Professional Documents
Culture Documents
Abstract - This paper considers the measurement and transformer (HFCT) sensors attached to the cable earths
propagation of partial discharge pulses on distribution class allow the circuits to be tested without de-energisation,
power cable circuits, with the idea of attempting to determine whilst the circuit experiences normal operational stresses
discharge location sites on cables based on the parameters of and loads. Fig. 1 shows a typical temporary HFCT sensor
individual pulses. Single-ended discharge location techniques
attachment for measuring any PD pulses present within the
based on partial discharge pulse parameters and shape will
cable sheath as a result of PD activity between phases and
not be as accurate as time-domain reflectometry methods but
can be done on-line without the need for double-ended earth.
techniques. Power cables used for the transmission of 50/60
Hertz electrical power, are by design not intended to carry
transients or partial discharge pulses. The geometry and
construction of such power cables present a transmission line
that can heavily attenuate and distort the partial discharge
pulses, making their detection and discrimination all the
more difficult. Experimental and field work has been carried
out to develop basic knowledge rules to describe how the
time-domain parameters of individual pulses alter as a
function of the distance propagated from the discharge sites
for medium voltage power cables.
978-1-4799-3254-2/13/$31.00 ©IEEE
locations and the end of the cable can often be observed as dependent upon the derivative of the angular frequency
a partial pulse reflection [4]. Although the TDR method is and the wavenumber given in (2).
typically accurate to within one per cent of the cable length
[5], the technique requires the setting up of the trigger unit 2
and the transponder. More importantly the pulse must be
observable at the cable far end. Fig. 2 below shows the
typical arrangement for an on-line TDR test with the From (2) it can be deduced that is not equal to a
trigger unit, the transponder and HFCT sensors for pulse constant, and is in fact a function of frequency, which
detection and injection. results in distortion of the pulse shape with distance
propagated. Each frequency component within the pulse
travels at its own velocity, hence the higher frequencies
move away from the front of the pulse and the peak,
resulting in pulse attenuation and broadening. The second-
order differential equations, known as the telegraph
equations allow for dispersive, travelling wave solutions.
These describe how pulses are distorted on power cables
and general transmission lines and are derived from
Maxwell’s equations. These relate the dielectric properties
of a waveguide to the distortion seen by a pulse at some
distance, see [6] for further details. Pulse magnitude
attenuation, and broadening are described by the real, and
imaginary parts of the frequency-dependent propagation
constant γ(ω) which appears in the exponent of the transfer
function H(ω) associated with pulses measured at distances
l and x, given in (3)
TABBLE I
VELOCITY OF PROPA
AGATION CONSTANTS
lit
Volts (mV)
5
0
ud
-5
-10 cable, using the pulse width as a locating parameter may
-15
e -20
prove more accurate as it appears to show more stable
-25
( 5
Time (µs)
6 7
results as a function of distance. Work on XLPE cables has
shown encouraging results, where PD locations can work
Fig. 12 Partial discharge pulse as measured at HV connector 1, 250 providing the propagation parameters can be estimated for
metres from the PD Location – PD 1 each cable type.