Professional Documents
Culture Documents
AM.07.360e Edition: 1
© N.V. ADB S.A., A Siemens Company
This manual or parts thereof may not be reproduced, stored in a retrieval system, or transmitted,
in any form or by any means, electronic, mechanical, photocopying, recording, nor otherwise,
without ADB's prior written consent.
This manual could contain technical inaccuracies or typographical errors.
ADB reserves the right to revise this manual from time to time in the contents thereof without
obligation of ADB to notify any person of such revision or change.
Details and values given in this manual are average values and have been compiled with care.
They are not binding, however, and ADB disclaims any liability for damages or detriments
suffered as a result of reliance on the information given herein or the use of products, processes
or equipment to which this manual refers. No warranty is made that the use of the information or
of the products, processes or equipment to which this manual refers will not infringe any third
party’s patents or rights. The information given does not release the buyer from making their own
experiments and tests.
Guarantee
N.V. ADB S.A. guarantees that the performance of the equipment described in this manual, when
sold by ADB or its licensed representatives, meets the requirements of FAA specification AC 150/
5345-10E and IEC 61822.
Any defect in design, material or workmanship, which may occur during proper and normal use
over a period of one (1) year from date of shipment, will be repaired or replaced by ADB free of
charge, ex. works. Operational failure resulting from lamps burned out, improper maintenance or
installation, damage due to runway maintenance equipment, snow ploughs or aircraft arresting
gear hooks is not considered a result of proper use and is beyond the scope of the warranty.
Warranty does not cover natural wear and tear or damage arising after delivery owing to faulty or
negligent handling, excessive strain, unsuitable materials for operation, deficient civil engineering
work, unsuitable soil conditions, and such chemical, electrochemical or electrical influences as
were not assumed at the time of the conclusion of the contract.
All liability for consequences of any inexpert alterations or repairs carried out by Purchaser or a
third party shall be waived. N.V. ADB S.A. shall in no event be liable to Purchaser for any further
claims, particularly claims for damages not affecting the goods themselves.
The above constitutes the limits of ADB’s liabilities in connection with the equipment covered by
this manual.
2
1. Safety
1.1. Warning signs .....................................................................................................................................7
1.2. Intended use .......................................................................................................................................8
1.3. Modifications .......................................................................................................................................8
1.4. Safety devices.....................................................................................................................................8
1.5. Safety precautions ..............................................................................................................................8
1.6. Users...................................................................................................................................................9
2. Specifications
2.1. MCR³ 2.5 to 12.5 kVa........................................................................................................................ 11
2.2. MCR³ 15 to 30 kVa............................................................................................................................ 14
2.3. Ambient conditions............................................................................................................................ 17
2.4. Power factor and efficiency ............................................................................................................... 17
2.5. Working principle .............................................................................................................................. 17
2.6. User interface.................................................................................................................................... 19
3. Pre-installation
3.1. Main pre-installation procedure......................................................................................................... 21
3.2. Substation specifications .................................................................................................................. 21
3.3. Cabling specifications ....................................................................................................................... 25
3.4. Power supply cabling specifications ................................................................................................. 27
3.5. Remote control cabling specifications............................................................................................... 29
3.6. Series circuit cabling specifications .................................................................................................. 30
3.7. Verifying pre-installation.................................................................................................................... 30
4. Installation
4.1. Main installation procedure ............................................................................................................... 31
4.2. Verifying pre-installation.................................................................................................................... 31
4.3. Tools required ................................................................................................................................... 31
4.4. Equipment supplied .......................................................................................................................... 32
4.5. Transporting the crate ....................................................................................................................... 32
4.6. Unpacking and positioning................................................................................................................ 33
4.7. Physical installation........................................................................................................................... 34
4.8. Electrical connections ....................................................................................................................... 35
4.9. Remote control connections ............................................................................................................. 49
4.10. Close panels ..................................................................................................................................... 53
5. Commissioning
5.1. Main commissioning procedure ........................................................................................................ 55
5.2. First start-up...................................................................................................................................... 55
5.3. Tap selection ..................................................................................................................................... 63
5.4. LFD calibration (option)..................................................................................................................... 70
5.5. EFD calibration (option) .................................................................................................................... 72
5.6. Select the correct brightness step..................................................................................................... 73
5.7. Remote control configuration: multiwire (option)............................................................................... 74
5.8. Remote control configuration: J-Bus (option).................................................................................... 75
6. Troubleshooting
6.1. General ............................................................................................................................................. 77
6.2. Preliminary checks............................................................................................................................ 77
6.3. Showing / hiding alarms.................................................................................................................... 77
6.4. Error messages................................................................................................................................. 78
6.5. Observed deviations ......................................................................................................................... 81
- - 3
7. PCB drawings and settings
7.1. Working with PCBs ........................................................................................................................... 85
7.2. UI - PCB1507 – 1593.14.000............................................................................................................ 86
7.3. Multiwire - PCB1486 – 1593.13.510 & 1593.13.520 (option)............................................................ 88
7.4. J-Bus - PCB1502 – 1590.03.490 (option) ......................................................................................... 94
7.5. LMC - PCB1513 – 1593.14.111 ........................................................................................................ 95
8. Appendix
8.1. Checks and measurements ............................................................................................................101
8.2. Local user interface.........................................................................................................................102
8.3. Configuration tool software .............................................................................................................109
8.4. Abbreviations .................................................................................................................................. 116
4 - -
About this manual
The Microprosessor Controlled Constant Current Regulator (MCR3), hereafter referred to as ‘the
regulator’, is manufactured by ADB. The regulator can be ordered in several different types.
These types are divided into two main groups based on the size of the regulator cabinet. These
two cabinets are hereafter referred to as follows:
This manual provides information about how to install and take the regulator into use.
Subject(s) Chapter(s)
Safety, Description 1, 2
Pre-installation 3
Installation 4
Commissioning 5
Troubleshooting 6
PCB drawings and settings 7
1 Safety
WARNING
Do not use the regulator unless you have read and understood all the
applicable safety regulations and standards.
Classes of safety Safety signs are of the three internationally accepted types as given below.
signs
Signs on the
equipment
ER
NG
- 83
DA VOLT
AGE
SCO
HIGH EUR
ION ULATOFF
OUT
CUT
UALING E TENS LE REG OR
D
MANRAT HAUT PERREGULAT
REA OPE UELN COU CH
DANGER DANGER
ORE MANTIO SWIT
BEF
Z LE LISA
LISE UTI
NT
AVA
DANG
ER
MANUAL
READ OPERAT
BEFORELE
MANUEL
LISEZ UTILISAT
AVANT
ING
ION
READ MANUAL
BEFORE OPERATING HAUTE TENSION HIGH VOLTAGE
LISEZ LE MANUEL COUPER LE REGULATEUR
AVANT UTILISATION SWITCH REGULATOR OFF
A CUTOUT SCO - 83
CONSTANT CURRENT REGULATOR
REGULATEUR A COURANT CONSTANT
SINGLE PHASE
READ MANUAL
TYPE : BIPHASE 2P + T
INPUT :
V A 50/60Hz
BEFORE OPERATING
ENTREE :
OUTPUT :
kVA A
PHASE+T
R 2P
SINGLE
CONSTANT BIPHASE
REGULATO 50/60Hz
SORTIE :
A COURANT
CURRENT
UR AA 8STEPS
CONSTANT MAX.
