Professional Documents
Culture Documents
Thermostatic Expansion Valves CAP. 1
Thermostatic Expansion Valves CAP. 1
EXPANSION VALVES
Ed. 2017
EXPANSION VALVES
VE-ED 01/2017 - ENG 1
CHAPTER 1
THERMOSTATIC EXPANSION VALVES
FOR REFRIGERATION PLANTS THAT USE HCFC OR HFC REFRIGERANTS
EXPANSION VALVES
6 VE-ED 01/2017 - ENG
This part can be ordered separately as repair kit, too. is the evaporating pressure at which the expansion valve
The main parts of body assembly are made with the will throttle liquid injection into the evaporator, preventing
following materials: the evaporating pressure from rising. The expansion valve
• Stainless steel for bulb, capillary tubing, diaphragm acts as superheating control in the normal working range
casing, diaphragm and rod and acts as a pressure regulator within MOP range.
• Hot forged brass EN 12420 – CW 617N for the body The MOP point will change if the factory superheating
• Brass EN 12164 – CW 614N for superheating set screw setting of the expansion valve is changed. Superheating
and spring holder adjustments influence the MOP point as follows:
• Steel DIN 17223-1 for spring • Increase superheating → Decrease MOP
• Copper pipe EN 12735-1 – Cu-DHP for solder • Decrease superheating → Increase MOP
connections
Superheating: this is the controlling parameter for
Orifice assembly: interchangeable orifice assembly the expansion valve. Superheating, measured at the
provides a wide capacity range, from 0.5 to 15.5 kW evaporator outlet, is defined as the difference between the
(nominal capacity with R22). The external cartridge actual bulb temperature and the evaporating temperature,
contains the following elements: housing, shutter deduced from evaporator pressure. In order to prevent
(metering device), seat, spring and filter. The solid liquid refrigerant from entering the compressor, a certain
construction of the orifice assembly and its internal minimum superheating value must be maintained. In
components ensure that shutter and seat can withstand all expansion valve operation, the following terms are used:
types of critical stresses (hammering, cavitation, sudden • Static superheating: this is the superheating above
pressure variations at temperature, or contaminants). The which the valve begins to open. Castel thermostatic
spring holds the shutter firmly in contact with the seat expansion valves are factory pre-set to the following
to minimize leakage through the valve. To guarantee static superheating values:
complete shut-off, a solenoid valve is required upstream • 5 °C for Castel valves without MOP
from the thermostatic expansion valve. Orifice assemblies • 5 °C for Castel valves with MOP
are available in these two solutions: Under nominal operating conditions (see Table 2)
• With conical flanged filter, for valves with SAE Flare • Opening superheating: this is the superheating, above
threaded connections. the static superheating, required to produce a given
• With flat flanged filter, for valves with ODS solder valve potential
connections, to use with adapters in series 2271. • Operating superheating: this is the sum of static and
Orifice assembly filters can be cleaned or replaced. In the opening superheating
event of replacement, the following two types of filters are
available for separate order: Subcooling: this is defined as the difference between
• Filter 2290, for valves with SAE Flare threaded the condensing temperature (deduced from condensing
connections. pressure) and the actual temperature at inlet valve.
• Filter 2290/S, for valves with ODS solder connections. Subcooling generally increases the refrigeration system
potential and must be accounted for when dimensioning an
expansion valve. Depending on system design, subcooling
THERMOSTATIC CHARGES may be necessary to prevent gas bubbles from forming
Liquid charge: ithe behaviour of valves with liquid charge
in the liquid line. If gas bubbles form in the liquid line, the
is exclusively determined by the temperature changes at
potential of the expansion valve will be reduced significantly.
the bulb and they are not subject to any environmental
All potential tables, provided in this chapter, are calculated
interference. They feature fast response time, reacting
for a subcooling value of 4 °C. If the actual subcooling value
quickly in the control circuit. Castel thermostatic
is higher than 4 °C, the valve potential is taken from the
expansion valves with liquid charge cannot incorporate
evaporator demand divided by the correction factor shown
MOP functions.
in the tables below each potential table.
