Professional Documents
Culture Documents
Operations Manual
DAQS TC SERIES
SOFTWARE CODE: XSDAQSBBSHB6
Microprocessor Controller
Operations Manual
Table of Contents
1.0 Display/Keypad 3
This publication is the sole property of DionX Air Quality Systems (DAQS) Ltd and may not be reproduced, in whole or
part, distributed or sold without permission of the owners. The contents of this manual are subject to revision without
notice due to the continued progress in methodology, design and manufacturing. While every endeavor is made to ensure
accuracy, DionX Air Quality Systems Limited accepts no responsibility or liability resulting from the use of this information.
-1-
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Note!
All DAQS Units are Pre-Set and Pre-Commissioned at the
factory (in-line with customer specifications), prior to field
installation. Consequently only a limited number of control
parameters should require site-adjustment.
Caution!
-2-
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
1.0 DISPLAY/KEYPAD
ALARM KEY – If the ALARM KEY is illuminated in red, it indicates the presence of an active
alarm. Refer to the Section 5.0 of this manual for further details.
PROGRAM KEY – The PROGRAM KEY is used to access the Menu Screens – refer to
section 2.2
ESCAPE KEY – The ESCAPE KEY is used to return operation to the previous screen.
↑ KEY – The ↑ KEY is used to move up through values/parameters in a Menu and to change the
value/parameter once it is selected with the ENTER KEY
ENTER KEY – The ENTER KEY is used to select values/parameters in a Menu and to set new
values/parameters once they have been changed.
↓ KEY – The ↓ KEY is used to move down through values/parameters in a Menu and to change
the value/parameter once it is selected with the ENTER KEY.
The Display/Keypad is used to monitor/adjust the unit operating parameters and settings. All unit
operating parameters are password protected
-3-
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+--------------------+
| 16:25 04:07:05 M1|
|Return T. 23.5ºC|
|Outside T. 15.2ºC|
|Unit ON |
+--------------------+
Fig. 2 – Home Screen
The “Home” or Default Screen M1 is shown in fig. 2 above. This is the screen which is normally
displayed on the Display/Keypad.
The screen displays the current day/date, the Return (or Room) Temperature and the Outside
Temperature (or Return Humidity, if so configured).
The screen also shows unit status – in fig. 2 above, it shows “Unit ON”.
The status line can also display:
Note in the case of “Off by Remote Input”, “Off by Alarms” and “Off by Service Timer”, the unit
can automatically re-start without warning.
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| Status M2|
|Dx Cooling |
|Heating |
|Damper = Free Cool |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
The Status Screen M2 displays the current operation of the unit. A filled box denotes that a
process is active, an empty box denotes that it is inactive. In the above example, DX cooling is
OFF, Heating is OFF and the Damper is in the Freecooling Position – the unit is in Freecooling
Mode.
-4-
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| Software Info M3|
|CODE : XSDAQSBBSHB6|
|Version : 1.1|
|Date : 29.10.06|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
The Software Info Screen M3 displays the Software Code and Version Information.
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|U:01 M4|
| Press Enter |
| To View Next Unit |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
This Screen is only visible if two or more AQC600TC-B6 units are connected via their controller
pLAN network, the network is enabled and appropriate addresses have been set at the two unit
controllers and their shared PGD.
-5-
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Main Menu 1 U:00|
|1:UNIT ON/OFF ~|
|2:SETPOINT ~|
|3:INPUTS/OUTPUTS ~|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
Fig. 3 – Main Menu 1
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Main Menu 2 U:00|
|4:MAINTENANCE ~|
|5:USER PARAM. ~|
|6:MANUFACT.PARAM. ~|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
Fig. 4 – Main Menu 2
-6-
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
- Press the PROGRAM KEY– Main Menu 1 (fig. 3) is displayed and the cursor is
positioned on Menu Option 1 - UNIT ON/OFF.