REGULATE MAN.
: 8BRILL.
TYPE V
:
kVA
:
INPUT : :
ENTREE
B LISEZ LE MANUEL
OPTIONS :
ID-Nº
SERIES NR :
NUMERO DE SERIE :
A Low-voltage compartment
B High-voltage compartment
Standard Description
ICAO Aerodrome Design Manual, Part 5 paragraphs
3.2.1.4/5/6
FAA AC 150/5345-10F and L829
IEC IEC 61822
Any other or additional use will be considered not to be in conformity with the purpose. Use this
regulator in a technical perfect condition in conformity with the purpose, described above.
Operation limits Do not operate the regulator outside the limits of the specifications.
For limits about ambient conditions, see section 2.3 Ambient conditions.
EMC conformity The regulator is designed to operate in an industrial electro-magnetic environment. The regulator
complies with IEC 61822, in accordance with IEC 61000-6-4 and IEC 6-6-2 (generic standard for
industrial environment). The regulator is, with adapted test levels, in accordance with IEC/
TS61000-6-5, G (substation environment, location G).
1.3 Modifications
WARNING
Do not try to make changes to the equipment without a prior express
agreement from ADB. Unauthorized modifications or changes to the
equipment could lead to serious personal injury, or death.
Signs on the The signs on the equipment are part of the safety provisions. They must not be covered over or
equipment removed. The signs must be present and legible during the entire life of the equipment.
- Check regularly;
- Replace or repair signs that have become illegible or damaged.
WARNING
Personnel must obey the safety regulations at all times.
Installation and Always follow the safe work procedures, which are defined by the standard IEC 618.9.
maintenance
Disconnection All regulator installations must have devices that disconnect the input and output current from
devices and to the regulator.
Live circuits Observe all safety regulations at all times. Do not make any adjustments on the regulator, lamps,
or the series circuit when the series circuit is energized.
See FAA Advisory Circular AC 150/5340-26 concerning safety precautions. See also IEC-61820.
WARNING
You must always wear protective gloves and shoes when you work with the
regulator or live circuits.
Electrostatic When you work with components that are susceptible to electrostatic damage:
Discharge (ESD) - Do not touch electronic components unless this is unavoidable, for example during part
replacement;
- Eliminate electronic charges from your own body immediately before you touch an
electronic component. To do this, touch, for example, a conductive earthed object;
- Store and transport electronic components in conductive packages. Avoid highly insulating
surfaces, like plastic sheets or synthetic fibre clothing.
1.6 Users
Personnel - All personnel must only carry out the work they have been trained to perform. This applies
qualifications to both maintenance work and equipment preparation.
- The operators must be familiar with all situations that may occur so that they can act rapidly
and effectively in the event of an emergency.
- All personnel must be trained in resuscitation and first aid techniques.
2 Specifications
A B C
J L N M I H R
P
O
A
B
E Q
Main items A Input terminals and fuses F2, F3 and F4 J Thyristor block module logic
B Earth fault detection module (option) K Power supply logic
C Output measurement transformers TI 2 L Current control logic
and TI 3 M Local master controller logic
D Tap S6-S1 N Lamp fault detection logic (option)
E Lightning arrestors LA1 and LA2 O Main contactor K1
F Output terminals P Input measurement transformer TI1
G Series choke L1 Q Output transformer
H Multiwire control logic (option) R Thyristor
I J-Bus logic (option)
Item Description
Rated powers [kVa] 2.5 / 4 / 5 / 7.5 / 10 / 12.5
a
Rated input voltage [V] FAA: 220 / 230 / 240 / 380 / 400 (± 15 %)
IEC: 230/ 400 (± 15 %)
Rated frequencies [Hz] 50 / 60 (± 7.5 %)
Output current [A] 6.6
Current regulation limits Current regulation is guaranteed under the following conditions
(±1.5 %):
- A minimum of 30 % of lamp transformers with an open
circuit in their secondary side. This is for a range from
half-load to full-load.
- For nominal input voltage:
- IEC: ± 10 %
- FAA: + 10 % / -5 %
A B C
H
F
J L N M I H R
P
O
B A
C Q
E F
Item Description
Rated powers [kVA] 15 / 20 / 25 / 30
ab
Rated input voltage [V] FAA: 220/ 230 /240/ 380 / 400 / 415 V (± 15%)
IEC: 200/ 400 V (±15 %)
Rated frequencies [Hz] 50 / 60 (± 7.5 %)
Output current [A] 6.6
Current regulation limits Current regulation is guaranteed under the following conditions
(±1.5 %):
- A minimum of 30 % of lamp transformers with an open
circuit in their secondary side. This is for a range from
half-load to full-load.
- For nominal input voltage:
- IEC: ± 10 %
- FAA: + 10 % / -5 %
Item Description
Temperature From -20 up to +55 °C
Altitude From 0 (sea level) up to 1000 meter
Relative humidity From 10 % up to 95 % RH without condensation
Standard Specification
FAA AC 150/5345-10F and L829
IEC IEC 61822
A B D E F
Regulator
B P
DS3 O
DS4
DS2
SW2
DS6
DS5
SW1 DS1
N
C01 C04
D F
A G E J6 J3 J1
D1
S3 C02 C03
J1 C07 C06
C07
SW1
DS1
SW1
C011 SW4
C06
S3
DS7
SW2
C012
DS8
M
DS2
C01
SW2 D2
SW2
S3 D3
D4
C013
C04
D5
C05
DS2
C014
DS11 DS9
SW6
SW5
DS1
DS3
DS10
SW7
DS4
DS4
DS3
C03
SW3
C08
DS2
C01
DS5
C02
DS3
C03
SW1
DS6
DS4
C09
DS1
C01
J5 J2
C04
D4
L
Q
D3
D2
SW1
J2
D5
I K
12
11
10
12
11
10
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
P1 P2
W5
W6
J1
P3
I
12
11
10
12
11
10
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
P1 P2
W5
C
W6
X3
J1
X8
P3
X2
I
12
11
10
12
11
10
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
P1 P2
X4
W5
W6
J1
X5
X1
P3
X6
X7
H
P4
P3
J
P6
P5
P2
P1
L
R
The current regulator holds the output current constant by varying the output voltage to the series
circuit. The voltage can be adapted by changing the conduction angle of the thyristors in both the
positive and the negative difference of the input signal.
- The TBM module fires the thyristors at the request of the CCL module.
- The TBM module receives a signal from the remote control system.
- The TMB module gives an output to a certain current level.
- The CCL compares the requested step & actual output current level.
- The CCL computes and sends the TBM a request to generate the required output voltage.
This process will be maintained until no output is anymore demanded or if any of the safety
features are triggered. The regulator stops immediately when triggered by a safety feature. The
safety can only be reset at the TBM module.
Multiwire (option) Each multiwire PCB consists of input and output terminals. These terminals handle the incoming
and outgoing signals between the regulator and the remote control system. The number of
multiwire PCBs on the regulator determines the maximum number of available signals.
- Cut-out SCO:
An output disconnecting device between the regulator and the series circuit. The cut-out
SCO isolates the series circuit from the regulator during maintenance or testing operations.
The cover can be locked with a key to prevent unauthorized access.
