You are on page 1of 45

New Automatic Test System AT-S+

© 2014 Eaton, All Rights Reserved.


More efficient Solutions for Emergency
Lighting Systems

Individual single luminaire monitoring of Central monitoring and control of self-


up to 20 luminaires per circuit without contained luminaires including
additional data line. automatic function- and duration test.

Free programmability of switching mode All well-proven advantages of the Comfortable visualization
of each individual luminaire STAR and CG Technology, now software which allows the
per circuit without additional data line. available for AC safety power configuration and monitoring
sources. of all CEAG systems.

© 2014 Eaton, All Rights Reserved. 2


System benefits
Automatic test system AT-S+ for safety luminaries in
projects with AC safety power source.
• Savings on installation, battery maintenance, battery
room
• Minimum inspection effort via automatic luminaire
monitoring
• Reduced installation costs via
programmable mixed operation
• Without additional data lines to the luminaires
• Small IP65 distribution box from plastic
• Multiple default settings for different applications
• Identical menu structure as ZB-S
• Up to 40 SOU S+ /SU S+ modules and
up to 25 DLS modules per control unit

Product designation AT-S+ C30


A = Automatic
T = Test
S = System
+ = AC monitoring
Not part of our C = Central, S = Sub Station
business
30 = Max. number of SU S+/SOU S+

© 2014 Eaton, All Rights Reserved. 3


Automatic Test System AT-S+

Automatic test system AT-S+


for safety luminaries in projects
with AC safety power source

© 2014 Eaton, All Rights Reserved.


AT-S+

Important

The new AT-S+ monitoring system is designed to monitor


emergency AC lighting luminaires.

The back-up power source (batteries, generator, 2nd grid) is


not part of our scope of supply. The system integration of
luminaires, mains power, second power source, system
testing, etc. is the responsibility of the System Integrator.

Care needs to be taken that the back-up power meets all


requirements, such as time required to switch over,
operating time, applicable for emergency lighting
installations.

© 2014 Eaton, All Rights Reserved. 5


Planning example for AT-S+ Planning example for AT-S+ with only one riser
3rd
floor

UVA UVA

DLS DLS
AT-S+ SU1 RV-E30 AT-S+ SU1

2nd
floor

UVA UVA

DLS DLS
AT-S+ SU1 RV-E30 AT-S+ SU1

1st
floor

UVA UVA

DLS DLS
AT-S+ SU1 RV-E30 AT-S+ SU1

cellar AT-S+ C4 AT-S+ C4


Operation Operation
Not part
of our
Aggregate on Aggregate on
business
Failure RV-E30 Failure
HVS HVS

DLS DLS

© 2014 Eaton, All Rights Reserved.


Terminator 6
Power supply E30 RS485
Planning example for AT-S+
3rd
floor

UVA

DLS

2nd
floor

UVA

DLS

1st
floor

UVA

DLS

cellar

Not part Operation


of our
business Aggregate on

Failure
HVS

© 2014 Eaton, All Rights Reserved. 7


AT-S+ C30 Power supply E30 RS485 Terminator
AT-S+ installation
230/400V 50-60Hz
example 14
1 2
1. AC power source for safety
15 3
service 20
3

2. AC power source, general


4 4
3. General lighting 5 5
4. Emergency lighting
5. DLS/3Ph/bus module
6. Connection terminals AT-S+ C30
7. Control unit CU S+ 6
16
8. DC/DC converter.2
17 18
9. AC supply DC/DC converter.2
10.Circuit switching modules
SU S+ 2 x 6 A 11

7 8 9
11.Internal field fusing
10 19 19
12.Mains fuse circuit breaker
13.Mains distribution box
14.AC power source, general
12 13
15.Rental current meter
16.Connection terminals AT-S+ SOU/2
17.Disconnector SV feed
18.Disconnector AV feed
19.Circuit switching modules
SOU S+ 2 x 6 A
20.CGVision

© 2014 Eaton, All Rights Reserved. 8


Automatic Test System AT-S+

Modules

© 2014 Eaton, All Rights Reserved.


