Interlock Circuits:
SPECIFICATIONS Start Interlocks (R4140G1049, G1056, G1064, G1114,
G1122, G1148 and G1171)—System controls must be
IMPORTANT in proper positions or programmer will not start.
The specifications given in this publication do not Preignition Interlocks (R4140G1007, G1015, and
include normal manufacturing tolerances. Therefore, G1106)—Must be closed to start programmer. Prevent
this unit may not match the listed specifications ignition trials if interlocks open during prepurge; timer
exactly. Also, this product is tested and calibrated recycles the programmer and system restarts if
under closely controlled conditions, and some minor condition is self-correcting.
differences in performance can be expected if those Running Interlocks (all models)—Must be closed (airflow
conditions are changed. must be proven, fuel pressure must not be too low or
too high) within 9.5 seconds after startup or ignition
MODELS: trials cannot be started. Running interlocks must remain
R4140G Flame Safeguard Programming Controls—Flame closed through the Run period or the automatic fuel
Safeguard protection and sequencing controls for use on gas, valves de-energize, the burner flame(s) goes out, and
oil, coal, or combination burners. See Table 1 for models the timer recycles the programmer.
available. Low Fire Interlock (all models)—Timer stops at 52 seconds
until low fire proving switch closes, indicating damper is
closed prior to ignition.
Table 1. Models Available.
Flame-Establishing
Timer Period (sec) Firing Rate
With Cycle Prepurge Early Spark Main Burner Postpurge Interlock Switching
Model Cover a (sec) (sec) Terminationb Pilotc (Field Selectable)c (sec) Circuits Circuit
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number or specify order number. Order separately:
1. Flame detection system (amplifier and matching flame detector). See Table 4.
2. Q520A1089 or Q520A1121 Wiring Subbase.
3. Accessories, if desired.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Logistics
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
60-2337—3 2
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
Safety Features: NOTE: Allowable inrush can be up to ten times the pilot duty
Safe Start Check—For the presence of a flame (or a rating.
condition simulating a flame) provided at startup and
during prepurge. If the flame relay 2K is pulled in at EXAMPLE: Pilot duty rating = 50 VA.
startup, 2K2 is open and the programmer cannot be
started. If the flame relay 2K pulls in during prepurge At 120V, running current is:
(before 57.5 seconds), 2K2 opens, relay 1K drops out,
and ignition trials cannot be started. Instead, the timer
50
completes its revolution and stops at the standby position 120 = 0.42A.
(zero seconds). If the flame relay 2K drops out by the end
of the cycle, the programmer restarts the system.
Safety Shutdown—Ignition transformer and all automatic Maximum allowable inrush is ten times
fuel valves de-energize. The lockout switch trips and 0.42A = 4.2A.
locks out the programmer. If used, the external alarm is
energized. The timer completes its revolution and locks Interlock Ratings:
up at the stand-by position (zero seconds). The lockout See Table 3.
switch must be manually reset to restart the system.
Safety Shutdown occurs on: Table 3. Interlock Ratings.
• Failure to ignite the pilot (or first stage burner if using
direct spark ignition). Requirements must be abIe to
• Failure to light the main burner (unless monitoring Interlocks carry and break current to:
an intermittent pilot). Limits, Burner Controller, Ignition transformer, pilot valve,
• Loss of flame during the Run period. and Running Interlocks and main fuel valve(s).
• Failure in the flame detection system (if a self- (including airflow switch)
checking system is used, see Table 4).
Flame Failure Response Time—2 to 4 seconds. Start or Preignition Programmer relay 1K (5W max).
Lockout Switch Timing—30 seconds (nominal). Interlocks
Electrical Ratings:
Voltage and Frequency: 120 Vac (102V minimum to 132V Ambient Operating Temperature Ratings:
maximum), 50/60 Hz. Minimum: Minus 40°F (minus 40°C).
R4140G1114: 240 Vac, 60 Hz. Maximum:
R4140G1122: 208 Vac, 60 Hz. Programmer Mounting Position
NOTE: Use of a 50 Hz power supply lengthens the Standard Vertical (With Handle Up) Any Other
sequence timings by a factor of 1.2.
+150°F (+66°C) +135°F (+57°C)
Power Consumption (With No Loads Connected to Output Storage Temperature Ratings:
Terminals): 13W maximum. Minus 60°F to plus 150°F (minus 51°C to plus 66°C).
Maximum Total Connected Load: 2000 VA.
Mounting:
Terminal Ratings:
3-sided Q520A1089 Wiring Subbase, or 4-sided Q520A1121
See Table 2.
Wiring Subbase; both have 20 knife-blade contacts (subbase
Table 2. Terminal Ratings. ordered separately).
