R4140G

Flame Safeguard Programming Controls


PRODUCT DATA
• R7247C or R7476A Dynamic Self-Check Amplifier,
when used with an ultraviolet flame detector with a
self-checking shutter (R7247C with a C7012E or F;
R7476A with a C7076), tests all electronic components
in the flame detection system (amplifier and detector)
60 to 240 times a minute during burner operation and
shuts down the burner if the detection system fails.
• R7247B Dynamic Self-Check Amplifier, when used with
a rectifying flame rod (which is considered fail-safe),
or R7248B Dynamic Ampli-Check Amplifier, when used
with a C7015A Infrared (lead sulfide) Flame Detector,
tests the flame signal amplifier at least 150 times a
minute during burner operation and shuts down the
burner if the amplifier fails.
• All models feature capability of proving low fire position
of the firing rate motor before starting ignition trials.
• Provisions for connecting preignition or start
interlocks (depending on model) to prove the proper
conditions for startup, and for a combustion airflow
switch to prove airflow throughout the operating cycle.
• All models have 4-wire firing rate switching circuitry—
firing rate can be modulated while the burner is firing,
and the firing rate motor can be driven to both low and
high fire positions during prepurge.
APPLICATION • Safe start check at startup and during prepurge. If
flame relay 2K is holding in at startup, the programmer
The R4140G Flame Safeguard Programmers provide cannot be started. If a flame (or a condition simulating
flameout protection plus automatic sequencing of the burner a flame) is detected during prepurge, ignition trials
motor (blower), firing rate motor, ignition, pilot valve, and main cannot be started and the programmer recycles.
fuel valve(s) for commercial and industrial burners using gas, • Safety shutdown occurs on failure to ignite the pilot or
oil, coal, or a combination of fuels. main burner, on loss of flame during the Run period,
or if the flame detection system fails (if a self-checking
system is used).
• All relays are visible, labeled, and easily accessible.
FEATURES • Alarm terminal is available to operate an external, line
voltage alarm on safety shutdown.
• Approvals: Underwriters Laboratories Inc. listed or
component recognized, Canadian Standards
Association certified, and Factory Mutual approved for
automatic fired burners.
• The R4140 directly replaces the R4150 for most
applications and mounts on the same Q520A Wiring
Subbase.
• Low-high-low purge programmers.
• Field selectable main burner flame-establishing Contents
period.
• Early spark termination (five-second ignition and five- Application .......................................................................... 1
second pilot only) available on some models. Features .............................................................................. 1
• Plug-in, solid state, flame signal amplifiers are color- Specifications ...................................................................... 2
coded and interchangeable to allow the use of any Ordering Information ........................................................... 2
type of flame detector-flame rod, photocell, infrared Operation ............................................................................ 6
detector, or ultraviolet detector. Wiring .................................................................................. 23
• Amplifier capability includes three standard models,
three Dynamic Self-Check models, and one Dynamic
Ampli-Check® model.

Copyright © 1996 Honeywell Inc. • All Rights Reserved X-XX UL 60-2337-3


R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

Interlock Circuits:
SPECIFICATIONS Start Interlocks (R4140G1049, G1056, G1064, G1114,
G1122, G1148 and G1171)—System controls must be
IMPORTANT in proper positions or programmer will not start.
The specifications given in this publication do not Preignition Interlocks (R4140G1007, G1015, and
include normal manufacturing tolerances. Therefore, G1106)—Must be closed to start programmer. Prevent
this unit may not match the listed specifications ignition trials if interlocks open during prepurge; timer
exactly. Also, this product is tested and calibrated recycles the programmer and system restarts if
under closely controlled conditions, and some minor condition is self-correcting.
differences in performance can be expected if those Running Interlocks (all models)—Must be closed (airflow
conditions are changed. must be proven, fuel pressure must not be too low or
too high) within 9.5 seconds after startup or ignition
MODELS: trials cannot be started. Running interlocks must remain
R4140G Flame Safeguard Programming Controls—Flame closed through the Run period or the automatic fuel
Safeguard protection and sequencing controls for use on gas, valves de-energize, the burner flame(s) goes out, and
oil, coal, or combination burners. See Table 1 for models the timer recycles the programmer.
available. Low Fire Interlock (all models)—Timer stops at 52 seconds
until low fire proving switch closes, indicating damper is
closed prior to ignition.
Table 1. Models Available.
Flame-Establishing
Timer Period (sec) Firing Rate
With Cycle Prepurge Early Spark Main Burner Postpurge Interlock Switching
Model Cover a (sec) (sec) Terminationb Pilotc (Field Selectable)c (sec) Circuits Circuit

R4140G1007 Yes 120 60 No 10 10 or 30 16 Preignition,


R4140G1015 No Running
R4140G1106 No 120 60 No 10 10 or 15 16 (including
Airflow
Switch) and 4-wire
Low Fire common,
R4140G1049 No 120 60 Yes 10 10 or 30 16 Start, high fire,
R4140G1056 Yes 120 60 Yes 10 10 or intermittent 16 Running low-fire,
R4140G1064 No 120 60 Yes 10 10 or intermittent 16 (including modulate)
R4140G1114 No 180 70 Yes 10 10, 30, or 60 25 Airflow
R4140G1122 No 180 70 Yes 10 10, 30 or 60 25 Switch) and
R4140G1148 No 120 60 Yes 10 10 or 15 16 Low Fire
R4140G1171 No 180 70 Yes 10 10 or 15 25
a 202050C Cover with reset button; heavy duty, metal cover for outside panel mounting.
b Early spark termination available on terminal 18 (5 second ignition and 5 second pilot only).
c If used for direct spark ignition (oil or gas), the flame-establishing period is 10 seconds.

ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number or specify order number. Order separately:
1. Flame detection system (amplifier and matching flame detector). See Table 4.
2. Q520A1089 or Q520A1121 Wiring Subbase.
3. Accessories, if desired.

If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Logistics
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.


International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

60-2337—3 2
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

Safety Features: NOTE: Allowable inrush can be up to ten times the pilot duty
Safe Start Check—For the presence of a flame (or a rating.
condition simulating a flame) provided at startup and
during prepurge. If the flame relay 2K is pulled in at EXAMPLE: Pilot duty rating = 50 VA.
startup, 2K2 is open and the programmer cannot be
started. If the flame relay 2K pulls in during prepurge At 120V, running current is:
(before 57.5 seconds), 2K2 opens, relay 1K drops out,
and ignition trials cannot be started. Instead, the timer
50
completes its revolution and stops at the standby position 120 = 0.42A.
(zero seconds). If the flame relay 2K drops out by the end
of the cycle, the programmer restarts the system.
Safety Shutdown—Ignition transformer and all automatic Maximum allowable inrush is ten times
fuel valves de-energize. The lockout switch trips and 0.42A = 4.2A.
locks out the programmer. If used, the external alarm is
energized. The timer completes its revolution and locks Interlock Ratings:
up at the stand-by position (zero seconds). The lockout See Table 3.
switch must be manually reset to restart the system.
Safety Shutdown occurs on: Table 3. Interlock Ratings.
• Failure to ignite the pilot (or first stage burner if using
direct spark ignition). Requirements must be abIe to
• Failure to light the main burner (unless monitoring Interlocks carry and break current to:
an intermittent pilot). Limits, Burner Controller, Ignition transformer, pilot valve,
• Loss of flame during the Run period. and Running Interlocks and main fuel valve(s).
• Failure in the flame detection system (if a self- (including airflow switch)
checking system is used, see Table 4).
Flame Failure Response Time—2 to 4 seconds. Start or Preignition Programmer relay 1K (5W max).
Lockout Switch Timing—30 seconds (nominal). Interlocks

Electrical Ratings:
Voltage and Frequency: 120 Vac (102V minimum to 132V Ambient Operating Temperature Ratings:
maximum), 50/60 Hz. Minimum: Minus 40°F (minus 40°C).
R4140G1114: 240 Vac, 60 Hz. Maximum:
R4140G1122: 208 Vac, 60 Hz. Programmer Mounting Position
NOTE: Use of a 50 Hz power supply lengthens the Standard Vertical (With Handle Up) Any Other
sequence timings by a factor of 1.2.
+150°F (+66°C) +135°F (+57°C)
Power Consumption (With No Loads Connected to Output Storage Temperature Ratings:
Terminals): 13W maximum. Minus 60°F to plus 150°F (minus 51°C to plus 66°C).
Maximum Total Connected Load: 2000 VA.
Mounting:
Terminal Ratings:
3-sided Q520A1089 Wiring Subbase, or 4-sided Q520A1121
See Table 2.
Wiring Subbase; both have 20 knife-blade contacts (subbase
Table 2. Terminal Ratings. ordered separately).

