Advanced Refrigeration University of Baghdad College of Engineering Mechanical Engineering Department PhD Program / (Thermo -fluids) field
Assessment By Dr. Issam Mohammed
By Maha Hasan Objects
• Expansion devices
• THERMOSTATIC EXPANSION VALVES
• The duty varies with pressure difference
• Electronic expansion valve
• Capillary tubes and restrictor
Expansion devices
Expansion devices in general use are the
:following 1. Capillary tubes, for small hermetic systems. These are factory selected and cannot be adjusted. 2. Solenoid valves with liquid level sensors or liquid level valves for flooded evaporators.
3. High-pressure float valves plus handset
throttle valves for some flooded and low- pressure receiver circuits.
4. Thermostatic expansion valves or
electronic expansion valves for direct expansion circuits. THERMOSTATIC EXPANSION VALVES
Direct expansion circuits must
be designed and installed so that there is no risk of liquid refrigerant returning to the compressor. To ensure this state, heat exchange surface in the evaporator is used to heat the dry saturated gas so that it becomes superheated. The amount of superheat is usually of the order of 5 K. Thermostatic expansion valves (TEVs) for such circuits embody a mechanism which will detect the superheat of the gas leaving the evaporator. Refrigerant boils in the evaporator at Te and pe , until it is all vapour, point A and then superheats to a condition Ts , pe , at which it passes to the suction line, point B. A separate container of the same refrigerant at temperature Ts would have pressure ps , and the difference ps − pe represented by C–B in is a signal directly related to the amount of superheat. The basic thermostatic expansion valve has a detector and power element, charged with the same refrigerant as in the circuit. The pressure ps generated in the phial by the superheated gas equalizes through the capillary tube to the top of the diaphragm. An adjustable spring provides the balance of ps − pe at the diaphragm, and the valve stem is attached at the center. Should the superheat fall for any reason, there will be a risk of liquid reaching the compressor. Superheat sensor on direct expansion circuit Ts will decrease with a corresponding drop in ps . The forces on the diaphragm are now out of balance and the spring will start to close the valve. Conversely if the load on the evaporator increases, refrigerant will evaporate earlier and there will be more superheat at the phial position. Then ps will increase and open the valve wider to meet the new demand. It is usual to select a thermostatic expansion valve for the maximum duty and at the summer condensing condition, taking into account the pressure
The duty varies with pressure difference
It might be thought that the duty varies with pressure difference according to fluid flow laws, but this will not be the case because phase change occurs as the pressure falls. This means that the valve may be able to pass more liquid at low condensing pressures. Conversely, if the valve is selected at a lower pressure difference (possibly corresponding to a condensing condition in the United Kingdom of 20–25°C), the valve will not be grossly oversized at the maximum summer condition. Although no standards exist for valve rating conditions it is conventional to state a nominal capacity at 38°C condensing, 4°C evaporating with 1 K sub-cooling and 3–4 K superheat A greater difficulty arises where the compressor may go down to 33 or 25% capacity and the thermostatic expansion valve is called upon to control a much reduced flow. Under such conditions, the thermostatic expansion valve may be unstable and ‘hunt’, with slight loss of evaporator efficiency. Since the required duty is less, this may appear to be of no great importance but should avoided. It is possible to fit two expansion valves in parallel and isolate one at part load, but this arrangement is not usually necessary. Low condensing-pressure operation should present no problem with float or electronic expansion valves, since these can open to pass the required flow of liquid if correctly sized. Electronic expansion valve
The electronic expansion valve offers a finer degree of control and
system protection. The benefits can be summarized as follows: 1. Precise flow control over a wide range of capacities. 2. Rapid response to load changes. 3. Better control at low superheats so that less evaporator surface is required for superheat. More surface for evaporation results in higher evaporating temperature and better efficiency. 4. Electrical connection between components offers greater flexibility in system layout, which is important for compact systems. 5. The valve can close when the system shuts down, which eliminates the need for an additional shut off solenoid valve Electronic expansion valve Capillary tubes and restrictions
The variable orifice of the expansion valve can be replaced, in small
systems, by a long thin tube. This is a non-modulating device and has certain limitations, but will give reasonably effective control over a wide range of conditions if correctly selected and applied. Mass flow is a function of pressure difference and the degree of liquid subcooling on entry. The capillary tube is used almost exclusively in small air conditioning systems and is self-regulating within certain parameters. Increasing ambient temperature results in increasing load on the conditioned space and the condensing pressure will rise, forcing more refrigerant flow. Tube bores of 0.8–2 mm with lengths of 1–4 m are common. The capillary tube is only fitted on factory-built and tested equipment, with exact refrigerant charges. It is not applicable to field-installed systems. Thank You