Modules – Control unit CU S+
Control unit CU S+
• Graphic display

• Foil keyboard

• Two supplementary signal contacts

• Access to servicing menu via special service SD card

• Displaced SD card slot

• Downwards-compatible to ST-S control unit

• New LED / button designations

• Web connection not directly accessible

• Energy buffer

© 2014 Eaton, All Rights Reserved. 10


Modules – Control unit CU S+
Technical data CU S+

Mechanic
Dimensions (WxHxD) 110 x 170 x 155 mm
Installation vertical RS485/CG-S Bus
Degree of protection IP20 Output voltage ≤ 30 V
Ambient temperature -5°C ... +55°C Polarity Independent
Relative humidity 10 to 95 % no condensation Keyboard Inputs Z1-Z4
Allowed degree of pollution 2 ≤ 2 V DC  OFF
Input voltage
Input voltage (Mains) 220…240 V AC ≥ 12 V DC  ON
Permissible mains frequency 47…63 Hz Input frequency ≤ 0,5 Hz
Power consumption 4,4 W Display
Dimensions (WxHxD) 110 x 170 x 155 mm Resolution 128 x 64 Pixel
Relayouputsoops S1S2 / S3S4 monochrome
Colour
S1S2: < 600 Ω or > 3200 Ω released (green-yellow backlight)
Range of resistor Keyboard
S3S4: < 600 Ω or > 3200 Ω mains failure
Output voltage ≤ 30 V DC, ≤ 10 mA Life cycles ≥ 50.000
Relayouputs Memory Card
Switching voltage ≤ 30 V DC/AC Type Secure Digital Memory Card
Continuous current ≤ 0,5 A Supply voltage 3…3,6 V DC
Inrush current ≤5A Supported capacity 8 MB - 1 GB

© 2014 Eaton, All Rights Reserved. 11


Modules – Control unit CU S+
3 freely programmable
Connection for blocking signal contacts
switch and external 2 contacts permanently
phase monitor programmed

3 buttons for: test (mains 3 freely assignable


failure battery operation), function buttons
function test,
duration test Graphic display, 4 x 20
characters, backlit, contrast and
brightness
SD card slot can be set via programmes

Status LED displays 7 control buttons for


user-friendly
navigation

4 freely assignable
RS 485 /
24 V analogue inputs
CG-S bus connection

© 2014 Eaton, All Rights Reserved. 12


Modules – Control unit CU S+

CU-S+

S3/S4: 24 V monitoring loop C0/14/12/24/22/34//32:


external phase monitors 3 freely programmable
S1/S2: External key-operated signal contacts
switch, system blocked C1/44/54:
2 contacts permanently
programmed

© 2014 Eaton, All Rights Reserved. 13


Modules – Control unit CU S+
Potential free relays

5 ralays,
contacts:
C0/14/12/24/22/34/32/
C1/44/54

© 2014 Eaton, All Rights Reserved. 14


Modules – Control unit CU S+

3 freely assignable function buttons for:


• Block/release system

• Manual reset

• Function test without forward run.

• Display error list

• Switch on/off maintained mode

• Switch on complete safety lighting (corridor lighting)

© 2014 Eaton, All Rights Reserved. 15


Modules – Control unit CU S+
LCD display, e.g.
• Date/time

• Manual reset

• Test operation

• Follow-on emergency light (residual time in mins.)

• Luminaire error with location specification

• UV-AV failure (location specification)

• Error info/programming info

© 2014 Eaton, All Rights Reserved. 16


Modules – Control unit CU S+
Secure digital card:
• Flexible data storage for system and log book configuration, e.g.
regulations-compliant archiving of inspection book information over at
least 4 years

• System programming is possible on any PC via optional SD card


reader and CEAG software. Texts can also be entered at the control
unit of the central unit

Saving of:

• 360,000 inspection book entries

• Target location texts of luminaires (20 digits per luminaire)

• Target location texts of external modules such as phase monitors,


DLS, TLS (20 digits per module)

• Names of circuits (20 digits per circuit)

• System name (20 digits)

© 2014 Eaton, All Rights Reserved. 17


Modules – Control unit CU S+

CG-S bus:
CGVision connection

RS 485 bus: Connection of


external modules, such as DLS,
SOU, SU-S

24 V In/Out connections: Connection


of 24 V supply of external modules,
such as DLS, F3 remote display

© 2014 Eaton, All Rights Reserved. 18


Modules – Control unit CU S+

© 2014 Eaton, All Rights Reserved. 19


Module – SU-S+ 2 x 6 A
Circuit module SU-S+ 2 x 6 A
• Minimum inspection effort required due to
automatic luminaire monitoring

• Reduced installation costs via programmable


mixed operation

• No additional data lines to the luminaires

© 2014 Eaton, All Rights Reserved. 20


Module – SU-S+ 2 x 6 A
Logging on to the control unit via the search function

CU S+ SU-S + 2 x 6 A
(up to 40 modules)