Maximum Rating at Dimensions:


Terminal Typical Load 120 Vac, 60 Hz See Fig. 1 and 2.
5 or 6 Ignition 4.5A ignition and 50 VA pilot duty or Weight (Without Plug-in Flame Signal Amplifier and
Transformer/Pilot 2.5A ignition and 75 VA pilot duty 202050C Cover):
Valve/First Stage 4 lb, 12 oz (2.15 kg).
Fuel Valve
7 Main Fuel Valve(s) 250 VA pilot duty or 65 VA pilot duty Flame Detection System (Ordered Separately):
(solenoid/motorized in parallel with motorized valve(s) Plug-in Flame Signal Amplifier and matching Flame Detector;
/diaphragm) and using a total of 1150 VA locked see Table 4.
Vent Valve if rotor (inrush),460 VA to open, and
required 250 VA to hold or motorized Approvals:
valve(s) using a total of 1500 VA Underwriters Laboratories Inc. Listed Section of Primary
locked rotor (inrush), 600 VA to Safety Control (120V Models With Covers): File No.
open, and 250 VA to hold MP268; Guide No. MCCZ.
Underwriters Laboratories Inc. Component Recognized
8 Burner Motor 9.8A full load, 58.8A locked rotor (120V Models Without Covers): File No. MP268; Guide
(blower) (inrush) No. MCCZ2.
9 120V Alarm 75 VA pilot duty Canadian Standards Association Certified: File No.
LR1620.
10, 11, 12, Firing Rate 50 VA pilot duty Factory Mutual Approved: Report No. 24180.
and 14 (damper) Motor
Contacts
18 Ignition 4.5A ignition
(if available) Transformer

3 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

2-3/8 (60) 2-11/32 (60) LOCKOUT SWITCH 47/64


RESET BUTTON (19)

35/64
202050C COVER (14)

2-5/64
(53)
1-51/64
7/8 (22) DIAMETER KNOCKOUT (2) (46)

13/64 (5) DIAMETER (4) 3/8 (10) (4)


(FOR MOUNTING ON
4 X 4 [102 X 102] JUNCTION BOX) 5/8 (16) (4)
6-1/2
(165)
3 5

4 L1 18 6

3-3/8 9 L2 17 7
(86)
10 12 16 8

11 G
6-5/32 13 15
(156)
F 14
7-3/16 (183)
202050C COVER
1-3/4
(45)

6
7/8 (22) DIAMETER (152)
15/16 31/32 KNOCKOUT (2)
(25) (2) 1
(24) (2)
5-7/8
1-27/32 3-3/8 (86) (149)
(47)
7 -1/16 (179)
5-5/8
7-3/16 (183) (143)

31/32
(25)
1-13/32 (36) 2-11/32 (60) 1-13/32 (36)

1-3/4 (ON Q520A1089 3-SIDED WIRING SUBBASE) M6777


(45)

3/4
(19) Fig. 2. Mounting dimensions of the R4140 Programmer
on the Q520A wiring subbase in in. (mm).
7/8 (22) DIAMETER KNOCKOUT (4)

1 OPEN ON 3-SIDED Q520A1089. M6776

Fig. 1. Mounting dimensions of the Q520A


wiring subbase in in. (mm).

60-2337—3 4
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

Accessories: R1298020 Cable; for flame detector (F lead-wire)


W136A Test Meter (includes 117053 Meter Connector installations in a high temperature environment; rated
Plug); has SPL position with damping for testing self- up to 400°F (204°C) for continuous duty; tested for
checking flame detection systems. operation up to 600V and breakdown up to 7500V.
117053 Meter Connector Plug (for older W136A models). R1239001 High Tension Ignition Cable; for ignition
123514A Flame Simulator (for use with R7247A installations in a contaminating environment; very
Rectification Amplifiers). resistant to severe conditions of oil, heat, and corona,
123514B Flame Simulator (for use with R7249A Ultraviolet and tested to withstand high voltages up to
Amplifiers). 25,000V rms in a salt bath for one minute without
139695C (Series 1 and 2) Cover with reset button; heavy breakdown; rated at 200°F (93°C) for continuous duty,
duty, metal cover for outside panel mounting. and up to 350°F (197°C) for intermittent use.
202050C (Series 3) Cover with reset button; heavy duty, Q624A Solid State Spark Generator; prevents detection of
metal cover for outside panel mounting. ignition spark when properly applied with flame
118760B (Series 1 and 2) Remote Reset Cover; heavy detection systems using C7027, C7035, or C7044
duty, metal cover with remote reset assembly; 120V, Minipeeper Ultraviolet Flame Detectors. For use only
60 Hz solenoid. with gas pilots.
202051B (Series 3) Remote Reset Cover; heavy duty, FSP5004 Tester; provides a quick operational check of
metal cover with remote reset assembly; 120V, 60 Hz most R4140 Flame Safeguard Programming Controls.
solenoid. Q520E1002 Service Tool; allows any of the programmer
R1061012 Ignition Cable; for ignition installations in a high terminals to be monitored while the programmer is
temperature environment; rated at 350°F (177°C) for operating.
continuous duty, and up to 500°F (260°C) for
intermittent use; tested to 25,000V.

Table 4. Flame Detection Systems

NOTE: Neither the R414G1114 or the R4140G1122 can be used with the C7012E or F Purple Peeper Ultraviolet Flame
Detector and with the R7247C Dynamic Self-Check Amplifier.
Plug-In Flame Signal Amplifiers Applicable Flame Detectors
Self- Flame Failure
Type Color Checking Model Response Time Fuel Type Models
Rectification Green No R7247A 2 to 4 sec Gas Rectifying Holdersa:C7004, C7007, C7011.
Flame Rods Complete assemblies: C7005,
C7008, C7009, Q179.
R7247A, 2 to 4 sec Oil Rectifying C7003, C7010, C7013, C7014.
R7247B b Photocells c
Gas, Ultraviolet C7012A or C.
Oil, (Purple
Coal Peeper)
Dynamic R7147B b 2 to 4 sec Gas Rectifying Holdersa: C7004, C7007, C7011.
Self- Flame Rods Complete Assemblies: C7005,
Check C7008, C7009, Q179.
R7247Cd 2 to 4 sec Gas, Ultraviolet C7012E or F
Oil, (Purple
Coal Peeper)
Infrared Red No R7248A 2 to 4 sec Gas, Infrared C7015.
Oil, (Lead
Coal Sulfide)
Dynamic R7248B b 2 to 4 sec Gas, Infrared C7015.
Ampli- Oil, (Lead
Check® Coal Sulfide)
Ultraviolet Purple No R7249A 2 to 4 sec Gas, Ultraviolet C7027, C7035, C7044.
Oil (Minipeeper)
Blue Dynamic R7476A d 2 to 4 sec Gas, Ultraviolet C7076.
Self- Oil, (Adjustable
Check Coal Sensitivity)
a Order flame rod separately; see Instructions for the holder.
b Circuitry tests the flame signal amplifier at least 150 times a minute during burner operation and shuts down the burner if the
amplifier fails.
c Use only Honeywell part no. 38316 Photocell.
d Circuitry tests all electronic components in the flame detection system (amplifier and detector) 60 to 240 times a minute during
burner operation and shuts down the burner if the detection system fails.

5 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

OPERATION
Models with Preignition Interlocks
Fig. 3 shows all contacts in the standby position (zero to each timer contact. Refer to Fig. 4 and the Step-by-Step
seconds). The opening and closing times are shown adjacent Operation section.

R4140G1007/G1015 SCHEMATIC 120V, 60 HZ


POWER SUPPLY
(WITH/WITHOUT HEAVY DUTY COVER)
L1 L2
(HOT)
INTERNAL EXTERNAL 1

UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.


O—OPENING TIME A TIMER CONTACTS SNAP CLOSED.
C—CLOSING TIME B CONTACTS SNAP OPEN.
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER
MASTER
SWITCH

1 L1 L2

2 NUMBERS BELOW
DESIGNATE LINE
3 9 13 5 8 12 10 LOCATIONS OF
3
RELAY CONTACTS.
FLAME SIGNAL (UNDERLINE
4 G F
METER JACK INDICATES A
PLUG-IN AMPLIFIER NORMALLY CLOSED
5 CONTACT.)
FLAME
6 DETECTOR 7 M11B
11 16
M9A 1K
17 C-15 O-70 C-57.5 O-109.5
2K - 13, 9, 8
7 TO 1K - 14, 14, 11
17
TIP JACK 2K TERMINAL
8 2
8 LS2
2K3
9 LS - 19, 9
M7A M7B M2B
BURNER C-57.5 O-111 O-9.5 C-116 2K2
10 O-70 LS HTR
LIMITS CONTROLLER
1K3 C-113.5
10 SECOND 3
11 4 16 3 5 INTERRUPTED
PILOT/IGNITION
M4A M6B
12 PREIGNITION RUNNING C-60 C-50 O-80
INTERLOCKS INTERLOCKS 2K1 O-85 4
(INCLUDING 30 SECOND
13 6 INTERRUPTED
1K1 1K2 AIRFLOW SWITCH) PILOT/IGNITION
M2A
14 C-70 5
M5B
O-109.5
15 O-104 MAIN FUEL
7
M3A TEST C-108 VALVES (S)
M1B O-52 C-66 NORM
16 C-4
8 13
LOW FIRE TIMER SWITCH
O-120 SWITCH TIMER MOTOR BURNER MOTOR
17
(BLOWER)
18
LS1
19 9 120 V ALARM

20
HIGH FIRE
21 10 B B
M10A C-4 O-41 COMMON
22 11 R R
M10B O-4 C-45
MODULATE
23 12 W W
M8A C-100 O-112 M8B O-100 C-116
LOW FIRE
24 14 FIRING SERIES 90
RATE CONTROLLER
MOTOR 6

1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION 3 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
AS REQUIRED.
4 30 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
2 TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F
OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING 5 FOR DIRECT SPARK IGNITION (GAS OR OIL,) A JUMPER IS INSTALLED
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17 BETWEEN TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C OF FIELD WIRING FOR HOOKUP.
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK
DIAGRAM OF FIELD WIRING. 6 USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.
M10149

Fig. 3. Simplified schematic diagram of R4140G1015 Programmer.

60-2337—3 6
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

TIMER 0 10 20 30 40 50 60 70 80 90 100 110 120


SECONDS

PREIGNITION INTERLOCKS 6
RUN 5
RUNNING INTERLOCKS (PROVEN AIRFLOW) PERIOD

IGN MAIN
TIMER DIAL PREPURGE PURGE
PILOT
START

START

START
STOP

STOP

STOP
TIMER
MOTOR 3 5

BURNER
MOTOR 8 1
(BLOWER)

5 10 SECONDS
INTERRUPTED
PILOT/IGNITION
6 30 SECONDS

MAIN FUEL
VALVE(S) 7
(GAS OR OIL)

HIGH FIRE POSITION MODULATE

FIRING RATE LOW FIRE POSITION


MOTOR 10 TO 11 1 12 TO 11
SWITCHING LOW LOW
14 TO 11

2 2 2
2
ACTUAL MOTOR 4
DAMPER
OPERATION MOTOR DRIVES
DRIVES DAMPER 3
MOTOR DRIVES
DAMPER CLOSED
DAMPER CLOSED
OPEN

1 TERMINAL NUMBERS (CIRCLED). 4 FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN
2 SLOPE DEPENDS ON MOTOR TIMING. PERIOD WHILE BURNER IS FIRING).

3 TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES. 5 TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE
BURNER FIRING.