3 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
35/64
202050C COVER (14)
2-5/64
(53)
1-51/64
7/8 (22) DIAMETER KNOCKOUT (2) (46)
4 L1 18 6
3-3/8 9 L2 17 7
(86)
10 12 16 8
11 G
6-5/32 13 15
(156)
F 14
7-3/16 (183)
202050C COVER
1-3/4
(45)
6
7/8 (22) DIAMETER (152)
15/16 31/32 KNOCKOUT (2)
(25) (2) 1
(24) (2)
5-7/8
1-27/32 3-3/8 (86) (149)
(47)
7 -1/16 (179)
5-5/8
7-3/16 (183) (143)
31/32
(25)
1-13/32 (36) 2-11/32 (60) 1-13/32 (36)
3/4
(19) Fig. 2. Mounting dimensions of the R4140 Programmer
on the Q520A wiring subbase in in. (mm).
7/8 (22) DIAMETER KNOCKOUT (4)
60-2337—3 4
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
NOTE: Neither the R414G1114 or the R4140G1122 can be used with the C7012E or F Purple Peeper Ultraviolet Flame
Detector and with the R7247C Dynamic Self-Check Amplifier.
Plug-In Flame Signal Amplifiers Applicable Flame Detectors
Self- Flame Failure
Type Color Checking Model Response Time Fuel Type Models
Rectification Green No R7247A 2 to 4 sec Gas Rectifying Holdersa:C7004, C7007, C7011.
Flame Rods Complete assemblies: C7005,
C7008, C7009, Q179.
R7247A, 2 to 4 sec Oil Rectifying C7003, C7010, C7013, C7014.
R7247B b Photocells c
Gas, Ultraviolet C7012A or C.
Oil, (Purple
Coal Peeper)
Dynamic R7147B b 2 to 4 sec Gas Rectifying Holdersa: C7004, C7007, C7011.
Self- Flame Rods Complete Assemblies: C7005,
Check C7008, C7009, Q179.
R7247Cd 2 to 4 sec Gas, Ultraviolet C7012E or F
Oil, (Purple
Coal Peeper)
Infrared Red No R7248A 2 to 4 sec Gas, Infrared C7015.
Oil, (Lead
Coal Sulfide)
Dynamic R7248B b 2 to 4 sec Gas, Infrared C7015.
Ampli- Oil, (Lead
Check® Coal Sulfide)
Ultraviolet Purple No R7249A 2 to 4 sec Gas, Ultraviolet C7027, C7035, C7044.
Oil (Minipeeper)
Blue Dynamic R7476A d 2 to 4 sec Gas, Ultraviolet C7076.
Self- Oil, (Adjustable
Check Coal Sensitivity)
a Order flame rod separately; see Instructions for the holder.
b Circuitry tests the flame signal amplifier at least 150 times a minute during burner operation and shuts down the burner if the
amplifier fails.
c Use only Honeywell part no. 38316 Photocell.
d Circuitry tests all electronic components in the flame detection system (amplifier and detector) 60 to 240 times a minute during
burner operation and shuts down the burner if the detection system fails.
5 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
OPERATION
Models with Preignition Interlocks
Fig. 3 shows all contacts in the standby position (zero to each timer contact. Refer to Fig. 4 and the Step-by-Step
seconds). The opening and closing times are shown adjacent Operation section.
1 L1 L2
2 NUMBERS BELOW
DESIGNATE LINE
3 9 13 5 8 12 10 LOCATIONS OF
3
RELAY CONTACTS.
FLAME SIGNAL (UNDERLINE
4 G F
METER JACK INDICATES A
PLUG-IN AMPLIFIER NORMALLY CLOSED
5 CONTACT.)
FLAME
6 DETECTOR 7 M11B
11 16
M9A 1K
17 C-15 O-70 C-57.5 O-109.5
2K - 13, 9, 8
7 TO 1K - 14, 14, 11
17
TIP JACK 2K TERMINAL
8 2
8 LS2
2K3
9 LS - 19, 9
M7A M7B M2B
BURNER C-57.5 O-111 O-9.5 C-116 2K2
10 O-70 LS HTR
LIMITS CONTROLLER
1K3 C-113.5
10 SECOND 3
11 4 16 3 5 INTERRUPTED
PILOT/IGNITION
M4A M6B
12 PREIGNITION RUNNING C-60 C-50 O-80
INTERLOCKS INTERLOCKS 2K1 O-85 4
(INCLUDING 30 SECOND
13 6 INTERRUPTED
1K1 1K2 AIRFLOW SWITCH) PILOT/IGNITION
M2A
14 C-70 5
M5B
O-109.5
15 O-104 MAIN FUEL
7
M3A TEST C-108 VALVES (S)
M1B O-52 C-66 NORM
16 C-4
8 13
LOW FIRE TIMER SWITCH
O-120 SWITCH TIMER MOTOR BURNER MOTOR
17
(BLOWER)
18
LS1
19 9 120 V ALARM
20
HIGH FIRE
21 10 B B
M10A C-4 O-41 COMMON
22 11 R R
M10B O-4 C-45
MODULATE
23 12 W W
M8A C-100 O-112 M8B O-100 C-116
LOW FIRE
24 14 FIRING SERIES 90
RATE CONTROLLER
MOTOR 6
1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION 3 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
AS REQUIRED.