Neuron Assignment
Installation location
ID number CU CG-S control unit
Building/ Room
1. In the "Circuit setup" SOU module Module support
floor number
submenu activate NID07 00 00C2 B9 01 1 1/EG 1105
search for external NID07 00 00C2 B9 02 2 1/EG 1105
SOU's. NID07 00 00C2 B9 03 3 1/EG 1105
NID07 00 00C2 B9 04 4 1/EG 1105
NID07 00 00C2 B9 05 5 1/EG 1105
NID07 00 00C2 B9 06 6 1/EG 1106
2. Assign a module number NID07 00 00C2 B9 07 7 1/EG 1106
NID07 00 00C2 B9 08 8 1/EG 1106
(1 up to 40)
NID07 00 00C2 B9 09 9 1/EG 1106
NID07 00 00C2 B9 10 10 1/EG 1106
NID07 00 00C2 B9 11 11 1/EG 1107
NID07 00 00C2 B9 12 12 1/EG 1107
NID07 00 00C2 B9 13 13 1/EG 1107
NID07 00 00C2 B9 14 14 1/EG 1107
NID07 00 00C2 B9 15 15 1/EG 1107

Note before the configuration


Assign during the configuration

© 2014 Eaton, All Rights Reserved. 21


Module – SU-S+ 2 x 6 A
Logging on to the control unit via the
service pin SU-S + 2 x 6 A
(max. 40 Module)

1. Press the service pin.

CU S+

2. Assign a module number (1 to 40)


to the assembly.

© 2014 Eaton, All Rights Reserved. 22


Module – Status output
Status output with flash code via
service pin
1. To activate the flash code, press the service pin for at least 5 seconds.

2. Red LEDs alternately flashing indicates the display mode 1 , 2 .


3. After 1 second, the code will be displayed for circuit 1
1
4. Briefly pressing the service button calls the next fault.

Flash code description: 2

• 1 flash = luminaire fault

• 2 flash = fuse fault

• 3 flash = overload

• 4 flash = over-temperature

5. This now proceeds with the second circuit (from step 3).

If point 4 is not implemented, normal display is resumed after approx. 30 s.

© 2014 Eaton, All Rights Reserved. 23


Module – SU-S+ 2 x 6 A

Mains connection
Connection for
luminaire circuits

LED circuit On

Fuse LED fault, circuit 1


Circuit 1 LED fault, circuit 2
Service button
Fuse
Circuit 2

RS 485 bus connection

© 2014 Eaton, All Rights Reserved. 24


Module – SU-S+ 2 x 6 A
Technical data SU S+ 2 x 6 A

Mechanic
Dimensions (WxHxD) 107 x 90 x 58 mm
Installation For top hat rail mounting Max. Inrush current 250 A/ms each circuit
Permissible mains
Degree of protection IP20 50 or 60 Hz
frequency
Climatic conditions
Over all power loss 10 W (at 2 x 6A)
Ambient temperature -10°C ... +55°C
Luminaire addresses Up to 20
Relative humidity 10 to 95 % no condensation Input Terminal blocks 0,2 to 6 mm² (solid)
Allowed degree of pollution 2 / wire gauge 0,2 to 4 mm² (stranded)
Electrical Parameter Output Terminal 0,2 to 4 mm² (solid)
blocks / wire gauge 0,2 to 2,5 mm² (stranded)
Input voltage (Mains) 220…240 V AC 0,2 to 4 mm² (solid)
Bus Terminal blocks /
Own power consumption <2W wire gauge 0,2 to 2,5 mm² (stranded)
Number of Circuits 2 RS485 Bus - LON

Continuous current rating 6 A pro Stromkreis Output voltage ≤ 30 V


Polarity Independent
10 AT per circuit, Miniature Fuses
Fusing 5 x 20 mm, High Breaking Capacity / 24V +/- Bus / In
H (1500 A) Input voltage 22…28,9 V DC

© 2014 Eaton, All Rights Reserved. 25


Module – SOU-S+ 2 x 4 A
SOU S+ 2 x 4 A
• Area-specific installation enables electricity cost assignment per
rental area

• Reduced installation costs via programmable mixed operation

• No additional data lines to the luminaires

© 2014 Eaton, All Rights Reserved. 26


Module – SOU-S+ 2 x 4 A

Safety power source Rental Connection RS 485 bus


230 V AC current of end circuits connection
feed 2x4A
230 V AV DIL switch
Terminator
Top hat rail
housing, 10
subunits LED On, circuit 1
LED fault, circuit 1