- Press the ENTER KEY to select Menu Option 1 - UNIT ON/OFF
+-------------------+
| |
|Off by Keyboard |
|- Press Enter To |
|- switch On |
+-------------------+
- Press the PROGRAM KEY– Main Menu 1 (fig. 3) is displayed and the cursor is
positioned on Menu Option 1 - UNIT ON/OFF.
- Press the ENTER KEY to select Menu Option 1 - UNIT ON/OFF
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| U:00|
|Unit ON |
|‐ Press Enter To ‐|
|‐ switch off ‐|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
-7-
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
The Temperature Set-Point is the Return Air Temperature maintained by the unit – it should not
be altered without the approval of the site manager.
- Press the PROGRAM KEY– Main Menu 1 (fig. 3) is displayed and the cursor is
positioned on Menu Option 1 - UNIT ON/OFF.
- Press the ↓ KEY once to position the cursor over Menu Option 2 – SETPOINT.
- Press the ENTER KEY to select Menu Option 2 – SETPOINT.
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| Setpoint oC S1|
|Minimum 18.0 |
| 22.0 oC |
|Maximum 28.0 |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- Press the ENTER KEY once to position the cursor over the SETPOINT field.
- Use the ↑ KEY & ↓ KEY to change the parameter to the required value.
- Note that the Minimum and Maximum values determine the range of adjustment
of the Setpoint – the Minimum and Maximum values can in turn be modified in
the User Menu.
- Press the ENTER KEY to set the new value.
- Press the ESCAPE KEY to return to the HOME SCREEN.
-8-
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
An alarm at the unit can only be reset, once the cause of the alarm has been remedied, i.e. if the
High Pressure alarm is triggered, it cannot be reset at the KeyPad until the cause of the High
Pressure alarm is removed and the High Pressure Switch is reset.
If the alarm does not clear, it is still active and the cause of the alarm must be investigated.
-9-
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
1.6 Viewing the Component Run Hour Log and the Event
History Log
The Run Hours of all major components in the unit are stored in the Run Hours Log.
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| A0|
|Insert Maintenance |
|Password 0000 |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- Press the ENTER KEY once to position the cursor over the Maintenance
Password field.
- Press the ↓ KEY once to change the Password to 9999 (This is the Default
Maintenance Password – if this has been changed, enter the new Password).
- Press the ENTER KEY.
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Maintenance A1|
|Fan Run Hrs 008714|
|Comp. Run Hrs 000515|
|Cond Fan Hrs 000515|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 10 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Maintenance A2|
|Free Cool Hrs 005728|
| 000000|
| 000000|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- Press the ↓ KEY to scroll to the next screen - the Event History Log
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| A3|
|* Event History *|
| Press Enter |
|* To Access *|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 11 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+--------------------+
| U:00|
|Unit ON |
|- Press Enter To -|
|- switch off -|
+--------------------+
Description
UNIT ON/OFF SCREEN
The Unit On/Off Screen switches the unit ON when it is in “Off by Keyboard” mode, the
Screen also switches the unit OFF when it is in “Unit ON” mode.
- 12 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| Access Setpoint S0|
|Insert Maintenance |
|Password 0000 |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| Setpoint oC S1|
|Minimum 18.0 |
| 22.0oC |
|Maximum 28.0 |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| Setpoint %RH S2|
|Minimum 45.0 |
| 55.0%RH |
|Maximum 75.0 |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Low Temperature S3|
|De‐Hum Limit |
|Offset From Setpoint|
| 03.0oC|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Temperature Alarm S4|
|Offset From Setpoint|
|High 10.0oC|
|Low 10.0oC|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 13 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
ACCESS SETPOINT SCREEN S0
SETPOINT SCREEN S1
This screen is used to set the unit’s Temperature Setpoint. The Temperature Setpoint is
used in conjunction with the Return Air Temperature Sensor to determine when cooling
and heating are required. The Minimum and Maximum allowable setpoints are
displayed above and below the Temperature Setpoint. If required, the Minimum and
Maximum allowable setpoints can be changed in the User Menu.