6 RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)


MUST REMAIN CLOSED THROUGH THE RUN PERIOD.
M10054

Fig. 4. Timer sequence for R4140G1015 Programmer.

Step-By-Step Operation (R4140G1015) and ignition trials cannot be started. Running interlocks
Start And Prepurge must remain closed through the Run period or the
0 seconds—On a call for heat, the burner controller system shuts down; the timer completes its revolution
contacts close. If the limits and preignition interlocks and recycles the programmer.
are closed and flame relay 2K is not holding in, relay 1K 15 seconds—M11B closes; flame relay 2K can pull in if a
pulls in through M7B, LS2, 2K2, and the LS HTR flame (or a condition simulating a flame) is detected. If
(lockout switch heater—thus proving its continuity). detected during prepurge (until 57.5 seconds), 2K pulls
— 1K1 closes and 1K2 opens, timer motor starts in, 2K2 opens, 1K drops out, and the system shuts
(through 1K1, M3A, and M5B), power is applied to down; the timer completes its revolution and recycles
terminal 8, starting the burner motor (blower); 1K3 the programmer (if 2K dropped out).
closes. 45 seconds—M10B closes; firing rate motor drives toward
— Prepurge begins. low fire position (closed).
4 seconds—M10A closes, M10B opens; firing rate motor 52 seconds—M3A opens; timer stops until the low fire
drives toward high fire position (open). proving switch closes; timer can be stopped by opening
—M1B closes, bypassing 1K1; the timer can complete the timer switch (until 66 seconds when M3A closes
its revolution if shutdown occurs. again).
9.5 seconds—M7B opens; running interlocks must close 57.5 seconds—M9A closes; the LS HTR (lockout switch
(airflow must be proven) or 1K drops out, 1K3 opens, heater) begins heating in preparation for ignition trials.
— M7A closes, bypassing the preignition interlocks.

7 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

Ignition Trials Run Period (Burner is Firing)


60 seconds—M4A closes; power is applied to terminals 5 Postpurge And Stop
and 6, energizing the ignition transformer and pilot 104 seconds—When the operating setpoint is reached, the
valve (or main fuel valve(s) on terminal 7 if using direct burner controller contacts open; relay 1K and the main
spark ignition). fuel valve(s) (terminal 7) de-energize.
— When a flame is detected, relay 2K pulls in, 2K2 — 1K2 closes; timer motor starts; postpurge begins.
opens, and the LS HTR stops heating; 2K1 and — When the flame goes out, relay 2K drops out.
2K3 close. 112 seconds—M8A opens; firing rate motor stops
66 seconds—M3A closes, bypassing the low fire switch modulating under control of the Series 90 Controller.
and the timer switch. 116 seconds—M8B closes; firing rate motor drives toward
70 seconds—M2B opens; pilot or ignition trial ends; a low fire position (closed).
flame must be detected by this time (2K pulled in and 120 seconds—M1B opens; timer and burner motor stop;
2K1 closed) or safety shutdown occurs and the lockout cycle ends.
switch trips.
— M2A closes; power is applied to terminal 7, Fig. 5 shows all contacts in the standby position (zero
energizing the main fuel valve(s). seconds). The opening and closing times are shown adjacent
— M11B opens; prevents 2K from pulling in after this to each timer contact. Refer to Fig. 6 and the Step-by-Step
time. Operation section.
80 seconds—M6B opens; 10 second interrupted pilot/
ignition (terminal 5) is de-energized.
100 seconds—M4A opens; 30 second interrupted pilot/
ignition (terminal 6) is de-energized.
— M8A closes, M8B opens; firing rate motor is
released to modulate under control of the Series 90
Controller.
104 seconds—M5B opens; timer stops with the system in
the Run condition.

60-2337—3 8
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

120V, 60 HZ
R4140G1106 SCHEMATIC POWER SUPPLY
L1 L2
(HOT)
1
INTERNAL EXTERNAL
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.
O—OPENING TIME A TIMER CONTACTS SNAP CLOSED.
C—CLOSING TIME
B CONTACTS SNAP OPEN.
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER
MASTER
SWITCH

1 L1 L2

2 NUMBERS BELOW
3 9 13 5 8 12 10 DESIGNATE LINE
3 LOCATIONS
FLAME SIGNAL RELAY CONTACTS.
4 G F METER JACK (UNDERLINE
PLUG-IN AMPLIFIER INDICATES A
5 NORMALLY CLOSED
CONTACT.)
FLAME
6 DETECTOR 7 M11B
11 16
M9A 1K
17 C-15 O-70 C-57.5 O-109.5
2K - 16, 10, 8
7 1K - 17, 17, 12
17 TO 8
2K
8 2
TIP JACK LS2
2K3
9 LS - 22, 8
M7A M7B M2B
BURNER C-57.5 O-111 O-9.5 C-116 2K2
10 O-70 LS HTR
LIMITS CONTROLLER 8
1K3 C-113.5
10 SECOND
11 4 16 3 5 INTERRUPTED
PILOT/IGNITION
M4A M6B 3
12 PREIGNITION RUNNING C-60 C-50 O-80
INTERLOCKS INTERLOCKS 2K1 O-85 9
(INCLUDING 15 SECOND
13 6 INTERRUPTED
1K1 1K2 AIRFLOW SWITCH) PILOT/IGNITION
M2A
14 C-70
M5B 7
O-109.5
15 O-104 MAIN FUEL
7
M3A TEST C-108 VALVES (S) 4
M1B O-52 C-66 NORM
16 C-4
B 13
LOW FIRE TIMER SWITCH 5
O-120 SWITCH TIMER MOTOR BURNER
17 MOTOR
18
LS1
19 9 ALARM

20
HIGH FIRE
21 10 B B
M10A C-4 O-41 COMMON
22 11 R R
M10B O-4 C-45
MODULATE
23 12 W W
M8A C-100 O-112 M8B O-100 C-116
LOW FIRE
24 14 FIRING SERIES 90
RATE CONTROLLER
MOTOR 6
1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED 5 TIMER SWITCH IS SHOWN IN "NORM" POSITION; IT IS OPEN IN "TEST"
POSITION.
2 TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F 6 USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.
PURPLE PEPPER ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17
7 FOR DIRECT SPARK IGNITION (OIL OR GAS), A JUMPER IS INSTALLED
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C
BETWEEN TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK
DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK DIAGRAM
DIAGRAM OF FIELD WIRING FOR HOOKUP.
OF FIELD WIRING.
8 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
3 FOR DIRECT SPARK IGNITION OR OIL, REFER TO SAMPLE BLOCK DIAGRAM
OF FIELD WIRING FOR HOOKUP OF IGNITION AND MAIN OIL VALVE SOLENOID.
9 15 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
4 SOME AUTHORITIES HAVING JURISDICTION PROHIBIT THE WIRING OF ANY LIMIT
OR OPERATING CONTACTS IN SERIES WITH THE MAIN FUEL VALVE(S). M10044

Fig. 5. Simplified schematic diagram of R4140G1106 Programmer.

9 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

TIMER 0 10 20 30 40 50 60 70 80 90 100 110 120


SECONDS

PREIGNITION INTERLOCKS 6
RUN
RUNNING INTERLOCKS (PROVEN AIRFLOW) PERIOD

IGN MAIN
TIMER DIAL PREPURGE PURGE
PILOT
START

START

START
STOP

STOP

STOP
TIMER
MOTOR 3 5

BURNER
MOTOR 8 1
(BLOWER)

5 10 SECONDS
INTERRUPTED
PILOT/IGNITION
6 15 SECONDS

MAIN FUEL
VALVE(S) 7
(GAS OR OIL)

HIGH FIRE POSITION MODULATE


FIRING RATE LOW FIRE POSITION
MOTOR 10 TO 11 1 12 TO 11
SWITCHING
LOW 14 TO 11 LOW

2 2 2
2
ACTUAL MOTOR 4
DAMPER
OPERATION MOTOR DRIVES
DRIVES DAMPER 3
MOTOR DRIVES
DAMPER CLOSED
DAMPER CLOSED
OPEN

1 TERMINAL NUMBERS (CIRCLED). 4 FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN
2 SLOPE DEPENDS ON MOTOR TIMING. PERIOD WHILE BURNER IS FIRING).

3 TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES. 5 TIMER STOPS AT 164 SECONDS FOR THE RUN PERIOD WITH
THE BURNER FIRING.

6 RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)


MUST REMAIN CLOSED THROUGH THE RUN PERIOD. M10052

Fig. 6. Timer sequence for R4140G1106 Programmer.

Step-By-Step Operation (R4140G1106)


Start and Prepurge
0 seconds—On a call for heat, the burner controller or the system shuts down; the timer completes its
contacts close. If the limits and preignition interlocks revolution and recycles the programmer.
are closed and flame relay 2K is not holding in, relay 1K 15 seconds—M11B closes; flame relay 2K can pull in if a
pulls in through M7B, LS2, 2K2, and the LS HTR flame (or a condition simulating a flame) is detected. If
(lockout switch heater—thus proving its continuity). detected during prepurge (until 57.5 seconds), 2K pulls
— 1K1 closes and 1K2 opens; timer motor starts in, 2K2 opens, 1K drops out, and the system shuts
(through 1K1, M3A, and M5B); power is applied to down; the timer completes its revolution and recycles
terminal 8, starting the burner motor (blower); 1K3 the programmer (if 2K dropped out).
closes. 45 seconds—M10B closes; firing rate motor drives toward
— Prepurge begins. low fire position (closed).
4 seconds—M10A closes, M10B opens; firing rate motor 52 seconds—M3A opens; timer stops until the low fire
drives toward high fire position (open). proving switch closes; timer can be stopped by opening
— M1B closes, bypassing 1K1; the timer can the timer switch (until 66 seconds when M3A closes
complete its revolution if shutdown occurs. again).
9.5 seconds—M7B opens; running interlocks must be 57.5 seconds—M9A closes; the LS HTR (lockout switch
closed (airflow must be proven) or 1K drops out, 1K3 heater) begins heating in preparation for ignition trials.
opens, and ignition trials cannot be started. Running — M7A closes, bypassing the preignition interlocks.
interlocks must remain closed through the Run period

