
Alarm distribute
43
EMUA alarm ports introduce
44
Cable connected from EMUA to BBU
Alarm Cable connected temperature and humidity sensor
Alarm Cable connected smoke sensor
Alarm Cable connected door sensor
Alarm Cable connected water sensor
Alarm Cable connected battery temperature sensor
Alarm Cable connected TTP48200
51
ETP48200 Alarm check/test on site
ALM1 AC power failures alarm Shut down AC input MCB Short the ALM dray
and power the system contact with a
with battery. nipper.
ALM2 DC input overvoltage and / Short the ALM dray
undervoltage alarm contact with a
nipper.
ALM3 Power system failures Block the rectifier fan Short the ALM dray
alarm to simulate a fan contact with a
alarm. nipper.
ALM4 SPD failure alarm Pull out a SPD module to Short the ALM dray
simulate a SPD alarm. contact with a
nipper.
ALM5 Fuse disconnection alarm Shut down DC output MCB Short the ALM dray
with load. contact with a
nipper.
ALM6 Battery protection alarm Battery voltage is lower Short the ALM dray
than 43.2v. contact with a
nipper.
52
5.Power on
Power on minishelter
54