Professional Documents
Culture Documents
OFFERS: REGISTERED MASTER ELECTRICIAN REVIEW| CALL/TEXT: 0977-789-4746| FB PAGE: Electromotive Force Review and Training Center
6. The locked rotor KVA per HP rating for a code letter design “E”
motor shall be ______
A. 3.2-3.9 C. 2.2-2.6
B. 4.5-4.99 D. 6.0-6.5
11. A branch circuit with a slash rating of 120/240 is rated for what
voltage to ground?
A. 115 volts to ground
B. 120 volts to ground
C. 240 volts to ground
D. Any voltage up to 240 volts
15. The maximum overcurrent device rating for each resistance welder
connected to an electrical system is ______
a. Not over 350% of the rated primary current of the welder
b. Not over 300% of the rated primary current of the welder
c. Not over 150% of the rated primary current of the welder
d. Not over 100% of the rated primary current of the welder
21. The minimum length required for a junction box in a straight pull
is ______ (RME APRIL 2022)
A. Six times the trade diameter of the largest raceway
B. Eight times the trade diameter of the largest raceway
C. Four times the cross-sectional area of the largest conductor
D. Eight times the cross-sectional area of the largest conductor
22. A 200 Ampere panelboard may supply a minimum load of ____ amperes
(RME APRIL 2022)
A. 200 B. 180 C. 160 D. 150
24. All branch circuits that supply 125 volt, 15 and 20 ampere
outlets installed in dwelling unit _____ shall be protected by an
arc-fault circuit interrupter listed to provide protection of the
entire branch circuit
A. Kitchen and laundry areas
B. Family and dining rooms
C. All of these
32. The branch circuit rating for flat cable assemblies shall
not exceed _____ amperes.
A. 15 B. 20 C. 25 D. 30
B. Porcelain coated
C. Shall not be of the interchangeable type
D. Heavy duty
43. Neutral conductors shall NOT be used for more than one ____
unless specifically permitted elsewhere in this Code.
A. Set of ungrounded feeder conductors
B. Multiwire branch circuit
C. Branch circuit
D. All of these