60-2337—3 10
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

Ignition Trials Run Period (Burner is Firing)


60 seconds—M4A closes; power is applied to terminals 5 Postpurge and Stop
and 6, energizing the ignition transformer and pilot 104 seconds—When the operating setpoint is reached, the
valve (or main fuel valve(s) on terminal 7 If using direct burner controller contacts open; relay 1K and the main
spark ignition). fuel valve(s) (terminal 7) are de-energized.
— When a flame is detected, relay 2K pulls in, 2K2 — 1K2 closes; timer motor starts; postpurge begins.
opens, and the LS HTR stops heating; 2K1 and — When the flame goes out, relay 2K drops out.
2K3 close. 112 seconds—M8A opens; firing rate motor stops
66 seconds—M3A closes, bypassing the low fire switch modulating under control of the Series 90 Controller.
and the timer switch. 116 seconds—M8B closes; firing rate motor drives toward
70 seconds—M2B opens; pilot or ignition trial ends; a low fire position (closed).
flame must be detected by this time (2K pulled in and 120 seconds—M1B opens; timer and burner motor stop;
2K1 closed) or safety shutdown occurs and the lockout cycle ends.
switch trips.
— M2A closes; power is applied to terminal 7,
energizing the main fuel valves(s).
— M11B opens; prevents 2K from pulling in after this
Models with Start Interlocks
time. Fig. 7 shows all contacts in the standby position (zero
80 seconds—M6B opens; 10 second interrupted pilot/ seconds). The opening and closing times are shown adjacent
ignition (terminal 5) de-energizes. to each timer contact. Refer to Fig. 8 and the Step-by-Step
85 seconds—M4A opens; 15 second interrupted pilot/ Operation section.
ignition (terminal 6) de-energizes.
100 seconds—M8A closes, M8B opens; firing rate motor is
released to modulate under control of the Series 90
Controller.
104 seconds—M5B opens; timer stops with the system in
the run condition.

11 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

120V, 60 HZ
R4140G1049 SCHEMATIC POWER SUPPLY
(WITH/WITHOUT HEAVY DUTY COVER) L1 L2
(HOT) 1
INTERNAL EXTERNAL
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.
O—OPENING TIME A TIMER CONTACTS SNAP CLOSED.
C—CLOSING TIME
B CONTACTS SNAP OPEN.
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER
MASTER
SWITCH

1 L1 L2

2 NUMBERS BELOW
DESIGNATE LINE
3 9 13 5 8 12 10 LOCATIONS OF
3
RELAY CONTACTS.
FLAME SIGNAL (UNDERLINE
4 G F
METER JACK INDICATES A
PLUG-IN AMPLIFIER NORMALLY CLOSED
5 CONTACT.)
FLAME
6 DETECTOR 7 M11B
11 16
17 C-15 O-70
7 M9A 1K
17 TO C-57.5 O-111
TIP JACK 2K 2K - 16, 10, 8
8 2 TERMINAL
8 1K - 17, 17, 12
BURNER START 2K3
9 LIMITS CONTROLLER 3 INTERLOCK(S) 4
10 16 4 LS - 22, 8
M7B
O-9.5 C-116 2K2
11 LS HTR

12 5 SECOND
3 18
M2B IGNITION
1K3 M9B
13 RUNNING INTERLOCKS O-70 C-30
(INCLUDING AIRFLOW SWITCH) C-113.5 O-65 10 SECOND 5
14 5 INTERRUPTED
M4A PILOT/IGNITION
M6B
15 C-60 C-50 O-80
2K1 O-85 6
30 SECOND
16 6 INTERRUPTED
1K1 1K2 PILOT/IGNITION
M2A
17 C-70 7
M5B
O-104 O-109.5
18 7 MAIN FUEL
M3A TEST C-108 VALVES (S)
M1B O-52 C-66 NORM
19 C-4
8 13
LOW FIRE TIMER SWITCH
O-120 SWITCH TIMER MOTOR BURNER MOTOR
20
(BLOWER)
21
LS1
22 9 120 V ALARM

23
HIGH FIRE
24 10 B B
M10A C-4 O-41 COMMON
25 11 R R
M10B O-4 C-45
MODULATE
26 12 W W
M8A C-100 O-112 M8B O-100 C-116
LOW FIRE
27 14 FIRING SERIES 90
RATE CONTROLLER
MOTOR 8

1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION 4 IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED
AS REQUIRED. BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE.

2 TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F 5 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17 6 30 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK 7 FOR DIRECT SPARK IGNITION (GAS OR OIL), A JUMPER IS INSTALLED
DIAGRAM OF FIELD WIRING. BETWEEN TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM
OF FIELD WIRING FOR HOOKUP.
3 TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT.
8 USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.
M10155

Fig. 7. Simplified schematic diagram of R4140G1049 Programmer.

60-2337—3 12
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

TIMER 0 10 20 30 40 50 60 70 80 90 100 110 120


SECONDS

6
RUN 5
RUNNING INTERLOCKS (PROVEN AIRFLOW) PERIOD

IGN MAIN
TIMER DIAL PREPURGE PURGE
PILOT
START

START

START
STOP

STOP

STOP
TIMER
MOTOR 3 5

BURNER
MOTOR 8 1
(BLOWER)

5 SECOND 18
IGNITION

5 10 SECONDS
INTERRUPTED
PILOT/IGNITION
6 30 SECONDS

MAIN FUEL
VALVE(S) 7
(GAS OR OIL)

HIGH FIRE POSITION MODULATE

FIRING RATE LOW FIRE POSITION


MOTOR 10 TO 11 1 12 TO 11
SWITCHING LOW LOW
14 TO 11

2 2 2
2
ACTUAL MOTOR 4
DAMPER
OPERATION MOTOR DRIVES
DRIVES DAMPER 3
MOTOR DRIVES
DAMPER CLOSED
DAMPER CLOSED
OPEN

1 TERMINAL NUMBERS (CIRCLED). 4 FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN
2 SLOPE DEPENDS ON MOTOR TIMING. PERIOD WHILE BURNER IS FIRING).

3 TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES. 5 TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE
BURNER FIRING.

6 RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)


MUST REMAIN CLOSED THROUGH THE RUN PERIOD.
M10055

Fig. 8. Timer sequence for R4140G1049 Programmer.

Step-By-Step Operation (R4140G1049)


Start and Prepurge
0 seconds—On a call for heat, the burner controller interlocks must remain closed through the Run period
contacts close. If the limits and start interlock(s) are or the system shuts down; the timer completes its
closed and flame relay 2K is not holding in, relay 1K revolution and recycles the programmer.
pulls in through M7B, 2K2, the LS HTR (lockout switch 15 seconds—M11B closes; flame relay 2K pulls in if a
heater—thus proving its continuity), and LS2. flame (or a condition simulating a flame) is detected. If
— 1K1 closes and 1K2 opens; timer motor starts detected during prepurge (until 57.5 seconds), 2K pulls
(through 1K1, M3A, and M5B); power is applied to in, 2K2 opens, 1K drops out, and the system shuts
terminal 8, starting the burner motor (blower); 1K3 down; the timer completes its revolution and recycles
closes. the programmer (if 2K dropped out).
— Prepurge begins. 45 seconds—M10B closes; firing rate motor drives toward
4 seconds—M10A closes, M10B opens; firing rate motor low fire position (closed).
drives toward high fire position (open). 52 seconds—M3A opens; timer stops until the low fire
— M1B closes, bypassing 1K1; the timer can proving switch closes; timer can be stopped by opening
complete its revolution if shutdown occurs. the timer switch (until 66 seconds when M3A closes
9.5 seconds—M7B opens; running interlocks must be again).
closed (airflow must be proven) or 1K drops out, 1K3 57.5 seconds—M7A closes; the LS HTR (lockout switch
opens, and ignition trials cannot be started. Running heater) begins heating in preparation for ignition trials.

13 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

Ignition Trials Run Period (Burner is Firing)


60 seconds—M4A closes; power is applied to terminals Postpurge and Stop
18, 5, and 6, energizing the ignition transformer and 104 seconds—When the operating setpoint is reached, the
pilot valve (or main fuel valve(s) on terminal 7 if using burner controller contacts open; relay 1K and the main
direct spark ignition). fuel valve(s) (terminal 7) de-energize.
— When a flame is detected, relay 2K pulls in, 2K2 — 1K2 closes; timer motor starts; postpurge begins.
opens, and the LS HTR stops heating; 2K1 and — When the flame goes out, relay 2K drops out.
2K3 close. 112 seconds—M8A opens; firing rate motor stops
65 seconds—M9B opens; 5 second ignition (terminal 18) modulating under control of the Series 90 Controller.
is de-energizes (pilot only until 70 seconds). 116 seconds—M8B closes; firing rate motor drives toward
66 seconds—M3A closes, bypassing the low fire switch low fire position (closed).
and the timer switch. 120 seconds—M1B opens; timer and burner motor stop;
70 seconds—M2B opens; pilot or ignition trial ends; a cycle ends.
flame must be detected by this time (2K pulled in and
2K1 closed) or safety shutdown occurs and the lockout Fig. 9 shows all contacts in the standby position (zero
switch trips. seconds). The opening and closing times are shown adjacent
— M2A closes; power is applied to terminal 7, to each timer contact. Refer to Fig. 10 and the Step-by-Step
energizing the main fuel valve(s). Operation section.
— M11B opens; prevents 2K from pulling in after this
time.
80 seconds—M6B opens; 10 second interrupted pilot/
ignition (terminal 5) de-energizes.
100 seconds—M4A opens; 30 second interrupted pilot/
ignition (terminal 6) de-energizes.
— M8A closes, M8B opens; firing rate motor is
released to modulate under control of the
Series 90 Controller.
104 seconds—M5B opens; timer stops with the system in
the run condition.

