The Raptor System

User guidelines
Raptor C-xx Systems Multi-function + current up to 15,000 A

Raptor System training course


MASTER UNIT
2 kV SLAVE

TRANSPORT
CASE

15 kA SLAVE

POLARITY
CABLES TESTER
Raptor C-xx Systems Multi-function + current up to 15,000 A

Raptor System training course


Raptor C-05 • Output power: 3 kVA
• Maximum current: 9600 A
• AC supply: 240 V / 20 A
Raptor C-xx Systems Multi-function + current up to 15,000 A

Raptor System training course


Raptor C-15 • Output power: 8 kVA
• Maximum current: 15000 A
• AC supply: 240 V / 55 A
Raptor C-xx Systems Multi-function + current up to 15,000 A

Raptor System training course


Raptor C-xx Systems Multi-function + current up to 15,000 A

Raptor System training course


What can the Raptor do?
• AC current up to 15 kA (up to 9.5 kA with master unit)
• Permanent current up to 3600 A
• Calculate the maximum possible current with your setup
• Inject voltage up to 200 VAC
• Measure external current, voltage, phase angle, frequency
• Calculate impedance, cos(ϕ), ratio, error %, power
• Measure time
• Save results and print reports
• Download firmware updates via Internet
Raptor C-xx Systems Multi-function + current up to 15,000 A

Raptor System training course


What can you do with the Raptor?
• Transport it in your own vehicle
• Test relays and circuit breakers
• Test current sensors
• Test reclosers
• Draw the saturation curve of a CT (knee point)
• Measure impedance
• Verify CT ratio, phase angle and burden
• Check the ground grid’s integrity
• Check continuity
• … etc
Raptor C-xx Systems Multi-function + current up to 15,000 A

Master unit (C-05)

Raptor System training course


Auxiliary 200V /
35 A output
Handle release Output fuse
IrDA port Option port
High current output

System reset Console port

Main power switch Binary input


Fuse Voltage input #2
240VAC input Voltage input #1

Current input
Raptor C-xx Systems Multi-function + current up to 15,000 A

Master unit

Raptor System training course


High current injection

Digital waveform
20-400 Hz variable frequency*
240 VAC supply 0-3 kVA power

* When used stand-alone

Output control
Raptor C-xx Systems Multi-function + current up to 15,000 A

Slave unit

Raptor System training course


High current injection

5 kVA power in 2 stages


Fixed frequency (AC supply)
AC power
Raptor C-xx Systems Multi-function + current up to 15,000 A

Master + slave units

Raptor System training course


High current injection

Master Slave
The master
synchronizes
itself to the slave
(AC supply signal) 3kVA + 5kVA = 8kVA

Frequency = 50 or 60 Hz
(AC supply)
Raptor C-xx Systems Multi-function + current up to 15,000 A

Supply requirements

Raptor System training course


for primary current injection

19 A permanent 026 A permanent 230-250 VAC,


38 A 3 minutes 052 A 3 minutes
74 A 3 seconds 104 A 3 seconds GROUND,
SAME PHASE

Master Slave
Raptor C-xx Systems Multi-function + current up to 15,000 A

Output power control

Raptor System training course


when using current slaves

0-3 VA 3-5.5 VA

5.5-8 VA 8-10,5 VA

10,5-13 VA FULL POWER


Raptor C-xx Systems Multi-function + current up to 15,000 A

Primary current injection

Raptor System training course


Circuit breaker test setup
Raptor C-xx Systems Multi-function + current up to 15,000 A

Primary current injection

Raptor System training course


Circuit breaker test setup
Raptor C-xx Systems Multi-function + current up to 15,000 A

Primary current injection

Raptor System training course


Winding the cable
Raptor C-xx Systems Multi-function + current up to 15,000 A

Primary current injection

Raptor System training course


Winding the cable
Raptor C-xx Systems Multi-function + current up to 15,000 A

Primary current injection

Raptor System training course


Optimizing high current connections
Raptor C-xx Systems Multi-function + current up to 15,000 A

Primary current injection

Raptor System training course


Optimizing high current connections
Raptor C-xx Systems Multi-function + current up to 15,000 A

Primary current injection

Raptor System training course


2 cable turns

Max. Voltage x 2
Max. Current ÷ 2
Raptor C-xx Systems Multi-function + current up to 15,000 A

Primary current injection

Raptor System training course


Output performance

Raptor system Compliance


voltage
Maximum current

C-05: 0.81 V 3,800 A Perm.


