Series TY-B, 5.6 K-factor


Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
General NOTICE
The Series TY-B Sprinklers described
Description herein must be installed and main-
tained in compliance with this docu-
The TYCO Series TY-B, 5.6 K-factor, ment, as well as with the applicable
Upright (TY315) and Pendent (TY325) standards of the National Fire Protec-
Sprinklers described in this data sheet tion Association, in addition to the stan-
are standard response, standard cov- dards of any other authorities having
erage, decorative 5 mm glass bulb jurisdiction. Failure to do so may impair
type spray sprinklers designed for use the performance of these devices.
in light, ordinary, or extra hazard, com-
mercial occupancies such as banks, The owner is responsible for main-
hotels, shopping malls, factories, refin- taining their fire protection system
eries, and chemical plants. and devices in proper operating con-
dition. Contact the installing contrac-
The recessed version of the Series tor or product manufacturer with any
TY-B Pendent Sprinkler, where applica- questions.
ble, is intended for use in areas with a
finished ceiling. This recessed pendent
sprinkler uses one of the following: Sprinkler
• A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
Identification
ment up to 5/8 in. (15,9 mm) from the
flush pendent position.
Numbers (SINs)
TY315 ������� Upright 5.6K, 1/2 in. NPT
• A two-piece Style 20 Recessed TY325 ������Pendent 5.6K, 1/2 in. NPT
Escutcheon with recessed adjust-
ment up to 1/2 in. (12,7 mm) from the
flush pendent position. Technical
The adjustment provided by the
Recessed Escutcheon reduces the
Data Operation
accuracy to which the fixed pipe drops Approvals The glass bulb contains a fluid which
to the sprinklers must be cut. Refer to Table A expands when exposed to heat. When
Intermediate level versions of Series Maximum Working Pressure the rated temperature is reached, the
TY-B Sprinklers are described in Tech- 175 psi (12.1 bar) fluid expands sufficiently to shatter the
nical Data Sheet TFP352. Sprinkler 250 psi (17.2 bar)* glass bulb, allowing the sprinkler to
guards and shields are described in * The maximum working pressure of 250 psi (17.2 bar)
activate and water to flow.
Technical Data Sheet TFP780. only applies to the listing by Underwriters Laborato-
ries, Inc. (UL).

Discharge Coefficient
Design
K = 5.6 GPM/psi½ (80,6 LPM/bar½) Criteria
IMPORTANT Temperature Ratings The TYCO Series TY-B, 5.6 K-factor,
Refer to Technical Data Sheet Refer to Table A Upright (TY315) and Pendent (TY325)
TFP2300 for warnings pertaining to Finishes Sprinklers are intended for fire protec-
regulatory and health information. Sprinkler: Refer to Table B tion systems designed in accordance
Always refer to Technical Data with the standard installation rules
Recessed Escutcheon: White Coated,
Sheet TFP700 for the “INSTALLER Black Coated, Chrome Plated, or Brass
recognized by the applicable Listing
WARNING” that provides cautions Plated or Approval agency (e.g., UL Listing
with respect to handling and instal- is based on the requirements of NFPA
lation of sprinkler systems and com- Physical Characteristics 13, and FM Approval is based on the
Frame �������������������������������������������������������Bronze requirements of the FM Loss Preven-
ponents. Improper handling and Button ������������������������������������������� Brass/Copper
installation can permanently damage tion Data Sheets). Only the Style 15
Sealing Assembly . . . Stainless Steel w/TEFLON
a sprinkler system or its compo- Bulb ������������������������������������������������������������� Glass
or Style 20 Recessed Escutcheon, as
nents and cause the sprinkler to fail Compression Screw ���������������������������������Bronze applicable, is to be used for recessed
to operate in a fire situation or cause Deflector ���������������������������������������������������Bronze pendent installations.
it to operate prematurely.