Temp. Setpoint - Enter a value between the Minimum and Maximum Setpoints 22
SETPOINT SCREEN S2
Note: This Screen is only visible when the unit is configured for Humidity Control.
This screen is used to set the unit’s Humidity Setpoint. The Humidity Setpoint is used in
conjunction with the Return Air Humidity Sensor to determine when humidification and
de-humidification are required. The Minimum and Maximum allowable setpoints are
displayed above and below the Humidity Setpoint. If required, the Minimum and
Maximum allowable setpoints can be changed in the User Menu.
45%
Hum. Setpoint - Enter a value between the Minimum and Maximum Setpoints
Note: This Screen is only visible when the unit is configured for Humidity Control.
- 14 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
RETURN TEMPERATURE ALARM SCREEN S4
The screen is used to generate the High and Low Temperature Alarms. The High
Temperature Alarm is generated when the Return Air Temperature is greater than
(Temperature Setpoint+High Offset) oC. The Low Temperature Alarm is generated
when the Return Air Temperature is less than (Temperature Setpoint-Low Offset) oC.
- 15 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| View I/O Status I0|
|Insert Maintenance |
|Password 0000 |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Analogue Inputs I1|
|B1 H.Press 07.3Bar|
|B2 Humidity 055.1%RH|
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Analogue Inputs I2|
|B3 Return T. 23.7oC|
|B4 Outside T. 17.6oC|
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Digital Inputs I3|
|ID1 Air Flow ■ |
|ID2 Filter ■ |
|ID3 HP Switch ■ |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Digital Inputs I4|
|ID4 LP Switch ■ |
|ID5 Service SW |
|ID6 Rem. On/Off |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 16 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Analogue Outputs I5|
|Y1 Supply Fan 10V|
|Y2 Cond. Fan 00V|
|Y3 Heating 00V|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Digital Outputs I6|
|NO1 Damper ■|
|NO2 Compressor |
|NO3 Heater Enable |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Digital Outputs I7|
|NO4 General Alarm |
|NO5 Critical Alarm |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
Description Default
These screens are READ ONLY and allow the user to view the current measured
values/status of all inputs and outputs to the unit controller.
They are categorized and displayed under 4 headings:
- 17 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| A0|
|Insert Maintenance |
|Password 0000 |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Maintenance A1|
|Fan Run Hrs 008714|
|Comp. Run Hrs 000515|
|Cond Fan Hrs 000515|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Maintenance A2|
|Free Cool Hrs 005728|
| |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| A3|
|* Event History *|
| Press Enter |
|* To Access *|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 18 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
MAINTENANCE SCREEN A0
MAINTENANCE SCREEN A1
This screen is a READ ONLY screen showing the current Run Hours of the following
devices.
MAINTENANCE SCREEN A2
This screen is a READ ONLY screen showing the current Run Hours of the following
devices.
Press ENTER to access the Alarm/Event History Log. All alarms (current and past) are
day/date stamped and stored in non-volatile memory. In addition, “Events” such as change of
temperature or humidity setpoint and changes to Manufacturers Parameters are also stored.
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| A4|
|Fan Run Hrs 008714|
|Reset Hours No |
|Threshold 012X1000|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 19 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| A5|
|Comp. Run Hrs 000515|
|Reset Hours No |
|Threshold 006X1000|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| A6|
|Freecool Hrs 005728|
|Reset Hours No |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
Description Default
MAINTENANCE SCREEN A4
This screen is used to generate a Maintenance Alarm when the device Run Hours exceed the
Alarm Threshold Value listed below. The device Run Hours can be reset if required. DAQS
recommend that the device Run Hours are only reset if a new component is fitted to the unit.
MAINTENANCE SCREEN A5
This screen is used to generate a Maintenance Alarm when the device Run Hours exceed the
Alarm Threshold Value listed below. The device Run Hours can be reset if required. DAQS
recommend that the device Run Hours are only reset if a new component is fitted to the unit.
MAINTENANCE SCREEN A6
The device Run Hours can be reset if required. DAQS recommend that the device Run Hours
are only reset if a new component is fitted to the unit.