3 kVA 0.42 V 7,500 A 3 min.
0.22 V 9,500 A 3 s.
1.62 V 1,900 A Perm.
0.84 V 3,750 A 3 min.
0.44 V 4,750 A 3 s.
C-15: 2.15 V 3,800 A Perm.
8 kVA 1.52 V 7,500 A 3 min.
0.26 V 15,000 A 3 s.
4.30 V 1,900 A Perm.
3.04 V 3,750 A 3 min.
1.66 V 7,500 A 3 s.
Raptor C-xx Systems Multi-function + current up to 15,000 A

Primary current injection

Raptor System training course


Raptor calculator (console & Windows)
Raptor C-xx Systems Multi-function + current up to 15,000 A

Setting up the system

Raptor System training course


Power-on
CONSOLE

SWITCH ON

POWER CORD
Raptor C-xx Systems Multi-function + current up to 15,000 A

Setting up the system

Raptor System training course


Power-on Enter the number of
cable turns used
(can be changed later)

02
Raptor C-xx Systems Multi-function + current up to 15,000 A

Output

Raptor System training course


Pass-through Secondary
High AC current

Keep the
non-used
open

Auxiliary output
Low AC current up to 35 A
Low AC voltage up to 200 V
Master unit only
Raptor C-xx Systems Multi-function + current up to 15,000 A

Input

Raptor System training course


Master unit only

Binary Input: test stop


Detects voltage on / off
Detects NO and NC
contact
Raptor C-xx Systems Multi-function + current up to 15,000 A

Input

Raptor System training course


Master unit only

V2 in
Voltage measurement
Up to 300 V AC or DC
Raptor C-xx Systems Multi-function + current up to 15,000 A

Input

Raptor System training course


Master unit only

A1 in
Current measurement
Up to 20 A AC or DC
V1 in
Very low voltage
measurement
Up to 3 V AC or DC
Raptor C-xx Systems Multi-function + current up to 15,000 A

Choose a template for your test

Raptor System training course


and view the connections diagram

Connection diagram
Raptor C-xx Systems Multi-function + current up to 15,000 A

Common template layout

Raptor System training course


Timing mode
Template’s name
Alarms panel
Chronometer / timer
Stop enablers
Hardware meters
5s. average on/off
Calculated meters
Output dial /
output options

Pre-injection mode Output type

Cable turns setting Safety lock

Freeze / release
Push button mode readings
Raptor C-xx Systems Multi-function + current up to 15,000 A

Adding meters to a template

Raptor System training course


Hardware meters go here

Calculated meters go here


Raptor C-xx Systems Multi-function + current up to 15,000 A

Hardware meters

Raptor System training course


Correspond to physical measurement inputs

V2in
A1in
EXCLUSIVE
V1in
Binary input
Phase angle: V2in-A1in
Phase angle: V2in-Iout
Phase angle: A1in-Iout
Phase angle: V2in-Iout
AC supply: Vin

Touch to add/remove
from the current template
Raptor C-xx Systems Multi-function + current up to 15,000 A

Calculated meters

Raptor System training course


Based on values in hardware meters
Available types:
Apparent power
Reactive power
Total power
Power factor
Impedance
Reactance
Resistance
Transformation ratio
Touch to add/remove
from the current template
Raptor C-xx Systems Multi-function + current up to 15,000 A

Chronometer / Timer

Raptor System training course


Starts automatically when test button is pressed
Can be set to countdown mode
Stop options: PUSH, BINARY IN, ZERO CURRENT
Raptor C-xx Systems Multi-function + current up to 15,000 A

Do the test

Raptor System training course


SET THE TEST VALUE ENABLE THE OUTPUT

TEST
Raptor C-xx Systems Multi-function + current up to 15,000 A

Pre-injection reminder

Raptor System training course


Load calibration required
Specially important for instantaneous trip tests.
• Set the maximum non-tripping current and do
a 1-second injection.
• The Raptor will calculate the required voltage.
• The chronometer will not run.
• The orange rectangle will go white. Test now.

BAD OR NO PRE-INJECTION GOOD PRE-INJECTION


Raptor C-xx Systems Multi-function + current up to 15,000 A

Saving your test setup as a custom template

Raptor System training course


Factory and user templates
Create a new custom template
including all changes made

Only in factory templates

Reset
(factory)
template

Load blank
template

COPY
Raptor C-xx Systems Multi-function + current up to 15,000 A

Reporting

Raptor System training course


Organize your test results in named Reports

Go to Reports, open
an existing report or
create a new one.

Reports are Press SAVE while


permanently stored in HOLD is active!
memory.
Raptor C-xx Systems Multi-function + current up to 15,000 A

Reporting

Raptor System training course


Download to your PC using RaptorSync
Raptor C-xx Systems Multi-function + current up to 15,000 A

Automatic test functions

Raptor System training course


Check for updates!

Analyze a re-closer’s SOTF sequence


Find the knee point and draw the curve
Inject a train of AC current or voltage pulses
Inject a ramp of AC current or voltage pulses
Find the knee point using high voltage*
Measure the step & touch voltage
Raptor C-xx Systems Multi-function + current up to 15,000 A

Automatic test functions

Raptor System training course


Example: CT magnetization (knee point)

Connection diagram

Enter the max. allowed voltage

Enter the max. allowed current


Raptor C-xx Systems Multi-function + current up to 15,000 A

SMC support

Raptor System training course


www.smcint.com/support

PRIVATE AREA

PUBLIC SUPPORT FORM

OR DIAL +34 91 8498980 (Spanish, English, German)


Raptor C-xx Systems Multi-function + current up to 15,000 A

SMC support

Raptor System training course


smc.force.com/selfservice (recommended, exclusive to customers)
Raptor C-xx Systems Multi-function + current up to 15,000 A

SMC support

Raptor System training course


Repair & calibration services

Submit your
request in
www.smcint.com

Do not ship
before obtaining
your RMA
Read the user’s manual!

Thank you