Page 1 of 4 AUGUST 2018 TFP152


TFP152
Page 2 of 4

Components:
1 - Frame 4 - Bulb
* Temperature rating is ** Pipe thread connections per ISO 7-1
indicated on Deflector. can be provided on special request.
2 - Button 5 - Compression STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16" (11,1 mm) RECESSED
Assembly 6 - Deflector * DEFLECTOR * SEATING SURFACE NPT ** NOMINAL MAKE-IN ESCUTCHEON
6*

5 7/16"
(11,1 mm)
4 NOMINAL 2"
MAKE-IN (50,8 mm)
2 2" 1-3/8"
(50,8 mm) (34,9 mm)
3 WRENCH
FLATS
1
1/2" NPT** DEFLECTOR * 2-7/8" (73,0 mm) DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-B UPRIGHT (TY315) AND PENDENT (TY325) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE

Installation Step 2. With pipe-thread sealant


applied to the pipe threads, hand-
The TYCO Series TY-B, 5.6 K-factor, tighten the sprinkler into the sprinkler
Upright (TY315) and Pendent (TY325) fitting.
WRENCH RECESS
(USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the
END "A") dance with this section. sprinkler fitting using only the W-Type
General Instructions 6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
FIGURE 2 Do not install any bulb type sprinkler
Sprinkler Wrench to the wrench flats.
W-TYPE 6 if the bulb is cracked or there is a loss
Torque sprinklers 7 to 14 lb-ft (9,5 to
SPRINKLER WRENCH of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble 19,0 N·m).
should be present. The diameter of the Recessed Pendent Sprinklers
WRENCH air bubble is approximately 1/16 in. The Series TY-B Recessed Pendent
RECESS (1,6 mm) for the 135°F (57°C) to 3/32 in. Sprinklers must be installed in accor-
(2,4 mm) for the 360°F (182°C) tempera- dance with the following instructions.
ture ratings.
Step A. After installing the Style 15 or
A leak-tight 1/2 in. NPT sprinkler joint Style 20 Mounting Plate, as applica-
should be obtained by applying a min- ble, over the sprinkler threads and with
imum-to-maximum torque of 7 to 14 pipe-thread sealant applied to the pipe
lb-ft (9,5 to 19,0 N·m). Higher levels of threads, hand-tighten the sprinkler into
torque may distort the sprinkler inlet the sprinkler fitting.
and cause leakage or impairment of
PUSH WRENCH the sprinkler. Step B. Tighten the sprinkler into the
IN TO ENSURE sprinkler fitting using only the W-Type
ENGAGEMENT
Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure
WITH SPRINKLER
insufficient adjustment in the escutch- 3). With reference to Figure 1, apply the
WRENCHING AREA
eon plate by under- or over-tightening W-Type 7 Recessed Sprinkler Wrench
the sprinkler. Readjust the position of to the sprinkler wrench flats. Torque
FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft (9,5 to 19,0 N·m).
W-TYPE 7 RECESSED
SPRINKLER WRENCH Upright and Pendent Sprinklers Step C. After the ceiling is installed or
The Series TY-B Upright and Pendent the finish coat is applied, slide on the
Sprinklers must be installed in accor- Style 15 or Style 20 Closure over the
dance with the following instructions. Series TY-B Sprinkler and push the
Step 1. Install pendent sprinklers in the Closure over the Mounting Plate until
pendent position; install upright sprin- its flange contacts the ceiling.
klers in the upright position.
TFP152
Page 3 of 4

Care and 2-7/8" DIA.


(73,0 mm)
Maintenance 2-1/4" DIA.
The TYCO Series TY-B, 5.6 K-factor, FACE OF (57,2 mm)
Upright (TY315) and Pendent (TY325) SPRINKLER
Sprinklers must be maintained and ser- FITTING 5/8" (15,9 mm)
viced in accordance with this section. FLUSH
Before closing a fire protection system 3/8±5/16"
main control valve for maintenance (9,5±7,9 mm)
work on the fire protection system
that it controls, obtain permission to 1/8"
shut down the affected fire protection MOUNTING
SURFACE (3,2 mm)
system from the proper authorities
and notify all personnel who may be 1-3/8" (34,9 mm)
CLOSURE SERIES MOUNTING
affected by this action.
TY-B PLATE 3/4" (19,1 mm)
Absence of the outer piece of an
escutcheon, which is used to cover FIGURE 4
a clearance hole, can delay sprinkler SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY (TY325)
operation in a fire situation. WITH TWO-PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only 2-7/8" DIA.
cleaned by means of gently dusting (73,0 mm)
with a feather duster; otherwise, non- FACE OF
operation in the event of a fire or inad- SPRINKLER 2-1/4" DIA.
vertent operation may result. FITTING (57,2 mm)