- 20 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| A7|
|De‐Hum Hrs 000022|
|Reset Hours No |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| A8|
|Heat Run Hrs 000150|
|Reset Hours No |
|Threshold 006X1000|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| A9|
|Cond Fan Hrs 000515|
|Reset Hours No |
|Threshold 000X1000|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
Description Default
MAINTENANCE SCREEN A7
The device Run Hours can be reset if required. DAQS recommend that the device Run Hours
are only reset if a new component is fitted to the unit.
MAINTENANCE SCREEN A8
This screen is used to generate a Maintenance Alarm when the device Run Hours exceed the
Alarm Threshold Value listed below. The device Run Hours can be reset if required. DAQS
recommend that the device Run Hours are only reset if a new component is fitted to the unit.
- 21 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
MAINTENANCE SCREEN A9
This screen is used to generate a Maintenance Alarm when the device Run Hours exceed the
Alarm Threshold Value listed below. The device Run Hours can be reset if required. DAQS
recommend that the device Run Hours are only reset if a new component is fitted to the unit.
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| Aa|
|Clock Settings |
|HR14:07 Date23/07/06|
|Day Monday |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| Ab|
|Change Maintenance |
|Password 0000 |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
This screen is used to set the controller RTC, set as appropriate. Set As Required
MAINTENANCE SCREEN Ab
- 22 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Temperature P1|
|Setpoint Limits |
|Minimum 18.0oC|
|Maximum 28.0oC|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Temperature P2|
|Deadzone |
|Heating 0.5oC|
|Cooling 0.5oC|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Temperature P3|
|Differential |
|Heating 02.5oC|
|Cooling 02.5oC|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
Description Default
USER PASSWORD SCREEN P0
This screen determines the upper and lower limits of adjustment of the Temperature
Setpoint.
- 23 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
The Temperature Differential is a temperature range either side of setpoint where full
control operation occurs. Two Differentials are available, a Heating Differential and a
Cooling Differential.
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Humidity P4|
|Setpoint Limits |
|Minimum 40.0%RH|
|Maximum 80.0%RH|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|De‐Humidify P5|
| |
|Deadzone 02.0%RH|
|Differential 08.0%RH|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Fan Speed Setting P6|
|F.COOL Min Sp 080.0%|
|Dx Speed 100.0%|
|Max Speed 100.0%|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Fan Speed Setting P7|
|De‐Hum Speed 080.0%|
| |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 24 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
HUMIDITY SETPOINT LIMITS SCREEN P4
This screen determines the upper and lower limits of adjustment of the Humidity
Setpoint.
DE-HUMIDIFY SCREEN P5
The Humidity Deadzone is a humidity range either side of Setpoint where no control
operation occurs.
The Humidity Differential is a humidity range either side of setpoint where full control
operation occurs.
2% RH
Deadzone –- Enter a value between 0 and 99.9 % RH
8% RH
Differential - - Enter a value between 0 and 99.9 %RH
This screen determines the speed (airflow/static) setting of the Supply Fan during various
Automatic Mode Operations of the unit.
80%
FreeCooling Minimum Speed – Enter a value between 0 and 100 % of Fan Speed
100%
DX Speed - Enter a value between 0 and 100 % of Fan Speed
100%
Max Speed: - Enter a value between 0 and 100 % of Fan Speed
This screen determines the speed (airflow/static) setting of the Supply Fan during various
Automatic Mode Operations of the unit.