60-2337—3 14
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

120V, 60 HZ
R4140G1056/G1064 SCHEMATIC POWER SUPPLY
(WITH/WITHOUT HEAVY DUTY COVER) L1 L2
(HOT) 1
INTERNAL EXTERNAL
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.
O—OPENING TIME A TIMER CONTACTS SNAP CLOSED.
C—CLOSING TIME
B CONTACTS SNAP OPEN.
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER
MASTER
SWITCH

1 L1 L2

2 NUMBERS BELOW
DESIGNATE LINE
3 9 13 5 8 12 10 LOCATIONS OF
3
RELAY CONTACTS.
FLAME SIGNAL (UNDERLINE
4 G F
METER JACK INDICATES A
PLUG-IN AMPLIFIER NORMALLY CLOSED
5 CONTACT.)
FLAME
6 DETECTOR 7 M11B
11 16
17 C-15 O-70
7 M7A 1K
2K - 16, 10, 8
17 TO C-57.5 O-111
TIP JACK 2K
8 2 TERMINAL 1K - 17, 17, 12
8
BURNER START 2K3 LS2
9 LIMITS CONTROLLER 3 INTERLOCK(S) 4
10 16 4 LS - 22, 8
M7B
O-9.5 C-116 2K2
11 LS HTR

12 5 SECOND
3 18
M2B IGNITION
1K3 M9B
13 RUNNING INTERLOCKS O-70 C-30
(INCLUDING AIRFLOW SWITCH) C-113.5 O-65 10 SECOND 5
14 5 INTERRUPTED
M4A PILOT/IGNITION
M6B
15 C-60 C-50 O-80 6
2K1 O-110
16 6 INTERMITTENT
1K1 1K2 PILOT/IGNITION
M2A
17 C-70
M5B
O-104 O-109.5
18 7 MAIN FUEL
M3A TEST C-108 VALVES (S)
M1B O-52 C-66 NORM
19 C-4
8 13
LOW FIRE TIMER SWITCH
O-120 SWITCH TIMER MOTOR BURNER MOTOR
20
(BLOWER)
21
LS1
22 9 120V ALARM

23
HIGH FIRE
24 10 B B
M10A C-4 O-41 COMMON
25 11 R R
M10B O-4 C-45
MODULATE
26 12 W W
M8A C-100 O-112 M8B O-100 C-116
LOW FIRE
27 14 FIRING SERIES 90
RATE CONTROLLER
MOTOR 7

1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION 4 IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED
AS REQUIRED. BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE.

2 TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F 5 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17 6 FOR DIRECT SPARK IGNITION (GAS OR OIL), REFER TO SAMPLE
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C BLOCK DIAGRAM OF FIELD WIRING FOR HOOKUP.
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK
DIAGRAM OF FIELD WIRING. 7 USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.
M10156
3 TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT.

Fig. 9. Simplified schematic diagram of the R4140G1056 and R4140G1064 Programmers.

15 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

TIMER 0 10 20 30 40 50 60 70 80 90 100 110 120


SECONDS

6
RUN 5
RUNNING INTERLOCKS (PROVEN AIRFLOW) PERIOD

IGN MAIN
TIMER DIAL PREPURGE PURGE
PILOT
START

START

START
STOP

STOP

STOP
TIMER
MOTOR 3 5

BURNER
MOTOR 8 1
(BLOWER)

5 SECOND
IGNITION 18

10 SECOND
INTERRUPTED 5
PILOT/IGNITION

INTERMITTENT PILOT
OR 1ST STAGE 6
FUEL VALVE

MAIN FUEL
VALVE(S) 7
(GAS OR OIL)

HIGH FIRE POSITION MODULATE

FIRING RATE LOW FIRE POSITION


MOTOR 10 TO 11 1 12 TO 11
SWITCHING LOW LOW
14 TO 11

2 2 2
2
ACTUAL 4
DAMPER MOTOR
OPERATION MOTOR
DRIVES
DRIVES 3
DAMPER MOTOR DRIVES
DAMPER
CLOSED DAMPER CLOSED
OPEN

1 TERMINAL NUMBERS (CIRCLED). 4 FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN
2 SLOPE DEPENDS ON MOTOR TIMING. PERIOD WHILE BURNER IS FIRING).

3 TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES. 5 TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE
BURNER FIRING.

6 RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)


MUST REMAIN CLOSED THROUGH THE RUN PERIOD.
M10056

Fig. 10. Timer sequence for R4140G1056 and R4140G1064 Programmers.

Step-By-Step Operation
(R4140G1056 and R4140G1064) opens, and ignition trials cannot be started. Running
Start and Prepurge interlocks must remain closed through the Run period
0 seconds—On a call for heat, the burner controller or the system shuts down; the timer completes its
contacts close. If the limits and start interlock(s) are revolution and recycles the programmer.
closed and flame relay 2K is not holding in, relay 1K 15 seconds—M11B closes; flame relay 2K can pull in if a
pulls in through M7B, 2K2, the LS HTR (lockout switch flame (or a condition simulating a flame) is detected If
heater—thus proving its continuity), and LS2. detected during prepurge (until 57.5 seconds), 2K pulls
— 1K1 closes and 1K2 opens; timer motor starts in, 2K2 opens, 1K drops out, and the system shuts
(through 1K1, M3A, and M5B); power is applied to down; the timer completes its revolution and recycles
terminal 8, starting the burner motor (blower); 1K3 the programmer (if 2K dropped out).
closes. 45 seconds—M10B closes; firing rate motor drives toward
— Prepurge begins. low fire position (closed).
4 seconds—M10A closes, M10B opens; firing rate motor 52 seconds—M3A opens; timer stops until the low fire
drives toward high fire position (open). proving switch closes; timer can be stopped by opening
— M1B closes, bypassing 1K1; the timer can the timer switch (until 66 seconds when M3A closes
complete its revolution if shutdown occurs. again).
9.5 seconds—M7B opens; running interlocks must be 57.5 seconds—M7A closes; the LS HTR (lockout switch
closed (airflow must be proven) or 1K drops out, 1K3 heater) begins heating in preparation for ignition trials.

60-2337—3 16
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

Ignition Trials Run Period (Burner is Firing)


60 seconds—M4A closes; power is applied to terminals Postpurge and Stop
18, 5, and 6, energizing the ignition transformer and 104 seconds—When the operating setpoint is reached, the
pilot valve (or first stage fuel valve when using direct burner controller contacts open; relay 1K, intermittent
spark ignition). pilot or first stage fuel valve (terminal 6), and the main
— When a flame is detected, relay 2K pulls in, 2K2 fuel valve(s) (terminal 7) de-energize.
opens, and the LS HTR stops heating; 2K1 and — 1K2 closes; timer motor starts; postpurge begins.
2K3 close. — When the flame goes out, relay 2K drops out.
65 seconds—M9B opens; 5 second ignition (terminal 18) 112 seconds—M8A opens; firing rate motor stops
de-energizes (pilot only until 70 seconds). modulating under control of the Series 90 Controller.
66 seconds—M3A closes, bypassing the low fire switch 116 seconds—M8B closes; firing rate motor drives toward
and the timer switch. low fire position (closed).
70 seconds—M2B opens; pilot or ignition trial ends; a 120 seconds—M1B opens; timer and burner motor stop;
flame must be detected by this time (2K pulled in and cycle ends.
2K1 closed) or safety shutdown occurs and the lockout
switch trips. Fig. 11 shows all contacts in the standby position (zero
— M2A closes; power is applied to terminal 7, seconds). The opening and closing times are shown adjacent
energizing the main fuel valve(s). to each timer contact. Refer to Fig. 12 and the Step-by-Step
— M11B opens; prevents 2K from pulling in after this Operation section.
time.
80 seconds—M6B opens; 10 second interrupted pilot/
ignition (terminal 5) de-energizes.
100 seconds—M8A closes, M8B opens; firing rate motor is
released to modulate under control of the Series 90
Controller.
104 seconds—M5B opens; timer stops with the system in
the run condition.

17 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

120V, 60 HZ
POWER SUPPLY
L1 L2
(HOT) 1
INTERNAL EXTERNAL
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.
O—OPENING TIME A TIMER CONTACTS SNAP CLOSED.
C—CLOSING TIME B CONTACTS SNAP OPEN.
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER
MASTER
SWITCH

1 L1 L2

2 NUMBERS BELOW
DESIGNATE LINE
3 9 13 5 8 12 10 LOCATIONS OF
3
RELAY CONTACTS.
FLAME SIGNAL (UNDERLINE
4 G F
METER JACK INDICATES A
PLUG-IN AMPLIFIER NORMALLY CLOSED
5 CONTACT.)
FLAME
6 DETECTOR 7 M11B
11 16
17 C-15 O-70
7 M7A 1K
2K - 8, 10, 16
17 TO C-67 O-168
TIP JACK 2K
8 2 TERMINAL 1K - 12, 17, 17
8
BURNER 2K3 LS2
9 START
LIMITS CONTROLLER 3 INTERLOCK(S) 4
10 16 4 LS - 8, 22,
M7B
O-13.5 C-174 2K2
11 LS HTR

12 5 SECOND
3 18
M2B IGNITION
1K3 M9B
13 RUNNING INTERLOCKS O-80 C-40 O-75
(INCLUDING AIRFLOW SWITCH) C-169
10 SECOND
14 5 INTERRUPTED
M6B PILOT/IGNITION
M4A C-60 O-90
15 C-70
2K1 O-110 30 OR 60 SECOND
16 6 INTERRUPTED
1K1 1K2 PILOT/IGNITION 5
5 M12B
17 C-90 6
M5B
O-140
18 O-155 MAIN FUEL
7
M3A TEST C-164 M2A C-80 VALVES (S) 7
M1B O-60 C-76 NORM O-163
19 C-6
8 13
LOW FIRE TIMER SWITCH
O-180 SWITCH 8 TIMER MOTOR
20 BURNER MOTOR
(BLOWER)
21
LS1
22 9 120V ALARM

23
HIGH FIRE
24 10 B B
M10A C-5 O-34 COMMON
25 11 R R
M10B O-5 C-40
MODULATE
26 12 W W
M8A C-148 O-168 M8B O-148 C-174
LOW FIRE
27 14 FIRING SERIES 90
RATE CONTROLLER
MOTOR 9

1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION 5 A JUMPER IS INSTALLED ON THE BACK OF THE PROGRAMMER TO OBTAIN 60
AS REQUIRED. SECOND INTERRUPTED PILOT/IGNITION AT TERMINAL 6; WITHOUT JUMPER,
IT IS 30 SECONDS.
2 TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR
F OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING 6 FOR DIRECT SPARK IGNITION OF OIL, A JUMPER IS INSTALLED BETWEEN
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17 TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM OF FIELD WIRING FOR
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C HOOKUP OF IGNITION AND MAIN OIL VALVE SOLENOID.
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE 7
BLOCK DIAGRAM OF FIELD WIRING. SOME AUTHORITIES HAVING JURISDICTION PROHIBIT THE WIRING OF ANY LIMIT OR
OPERATING CONTACTS IN SERIES WITH THE MAIN FUEL VALVE(S).
3 TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT. 8
TIMER SWITCH IS SHOWN IN NORM POSITION; IT IS OPEN IN TEST POSITION.
4 IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED 9
BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE. USE A SERIES 90 MODULATING MOTOR. M10158

Fig. 11. Simplified schematic diagram of R4140G1171, R4140G122 and R4140G1114 Programmers.

