NOTES FOR VENDORS

Temperature Gauges
Local indication of temperature shall be by bi-metallic, gas or liquid filled dial thermometers calibrated in °C.
Dials shall be 150 mm in diameter or Manufacturer / Supplier’s nearest standard and shall have black numerals on a white bac
standard.
Negative temperatures shall be red numerals on a white background.
Connection between the gauge and thermowell shall be by ½” NPT adjustable unions.
Mercury in steel thermometers for local indication shall not be used.
Bi-metallic dial thermometers shall be weatherproof, hermitically sealed and every angle, with external pointer adjustment. St
shall be Manufacturer/Supplier’s standard.
Materials shall be corrosion resistant suitable for the environment.
Bi-metallic thermometers shall only be used where errors in excess of one percent of span are acceptable.
Temperature Gauge process connections should be ½” Screwed connection.