- Hour counters:
Measure the number of hours the regulator is ON, or the number of hours the regulator is
ON and produces output current that is higher than a set value.
Mode Description
Local Control the regulator through the local user interface. All the
parameters are accessible for reading and modifying. See section
8.2 Local user interface.
Remote Control the regulator through a remote control system. All the
parameters can be read but nothing can be modified.
Dongle Control the regulator through a dongle and a software tool. The
display is locked and nothing can be visualized or modified. See
section 8.3 Configuration tool software.
3 Pre-installation
3.2.1 Substation
Table: 1 Substation specifications
Item Description
Shelter - Clean and dry;
- Lockable;
- Fireproof;
- Separate construction with reinforced concrete floors and
walls;
- Adequate drainage;
- Sufficient room and lighting for personnel to do maintenance
work.
Location - Reasonable distance from the control tower to allow applicable
cable lengths;
- Leaves limitation surfaces free;
- Accessible in all weather conditions;
- Minimum interference with aircraft traffic.
Ventilation Good ventilation to prevent the equipment to become overheated.
Electrical connections - Sufficient number of conduits and cable entrance accesses;
- Sufficient power supply;
- Access to the required power supply, remote control and series
circuit cabling;
- Ground network;
- External fuse and an electrical distribution cabinet;
- Disconnection devices for the input and output current.
± 500 mm > 50 mm
3.2.3 Planning
CAUTION
Make sure that the supply voltage of the regulator is in accordance with the
local supply voltage.
1. Make a plan that identifies the regulator that is connected to each series circuit.
2. Make sure that each regulator has a power supply, which is applicable to the series circuit
power consumption.
3. Plan the necessary cabling and cabling layout.
A B
930 mm
1260 mm
500 mm
500 mm
Type Size
gL/gG One size higher than the internal fuses of the regulator.
Example
A regulator with a full load has the heat dissipation (connection cable losses not included) shown
in table 5:
Ambient conditions All regulators are air-cooled without fans. Thus, all regulators must have a good airflow,
especially if they operate near the maximum temperature.
Item Description
Temperature From -20 up to +55 °C
Altitude From 0 (sea level) up to 1000 meter
Relative humidity From 10 % up to 95 % RH without condensation
Ventilation
1. Make sure that the ventilation grids (A) on
the sides and bottom of the regulator are
not blocked. Without sufficient air-flow, the
regulator components become too hot. B A
2. Handle the heatsink for the thyristors (B)
with care. The heatsink becomes hot during
operation.
CAUTION
Keep power and remote control cables separated.
When you install the necessary cables, keep in mind that the small and big cabinets must have
different cable layouts. Install the cables so that they can be routed trough the bottom plate of the
cabinet as follows:
Small cabinet
1. Plan the placing of the different cables as
follows:
Back
- A: power input supply cables
- B: power output supply cables from C D
output terminals
- C: power output supply cables from a
circuit selector (option)
- D: remote control cables
- E: power output supply cables from a
cut-out SCO (option)
A E B
Front
Big cabinet
1. Plan the placing of the different cables as
follows:
- A: power input supply cables
Back
- B: power output supply cables from A+C D
output terminals
- C: power output supply cables from a
circuit selector (option)
- D: remote control cables
- E: power output supply cables from a
cut-out SCO (option)
E B
Front
A
B
CAUTION
Keep power and remote control cables separated.
For cable specifications see sections 3.4 Power supply cabling specifications, 3.5.1 Multiwire
(option) and 3.6 Series circuit cabling specifications.
Wire sections The voltage drop must be equal to or less than the maximum permitted voltage drop. To
determine the necessary wire sections, check the values for these items:
- Tolerances of the power supply;
- The maximum permitted voltage drop on the line. This is the minimum available power
supply voltage minus the minimum required voltage for the load;
- The typical resistance for wires at an ambient temperature of 55°C:
- Wires with a diameter 0.5 mm (about 0.2 mm²): 0.1 Ohm/m;
- Wires with a diameter of 0.8 mm (about 0.5 mm²): 0.04 Ohm/m.
- The required load current in each line;
- The number of signals that may exist at the same time.
Example:
- If you use a copper wire and only one signal is transmitted at a time, you can use the
maximum length of the cable.
- If two signals are sent at the same time, the diameter of the common wire must be double.
- Alternatively, the maximum cable length is only 2/3 of the indicated value.
CAUTION
Do not mix Bus A and Bus B signals in one pair.
Wire sections
Table: 12 Wire sections for J-Bus cables
Cable type Factor Cross-section [mm2]
JE-LiYCY (with armouring type R, B, Q or Z) 2 pairs twisted 0.5
TWAVB 4 x 0.8mm 0.8
Type Description
Conductor Stranded, copper single-conductor with a 8.3 mm2 cross-section.
Insulation Cross-linked polyethylene, ethylene-propylene-rubber, or buna-
rubber.
Jacket Chlorosulfonated polyethylene, polyvinyl chloride, polyethylene, or
heavy duty neoprene jacketed.
Shield type Metal-tape shielding between the insulation and the jacket or
between the jacket and a non-metallic covering.
Checked Item
Substation meets the general requirements.
Cables have been installed according to an applicable layout.
All cables have enough slack for connecting to the regulator.
For each regulator there is a power supply cable available.
For each regulator there is a remote control cable available.
For each regulator there is a series circuit cable available.
4 Installation
Checked Item
Substation meets the general requirements.
Cables have been installed according to an applicable layout.
All cables have enough slack for connecting to the regulator.
For each regulator there is a power supply cable available.
For each regulator there is a remote control cable available.
For each regulator there is a series circuit cable available.
CAUTION
Use an isolating measurement transformer on the 5000 V AC line.
The output voltage of the 30 kVA / 6.6 A regulator can reach approximately
4600 V at full load.
- Multimeter;
- Insulation tester "Megger" 5000 V or 10000 V;
- AC True RMS measurement device, scale 10 and 30 A.
CAUTION
The current regulation is +/- 1 %. To make an acceptable readjustment of the
output current, the precision of the meter should be better than
0.5 % for the adjusted value.
Inspect at 1. Make sure that the regulator corresponds to your order. See section Nameplate.
delivery 2. Make sure that the regulator is at the correct substation. See section Nameplate.
3. Check that the crate is not damaged.
4. If the crate is damaged, tell the carrier immediately.
SERIES NR :
NUMERO DE SERIE :
MADE IN BELGIUM
CAUTION
- The maximum weight of the regulator is approximately 380 kg.
- Keep the MCR³ in a vertical position at all times.
- Do not let the regulator tilt or fall.
- The centre of gravity of the regulator is not the same as the physical
centre of the regulator.
A B A B
CAUTION
- The maximum weight of the regulator is approximately 380 kg.
- Always use lifting lugs (option) and adequate hoisting cables to lift the
load.
- Do not let the load swing without control.
Regulator without
wheels 1. Leave an applicable amount of slack for the
cables.
2. Attach the regulator to the floor. Use bolts
in the four slots (A).
Regulator with
wheels (option) 1. Push the regulator to the correct place.
2. Leave an applicable amount of slack for the
cables.
Clearance
specifications Table: 2 Clearances for regulators
WARNING
Make sure that the power is OFF during all installation procedures.
Small cabinet
1. Switch OFF the main power supply at the
disconnection device.
2. Switch OFF the fused input switch of the
regulator. See the graphic.