60-2337—3 18
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

TIMER 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180
SECONDS

RUNNING INTERLOCKS (PROVEN AIRFLOW)

IGN MAIN
TIMER DIAL PREPURGE PURGE
PILOT
START

START

START
STOP

STOP

STOP
TIMER MOTOR 3 5

BURNER
MOTOR 8 1
(BLOWER)

5 SECOND
INGITION 18

5 10 SECONDS
INTERRUPTED
PILOT/INGITION 6 30 SECONDS (WITHOUT JUMPER)

6 60 SECONDS (WITH JUMPER)

MAIN FUEL
VALVE(S) 7
(GAS OR OIL)

HIGH FIRE POSITION MODULATE

10 TO 11 1 LOW FIRE POSITION 12 TO 11


LOW LOW
14 TO 11
2
2
2 2
ACTUAL 4
DAMPER MOTOR MOTOR
OPERATION DRIVES DRIVES
DAMPER DAMPER
OPEN MOTOR DRIVES
3 CLOSED
3 DAMPER CLOSED

1 TERMINAL NUMBERS (CIRCLED). 4 FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 148 TO 168 SECONDS (INCLUDING RUN
2 SLOPE DEPENDS ON MOTOR TIMING. PERIOD WHILE BURNER IS FIRING).

3 TIMER STOPS AT 60 SECONDS UNTIL LOW FIRE PROVING 5 TIMER STOPS FOR THE RUN PERIOD WITH THE BURNER FIRING.
SWITCH CLOSES.
6 RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)
MUST REMAIN CLOSED THROUGH THE RUN PERIOD.
M10057

Fig. 12. Timer sequence for R4140G1171, R4140G1122 and R4140G1114 Programmers.

Step-By-Step Operation
(R4140G1171, R4140G1122 and R4140G1114)
Start and Prepurge
0 seconds—On a call for heat, the burner controller contacts down; the timer completes its revolution and recycles
close. If the limits and start interlock(s) are closed, relay the programmer.
1K pulls in through M7B, 2K2, the LS HTR (lockout 13.5 seconds—M7B opens; running interlocks must be
switch heater—thus proving its continuity), and LS2. closed (airflow must be proven) or 1K drops out, 1K3
— 1K1 closes and 1K2 opens; timer starts (through opens, and ignition trials cannot be started. Running
M3A and M5B); power is applied to terminal 8, interlocks must remain closed through the Run period
starting the burner motor (blower); 1K3 closes. or the system shuts down; the timer completes its
— Prepurge begins. revolution and recycles the programmer.
5 seconds—M10A closes, M10B opens; firing rate motor 40 seconds—M10B closes; firing rate motor drives toward
drives toward high fire position (open). low fire position (closed).
6 seconds—M1B closes, bypassing 1K1; the timer 60 seconds—M3A opens; timer stops until the low fire
completes its revolution if shutdown occurs. proving switch closes; timer can be stopped by opening
10 seconds—M11B closes; flame relay 2K can pull in if a the timer switch (until 76 seconds when M3A closes
flame (or a condition simulating a flame) is detected. If again).
detected during prepurge (until 67 seconds), 2K pulls 67 seconds—M7A closes; the LS HTR (lockout switch
in, 2K2 opens, 1K drops out, and the system shuts heater) begins heating in preparation for ignition trials.

19 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

Ignition Trials 148 seconds—M8A closes, M8B opens; firing rate motor is
70 seconds—M4A closes; power is applied to terminals released to modulate under control of the Series 90
18, 5 and 6, energizing the ignition transformer and Controller.
pilot valve (and terminal 7, main oil valve solenoid, if 155 seconds—M5B opens; timer stops with the system in
using direct spark ignition of oil). the Run condition.
— When flame is detected, relay 2K pulls in, 2K2
opens, and the LS HTR stops heating; 2K1 and
2K3 close. Run Period (Burner is Firing)
75 seconds—M9B opens; 5 second ignition (terminals 18) Postpurge and Stop
de-energizes (pilot only until 80 seconds). 155 seconds—When the operating setpoint is reached, the
76 seconds—M3A closes, bypassing the low fire switch burner controller contacts open; relay 1K and the main
and the timer switch. fuel valve(s) (terminal 7) de-energizes.
80 seconds—M2B opens; pilot or ignition trial ends; flame — 1K2 closes; timer motor starts; postpurge begins.
must be detected by this time (2K pulled in and 2K1 — When flame goes out, relay 2K drops out.
closed) or safety shutdown occurs and the lockout 168 seconds—M8A opens; firing rate motor stops
switch trips. modulating under control of the Series 90 Controller.
— M2A closes; power is applied to terminal 7, 174 seconds—M8B closes; firing rate motor drives toward
energizing the main fuel valve(s). low fire position (closed).
— M11B opens; prevents 2K from pulling in after this 180 seconds—M1B opens; timer and burner motor stop;
time. cycle ends.
90 seconds—M6B opens; 10 second interrupted pilot/
ignition (terminal 5) de-energizes. Fig. 13 shows all contacts in the standby position (zero
110 seconds—M4A opens; 30 second interrupted pilot/ seconds). The opening and closing times are shown adjacent
ignition (terminal 6) de-energizes if jumper was not to each timer contact. Refer to Fig. 14 and the Step-by-Step
installed on back of programmer. Operation section.
140 seconds—M12B opens; 60 second interrupted pilot/
ignition (terminal 6) de-energizes if jumper was installed
on back of programmer.

60-2337—3 20
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

120V, 60 HZ
R4140G1148 SCHEMATIC POWER SUPPLY
(WITH/WITHOUT HEAVY DUTY COVER) L1 L2
(HOT) 1
INTERNAL EXTERNAL
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.
O—OPENING TIME A TIMER CONTACTS SNAP CLOSED.
C—CLOSING TIME
B CONTACTS SNAP OPEN.
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER
MASTER
SWITCH

1 L1 L2

2 NUMBERS BELOW
DESIGNATE LINE
3 9 13 5 8 12 10 LOCATIONS OF
3
RELAY CONTACTS.
FLAME SIGNAL (UNDERLINE
4 G F
METER JACK INDICATES A
PLUG-IN AMPLIFIER NORMALLY CLOSED
5 CONTACT.)
FLAME
6 DETECTOR 7 M11B
11 16
17 C-15 O-70
7 M9A 1K
2K - 16, 10, 8
17 TO C-57.5 O-111
TIP JACK 2K
8 2 TERMINAL 1K - 17, 17, 12
8
BURNER 2K3 LS2
9 START
LIMITS CONTROLLER 3 INTERLOCK(S) 4
10 16 4 LS - 22, 8
M7B
O-9.5 C-116 2K2
11 LS HTR

12 5 SECOND
3 18
M2B IGNITION
1K3 M9B
13 RUNNING INTERLOCKS O-70 C-30 O-65
(INCLUDING AIRFLOW SWITCH) C-113.5
10 SECOND 5
14 5 INTERRUPTED
M4A PILOT/IGNITION
M6B
15 C-60 C-50 O-80
2K1 O-85 6
15 SECOND
16 6 INTERRUPTED
1K1 1K2 PILOT/IGNITION
M2A
17 C-70 7
M5B
O-104 O-109.5
18 7 MAIN FUEL
M3A TEST C-108 VALVES (S)
M1B O-52 C-66 NORM
19 C-4
8 13
LOW FIRE TIMER SWITCH
O-120 SWITCH TIMER MOTOR BURNER MOTOR
20
(BLOWER)
21
LS1
22 9 120V ALARM

23
HIGH FIRE
24 10 B B
M10A C-4 O-41 COMMON
25 11 R R
M10B O-4 C-45
MODULATE
26 12 W W
M8A C-100 O-112 M8B O-100 C-116
LOW FIRE
27 14 FIRING SERIES 90
RATE CONTROLLER
MOTOR 8

1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION 4 IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED
AS REQUIRED. BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE.

2 TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F 5 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17 6 15 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK 7 FOR DIRECT SPARK IGNITION (GAS OR OIL), A JUMPER IS INSTALLED
DIAGRAM OF FIELD WIRING. BETWEEN TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM
OF FIELD WIRING FOR HOOKUP.
3 TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT.
8 USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED. M10157

Fig. 13. Simplified schematic diagram of R4140G1148 Programmer.

21 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

TIMER 0 10 20 30 40 50 60 70 80 90 100 110 120


SECONDS

6
RUN 5
RUNNING INTERLOCKS (PROVEN AIRFLOW) PERIOD

IGN MAIN
TIMER DIAL PREPURGE PURGE
PILOT
START

START

START
STOP

STOP

STOP
TIMER
MOTOR 3 5

BURNER
MOTOR 8 1
(BLOWER)

5 SECOND 18
IGNITION

5 10 SECONDS
INTERRUPTED
PILOT/IGNITION
6 15 SECONDS

MAIN FUEL
VALVE(S) 7
(GAS OR OIL)

HIGH FIRE POSITION MODULATE

FIRING RATE LOW FIRE POSITION


MOTOR 10 TO 11 1 12 TO 11
SWITCHING LOW LOW
14 TO 11

2 2 2
2
ACTUAL MOTOR 4
DAMPER
OPERATION MOTOR DRIVES
DRIVES DAMPER 3
MOTOR DRIVES
DAMPER CLOSED
DAMPER CLOSED
OPEN

1 TERMINAL NUMBERS (CIRCLED). 4 FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN
2 SLOPE DEPENDS ON MOTOR TIMING. PERIOD WHILE BURNER IS FIRING).