80%
De-Hum Speed – Enter a value between 0 and 100 % of Fan Speed
- 25 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Fan Timing P8|
|Delay On 002Sec|
|Delay Off 015Sec|
|Device Delay 035Sec|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Fan 2 Output P9|
|Speed Setting 100.0%|
| |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Heating Output P9|
|Max Limit 100.0%|
| |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Delta Temp. To En Pa|
|F.Cool Damper 03.0oC|
|Priority Time |
|Over Compressor 10M |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Condenser Fan Pb|
| |
|Setpoint 17.0Bar|
|Diff 04.0Bar|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|High Pressure Pc|
|Pre‐Alarm |
|Setpoint 26.5Bar|
|Diff 04.0Bar|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 26 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
FAN TIMING SCREEN P8
The Delay On parameter sets the time delay between switching ON the unit from the
KeyPad and the fans starting. The Delay Off parameter sets the time delay between
switching OFF the unit from the KeyPad and the fans stopping. The Device Delay
parameter sets the time delay between switching ON the unit and the starting of all other
control functions, heating, cooling, Hum and De-Hum.
The Max. Limit parameter determines the Maximum Heat output of the unit when the
unit is configured for 0-10V Heating (this parameter has no effect if the unit is configured
for ON/OFF Heating).
The Delta Temp. is a temperature differential between the measured Return Air
Temperature and the measured Outdoor Air Temperature. When the measured differential
is greater than the Delta Temp, Freecooling is enabled, when the measured differential is
less, Freecooling is disabled.
For example, with a Setpoint of 22oC, and a Delta Temp. of 3oC, Freecooling is available
at Outdoor Temperatures below 19oC - it is not available at Outdoor Temperatures above
19oC.
The Priority Time Over Compressor parameter sets a time limit on Freecooling
Operation. If the unit runs in FreeCooling Mode for longer than the Priority Time Over
Compressor and Setpoint has not yet been achieved – DX Cooling will begin.
- 27 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
This screen controls the operation of the condenser fan in conjunction with the
Refrigerant Pressure Transducer. The Setpoint parameter determines the pressure at
which the fan starts. The Diff parameter determines the pressure range over which the fan
ramps from 0 to 100%.
The HP Pre-Alarm is used to stop the compressor at a refrigerant pressure level which
would be considered outside normal operating conditions. The Setpoint parameter should
always be set to a lower value than the setting of the HP Switch. The Diff parameter
determines the pressure level at which the compressor restarts ((Setpoint-Diff) Bar).
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Alarm Delay Pd|
|Airflow 040S|
|Filter 300S|
|Temperature 180S|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Alarm Delay Pe|
|Cool Fail 010Min|
|LP Start‐Up 120S|
|LP Running 010S|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Auto Reset Pf|
|Airflow Alarm |
|Enable? Yes |
|Delay To Reset 05Min|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 28 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
ALARM DELAY SCREEN Pd
The Alarm Delay parameters determine the time delays between detection of an alarm
condition and the generation of the alarm screen (and related contact closure, if so
configured). The alarm condition must exist for the full duration of the relevant alarm
delay.
The Alarm Delay parameters determine the time delays between detection of an alarm
condition and the generation of the alarm screen (and related contact closure, if so
configured). The alarm condition must exist for the full duration of the relevant alarm
delay.
This parameter when enabled, allows the Airflow Alarms to automatically reset after the
Delay to Reset time period has elapsed. The alarm can only reset if the alarm condition
has cleared.
Note: This parameter should only be enabled for Stand-alone units – it should not be
enabled in Run/Standby applications
YES
Enable? – Enter YES or NO 5M
Delay to Reset - Enter a value between 0 and 99 minutes
- 29 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| Pg|
|Enable Rem. On/Off N|
|Enable Maint. T. N|
|Maint. Off T. 015Min|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|BMS Communication Ph|
|Unit Address : 000|
|Protocol : Carel |
|En BMS Unit On/Off N|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Master ‐ Slave Pi|
|Networking Setup |
|Enable pLAN No |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Network Mode Pj|
|Number Of Permitted |
|Compressors 1|
|Heaters 1|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| Calibration Pk|
|B1 H.Press 0.0Bar|
|B2 Humidity 0.0%RH|
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Calibration Pl|
|B3 Return T. 0.0ßC|
|B4 Outside T. 0.0ßC|
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 30 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
ENABLE SCREEN Pg
This screen enables/disables the operation of the Remote ON/OFF and the
Maintenance Timer digital inputs.