Big cabinet
1. Switch OFF the main power supply at the
disconnection device.
2. Switch OFF the fused input switch of the
regulator. See the graphic.
III
II I
CAUTION
- Do not operate the regulator with any of the panels removed.
- Do not mix panels from different regulators.
- Always connect the ground wires before you put the panels back.
A
8
Top panel
1. Loosen the four bolts (A) or the optional
lifting lugs (B).
A
UI panel: small
1. Loosen the four screws (A). B A
cabinet
2. Take out the panel (B).
J1
J2
D2
D3
D4
D5
SW2
D C
UI panel: big
1. Take out the fused input switch and the
cabinet
complete handle (A). Open the fuse (I), lift
the handle up (II), and pull the handle out
(III).
III
II I
A
J1
J2
D2
D3
D4
D5
SW2
E D
Overview
D
C
B
F
E
A Shaft A D Shaft D
B Shaft B E Front gland plate
C Shaft C F Back gland plate
Route cables Use gland plates and correctly sized glands to route the cabling. Tie the cables to the shaft walls
with cable tie. Route the cables as follows:
CAUTION
Keep the power cables separated from other cables.
Tie
CAUTION
Do not let the series circuit cables touch the transformer winding. The
transformer winding becomes extremely hot during operation.
Check cable 1. Make sure that the input and ground cable sections are correct. See tables 6 and 7 below.
sections 2. Strip the input and ground cables. See tables 6 and 7 below.
3. Connect the cables to the input and ground terminals. See Wire sections up to 35 mm2 and
Wire sections above 35 mm2 below.
Cable
specifications Table: 6 Input supply voltages for regulators 220 / 230 / 240 V
Output power Section supply Stripping [mm] Section ground Stripping [mm]
[kVA] wire [mm2] wire [mm2]
2.5 4 16 4 16
4 6 16 6 16
5 10 16 10 16
7.5 16 16 16 16
10 25 22 16 18
12.5 35 22 16 18
15 35 22 16 18
20 50 22 25 18
Output power Section supply Stripping [mm] Section ground Stripping [mm]
[kVA] wire [mm2] wire [mm2]
2.5 4 16 4 16
4 4 16 4 16
5 4 16 4 16
7.5 6 16 6 16
10 10 16 10 16
Output power Section supply Stripping [mm] Section ground Stripping [mm]
[kVA] wire [mm2] wire [mm2]
12.5 16 18 16 18
15 16 18 16 18
20 25 22 16 18
25 35 22 16 18
30 50 22 25 18
Wire sections up to For wire sections up to 35 mm2, the connection is based on screw terminals.
35 mm2
1. Strip the cables at the end. See tables 6
and 7 above.
2. Connect the input power cables to the
terminals (A).
3. Connect the ground wire to the terminal (B).
A
B
A
Wire sections For wire sections above 35 mm2, the connection is based on 70 mm2 bolt terminals.
above 35 mm2
A
B
CAUTION
If the series circuit cable is screened, you must connect the screen to a
ground network either inside or outside the regulator.
Small cabinet
1. Strip the cables at the end. For unscreened A B
cables, see (A). For screened cables, see
(B).
≤ ø12 mm
50 mm
≤ ø7 mm
16 mm
14 mm
≤ ø7 mm
A
B
A
Big cabinet
1. Strip the cables at the end. For unscreened A B
cables, see (A). For screened cables,
see (B).
100 mm
≤ ø12 mm
≤ ø7 mm ≤ ø7 mm
M10 M10
CAUTION
Make sure you connect all terminals. If you do not want to use all terminals,
put the free terminals into short-circuit.
Small cabinet
1. Strip the cables at the end. If you have a
screened cable, take off the outer sheet of C
the cable between the terminals and the
ground bar.
2. Connect the two cables for each series
circuit to the corresponding output A
terminals (A). B
3. Connect the cables to the ground bar (B).
Use grounding clamps. D
- Screened cable: connect the screen to
the ground bar (B);
- Unscreened cable: connect the cable
to the ground bar (B) for stress relief.
Big cabinet
1. Strip the cables at the end. f you have a
screened cable, take off the outer sheet of
the cable between the terminals and the
ground bar.
2. Connect the two cables for each series A
circuit directly to the corresponding high-
voltage contactors (A). Between two B
circuits, connect one cable from each
circuit to the same terminal (B).
3. Connect the cables to the ground bar (C).
Use grounding clamps.
- Screened cable: connect the screen to
the ground bar (C); C
- Unscreened cable: connect the cable
to the ground bar (C) for stress relief.
Built-in cut-out
1. Take out the cover (A) of the cut-out SCO.
SCO
10 mm
For unscreened cables, see (B). For
≤ ø12 mm
screened cables, see (C).
29 mm
≤ ø7 mm
≤ ø7 mm
14 mm
14 mm
External cut-out
SCO
CAUTION
Use only unscreened, high-voltage, 5 kV cables to connect the regulator
output terminals to the external cut-out SCO.
16 mm
M10
These signals must have simple, potential free contacts. The maximum contact load is:
- AC - 110 V - 2 A - 220 VA;
- DC - 110 V - 2 A - 60 VA.
1
X73
2 4
X6
1 2 1
X5
2 3
Connector X7 Connect the wires to the connector X7 of the Power Supply Logic (PSL) as follows:
Terminal Description
1 ON
2 COMMON (for contacts to terminal 1, 3 and 4)
3 REG.ERR./NC (normally closed contact)
4 REG.ERR./NO (normally open contact)
NOTE
If you do not use the grounding clamp, connect the screen to terminal 12 (PE).
12
11
P1
7
J1
6
normally.
W6
5
W5
4
3
2
P3
1
12
P1
7
J1
10
W6
5
W5
8 4
7 3
P2
6 2
5
P3
1
equipment. P4
4
3
2
1
12
11
P3 10
9
W5
P2 8
7
P2
P1 6
5
P3
4
3
2
1
P5
B
A
Connect cables
1. Connect the cables to connectors on the
PCBs (A) as shown in section 5.7 Multiwire
- PCB1486 – 1593.13.510 & 1593.13.520.
J1
W6
7
J1
4
3
2
P3
1
P6 12
11
7
J1
10 6
9 5
W6
8
W5
6 2
5
P3
1
4 12
3 11
2 10
1 9
P3 10 7
6
9 5
8
W5
P2
4
7 3
P2
P1 6 2
1
4
3
2
1
12
11
6
5
4
NOTE
Configure a specific signal only to one terminal. If you try to configure the same
signal to several terminals, only one of those signals works appropriately.
Input terminal Connect the control signal wires to the input connector P2.
connections (P2) See section 5.7 Multiwire - PCB1486 – 1593.13.510 & 1593.13.520.
A B C
Back External power supply Internal power supply Internal power supply
indication (A) (polarized contacts (polarized contacts
positive) (B) negative) (C)
Remarks Remove strap W5, Install strap W5 Remove strap W5
24 V DC (PCB
1593.13.510) 48 V DC
(PCB 1593.13.520)
Output terminal Connect the control signal wires to the output connector P1.
connections (P1) See also section 5.7 Multiwire - PCB1486 – 1593.13.510 & 1593.13.520.