3 TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING 5 TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE
SWITCH CLOSES. BURNER FIRING.

6 RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)


MUST REMAIN CLOSED THROUGH THE RUN PERIOD.
M10058

Fig. 14. Timer sequence for R4140G1148 Programmer.

Step-By-Step Operation (R4140G1148)


Start and Prepurge
0 seconds—On a call for heat, the burner controller interlocks must remain closed through the Run period
contacts close. If the limits and start interlock(s) are or the system shuts down; the timer completes its
closed and flame relay 2K is not holding in, relay 1K revolution and recycles the programmer.
pulls in through M7B, 2K2, the LS HTR (lockout switch 15 seconds—M11B closes; flame relay 2K can pull in if a
heater—thus proving its continuity), and LS2. flame (or a condition simulating a flame) is detected. If
— 1K1 closes and 1K2 opens; timer motor starts detected during prepurge (until 57.5 seconds), 2K pulls
(through 1K1, M3A, and M5B); power is applied to in, 2K2 opens, 1K drops out, and the system shuts
terminal 8, starting the burner motor (blower); 1K3 down; the timer completes its revolution and recycles
closes. the programmer (if 2K drops out).
— Prepurge begins. 45 seconds—M10B closes; firing rate motor drives toward
4 seconds—M10A closes, M10B opens; firing rate motor low fire position (closed).
drives toward high fire position (open). 52 seconds—M3A opens; timer stops until the low fire
— M1B closes, bypassing 1K1; the timer can proving switch closes; timer can be stopped by opening
complete its revolution if shutdown occurs. the timer switch (until 66 seconds when M3A closes
9.5 seconds—M7B opens; running interlocks must be again).
closed (airflow must be proven) or 1K drops out, 1K3 57.5 seconds—M7A closes; the LS HTR (lockout switch
opens, and ignition trials cannot be started. Running heater) begins heating in preparation for ignition trials.

60-2337—3 22
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

Ignition Trials Run Period (Burner is Firing)


60 seconds—M4A closes; power is applied to terminals Postpurge and Stop
18, 5 and 6, energizing the ignition transformer and 104 seconds—When the operating setpoint is reached, the
pilot valve (or main fuel valve(s) on terminal 7 if using burner controller contacts open; relay 1K and the main
direct spark ignition). fuel valve(s) (terminal 7) de-energizes.
— When a flame is detected, relay 2K pulls in, 2K2 — 1K2 closes; timer motor starts; postpurge begins.
opens, and the LS HTR stops heating; 2K1 and — When the flame goes out, relay 2K drops out.
2K3 close. 112 seconds—M8A opens; firing rate motor stops
65 seconds—M9B opens; 5 second ignition (terminal 18) modulating under control of the Series 90 Controller.
de-energizes (pilot only until 70 seconds). 116 seconds—M8B closes; firing rate motor drives toward
66 seconds—M3A closes, bypassing the low fire switch low fire position (closed).
and the timer switch. 120 seconds—M1B opens; timer and burner motor stop;
70 seconds—M2B opens; pilot or ignition trial ends; a cycle ends.
flame must be detected by this time (2K pulled in and
2K1 closed) or safety shutdown occurs and the lockout
switch trips.
— M2A closes; power is applied to terminal 7, WIRING (FIG. 15 AND 16)
energizing the main fuel valve(s).
— M11B opens; prevents 2K from pulling in after this
time. CAUTION
80 seconds—M6B opens; 10 second interrupted pilot/ 1. Disconnect power supply before beginning wiring
ignition (terminal 5) de-energizes. to prevent electrical shock and equipment
85 seconds—M4A opens; 15 second interrupted pilot/ damage.
ignition (terminal 6) de-energizes. 2. Wiring must comply with all applicable local
100 seconds—M8A closes, M8B opens; firing rate motor is electrical codes, ordinances, and regulations.
released to modulate under control of the Series 90 3. All wiring must be NEC Class 1 (line voltage).
Controller.
104 seconds—M5B opens; timer stops with the system in
the run condition.

23 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

FOR DIRECT SPARK IGNITION (OIL OR GAS)

IGNITION
5
TRANSFORMER

JUMPER
TO 6
L2

MAIN FUEL
VALVE (S) 7

2
WIRING
SUBBASE RUNNING
TERMINAL INTERLOCKS
STRIP (4) (INCLUDING
AIRFLOW SWITCH) 10 SECOND
3 5
INTERRUPTED
3 PILOT/IGNITION
PREIGNITION
INTERLOCK(S) 5
18 30 (OR 15) SECOND
INTERRUPTED 6
BURNER
4 LIMITS L1 PILOT/IGNITION 4
CONTROLLER

17 MAIN FUEL 7
VALVE(S)
L2 9
9 120V ALARM
16
BURNER MOTOR 8
(BLOWER)
HIGH FIRE
10 12
15
LOW FIRE
COMMON SWITCH G
11
13 14
RECTIFYING FLAME
ROD, RECTIFYING
PHOTOCELL, OR
B B INFRARED
F 6 (LEAD SULFIDE)
R R FLAME DETECTOR
MODULATE
OR
LOW FIRE
W W
BLUE C7027A, C7035A, OR WHITE
C7044A ULTRAVIOLET
SERIES 90 SERIES 90 FLAME DETECTOR
CONTROLLER FIRING RATE OR
MOTOR
BLUE C7012A,C,E,F YELLOW
1 OR C7076A 7
120V, 60 HZ L1 (HOT) ULTRAVIOLET
POWER FLAME DETECTOR
L2 WHITE
SUPPLY
MASTER
SWITCH WHITE 10
L2
BLACK
L1
7 BLACK
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD L2
1
PROTECTION AS REQUIRED.
7 C7012 OR C7076 MUST BE RATED FOR 120 V, 60Hz. TWO DETECTORS
2 USE ALL NEC CLASS 1 WIRING. WITH THE SAME MODEL NUMBER CAN BE WIRED IN PARALLEL TO
THE SAME TERMINALS. C7076A DOES NOT HAVE LEADWIRES. (FOR
3 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD. INSTRUCTIONS, SEE FORM NUMBERS: 60-2046 FOR C7012A,C MODELS
WITH ELECTRON TUBES; 60-2044 FOR C7012E,F MODELS WITH ELECTRON
4 30 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD (MBFEP) ON TUBES; 60-2398 FOR C7012A,C,E,F SOLID STATE MODELS; 95-8269 FOR
THE R4140G1007 and R4140G1015 MODELS; 15 SECOND MBFEP ON THE C7076A.)
THE R4140G1106 MODEL.
8 WHITE SHUTTER LEADWIRES ARE ONLY ON THE C7012E OR F PURPLE PEEPER
5 FOR DIRECT SPARK IGNITION (OIL OR GAS) CONNECT THE IGNITION ULTRAVIOLET FLAME DETECTORS WITH SELF-CHECKING FEATURE; C7076A
TRANSFROMER AND FUEL VALVE(S) AS SHOWN IN THE INSET. ADJUSTABLE SENSITIVITY ULTRAVIOLET FLAME DETECTORS DO NOT
HAVE LEADWIRES.
6 FOR THE C7015A INFRARED (LEAD SULFIDE) FLAME DETECTOR, EITHER
LEADWIRE CAN BE CONNECTED TO THE F TERMINAL. RUN THE C7015A 9 TERMINAL 17 IS USED ONLY FOR THE SHUTTER ON SELF-CHECKING
LEADWIRES ALONE IN CONDUIT ALL THE WAY TO THE WIRING SUBBASE C7012E,F OR C7076A FLAME DETECTORS.
AND GROUND THE CONDUIT AT THE SUBBASE. (REFER TO PUBLICATION M10131
60-2306 FOR DETAILED INSTRUCTIONS.)

Fig. 15. Sample block diagram of field wiring for R4140G1007, R4140G1015 and R4140G1106 Programmers.

60-2337—3 24
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

FOR DIRECT SPARK IGNITION (OIL OR GAS) FOR DIRECT SPARK IGNITION (OIL OR GAS)
ON MODELS WITH INTERRUPTED ON MODELS WITH INTERMITTENT
PILOT/IGNITION ON TERMINAL 6 PILOT/IGNITION ON TERMINAL 6.

IGNITION IGNITION 5
5
TRANSFORMER TRANSFORMER

JUMPER
1ST STAGE 6
TO 6 TO FUEL VALVE
L2 L2

MAIN FUEL 2ND STAGE FUEL


VALVE (S) 7 7
VALVE (OPTIONAL)

2 5 SECOND IGNITION
WIRING (EARLY SPARK
SUBBASE 4
RUNNING TERMINATION)
TERMINAL INTERLOCKS
STRIP (4) (INCLUDING
AIRFLOW SWITCH) 10 SECOND
5 5
INTERRUPTED
3 PILOT/IGNITION
START
INTERLOCK(S) 3
7
18
PILOT/IGNITION 6
BURNER LIMITS 6
4 L1
CONTROLLER

