I - electrical installations
II - railroad installations
A. I only
B. II only
C. both I & II
D. neither I nor II
CORRECT: B NEC 1
32 The code has assigned the color ____ to the high leg of
a 4-wire delta connected secondary.
A. orange
B. paungo pink
C. red with green tracer
D. turbo black
CORRECT: A NEC 110.15
C. 36"
D. 38"
CORRECT: C NEC 110.34 (A) Table
Refer to the chart on page 32 of the 1999 NEC. You'll Electrical Equipment Room
need to look at the diagram and interpret it to arrive at the
correct answer. This drawing shows condition 1, for 600
Volts.
I. clock outlet
II. outdoor receptacle
A. I only
B. II only
C. both I & II
D. neither I nor II
CORRECT: A NEC 210.52 (B)(2) exception 1
Solution:
Comment: NEC 1996 & 1999 reference 220-3 (b) &
Table 220-11; NEC 2002 reference 220.3 (A) & Table
220.11.
117 A show window is 240 feet long. How many 120 volt,
20 amp branch circuits will be required for this load?
A. 20 Branch circuits
B. 15 Branch circuits
C. 25 Branch circuits
D. 18 Branch circuits
CORRECT: A NEC 220.43 (A)
150 volts!
Comment: NEC 1996 reference is 250-123 (c).
238 Using the information shown in the transformer 102/208 Secondary Transfomer
diagram, Determine the minimum size THW aluminum L1
conductor, allowed by the NEC for the grounded
service conductor, given: ungrounded service 120
conductors are aluminum 1/0 THW in conduit and no
208 volt loads.
N
A. 1/0 AWG
120 208
120
B. 3 AWG
L2
C. 5 AWG
208
D. 7 AWG L3
CORRECT: A NEC 250.66 Table
The NEC says that "the upper end of the electrode shall
be flush with or below ground level unless the above
ground end and the grounding conductor attachment are
protected against physical damage as specified 250.10."
Comment: NEC 1996 reference is 250-83 (c)(3) and
NEC 1999 reference is 250-52 (c)(3).
276 Cable that is run parallel with the studs that is not
provided with special protection shall be placed a
minimum of ___ inches from the edge of the stud.
A. 3/4"
B. 1 1/4"
C. 1 1/2"
D. 2"
CORRECT: B NEC 300.4 (A)(1)
293 The minimum burial depth for PVC conduit under a 4"
concrete slab is ____inches.
A. 24
B. 18
C. 4
D. 0
CORRECT: C NEC 300.5 Table
Comment: NEC 1996 & 1999 reference 300-5 Table.
A. 6"
B. 12"
C. 15"
D. 18"
CORRECT: D NEC 300.5 Table & 250.80
331 A 50 HP, 208 volt, three phase wound rotor motor is 500 kcmil
supplied by tap conductors as shown in the drawing. copper
THW
For calculation purposes, consider all termination to be 50 HP - 208 Volt
rated at 75 degrees C. According to the NEC, the 3 phase
minimum size copper THW tap conductors shall be no wound rotor motor
less than ___ AWG.
THW tap conductors
A. 8
B. 6
21'
Fused
C. 4 Motor
Disconnect
D. 1
CORRECT: B NEC 310.16 Table
Solution: 50 X 746 (watts per HP) = 37,300 watts.
37,300 divided by 208 Volt = 179.33 amps. 179.33
divided by 3 = 59.78 amps per phase. Look up in table
310-16.
A. 4.5 FC1
B. 5.5
C. 8.5
D. depends on type of fitting at the conductor
entrance
CORRECT: C NEC 312.6 (A) Table and 312.6 1-A
(B) Table
Comment: NEC 1996 & 1999 refer to article 373.
Comment: NEC 1996 & 1999 reference 370-16 (a) & (b).
401 Using the following information and the diagram, what "A"
is the minimum size of the box at "A"?
1. Three feeders.
2. Three-350 KCMIL in the 3" conduits. 3" 3"
3. Eight-#10 AWG in the 1" conduits.
4. Four-#2 AWG in 2" conduits.
2" 2" "B"
A. 18"
B. 19"
C. 22" 1" 1"
D. 24"
CORRECT: D NEC 314.28 (A)(1)
The largest raceway is 3 in. so 3 in. x 8 = 24".
Comment: NEC 1996 & 1999 refer to article 370.
402 Size 350 Kcmil conductors are pulled through this box
in the image. What is the minimum number of inches
allowed between the 2 three inch conduits which is
dimension B:
A. 12
B. 18
C. 24
D. 36
CORRECT: B NEC 314.28 (A)(1)
5 x ½" = 2½"
Comment: NEC 1996 & 1999 reference 336-16.