Gas charge: the behaviour of valves with gas charge will
be determined by the lowest temperature at any part of SELECTION
the expansion valve (thermostatic element, capillary tube To dimension a thermostatic expansion valve for a
or bulb). If any parts other than the bulb are subjected refrigerating system correctly, the following design
to the lowest temperature, the malfunctioning of the parameters must be available:
expansion valve can occur (charge migration). Castel • Type of refrigerant
thermostatic expansion valves with gas charge always • Evaporator capacity, Qe
feature MOP function and include ballast bulb. The ballast • Evaporating temperature/pressure, Te / pe
has a damping effect on the valve regulation and leads to • Minimum condensing temperature/pressure, Tc / pc
slow opening and fast closure of the valve. • Liquid refrigerant temperature at valve inlet, Tl
• Pressure drop in the liquid line, distributor and
MOP (Maximum Operating Pressure): this function evaporator, Δp
limits the evaporator pressure to a maximum value to
protect the compressor from the overload condition. MOP The following procedure helps the correct dimensioning of
EXPANSION VALVES
VE-ED 01/2017 - ENG 7
an expansion valve for a refrigeration plant. DIMENSIONING EXAMPLE
• Type of refrigerant R134a
Step 1 • Evaporator capacity, Qe 6 kW
Determine the pressure drop across the valve. The • Evaporating temperature, Te - 10 °C
pressure drop is calculated using the equation: • Minimum condensing temperature, Tc + 30 °C
• Liquid refrigerant temperature, Tl + 20 °C
• Pressure drop in the liquid line, distributor
and evaporator, Δp 1.5 bar
where:
• Pc = condensing pressure Step 1 - Determine the pressure drop across the valve.
• Pe = evaporating pressure
• Δp = sum of pressure drops in the liquid line, • Condensing pressure at + 30 °C - Pc = 6.71 bar
distributor and evaporator • Evaporating pressure at – 10 °C - Pe = 1.01 bar
EXPANSION VALVES
8 VE-ED 01/2017 - ENG
EXPANSION VALVES
VE-ED 01/2017 - ENG 9
TABLE 1: General caracteristics of body assemblies of liquid charge thermostatic expansion valves
Max Risk
Catalogue Number Connections Category
Evaporating bulb TS [°C] TA [°C]
PS accord-
Refrigerant Temperature MOP tem-
SAE Flare ODS [mm] ODS [in] [bar] ing to
internal external Range [°C] perature PED
equalizer equalizer IN OUT Equal. OUT Equal. OUT Equal. [°C] min max min max Recast
2210/4 1/2" - - -
2210/M12S - - 12 - -
2210/4S - - 1/2" - R22
3/8"
2210/4E 1/2" 1/4" - - R407C
- 2210/M12SE - 12 6 -
2210/4SE - - 1/2" 1/4"
2220/4 1/2" - - -
2220/M12S - - 12 - -
2220/4S - - 1/2" -
3/8" R134a - 40 → + 10
2220/4E 1/2" 1/4" - -
- 2220/M12SE - 12 6 -
2220/4SE - - 1/2" 1/4" 100
without 34 - 60 + 120 - 40 + 50 Art. 4.3
2230/4 1/2" - - - (1)
2230/M12S - - 12 - -
2230/4S - - 1/2" -
3/8"
2230/4E 1/2" 1/4" - -
- 2230/M12SE - 12 6 -
2230/4SE - - 1/2" 1/4" R404A
2239/4 1/2" - - - R507A
2239/M12S - - 12 - -
2239/4S - - 1/2" -
- 60 → -25
2239/4E 1/2" 1/4" - -
- 2239/M12SE - 12 6 -
2239/4SE - - 1/2" 1/4"
(1) : when valve is installed. 60 °C with element not mounted