17 MAIN FUEL 7
VALVE(S) 4
L2 11
9 ALARM
16
BURNER MOTOR 8
(BLOWER)
12
HIGH FIRE
10 12
15
LOW FIRE
COMMON SWITCH G
11
13 14
RECTIFYING FLAME
ROD, RECTIFYING
PHOTOCELL, OR
B B INFRARED
F 8 (LEAD SULFIDE)
R R FLAME DETECTOR
MODULATE
OR
LOW FIRE
W W
BLUE C7027A, C7035A, OR WHITE
C7044A ULTRAVIOLET
SERIES 90 SERIES 90 FLAME DETECTOR
CONTROLLER FIRING RATE OR
MOTOR
BLUE C7012A,C,E,F YELLOW
1 OR C7076A 9
120V, 60 HZ L1 (HOT) ULTRAVIOLET
POWER FLAME DETECTOR
L2 WHITE
SUPPLY
MASTER
SWITCH WHITE 10
L2
BLACK
L1
9 BLACK
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD L2
1
PROTECTION AS REQUIRED.
8 FOR THE C7015A INFRARED (LEAD SULFIDE) FLAME DETECTOR, EITHER
2 USE ALL NEC CLASS 1 WIRING. LEADWIRE CAN BE CONNECTED TO THE F TERMINAL. RUN THE C7015A
LEADWIRES ALONE IN CONDUIT ALL THE WAY TO THE WIRING SUBBASE
3 IF START INTERLOCK(S) IS NOT USED, INSTALL A JUMPER AND GROUND THE CONDUIT AT THE SUBBASE. (REFER TO PUBLICATION
BETWEEN TERMINALS 4 AND 16. 60-2306 FOR DETAILED INSTRUCTIONS.)
4 5 SECOND IGNITION IS AVAILABLE ONLY ON THE R4140G1049, 9 C7012 OR C7076 MUST BE RATED FOR 120V, 60Hz. TWO DETECTORS
G1056, G1064, G1114, G1122, G1148, AND G1171 MODELS. WITH THE SAME MODEL NUMBER CAN BE WIRED IN PARALLEL TO
THE SAME TERMINALS. C7076A DOES NOT HAVE LEADWIRES. (FOR
5 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD. ON R4140G114, INSTRUCTIONS SEE FORM NUMBERS; 60-2046 FOR C7012A, C MODELS
G1122, G1171 FOR 60 SECOND INTERRUPTED PILOT IGNITION, INSTALL WITH ELECTRON TUBES; 60-2044 FOR C7012E,F MODELS WITH ELECTRON
JUMPER (IN 4074B2V BAG ASSEMBLY) ON BACK OF PROGRAMMER TUBES; 60-2398 FOR C7012A,C,E,F SOLID STATE MODELS; 95-8269 FOR THE
BETWEEN SCREW TERMINALS LABELED "JUMPER TO EXTEND MAIN C7076A.) C7012E,F UV FLAME DETECTORS WITH SELF CHECKING FEATURE
IGNITION TRIAL." CANNOT BE USED WITH THE R4140G1122 OR R4140G1114.

6 30 SECOND INTERRUPTED PILOT/IGNITION (30 SECOND MAIN BURNER 10 WHITE SHUTTER LEADWIRES ARE ONLY ON THE C7012E OR F PURPLE PEEPER
FLAME-ESTABLISHING PERIOD, MBFEP) ON THE R4140 AND ULTRAVIOLET FLAME DETECTORS WITH SELF-CHECKING FEATURE; C7076A
R4140G1049, G1114, G1122, G1171, 15 SECOND INTERRUPTED PILOT/ ADJUSTABLE SENSITIVITY ULTRAVILOET FLAME DETECTOR DO NOT
IGNITION (15 SECOND MBFEP) ON THE R4140G1148. INTERMITTENT HAVE LEADWIRES.
PILOT/IGNITION ON THE R4140G1056, AND R4140G1064.
11 TERMINAL 17 IS USED ONLY FOR THE SHUTTER ON SELF-CHECKING
7 FOR DIRECT SPARK IGNITION (OIL OR GAS) CONNECT THE IGNITION C7012E,F OR C7076A FLAME DETECTORS.
TRANSFROMER AND FUEL VALVE(S) AS SHOWN IN THE APPROPRIATE INSET.
12 TERMINAL 16 IS USED ONLY AS A TIE POINT. M10059

Fig. 16. Sample block diagram of field wiring for R4140G1049, R4140G1056, R4140G1064,
R4140G1114, R4140G1122, R4140G1148 and R4140G1171 Programmers.

25 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

Optional Hookups for Two-Stage Switching or R4140G PARTIAL SCHEMATIC


Intermittent Pilot/Ignition TO M2B, 2K1, AND L1 L2
1
(Nonmodulating Oil Burners)
20 SECOND
If modulation of the firing rate is not required, an R4140G can 5 INTERRUPTED
be used to provide two-stage switching for an oil burner; also, M4A M6B
PILOT/IGNITION
an R4140G with interrupted pilot/ignition on terminal 6 can be C-60 C-50
O-80
wired to provide an intermittent pilot/ignition. Refer to Fig. 17 O-100 INTERMITTENT
for the necessary wiring changes and make these changes in 2 6 PILOT/IGNITION
OR 1ST STAGE OIL
the field wiring to the Q520A Wiring Subbase. VALVE SOLENOID
쐃 Remove all wiring from terminals 5,6,7,10,11, 12, and 14. JUMPER

쐇 Install a jumper wire between terminals 6 and 7. 7


3

(If using an R4140G1056 or R4140G1064, this jumper


M2A C-70 O-109.5
is not necessary.) JUMPER
쐋 Install a jumper wire between terminals 7 and 11.
쐏 Connect the ignition transformer between terminals 5 10

and L2 (for 20 second interrupted ignition), or between 11


terminals 6 and L2 (for intermittent ignition). M10B MAIN FUEL VALVE
OR 2ND STAGE OIL
쐄 For two-stage switching: O-4
C-45 12 VALVE SOLENOID
a. Connect the first stage oil valve solenoid between M8A C-100 O-112 (ENERGIZED AT
100 SECONDS) 4
terminals 6 and L2. 14 2ND STAGE
CONTROLLER
b. Connect the second stage controller (if used) and (IF USED)
second stage oil valve solenoid in series between
terminals 12 and L2. 1 REFER TO SCHEMATIC DIAGRAMS FOR COMPLETE INTERNAL WIRING
쐂 For an intermittent pilot: AND CONTACT SWITCHING.

a. Connect the intermittent pilot between terminals 6 2 M4A O-85 ON THE R4140G1106, AND R4140G1148; O-110 ON THE
and L2. R4140G1056, R4140G1064, R4140G1114, R4140G1122, AND R4140G1171.

b. Connect the main fuel valve between terminals 3 JUMPER IS NOT NECESSARY TO OBTAIN INTERMITTENT PILOT/IGNITION
12 and L2. ON THE R4140G1056, OR R4140G1064; THESE MODELS PROVIDE
INTERMITTENT PILOT/IGNITION ON TERMINAL 6.

IMPORTANT 4 IF A 2ND STAGE CONTROLLER IS USED, THE 2ND STAGE OIL VALVE
SOLENOID IS NOT ENERGIZED UNTIL THE 2ND STAGE CONTROLLER
The fuel valve or solenoid connected to terminal 12 CONTACTS CLOSE.
must not exceed the electrical rating of terminal 7. M10060

NOTE: The maximum Pilot or First Stage Flame- Fig. 17. Field wiring changes (dashed) to provide
Establishing Period is ten seconds. two-stage switching or intermittent pilot/ignition
for a nonmodulating oil burner.
For a description of the Ignition Trials for this hookup, refer to
Fig. 18 and the Step-by-Step Operation section.

60-2337—3 26
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

TIMER 0 10 20 30 40 50 60 70 80 90 100 110 120


SECONDS

20 SECOND
INTERRUPTED 5
PILOT/IGNITION 1

INTERRUPTED
PILOT/IGNITION 6
OR 1ST STAGE
OIL VALVE
2
RUN
PERIOD
MAIN FUEL VALVE
OR 2ND STAGE 12 3
OIL VALVE

1 TERMINAL NUMBERS (CIRCLED). 3 IF A 2ND STAGE CONTROLLER IS USED, THE 2ND STAGE OIL VALVE
IS ENERGIZED ONLY WHEN THERE IS A DEMAND FOR MORE HEAT
2 TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE AND THE 2ND STAGE CONTROLLER CONTACTS CLOSE.
BURNER FIRING.
M10061

Fig. 18. Partial timer sequence for optional hookups of R4140G Programmers.

Step-By-Step Operation
(for Two-Stage Switching or Intermittent Pilot/
Ignition of a Nonmodulating Oil Burner)
Ignition Trials
60 seconds—M4A closes; power is applied to terminals 5 NOTE: If using two-stage switching with a second stage
and 6, energizing the ignition transformer and pilot controller, the second stage oil valve solenoid
valve (or first stage oil valve solenoid when using two- energizes only when there is a demand for more
stage switching). heat and the second stage controller contacts close.
— When a flame is detected, 2K pulls in, 2K2 opens,
and the LS HTR stops heating; 2K1 and 2K3 close. 104 seconds—M5B opens; timer stops with the system in
70 second—M2B opens; pilot or ignition trial ends; a flame the run condition.
must be detected by this time (2K pulled in and 2K1
closed) or safety shutdown occurs and the lockout NOTE: Intermittent pilot/ignition and all fuel valves and
switch trips. solenoids (terminals 6 and 12) de-energize when the
— M2A closes; power is applied to terminal 7, Run period is complete and the main burner
maintaining power at terminals 6 and 11 (through controller contacts open.
the jumpers) until the Run period is completed.
80 seconds—M6B opens: 20 second interrupted pilot/ For complete installation, checkout, troubleshooting, and
ignition (terminal 5) de-energizes. service information, refer to form 60-0770.
100 seconds—M8A closes; power is applied to terminal
12, energizing the main fuel valve (or second stage oil
valve solenoid when using two-stage switching).

27 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS

Home and Building Control Home and Building Control Honeywell Asia Pacific Inc.
Honeywell Internationsl, Inc. Honeywell Limited-Honeywell Limitée Room 3213-3225
1985 Douglas Drive North 35 Dynamic Drive Sun Hung Kai Centre
Golden Valley, MN 55422 Scarborough, Ontario No. 30 Harbour Road
M1V 4Z9 Wanchai
Hong Kong
Honeywell Latin American Division Honeywell Europe S.A.
Miami Lakes Headquarters 3 Avenue du Bourget
14505 Commerce Way Suite 500 B-1140 Brussels Belgium
Miami Lakes FL 33016

Printed in U.S.A. on recycled


paper containing at least 10%
60-2337—3 E.C. Rev. 8-96
60-2337—3 post-consumer paper28 fibers. www.honeywell.com

You might also like