This screen is used to configure the unit for communication with a Building
Management System.
The unit should be connected via its pLAN port to another unit with the
appropriate address.
This Screen is used to control the operation of the 2 networked units, primarily
for the purpose of limiting AC current usage.
- 31 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
CALIBRATION SCREEN Pk
This screen is used to calibrate sensor inputs to the DAQS unit. The value entered
on this screen is added/subtracted to/from the measured value of the input.
CALIBRATION SCREEN Pl
This screen is used to calibrate sensor inputs to the DAQS unit. The value entered
on this screen is added/subtracted to/from the measured value of the input.
0.0
B3 Return Temp. – Enter a value between 0 and 9.9 oC
0.0
B4 Outdoor Temp. - Enter a value between 0 and 9.9 oC
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| Manual Operation Pm|
|* Unit Must Be Off *|
| To Proceed |
|*Auto End In 5 Min *|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Fans Manual Pn|
|Enable Fan1 N N|
|Fan 1 Output 000.0%|
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 32 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
MANUAL MODE OPERATION SCREEN Pm
The following screens (Pn, Po, Pp, Pq) are normally used in commissioning,
maintenance, troubleshooting etc. They are used to manually operate each of the
outputs from the unit.
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Cooling Manual Po|
|Compressor N|
|Condenser Fan EN N|
|Fan Output 000.0%|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Damper N Pp|
| |
|Heat Output 000.0%|
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Alarm Relay Pq|
|Manual Operation |
|NO4 General Relay N|
|NO5 Critical Relay N|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
| Pr|
|Change User |
|Password 0000 |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 33 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
MANUAL MODE SCREEN Po
0%
Heat Output: - Enter a value between 0 and 100% of Heat Output
- 34 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Temperature C1|
|Regulation Type |
|P+I |
|Integral Time 0600S|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Cond. Fan Ctrl C2|
|Proportional |
|Integral Time 0600S|
|Comp/Fan Intrlk No |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Function Enable C3|
|En Freecool Yes |
|En HP Pre Al Yes |
|En Hum. Ctrl. No |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Humidity Sensor C4|
|Range Lower 10.0%RH|
| Upper 100.0%RH|
|Priority ‐ Freecool |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Humidity C5|
|Regulation Type |
|P+I |
|Integral Time 0600S|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 35 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
MANUFACTURERS PASSWORD SCREEN C0
The Manufacturers password is the highest level of password access; it should only
be available to trained, qualified personnel. Changes to Manufacturers Parameters
should only be made by trained, qualified personnel who have read and fully
understood this manual.
This screen determines the type of control algorithm to be used for temperature
control. The options are Proportional or Proportional Integral. Proportional P+I
control defines a linear relationship between change in temperature and change in
Heating/Cooling outputs. Proportional Integral control utilizes an additional
parameter, the Integral Time to enhance control accuracy.
This screen determines the type of control algorithm to be used for condenser fan
control. The options are Proportional or Proportional Integral. Proportional
control defines a linear relationship between change in refrigerant pressure and P
change in condenser fan speed. Proportional Integral control utilizes an additional
parameter, the Integral Time to enhance control accuracy.
- 36 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
This screen calibrates the DAQS unit for use with a range of 4-20mA Humidity
Sensors. It determines the upper and lower values of the range of the Humidity
Sensor.
10%
Lower – Enter a value between 0 and 100% RH
90%
Upper - Enter a value between 0 and 100%RH
This screen determines the type of control algorithm to be used for humidity control.
The options are Proportional or Proportional Integral. Proportional control P+I
defines a linear relationship between change in humidity and change in Hum/De-
Hum outputs. Proportional Integral control utilizes an additional parameter, the
Integral Time to enhance control accuracy.
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Comp Timings C6|
| |
|Min On Time 180S|
|Min Off Time 180S|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Analogue Output C7|
|3 Configuration |
|Heating |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Digital Output C8|
|3 Configuration |
|Aout Heat Enable |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 37 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
COMPRESSOR CONTROL SCREEN C6
This screen determines the minimum on time and minimum off time of the unit
compressor. The timings are intended to ensure maximum service life of the
compressor by ensuring that it does not “hunt”.
