You are on page 1of 6

Flow senor - Installation Basics

TM/BUAP/FS/SCHO
1
12/2012
Flow sensors – Mounting vs rest areas

5 x di 3 x di

3 x di

< 8 x di
5 x di
5 x di

flow direction
Positioning ok
3 x di Positioning not ok

TM/BUAP/FS/SCHO
2
12/2012
Flow sensors – Mounting areas in vertical pipes

flow direction

Rising pipe EVER


Downpipe NEVER

TM/BUAP/FS/SCHO
3
12/2012
Flow sensors – Mounting areas in non homogene media

The sensor cone end


• must be compeltely dipped into the medium
Air cushion
• should be located as close as possible to the middle of
Deposit the flow channel
Recommended positioning area • should not abut against the opposite tube wall

TM/BUAP/FS/SCHO
4
12/2012
Flow sensors – Flow velocity profile vs immersion length

laminar flow

turbulent flow

Recommended positioning area


Recommended immersion length

TM/BUAP/FS/SCHO
5
12/2012
Flow sensors – Flow temperature profile

Highest temperature
Lowest temperature

Is the medium temperature above the ambient temperature, it’ll come to a temperature
gradient to the tube edges.

TM/BUAP/FS/SCHO
6
12/2012

You might also like