A B C
Back External power supply Internal power supply Internal power supply
indication (A) (polarized contacts (polarized contacts
positive) (B) negative) (C)
Remarks Remove strap W6, Remove strap W6 Install strap W6
Max. 110 V DC, polarity is
not important
Overview
P6 P6 P6
1
P1 P2 P3 P4 P1 P2 P3 P4 P1 P2 P3 P4 2
1
2
3
A B 3
4
5 (4)
6
P5 P5 P5
D E F
The J-Bus interface uses a single or dual databus(es) to allow remote monitoring of a bigger
quantity of parameters.
Connect cables
CAUTION
Make sure that the bus polarity is the same in all contacts that have the same
type or are in the same wire. Otherwise, the regulator is not able to
communicate with the LMC unit.
Slave connections The following figures show the wire connections for the slave side. The connections for the
master side depend on the used hardware.
Four-wire dual databus for Bus A and Bus B (RS-422 protocol standard):
P1 P2 P3 P4
P1 P2
Two-wire dual databus for Bus A and Bus B (RS-485 protocol standard):
P1 P2 P3 P4
P1 P2
5 Commissioning
WARNING
It is recommended that only qualified personnel, who are trained to use the
regulator, are allowed to work on the regulator and the series circuit.
Otherwise, there is a risk of damage to the series circuit, personal injury, or
even death.
WARNING
Use a cut-out SCO or put the regulator in short-circuit when instructed in this
chapter. This makes sure that excessive output current does not damage the
series circuit.
WARNING
It is recommended that only qualified personnel, who are trained to use the
regulator, are allowed to work on the regulator and the series circuit.
Otherwise, there is a risk of damage to the series circuit, personal injury, or
even death.
Test the series circuit insulation resistance and continuity to make sure that the series circuit is in
accordance with all local safety regulations.
NOTE
You need the configuration tool to perform this procedure. See section
8.3 Configuration tool software.
WARNING
Discharge the series circuit before reconnecting the tap wires. Any
remaining power in the series circuit may be lethal. Either put the cut-out
SCO to grounded mode or attach a ground wire between the output
terminal.
Example This example shows how to select and wire a tap for a 7.5 kVA regulator with a supply voltage of
380 A. The measured voltage reading on the terminals of fuse holder F3 is 210 V.
Selecting a table The tables describe the correct tap settings for regulators with different power ratings.
CAUTION
The LFD module does not work if the series circuit includes these lamps:
- LED lights;
- PVO lights (guidance lights);
- WIGWAG (runway guard lights).
NOTE
We recommend to use the configuration tool to perform this procedure. See section
8.3 Configuration tool software.
Calibration, In the following procedure, the configuration tool is used as an example. For more information on
step 1 how to do this with the local user interface, see section 8.2 Local user interface. If you use the
local user interface, switch the regulator OFF and back ON after each setting.
Calibration,
1. Select Do the reference measurement.
step 2
See the graphic. Wait while the regulator
goes through the calibration procedure.
2. Switch the regulator OFF. Use the fused
input switch.
3. Do remove the transformer from the
circuitmake sure that the secondary side of
the isolating transformer is in open circuit
condition
4. Switch the regulator ON. Use the fused
input switch.
NOTE
We recommend to use the configuration tool to perform this procedure. See section
8.3 Configuration tool software.
In the following procedure, the configuration tool is used as an example. For more information on
how to do this with the local user interface, see section 8.2 Local user interface. If you use the
local user interface, switch the regulator OFF and back ON after each setting.
Example:
The regulator is set to have five steps available. If you set the regulator to use step 3, the current
value is 4.1 A.
These values apply when the minimum current is 1.8 A and the maximum current is 6.6 A.
NOTE
You need the configuration tool to perform this procedure. See section
8.3 Configuration tool software.
Set dip-switches To configure the databus connection, you must change the dip-switch settings of the LMC
module. Set these dip-switches according to the databus connection of the regulator. For details
see, section 7.5 LMC - PCB1513 – 1593.14.111.
Set address Each slave on the databus must have a unique binary address. Note that there can be a
maximum of 16 regulators in a databus. To configure the databus connection, change the
settings of the dip-switch SW4 in the LMC module. For details see, section 7.5 LMC - PCB1513 –
1593.14.111.
Example
To set the binary address of the regulator to 12, set the:
- Switch 3 to ON
- Switch 4 to ON
- All other switches to OFF.
Set two/four wire To set a two-wire communication, you must set the dip-switches on the LMC PCB. If you only
communication have a single databus, set the switch SW1. If you have a dual databus, set both switches SW1
and SW2. Table 14 and table 15 below show the settings required for either a two or a four wire
system. For details, see also section 7.5 LMC - PCB1513 – 1593.14.111.
Switch Function
1 ON: Transmit / E – pull up 680 Ohm
2 ON: Line termination 150 Ohm. Set this ON only for the last
regulator on the databus.
3 ON: Transmit / E – pull down 680 Ohm
4 OFF = 2 wire
Switch Function
1 ON: Transmit / E – pull up 680 Ohm
2 ON: Transmit / E – line termination 150 Ohm. Set this ON only for
the last regulator on Bus A.
3 ON: Transmit / E – pull down 680 Ohm
4 ON = 4 wire
5 ON: Receive / R – pull up 680 Ohm
6 ON: Receive / R – Line termination 150 Ohm. Set this ON only for
the last regulator on Bus A.
7 ON: Receive / R – pull down 680 Ohm
Terminate line J-Bus communication for Bus A and Bus B must be separately closed at the last regulator of a
set of many regulators. With a dual databus, Bus A and Bus B must be closed separately.
NOTE
With a dual databus, the physical route of Bus A and Bus B must go in opposite
directions. This means that first regulator for Bus A is the last regulator for Bus B.
For the applicable dip-switch settings, see section 7.5 LMC - PCB1513 – 1593.14.111. The
termination resistance must be set on the last unit of the databus to 150 Ohm.
Check Connect from a place where the remote control connection already works.
connection
6 Troubleshooting
WARNING
Do not attempt to do any maintenance work on the regulator unless you have
read and understood all the information in the chapter Safety and you are
qualified to work on high-voltage systems.
6.1 General
The control panel only displays information about errors that are detected by the machine
control. When a critical error occurs, the machine stops automatically. The control can not detect
every error that results in an unacceptable output. The operator has to observe whether the
machine functions correctly.
WARNING
- Set the regulator to local control before you do any maintenance work on
the regulator.
- Switch the regulator OFF from the main switch before you replace any
parts on the regulator.
- Set the regulator to brightness step OFF before inspection of the series
circuit;
- Refer to chapter 1: Safety.
Errors and
warnings Table: 1 Regulator faults
WARNING
- Do not attempt to use the machine unless you have read and understood
all the information in the safety chapter and you are sure of your ability to
use the machine safely;
- Do not attempt to use the machine unless you know how to stop it in an
emergency as described under emergency stop in the chapter Safety.