End circuit fuse,


circuit 1 LED On, circuit 2
(8AT 6.3 x 32)
LED fault, circuit 2

End circuit fuse,


circuit 2 Service pin
(8AT 6.3 x 32)

© 2014 Eaton, All Rights Reserved. 27


Module – SOU-S+ 2 x 4 A
Technical Data SOU S+ 2 x 4 A

Mechanic
Dimensions (WxHxD) 178 x 108 x 60 mm
Installation For top hat rail mounting
Degree of protection IP20
Climatic conditions Maximum Inrush current 250 A/ms per circuit
Permissible mains
Ambient temperature -10 … +55° C 50 or 60 Hz
frequency
Relative humidity 10 … 95 % no condensation Over all power loss ≤ 9 W (at 2 x 4 A)
Allowed degree of pollution 2 Luminaire addresses Up to 20
Electrical Parameter Solid: 0,2…4,0 mm2
Connecting terminals
Input voltage Mains 220…240 V AC Stranded: 0,2…2,5 mm2
RS485 Bus - LON
Input voltage Battery 183…275 V DC
Number of Circuits 2 Input/Output voltage ≤ 30 V
Continuous current rating 4 A per circuit Polarity Independent
16 A per circuit, fuses 6,3 x 32 mm, 24V +/- Bus / In
Input Fusing
Max. high breaking capacity1500 A DC
Input voltage 22…28,9 V DC
8 AT per circuit, fuses 6,3 x 32 mm, Input current ≤ 50 mA
Output Fusing
Max. high breaking capacity1500 A DC
Inrush current ≤ 500 mA

© 2014 Eaton, All Rights Reserved. 28


Automatic Test System AT-S+

Cabinet Variants

© 2014 Eaton, All Rights Reserved.


Cabinet Variants

View

Designation AT-S+ C30 AT-S+ C16 AT-S+ C4 AT-S+ C0

Number of outgoing
6 6 6 -
circuits

Rated voltage 400/230 V 400/230 V 400/230 V 230 V

Insulation class 1 1 1 1

Degree of protection IP21 IP21 IP21 IP54

Material/Design Sheet steel / Cabinet Sheet steel / Cabinet Sheet steel / Wall cabinet Sheet steel / Wall cabinet

© 2014 Eaton, All Rights Reserved. 30


Cabinet Variants

View

Designation AT-S+ SU4 AT-S+ SU2 AT-S+ SOU2 AT-S+ SU1 AT-S+ SOU1
Order number 40071360504 40071360505 40071360508 40071360506 40071360509
Dimensions
590 x 300 x 130 460 x 300 x 130 590 x 300 x 130 460 x 300 x 130 460 x 300 x 130
(max., H x W x D)
Control unit: CU S+ - - - - -
DC/DC converter.2 - - - - -
AC module - - - - -
Circuit switching module
4 2 - 1 -
SU S+ 2 x 6 A
Circuit switching module
- - 2 - 1
SOU S+ 2 x 4 A

Mains rated power [KVA] 5,7 3,7 5,7 2,3 2,3

No. of end circuit


8 4 4 2 2
connections

© 2014 Eaton, All Rights Reserved. 31


Cabinet Variants

View

Designation AT-S+ SU4 AT-S+ SU2 AT-S+ SOU2 AT-S+ SU1 AT-S+ SOU1
Number of outgoing
- - - - -
circuits
Rated voltage 230 V 230 V 230 V
Insulation class 2 2 2 2 2
Degree of protection IP65 IP65 IP65 IP65 IP65
Plastic / Small Plastic / Small Plastic / Small Plastic / Small Plastic / Small
Material/Design
distribution board distribution board distribution board distribution board distribution board

© 2014 Eaton, All Rights Reserved. 32


AT-S+ C30 cabinet design
Cable infeed from above
Triple-deck tension spring
installation terminal with neutral
wire disconnect terminal
Lütze mounting system
Control unit CU S+

DC/DC converter.2

AC module
Circuit switching modules
30 x SU-S+ 2 x 6 A
Fuse circuit breaker
D02 25 A per field

6-fold mains distribution box D02 16 A


Fuse circuit breaker NH 00

Cable infeed from below

© 2014 Eaton, All Rights Reserved. 33


AT-S+ C16 cabinet design
Cable infeed from above

Triple-deck tension spring installation


terminal with neutral wire disconnect
terminal
Control unit CU S+ Lütze mounting system

