Tmax Molded Case Circuit-Breakers

You might also like

You are on page 1of 5

Product data sheet

Tmax molded case circuit-breakers


Tmax T7

Compliance with Standards Type of circuit-breaker Tmax T7


UL489 Frame 1000/1200
CSA C22.2 No. 5.1 Rated ultimate short-circuit breaking capacity, Icu S H L
IEC 60947-2 (AC) 50-60 Hz 240 V [kA] 65 100 150
EC Directive: (AC) 50-60 Hz 277 V [kA] – – –
- “Low voltage directives” (LVD) no. 73/23 EEC (AC) 50-60 Hz 347 V [kA] – – –
- “Electromagnetic compatibility directive” (EMC) no. 89/336 (AC) 50-60 Hz 480 V [kA] 50 65 100
EEC
(AC) 50-60 Hz 600Y/347 V [kA] – – –
(AC) 50-60 Hz 600 V [kA] 25 50 65
(DC) 250 V-2 poles in series [kA] – – –
(DC) 500 V-2 poles in series [kA] – – –
(DC) 500 V-3 poles in series [kA] – – –
(DC) 600 V-3 poles in series [kA] – – –
Trip units:
T fixed, M fixed (10xIn) TMF –
T adj., M fixed (10xIn) TMD –
ThermomagneticT adj., M adj. (5...10xIn) TMA –
T adj., M fixed (3xIn) TMG –
T adj., M adj. (2.5...5xIn) TMG –
Magnetic only M adjustable (6...12xIn) MA –
PR231/P •
Electronic
PR232/P •
PR331/P •
PR332/P •
Versions F-W
F-FC CuAl
Fixed (F)
HR/VR
Terminals Plug-in (P) –

Withdrawable (W) HR/VR


Fixing on DIN rail –
Mechanical life [No. operations /hourly oper.] 10000/60

Electrical life [No. operations /hourly oper.] 2000/60


W [mm] 210/280
154/154 Manual
Basic fixed dimensions 3/4 pole D [mm]
178/178 Motorized
H [mm] 268/268
9.7/12.5 Manual
fixed 3/4 pole [kg]
11/14 Motorized
Weights plug-in 3/4 pole [kg] –
29.7/39.6 Manual
Withdrawable 3/4 pole [kg]
32/42 Motorized
Tmax molded case circuit-breakers
Dimensions T7/T7M series
Overall dimensions T7
125 1 Front terminals for flat con-
4.92
97 nection
10 3.82
50 103.6
1.97 4.08 0.39 10
25
0.98 6
10
0.39
0.39 2 Busbars
70 70 70 0.24
2.76 2.76 2.76 24
0.94
3 Flange for the compartment
door

147.5
5.81

0.58
14.5
5.28
134
4 Flange fixing screws

18.75
0.74

4.02
102
7 Tightening torque: 18 Nm
10.55

8.03
204
268

8 Key lock (optional)

4.13
105
9 Padlock (optional)
10 Tightening torque: 2.5 Nm

210
3
0.12 2
13 Terminal for auxiliary con-
8.27
280
11.02
225
8.86
0.08
tacts

With flange Without flange


4.92
125

A (mm) 125...141 147


154.25
5.98
152

6.07
160
6.3

A (in) 4.92...5.55 5.79

190
7.48
206
8.11

Drilling template for support sheet

3P 4P
C (mm) 70 140
C (in) 2.76 5.51
122.5
4.82

35
1.38
9.65
245

Ø 5.5 - M5
Ø 0.22
Tmax molded case circuit-breakers
Dimensions T7/T7M series
Overall dimensions T7M
125 1 Front terminals for flat con-
4.92
50
1.97 97 nection
3.82
103.6
25 4.08 10
70
0.98
70 70
6 0.39 10 2 Busbars
0.24 0.39
2.76 2.76 2.76 24 10
0.94 0.39 3 Flange for the compartment
door

147.5
5.81
4 Flange fixing screws
5.28

0.58
14.5
134

118.5
4.66

4.02
102
7 Tightening torque: 18 Nm
10.55

9.34

8.03
237

204
268

8 Key lock (optional)


9 Padlock (optional)
10 Tightening torque: 2.5 Nm
13 Terminal for auxiliary con-
≥3 tacts
210 ≥ 0.12 2
280 8.27 0.079
193.5
11.02
7.62

With flange Without flange


A (mm) 125...141 147
4.92
125

A (in) 4.92...5.55 5.79


7.01

6.89
178

175

Standard Ronis Profalux Kirk Castell


B (mm) 208 216 224 – –
B (in) 8.19 8.5 8.82 – –
190
7.48
206
8.11

Drilling template for support sheet

3P 4P
C (mm) 70 140
C (in) 2.76 5.51
122.5
4.82

35
1.38
9.65
245

Ø 5.5 - M5
Ø 0.22
Contact us

Canada While all care has been taken to ensure that the information

1SXP210009D0201 / August 2011


contained in this publication is correct, no responsibility
ABB Inc. can be accepted for any inaccuracy. The Company reserves
Low Voltage Products the right to alter or modify the information contained herein
at any time in the light of technical or other developments.
2117 – 32nd Avenue Technical specifications are valid under normal operating
Lachine, QC, CANADA H8T 3J1 conditions only. The Company does not accept any
responsibility for any misuse of the product and cannot be
Tel.: 514-420-3100 held liable for indirect or consequential damages.
Fax: 514-420-3137
© Copyright 2011 ABB Inc. All rights reserved.
Toll Free: 1-800-567-0283

www.abb.ca

You might also like