This screen allows the NO3 digital output to be configured as either an on/off signal
Heating
for Heating Output or an on/off signal for the Fan 2 Output.
- 38 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Al Relay Config. C9|
|AL:001 – Critical |
|AL:002 ‐ Critical |
|AL:003 ‐ Critical |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Al Relay Config. Ca|
|AL:004 ‐ Critical |
|AL:005 ‐ Critical |
|AL:006 – General |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Al Relay Config. Cb|
|AL:007 – Critical |
|AL:008 ‐ Critical |
|AL:009 ‐ Critical |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Al Relay Config. Cc|
|AL:010 ‐ General |
|AL:011 ‐ General |
|AL:012 ‐ General |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Al Relay Config. Cd|
|AL:013 ‐ General |
|AL:014 ‐ General |
|AL:015 ‐ Critical |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Al Relay Config. Ce|
|AL:016 ‐ Critical |
| |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 39 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
ALARM RELAY CONFIGURATION SCREENS
The Alarm Relay Configuration Screens (C9, Ca, Cb, Cc, Cd, and Ce) are used to
determine which alarm relay should operate in the event of a specific alarm
condition generated by the controller.
Two Alarm Relay outputs are provided, the General Alarm Relay, NO4 and the
Critical Alarm Relay, NO5. Each Alarm can be configured to trigger either the
Critical Alarm Relay, the General Alarm Relay, both Relays or none.
- 40 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Enable pLAN Cf|
|Display Jump To |
|Unit In Alarm No |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Unit Location Cg|
|Ireland Or UK |
|Reset Parameters |
|To Default No |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Reset Alarm Ch|
|History No |
| |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|Change Passwords Ci|
|Maintenance 0000|
|User 0000|
|Manufacturer 0000|
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 41 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
Description Default
ENABLE PLAN DISPLAY TO JUMP TO UNIT IN ALARM SCREEN Cf
This Screen forces the shared Display/Keypad to automatically switch to any unit on Y
the network with an active Alarm.
This screen resets all unit parameters to their Factory Default Values. Two sets of
Defaults are available – select the relevant location.
- 42 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:001 U:00|
| Refrigerant |
|Pressure Sensor (B1)|
| Failure |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:002 U:00|
| Return Air |
| Hum. Sensor (B2) |
| Failure |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:003 U:00|
| Return Air |
| Temp. Sensor (B3) |
| Failure |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
al_4
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:004 U:00|
| Outside Air |
| Temp. Sensor (B4) |
| Failure |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
al_5
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:005 U:00|
| Airflow |
| Alarm |
| (ID1) |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 43 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:006 U:00|
| Filter |
| Alarm |
| (ID2) |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:007 U:00|
| HP Switch |
| Trip |
| (ID3) |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:008 U:00|
| LP Switch |
| Trip |
| (ID4) |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:009 U:00|
| High Return |
| Temperature |
| Alarm |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:010 U:00|
| Low Return |
| Temperature |
| Alarm |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:011 U:00|
| Maintenance Alarm |
| Fan Run Hours |
| Exceeded |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:012 U:00|
| Maintenance Alarm |
| Heater |
| Run Hours Exceeded |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 44 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Microprocessor Controller
Operations Manual
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:013 U:00|
| Maintenance Alarm |
| Compressor |
| Run Hours Exceeded |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:014 U:00|
| Maintenance Alarm |
| Condenser Fan |
| Run Hours Exceeded |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:015 U:00|
| Cool Fail |
| Alarm |
| |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
|AL:016 U:00|
| Unit 1 |
| Offline |
| Check Network |
+‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐+
- 45 -
TC Controller Manual Ref:
XSDAQSBBSHB6- 0907 – Rev1
Link House, 62 Clontarf Road, Clontarf, Dublin 3, Ireland.
Tel: +353-1-8335043 Fax: +353-1-8335283