DC/DC converter.2

AC module Circuit switching modules


16 x SU-S+ 2 x 6 A
Fuse circuit breaker
D02 25 A per field

Fuse circuit breaker NH 00 6-fold mains distribution box D02 16 A

Cable infeed from below

© 2014 Eaton, All Rights Reserved. 34


AT-S+ C4 cabinet design

Cable infeed from above


6-fold mains distribution box D02 16 A

Fuse circuit breaker NH 000

Control unit CU S+ Triple-deck tension spring installation


terminal with neutral wire disconnect
terminal
DC/DC converter.2

AC module Circuit switching modules


4x SU-S+ 2 x 6 A

© 2014 Eaton, All Rights Reserved. 35


AT-S+ C0 cabinet design

Cable infeed from above


Triple-deck tension spring installation
terminal with neutral wire disconnect
terminal

1. Control unit CU S+

DC/DC converter.2

AC module 2. Control unit CU S+ (optional)

DC/DC converter.2 (optional)

AC module (optional)

© 2014 Eaton, All Rights Reserved. 36


AT-S+ SOU2 cabinet design
Cable infeed
from above
Two feeders (rental
Type plate, current and power source
quick start guide for safety service)

End circuit
terminals
RS 485 bus
connection

Sighting window

Circuit switching module


SOU S+ 2 x 4 A
Circuit
designation field
Cable infeed
from below

© 2014 Eaton, All Rights Reserved. 37


AT-S+ SOU1 cabinet design

Cable infeed
from above

Two feeders (rental


current and power source
for safety service)
Type plate,
quick start guide End circuit
terminals

RS 485 bus
connection

Circuit switching module


Sighting window
SOU S+ 2 x 4 A
Circuit
designation field
Cable infeed
from below

© 2014 Eaton, All Rights Reserved. 38


AT-S + SU4 cabinet design
Cable infeed
from above

Type plate, Power source feed


quick start guide for safety service

End circuit
terminals
RS 485 bus
connection

Sighting window

Circuit switching module


SU S+ 2 x 6 A
Circuit
designation field

Cable infeed
from below

© 2014 Eaton, All Rights Reserved. 39


AT-S + SU2 cabinet design
Cable infeed from
above

Power source feed for


safety service
Type plate,
quick start guide End circuit
terminals

RS 485 bus
connection

Circuit switching module


Sighting window
SU S+ 2 x 6 A
Circuit
designation field
Cable infeed from
below

© 2014 Eaton, All Rights Reserved. 40


AT-S+ SU1 cabinet design

Cable infeed from


above

Power source feed for


safety service
Type plate,
quick start guide End circuit
terminals

RS 485 bus
connection
Circuit switching module
Sighting window
SU S+ 2 x 4 A
Circuit
designation field
Cable infeed from
below

© 2014 Eaton, All Rights Reserved. 41


Automatic Test System AT-S+

Bus Systems

RS485 Bus

© 2014 Eaton, All Rights Reserved.


Bus Systems
CU S+ SOU S+ 2 x 4 A SU S+ 2 x 6 A DLS 3-Ph Bus Modul
(together max. 40 modules) (max. 25 modules)

Terminator Terminator
120  120 
2
1

Max. Buslänge 1200 m mit JY(ST)Y 4 x 2 x 0,8 mm


RS485 Bus

RS 485 bus Notes:


Bus topology: linear, double terminated (no branch cables permissible).
RS 485 bus for communication with external
The mandatory terminating resistors are contained in the switching
modules (SOU S+ module, DLS/3PH and
cabinet.
TLS bus-module).
Cable type (minimum requirement):
The terminator (120 , 0.5 W) can be switched in the
JY(ST)Y 4 x 2 x 0.8 mm (twisted pair, shielded)
DLS/3Ph-, TLS bus-module modules by wiring a
The cable cross-section required for the 24 V bus voltage depends on the
bridge at the connection terminals B1; B2 (1) and with
cable length and number of bus modules (Umin = 19 V DC).
the SOU modules via a DIL switch (2).
A resistor in also included in the scope of supply of
the ZB-S switching cabinet. If only one cable is SOU = Switching Over Unit
installed this must be applied here. DLS = external maintained mode switching module
(DLS/3PH bus module)
TLS = external stairway light switching module

© 2014 Eaton, All Rights Reserved. 43


Bus Systems

SU S+
DLS

SOU S+ DLS

RS485 Bus

RS485 Bus

CG-S bus
(FTT10A)

• CG Controller ZB-S
• CG Vision AT-S+ C0

© 2014 Eaton, All Rights Reserved. 44


CEAG Notlichtsysteme GmbH, Senator-Schwartz-Ring 26, D-59494 Soest
www.ceag.de

© 2014 Eaton, All Rights Reserved. 45