5 x ½" = 2½"
Comment: NEC 1996 & 1999 reference 336-16.
Comment: NEC 1996 & 1999 reference 331-4 (5) & 347-
2 (g).
1. 8 # 1 AWG
2. 7 # 2 AWG
3. 4 #3 AWG
4. 6 #6 AWG
487 Consealed knob and tube wiring shall be used only for:
A. houses and out buildings
B. well houses
C. extensions of existing installations
D. accessible locations
CORRECT: C NEC 394.10 (1)
Comment: NEC 1996 & 1999 reference is 324-3 (1).
517 Branch circuit wires are 2" from the ballast within the
ballast compartment of a fluorescent lighting fixture.
Which type of conductors may be used?
A. THW or THHN
B. RH or RHW
C. CHF or THWN
D. T or TW
CORRECT: A NEC 410.33 & Table 310-13
Comment: NEC 1996 & 1999 reference 410-31.
1
oL
Amps Total
following: 25% of
dt
rs
Motor/Equipment being served From Amps
c te
oto
Largest
ne
#M
Tables Per Line
on
#C
1-15HP, 240V, 3-phase, wound rotor 1 1 15 Hp, 240 Volt 3-Phase 42 10.5 52.5
motor
4-5HP, 240V, 3-phase, wound rotor 4 4 5 Hp, 240 Volt 3-Phase 15.2 X 60.8
motors
28 X 56
6-5HP, 240V, 1-phase motors 6 2 5 Hp, 240 Volt, Single Phase
8
Each ungrounded conductor in the sub-feeder to this 14 173.5
647 According to the NEC, Class III locations are those that
are hazardous because of the presence of:
A. flammable vapors
B. organic dust
C. combustible dust
D. ignitable flyings
CORRECT: D NEC 500.5 (D)
681 According to the NEC, what are the two branches of the
hospital emergency system?
A. the emergency branch and the standby branch
B. the life safety branch and the critical branch
C. the normal branch and the alternative branch
D. the essential branch and the non-essential
branch
CORRECT: B NEC 517.31
Comment: NEC 1996 & 1999 reference 517-31.
715 The length and design of neon tubing shall not cause a
continuous ___ beyond the design loading of the
transformer or electronic power supply.
A. overcurrent
B. undercurrent
C. overvoltage
D. undervoltage
CORRECT: A NEC 600.41 (A)
Comment: NEC 1996 & 1999 reference 600-41 (a).
726 Enclosures for outdoor signs must have drain holes that
have a maximum size of:
A. 1/2"
B. 1/4"
C. 3/4"
D. 1"
CORRECT: A NEC 600.9 (D)(1)
753 How many feet from the edge of a swimming pool must
a junction box be located that serves a 120 volt wet
niche lighting fixture?
A. 2
B. 3
C. 4
D. 5
CORRECT: C NEC 680.24 (A)(2)(b)
Comment: NEC 1996 reference 680-21 (a)(4); NEC 1999
reference 680-21 (a)(5).
762 All electrical spa or hot tub heaters shall be listed and
shall have its heating elements subdivided into loads
not exceeding 48 amperes and protected at not more
than ___ amperes
A. 48
B. 60
C. 72
D. 84
CORRECT: B NEC 680.9
Comment: NEC 1996 & 1999 reference 680-9.
765 All of the following battery types are permitted for use
in emergency lighting except:
A. lead acid
B. glass jar
C. NI CAD
D. automotive
CORRECT: D NEC 700.12 (A)
Class 1
Comment: NEC 1996 & 1999 reference is 225-8 (a),
NEC 2002 reference is 225.8 (A).
I. Type CL2P
II. Type CL3P
A. I only
B. II only
C. either I or II
D. neither I nor II
CORRECT: C NEC 725.61 (A)
Comment: NEC 1996 & 1999 reference 725-61 (a).
789 When Class 3 cables are used for a signal circuit it shall
have a voltage rating of not less than:
A. 200-volts
B. 240-volts
C. 360-volts
D. 300-volts
CORRECT: D NEC 725.82 (G)
Comment: NEC 1996 & 1999 reference 725-71 (f); NEC
2002 reference 725.71 (F).
I. In a neat manner
II. In a workmanlike manner
A. I only
B. II only
C. both I and II
D. either I or II
CORRECT: C NEC 760.8
I. Non-conductive, conductive
II. Low-capacitive, capacitive
A. I only
B. II only
C. both I and II
D. neither I nor II
CORRECT: B NEC 770.9
1-10 kw range
1-electric dryer
1-6kw hot water heater
no A/C or Heat
Single phase 240 V.