Sprinklers which are found to be 5/16±1/4"


leaking or exhibiting visible signs of 1/2" (12,7 mm)
(7,9±6,4 mm)
corrosion must be replaced. FLUSH
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced. MOUNTING 1/8"
Sprinklers that have been exposed to SURFACE (3,2 mm)
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
by wiping the sprinkler with a cloth or TY-B PLATE 7/8" (22,2 mm)
by brushing it with a soft bristle brush. FIGURE 5
Care must be exercised to avoid SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY (TY325)
damage to the sprinklers before, WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
during, and after installation. Sprin- RECESSED ESCUTCHEON
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must Automatic sprinklers are recommended Sprinkler Assemblies with NPT
be replaced. Also, replace any sprin- to be inspected, tested, and maintained Thread Connections
kler that has a cracked bulb or that has by a qualified Inspection Service in Specify: Series TY-B Upright or
lost liquid from its bulb. (Ref. Installa- accordance with local requirements Pendent (specify) Sprinkler, SIN
tion Section.) and/or national codes. (specify), K=5.6, Standard Response,
Thereafter, annual inspections per (specify) temperature rating, (specify)
NFPA 25 are required; however, instead
of inspecting from the floor level, a
Limited finish, P/N (specify, refer to Table B)
Recessed Escutcheon
random sampling of close-up visual
inspections should be made.
Warranty Specify: Style 15 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
For warranty terms and conditions, visit
The owner is responsible for the www.tyco-fire.com. Specify: Style 20 Recessed Escutch-
inspection, testing, and maintenance of eon with (specify*) finish, P/N (specify*)
their fire protection system and devices
in compliance with this document, as Ordering * Refer to Technical Data Sheet TFP770

well as with the applicable standards


of the National Fire Protection Asso- Procedure Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
ciation (e.g., NFPA 25), in addition to P/N 56-000-6-387
Contact your local distributor for avail-
the standards of any other authorities
ability. When placing an order, indicate Specify: W-Type 7 Sprinkler Wrench,
having jurisdiction. Contact the install-
the full product name and Part Number P/N 56-850-4-001
ing contractor or product manufacturer
(P/N).
with any questions.
TFP152
Page 4 of 4

SPRINKLER FINISH (7)


BULB
SPRINKLER TEMPERATURE
K LIQUID
TYPE RATING NATURAL CHROME
COLOR POLYESTER**
BRASS PLATED

135°F (57°C) Orange


UPRIGHT 155°F (68°C) Red
(TY315)
and 175°F (79°C) Yellow
1, 2, 3, 4, 5, 6,
PENDENT 200°F (93°C) Green
(TY325)
Figure 1 286°F (141°C) Blue
5.6
1/2 in. 360°F (182°C) Mauve
NPT
135°F (57°C) Orange
RECESSED 155°F (68°C) Red
PENDENT 1, 2, 3, 4,
175°F (79°C) Yellow
(TY325)*
Figures 4 and 5 200°F (93°C) Green
286°F (141°C) Blue 1, 2
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL)
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL)
3. Approved by FM Global (FM Approvals)
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/03)
5. VdS Approved (For details contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444 / Fax 31-53-428-3377)
6. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05)
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
* Installed with Style 15 (1/2 in. NPT) 5/8 in. Total Adjustment Recessed Escutcheon, as applicable
** Frame and deflector only
N/A – Not Applicable
TABLE A
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
LABORATORY LISTINGS AND APPROVALS

P/N* 77 – XXX – X – XXX

SPRINKLER TEMPERATURE
SIN FINISH RATINGS

570 5.6K UPRIGHT (1/2 in. NPT) TY315 1 NATURAL BRASS 135 135°F (57°C)

PURE WHITE (RAL9010)**


571 5.6K PENDENT (1/2 in. NPT) TY325 3 155 155°F (68°C)
POLYESTER
SIGNAL WHITE (RAL9003)
4 175 175°F (79°C)
POLYESTER
JET BLACK (RAL9005)
5 200 200°F (93°C)
POLYSTER

9 CHROME PLATED 286 286°F (141°C)

360 360°F (182°C)


* Use suffix “I” for ISO 7-1 connection; for example, 77-570-4-175-I
** Eastern Hemisphere sales only 000 OPEN***
*** OPEN indicates sprinkler assembly without Glass Bulb, Button, and Sealing Assembly

TABLE B
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;