TABLE 2: General caracteristics of body assemblies of MOP charge thermostatic expansion valves
Max Risk
Catalogue Number Connections Category
Evaporating bulb TS [°C] TA [°C]
PS accord-
Refrigerant Temperature MOP tem-
SAE Flare ODS [mm] ODS [in] [bar] ing to
internal external Range [°C] perature PED
equalizer equalizer IN OUT Equal. OUT Equal. OUT Equal. [°C] min max min max Recast
2211/4 1/2" - - -
2211/M12S - - 12 - -
2211/4S - - 1/2" - + 15
R22
3/8" °C
2211/4E 1/2" 1/4" - - R407C
(95 psi)
- 2211/M12SE - 12 6 -
2211/4SE - - 1/2" 1/4"
2221/4 1/2" - - -
2221/M12S - - 12 - -
2221/4S - - 1/2" - + 15
3/8" R134a - 40 → + 10 °C
2221/4E 1/2" 1/4" - - (55 psi)
- 2221/M12SE - 12 6 -
2221/4SE - - 1/2" 1/4" 100
34 - 60 + 120 - 40 + 50 Art. 4.3
2231/4 1/2" - - - (1)
2231/M12S - - 12 - - + 15
2231/4S - - 1/2" - °C
2231/4E 1/2" 1/4" - - (120
- 2231/M12SE - 12 6 - psi)
2231/4SE - - 1/2" 1/4" R404A
3/8"
2234/4 1/2" - - - R507A
2234/M12S - - 12 - -
2234/4S - - 1/2" - - 20 °C
- 60 → -25
2234/4E 1/2" 1/4" - - (30 psi)
- 2234/M12SE - 12 6 -
2234/4SE - - 1/2" 1/4"
(1) : when valve is installed. 60 °C with element not mounted
EXPANSION VALVES
10 VE-ED 01/2017 - ENG
TABLE 3: Orifice Assemblies - Rated Capacities in kW
Catalogue Number Evaporating Temperature Range [°C]
- 40 → + 10 - 60 → - 25
Valves with SAE Flare Valves with ODS con-
connections nections R22 R404A R404A
R134a
R407C R507A R507
2271/M6S - 6
2271/2S 1/4" -
2271/3S 3/8" -
2271/M10S - 10
EXPANSION VALVES
VE-ED 01/2017 - ENG 11
Table 5A: Refrigerant R22/R407C - Capacities in kW for temperature range - 40°C → + 10°C
Orifice Pressure drop across valve [bar] Orifice Pressure drop across valve [bar]
code 2 4 6 8 10 12 14 16 code 2 4 6 8 10 12 14 16
EXPANSION VALVES
12 VE-ED 01/2017 - ENG
Table 6A: Refrigerant R134a - Capacities in kW for temperature range - 40°C → + 10°C
Pressure drop across valve [bar] Pressure drop across valve [bar]
Orifice code Orifice code
2 4 6 8 10 2 4 6 8 10
EXPANSION VALVES
VE-ED 01/2017 - ENG 13
Table 7A: Refrigerant R404A/R507A - Capacities in kW for temperature range - 40°C → + 10°C
Orifice Pressure drop across valve [bar] Orifice Pressure drop across valve [bar]
code 2 4 6 8 10 12 14 16 code 2 4 6 8 10 12 14 16
EXPANSION VALVES
14 VE-ED 01/2017 - ENG
Table 8A: Refrigerant R404A/R507A - Capacities in kW for temperature range - 60°C → - 25°C
Orifice Pressure drop across valve [bar] Orifice Pressure drop across valve [bar]
code 2 4 6 8 10 12 14 16 code 2 4 6 8 10 12 14 16
EXPANSION VALVES
VE-ED 01/2017 - ENG 15
www.castel.it
Castel can accept no responsibility for any errors or changes in the catalogues, handbooks, brochures and
other printed material. Castel reserves the right to make changes and improvements to its products without
notice. All trademarks mentioned are the property of their respective owners.
The name and Castel logotype are registered trademarks of Castel Srl.
All rights reserved.
EXPANSION VALVES
ed.
100001-VE-ENG Castel Srl - Via Provinciale 2-4 - 20060 Pessano con Bornago - MI VE-ED 01/2017 - ENG