D5
J2
SW1
D2
D3
D4
SW2
J1
7.2.2 Connectors
Table: 2 UI connectors
Connector Connection to
J1 Power supply
J2 Local bus
7.2.3 Dip-switches
Factory setting of the switches:
SW1 - all OFF
SW2 - 1:OFF 2:OFF 3:OFF 4:OFF 5:OFF 6:ON 7:ON 8:ON
Switch Function
1 ON: Transmit / E – pull up 680 Ohm
2 ON: Transmit / E – line termination 150 Ohm
3 ON: Transmit / E – pull down 680 Ohm
4 Not used
SW2 Various
functions Table: 4 SW2 various functions
Switch Function
1 Not used
2 Not used
3 ON: Lock in boot-loading mode
4 Not used
5 Local Bus - 0 9600 1 19200 0 38400 1 9600
baudrate: Bd Bd Bd Bd
6 0 0 1 1
7 Local Bus - 0 NO 1 NO 0 ODD 1 EVEN
parity: parity parity parity parity
8 0 0 1 1
7.2.4 LEDs
Table: 5 UI LED RUN light functions
LED Function
D2 Local Bus – RXD
D3 Local Bus – TXD
D4 Microcontroller – RUN
D5 Local Bus – isolated 5 V present
Each multiwire PCB has eight input and eight output terminals. They handle incoming and
outgoing signals between the regulator and the remote control. The number of multiwire PCBs
on the regulator determines the maximum number of available signals. You can configure these
signals by using the configuration tool software.
NOTE
It is impossible to attribute the same function to more than one terminal.
For each signal, you can set either a POSITIVE or a NEGATIVE logic. For example, if you
configure an output signal for function A and if the condition of function A becomes TRUE, the
signal contact closes in positive logic and opens in negative logic.
To read the present settings in the configuration tool, see the section 8.3.7 IO menu.
W6
12 PE
J1
12 11 Vext
11 10 GNDext
10 9 Common
9
8 8 Output 8
P1
7 7 Output 7
6 6 Output 6
5 5 Output 5
4
3 4 Output 4
2 3 Output 3
W5
1 2 Output 2
1 Output 1
12 PE
12 11 GNDext
11
10 10 Vext
9 9 Common
P3
8 8 Input 8
7 7 Input 7
P2
6
5 6 Input 6
4 5 Input 5
3 4 Input 4
2 3 Input 3
1
2 Input 2
1 Input 1
7.3.2 Connectors
Table: 7 MW connectors
Connector Connection to
P1 Back-indication/output signals
P2 Control/input signals
P3 LMC
J1 Power supply
The following table shows the factory settings for the control signals. Connect the wires
according to these settings.
Function Description
Free This terminal is not in use.
ON / OFF A separate ON / OFF signal.
Function Description
Step 1 Selection for brightness steps.
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
Step 8
Reset EFD error Reset EFD alarms, levels 1 and 2.
Use LFD degraded mode Cancel the back-indication of LFD alarm, level 1.
Allow WRITE via bus An external signal that allows the bus to change parameters in
multiwire control. This works only if you set the arbiter to Multiwire
control, Bus A monitoring or Multiwire control, Bus B monitoring.
Function Description
Free This terminal is not in use.
Circuit 1 Selection for circuits.
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
Circuit 8
NOTE
Warnings are only available if you activated that option through the user interface.
Otherwise, only errors are available.
Function Description
Free This terminal is not in use.
Step 1 obtained Back-indication for actual brightness steps.
Step 2 obtained
Step 3 obtained
Step 4 obtained
Step 5 obtained
Step 6 obtained
Step 7 obtained
Step 8 obtained
Overcurrent alarm Regulator has switched itself OFF because of overcurrent in the
loop.
Open circuit alarm Regulator has switched itself OFF because of an open circuit in the
loop.
EFD warning level Level 1 has been exceeded. The actual fault condition may not be
present any more.
EFD alarm level Level 2 has been exceeded. The actual fault condition may not be
present any more.
LFD warning level Level 1, preset quantity of burnt lamps, has been reached. The
warning disappears after the condition is no longer detected.
LFD alarm level Level 2, preset quantity of burnt lamps, has been reached. The
warning disappears after the condition is no longer detected.
LFD VA warning level Level 1, the preset value for VA drop has been exceeded.
LFD VA error level Level 2, the preset value for VA drop has been exceeded.
Lamp life warning Preset time for the lamp is exceeded.
Local bus error One or more modules on the local bus do not communicate.
Bus A down Bus A does not receive messages.
Bus B down Bus B does not receive messages.
Overtemperature This terminal becomes activated when the inside temperature of the
regulator (measured on the LMV) becomes more than the set
maximum temperature. As soon as the temperature goes under the
the set maximum temperature, the terminal becomes nonactive.
MOV blown alarm The system cannot detect the optional lightning arrestor protection
of the input voltage or it must be replaced.
MCR is ON The regulator is ON.
MCR is in local The regulator in is in the local mode.
MCR is in MW remote The regulator in is in the remote mode.
Regulation error
Door OPEN alarm
CSM fault
Function Description
Free This terminal is not in use.
Circuit 1 Selection for circuits.
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
Circuit 8
CS fault The requested circuits are different than the actual circuits detected.
P6
P1 P2 P3 P4
P5
7.4.2 Connectors
Table: 14 J-Bus connectors
Connector Connection to
P1 J-Bus control for Bus A
P2 J-Bus control for Bus A
P3 J-Bus control for Bus B
P4 J-Bus control for Bus B
P5 PE
P6 LMC
C07 C06
DS1
SW1
C011 SW4
DS7
C012
DS8
C01
SW2
C013
DS2
C014
DS11 DS9
SW6
SW5
DS10
SW7
C08 SW3
DS5
DS3
C03
DS6
DS4
C09
C04
C010 C05
7.5.2 Connectors
Table: 15 LMC connectors
7.5.3 Dip-switches
Factory setting of the switches:
SW1 - all OFF
SW2 - all OFF
SW3 - 1:ON 2:ON 3:ON 4:OFF 5:OFF 6:OFF 7:OFF 8:OFF
SW4 - J-Bus slave number
SW5 - Depending on the presence of the modules
SW6 - 1:OFF 2:OFF 3:OFF 4:OFF 5:OFF 6:ON 7:ON 8:ON
SW1 J-Bus A - This switch handles line termination for J-Bus A. The switch also determines the use of two- or
Line termination four-wire transmission.
Terminating the line at both ends of the databus with straps helps to match the load closely to the
characteristic line impedance. This creates a reflection-free communication bus that has less
disturbances. Set the straps as follows:
- For a two-line system, set only the straps for the line “Transmit / E”.
- For a four-line system, set the straps for both lines “Transmit / E” and “Receive / R”.
NOTE
Make sure that you only place the line termination resistors at the end of the line. If
you set the straps also elsewhere on the line, the signals are weakened. This can
cause the regulator to not function correctly!
SW2 J-Bus B - This switch handles line termination for J-Bus B. The switch also determines the use of two- or
Line termination four-wire transmission.
Terminating the line at both ends of the databus with straps helps to match the load closely to the
characteristic line impedance. This creates a reflection-free communication bus that has less
disturbances. Set the straps as follows:
- For a two-line system, set only the straps for the line “Transmit / E”.
- For a four-line system, set the straps for both lines “Transmit / E” and “Receive / R”.
NOTE
Make sure that you only place the line termination resistors at the end of the line. If
you also place other straps, the signals on the line are weakened. This can cause an
incorrect functioning of the MCR³!
SW4 J-Bus slave J-Bus slave number, composed by the switches in the position OFF:
number
SW5 Local Bus - This switch allows you to enable or disable Local Bus modules. The switch setting on LMC
modules permits disabling the detection of the optional units. This means that the Local Bus to these units
is deactivated.
Switch Function
1 ON: UI enabled
2 ON: EFD enabled
3 ON: LFD enabled
4 Not used
5 Not used
6 Not used
7 Not used
8 ON: dongle enabled
SW6 Various
functions Table: 21 SW6 various functions
Switch Function
1 ON: Local Kill
2 ON: E2P init
3 ON: Lock in boot-loader
4 Not used
5 Local Bus - 0 9600 1 19200 0 38400 1 9600
baudrate: Bd Bd Bd Bd
6 0 0 1 1
7 Local Bus - 0 NO 1 NO 0 ODD 1 EVEN
parity: parity parity parity parity
8 0 0 1 1
7.5.4 LEDs
Table: 22 LMC LED RUN light functions
LED Function
DS1 J-Bus A – isolated 5 V present
DS2 J-Bus B – isolated 5 V present
DS3 Local Bus – isolated 5 V present
DS4 Local Bus – TXD
DS5 Sync line signal
DS6 Local Bus – RXD
DS7 J-Bus A – RXD
DS8 J-Bus A – TXD
DS9 J-Bus B – RXD
DS10 J-Bus B – TXD
DS11 Microcontroller - RUN
8 Appendix
Example
circuit length is 8000m
cable section is 6mm2
Rprim = ρ x 8000:6 = 24 Ohm
If the cable capacitance is 1 µF, the measured voltage decreases from 400 V DC to 147 V DC
(=0.37x400) in approximately 10 seconds.
If the voltage you measure with the LFD module connected is already 330 V DC, the cable
leakage resistance is approximately 10 MOhm. In this case, the discharge time is approximately
5 seconds for a cable capacitance of 1 µF.
Screen
D
C
B
A
A Push-buttons C Menu rows
B Push-button functions D Title row
Navigate the local Use the push-buttons to navigate through the menus. The selected function of each push-button
use interface shows on the screen above the button. The table shows the available functions for the push-
buttons:
Function Action
ABORT Stop the selected action and to return to the previous menu.
BACK Go back to the previous menu.
CLEAR Clear the error list.
CONTINUE Confirm an action and go to the next step.
DOWN Scroll down on a menu that has more lines that the screen can show
at one time.
MENU On the start page, push Menu to browse the available menus.
RESET When a fatal errors occur, you can clear the error after you have
found the cause.
SELECT Confirm a selection.
START Push Start to open the menu that is selected on the screen.
TOGGLE Push Toggle to choose an option from a list.
UP Scroll up on a menu that has more lines that the screen can show at
one time.
The menu allows you to change between local and remote control. You can also change the
selected brightness step and select the circuits for a circuit selector (option).
Item Range
MCR master Change between local and remote mode.
Step Change the selected brightness step.
Circuit 1-8 Set the enabled circuits ON or OFF if the regulator has a circuit
selector.
CAUTION
Be careful when you clear the screen because error messages are not stored.
The clear button does not solve the errors.
Output current The menu allows you to change the settings for the output current.
Step data The menu allows you to set the number of brightness steps available.
Item Description
Number of steps Set to a minimum of 3 and maximum of 8 steps.
Step 1 [0.01 A] 1.8 up to the value of the next step.
Step 2 - 7 Set a value from the previous step to the next step. For a 6.6 A
regulator, set a difference of at least 0.1 A between two steps.
For a 20 A regulator, set a difference of at least 0.3 A between
two steps.
Step 8 Set the value from the previous step to the maximum value.
Default mode The menu allows you to set default values that the regulator uses when the remote control (J-
Bus) connection is down for longer than the time set in the menu.
Item Description
Default mode Set the parameter either to Use default or Use actual. You can
only set default values if you select Use default.
Default time [s] The time after which the regulator start using the default
settings.
Default step Choose a default step. You can set the parameter either to OFF
or from 1 to 8.
Default CSM Set each circuit to ON / OFF.
Supply voltage
CAUTION
Do not change these parameters without a recommendation from ADB.
Wrongly set parameters can damage the regulator.
IO
Table: 9 IO menu
Item Range
Multiwire 1 The system detects the available multiwire modules. Multiwire 3
is reserved for the circuit selector. You cannot change the input /
Multiwire 2
output functions wit the local interface. To change these
Multiwire 3 functions, use the configuration tool, see section 8.3.7 IO menu.
Bus A The J-Bus(ses) must be enabled before you can use them. This
section allows you to monitor the slave number for Bus A. You
Bus B
can also change J-Bus baudrate and parity settings separately
for Bus A and B.
Item Range
Arbiter Set the signal source for remote control. You can also set a
priority for different systems. If you set this parameter to
disabled, remote control is not possible.
Local kill Disable local control.
Temperature limit Set an upper temperature limit between 20 oC and 70 oC. This
gives only an alert, it does not shut down the regulator.
Mains protection Option.
Door open Option.
Versions This menu shows the present software version of each module. If the local bus does not detect a
module, the marking -.-- shows instead of the software version. You can update these software
versions only with the configuration tool. See section 8.3 Configuration tool software.
Serial numbers This menu shows the serial number of each module. If the local bus does not detect a module,
the marking -.-- shows instead of the module serial number. You cannot change these numbers.
Item Range
AGLAS installed The parameter shows whether the AGLAS system is detected.
CSM installed The parameter shows whether the CSM is detected.
CSM mode The available modes:
- Simultaneous: the regulator can connect to a number of the
available circuits at the same time;
- Alternate: the regulator can connect to only one circuit at a
time.
Circuit 1 - 8 Set each circuit to enabled / disabled.
Item Range
EFD Control Disabled / enabled
EFD Reset error YES / NO
EFD ON if MCR is OFF YES / NO
If this is set to YES, the EFD works even if the regulator is
switched OFF.
EFD Startup [s] 4 - 120
EFD Level 1 [MOhm] 1 - 255
You can set a warning level even if you do not specify a value.
EFD Level 2 [MOhm] 0.06 - 9.99
You can set an error level even if you do not specify a value.
EFD Calibration Start the calibration.
CAUTION
- Level 1 and level 2 both have a range of up to 31, but level 2 must always
be larger than level 1.
- LFD VA-drop levels: both can be set to any value between 1 and 50, but
level 2 must always be higher than level 1.
Item Description
LFD View sets Display the different circuit combinations (sets) for the LFD
calibration. There are 1, 2, 4, or 8 sets available, depending on
the installed options.
LFD Active set Select the circuit combination (set) to be calibrated.
If no sets are selected, the display shows Invalid.
LFD Select CSM circuits Select the circuit combination for which the LFD calibration is
performed.
LFD Warm-up time [s] Set the time to 10 - 1200 seconds. The time depends on the
length of the circuit and the number of transformers.
LFD Do REFERENCE Start the calibration.
Calibration
LFD No. of lamps removed Set the number of lamps to be removed to a value from 1 to 31.
LFD LAMPS REMOVED Start the calibration.
Calibration
LFD Erase calibration Erase LFD calibrations for the active set.
Hour counters are set to disabled by default. If a CSM is installed, you can enable hour counters
for different circuits.
Item Description
Hour counters (h) There are two types of hour counters:
- Counters that measure the number of hours the regulator is
ON.
- Counters that measure the number of hours the regulator is
ON and produces output current that is higher than a set
value.
If the regulator has a circuit selector, each circuit has its own
hour counter.
Hour Limits Set the values that the hour counters use to monitor the output
current.
Hour Counters Reset Reset hour counters.
8.2.10 Display
Item Description
Display Contrast [%] The contrast of the display is locked to 100 %.
Display time-out [s] Set the parameter from 5.0 to 124.5 seconds. The last value
locks the display, that is, the backlight always remains ON and
the display shows LOCK.
Embedded language Shows the main language of the user interface.
Extra language Choose an alternative language if another language is available.
WARNING
Do not use the configuration tool unless you have permission to do so. If you
activate the configuration tool, you transfer all control of the regulator to the
tool. In this situation, remote or local control of the regulator is not possible.
NOTE
If you want to use a dongle for the FCU system with the regulator, you must install
the applicable dongle software in the configuration tool, from the menu Configuration
> Software update.
Connect cables
1. Make sure the regulator is switched OFF.
2. Take off the front panel.
3. Connect the extension cable to the dongle
(B) and to the PC connector of the regulator
(A). You can connect directly to any A
regulator or to an LMC unit. B
4. Put back the front panel. Use a clamp to C
hold the panel to its place so that the cable
can come out freely.
5. Connect the cable null modem to the
dongle (B) and to the serial communication
port of your PC (C).
Start software 1. Switch the regulator ON. The regulator also supplies power to the dongle.
2. Start the configuration tool. Go to Start > All programs > MCR_WIN > MCR_WIN.
Alternatively click the MCR_WIN.exe file in the directory where you installed the software.
The configuration tool opens.
3. Select the menu Configuration.
4. Select the applicable serial communication port (COM) to which you connected the dongle.
NOTE
The baud rate and parity settings for the communication between the PC, dongle
and the regulator must be the same. For the dongle, the default baud rate is 38400
and the default parity setting is EVEN.
E
C
Item Range
Step You can change the selected brightness step.
Circuit 1 - 8 If the regulator has a circuit selector, you can set the enabled
circuits ON or OFF.
Remote reset You can reset the regulator.
Identification and The menu shows you the software versions and serial numbers of all the PCBs installed in the
software versions regulator. If a mode is not detected, the marking -.-- shows instead of the software version. Note
that you cannot change the software version without a corresponding software upload.
Output current The menu allows you to change the default settings for output current.
Item Description
Output current Shows the maximum and minimum output current of the
regulator. You can change this value in the Installation menu.
Steps Set the number of brightness steps available. For each step, you
can set a step value. For a 6.6 A regulator, set a difference of at
least 0.1 A between two steps. For a 20 A regulator, set a
difference of at least 0.3 A between two steps.
Item Description
Shut-down If the regulator has a circuit selector, you can set a Shut-down
current value. When you switch OFF a circuit, the regulator
lowers temporarily the output current of the circuit to this value.
Overcurrent alarm levels Set alarm levels for overcurrent situations.
Mode of operation Set parameters that define the operation mode for the output
current.
Remote reset Reset the regulator. The Remote reset allowed parameter shows
you if a reset is possible.
Default operation Set parameters for default mode operation. These parameters
are used during a communication failure between the regulator
and remote control or LMC/CCL modules.
Mains supply This menu shows the present mains supply values.
Item Range
Mains supply & frequency This section shows information about the mains supply. You can
only change these values in the Installation menu.
Alarm levels Define alarm levels for mains supply.
Circuit selector If the regulator has a Circuit selector, this menu allows you to enable or disable circuits.
Item Range
Mode of operation This section shows if a Circuit selector is installed. You can also
set the mode of operation to alternate or simultaneous.
Circuits This section allows you to enable or disable circuits.
Error simulation This menu allows you to simulate errors. You can use the simulated errors to test the connection
between the regulator and the remote control system.
Item Range
Output current Simulate output current errors. Available options are:
overcurrent, open circuit, overload, output current deviates, or
output current unstable.
Mains voltage Simulate mains voltage errors. Available options are: mains
voltage too low, mains voltage too high, or mains voltage
unstable.
Input/output This menu shows the status data for different input and output values. The menu also lets you to
measurements calibrate some measurements for the CCL module.
WARNING
Any calibration is potentially harmful because high voltages and currents are
involved.
Item Range
Measurements This section shows the different input and output values.
Calibration Calibrate input and output measurements for the CCL module.
You must do this every time after you replaced the CCL unit.
When other PCBs are exchanged, a calibration is not required.
When the regulator is in short-circuit, you can calibrate the
regulator only roughly. For fine-tuning, the regulator must be in
full load.
For most values, when you start a calibration, there is first an
offset adjustment. This means that the regulator switches OFF.
Then it switches to the maximum output current and requests
you to enter the correct reading.
Hour counters Hour counters are set to disabled by default. If a CSM is installed, you can enable hour counters
for different circuits.
Item Description
Hour counters [hour] There are two types of hour counters:
- Counters that measure the number of hours the regulator is
ON.
- Counters that measure the number of hours the regulator is
ON and produces an output current that is higher than a
user-defined value.
If the regulator has a circuit selector, each circuit has its own
hour counter.
Hour Limits Set the upper limit of hour counters. When this limit is exceeded,
an alert is generated.
Item Range
Control commands This section allows you to enable or disable the LFD module.
Alarms Set alarm levels to warn about leakages and simulate an LFD
errors.
LFD Calibration Start the calibration.
8.3.7 IO menu
Table: 25 IO menu
Item Description
Hardware present Shows the detected hardware modules.
IO Arbiter Set the signal source for remote control. You can also set a
priority for different systems. If Arbiter is set to disabled, remote
control is not possible.
Local Kill Allows you to disable local control.
Warning messages Shows the UI and J-Bus warnings detected by the system.
Temperature Set an upper temperature limit between 20 oC and 70 oC to
protect the regulator from overheating.
Bus If ADB has enabled J-Bus, you can change the J-Bus baudrate
and parity settings separately for Bus A and B. You can also
monitor the slave number value.
Multiwire Change the back-indication/control functions of each signal for
MW 1, MW 2, and MW 3. MW 3 is reserved for the circuit
selector.
8.3.8 Save
This menu allows you to save and restore IO profiles.
Item Description
Save Save the IO settings parameters as a profile on your PC. You
can later restore the profile if necessary or upload the profile to
another regulator.
Restore Upload an IO settings profile to the regulator. Before you can do
this, you must have a profile saved on your PC.
8.3.9 Installation
This menu allows you to view and change factory settings of the regulator.
CAUTION
Do not change these parameters without a permission from ADB. If you give
wrong values to these parameters, you can damage the regulator and the load.
8.3.10 Configuration
This menu allows you to configure the communication between the regulator and your PC. It also
configures this software and allows you to upload new software versions to the regulator.
8.4 Abbreviations
Table: 29 Abbreviations
Abbreviation Description
AGLAS Airfield Ground Lighting Automation System
CCL Current Control Logic
CS Circuit Selector
CSM Circuit Selector Module
EFD Earth Fault Detection
LA Lightning arrestor
LFD Lamp Fault Detection
LMC Local Master Circuit
MW Multiwire
PCB PC Board
PE Protective Earth
PSL Power Supply Logic
TBM Thyristor Block Module
UI User Interface
Registered Office
ADB NV/SA
Marie Curiesquare 30
1070 Brussels
Belgium