4 30 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
2 TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F
OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING 5 FOR DIRECT SPARK IGNITION (GAS OR OIL,) A JUMPER IS INSTALLED
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17 BETWEEN TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C OF FIELD WIRING FOR HOOKUP.
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK
DIAGRAM OF FIELD WIRING. 6 USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.
M10149
60-2337—3 6
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
PREIGNITION INTERLOCKS 6
RUN 5
RUNNING INTERLOCKS (PROVEN AIRFLOW) PERIOD
IGN MAIN
TIMER DIAL PREPURGE PURGE
PILOT
START
START
START
STOP
STOP
STOP
TIMER
MOTOR 3 5
BURNER
MOTOR 8 1
(BLOWER)
5 10 SECONDS
INTERRUPTED
PILOT/IGNITION
6 30 SECONDS
MAIN FUEL
VALVE(S) 7
(GAS OR OIL)
2 2 2
2
ACTUAL MOTOR 4
DAMPER
OPERATION MOTOR DRIVES
DRIVES DAMPER 3
MOTOR DRIVES
DAMPER CLOSED
DAMPER CLOSED
OPEN
1 TERMINAL NUMBERS (CIRCLED). 4 FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN
2 SLOPE DEPENDS ON MOTOR TIMING. PERIOD WHILE BURNER IS FIRING).
3 TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES. 5 TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE
BURNER FIRING.
Step-By-Step Operation (R4140G1015) and ignition trials cannot be started. Running interlocks
Start And Prepurge must remain closed through the Run period or the
0 seconds—On a call for heat, the burner controller system shuts down; the timer completes its revolution
contacts close. If the limits and preignition interlocks and recycles the programmer.
are closed and flame relay 2K is not holding in, relay 1K 15 seconds—M11B closes; flame relay 2K can pull in if a
pulls in through M7B, LS2, 2K2, and the LS HTR flame (or a condition simulating a flame) is detected. If
(lockout switch heater—thus proving its continuity). detected during prepurge (until 57.5 seconds), 2K pulls
— 1K1 closes and 1K2 opens, timer motor starts in, 2K2 opens, 1K drops out, and the system shuts
(through 1K1, M3A, and M5B), power is applied to down; the timer completes its revolution and recycles
terminal 8, starting the burner motor (blower); 1K3 the programmer (if 2K dropped out).
closes. 45 seconds—M10B closes; firing rate motor drives toward
— Prepurge begins. low fire position (closed).
4 seconds—M10A closes, M10B opens; firing rate motor 52 seconds—M3A opens; timer stops until the low fire
drives toward high fire position (open). proving switch closes; timer can be stopped by opening
—M1B closes, bypassing 1K1; the timer can complete the timer switch (until 66 seconds when M3A closes
its revolution if shutdown occurs. again).
9.5 seconds—M7B opens; running interlocks must close 57.5 seconds—M9A closes; the LS HTR (lockout switch
(airflow must be proven) or 1K drops out, 1K3 opens, heater) begins heating in preparation for ignition trials.
— M7A closes, bypassing the preignition interlocks.
7 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
60-2337—3 8
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
120V, 60 HZ
R4140G1106 SCHEMATIC POWER SUPPLY
L1 L2
(HOT)
1
INTERNAL EXTERNAL
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.
O—OPENING TIME A TIMER CONTACTS SNAP CLOSED.
C—CLOSING TIME
B CONTACTS SNAP OPEN.
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER
MASTER
SWITCH
1 L1 L2
2 NUMBERS BELOW
3 9 13 5 8 12 10 DESIGNATE LINE
3 LOCATIONS
FLAME SIGNAL RELAY CONTACTS.
4 G F METER JACK (UNDERLINE
PLUG-IN AMPLIFIER INDICATES A
5 NORMALLY CLOSED
CONTACT.)
FLAME
6 DETECTOR 7 M11B
11 16
M9A 1K
17 C-15 O-70 C-57.5 O-109.5
2K - 16, 10, 8
7 1K - 17, 17, 12
17 TO 8
2K
8 2
TIP JACK LS2
2K3
9 LS - 22, 8
M7A M7B M2B
BURNER C-57.5 O-111 O-9.5 C-116 2K2
10 O-70 LS HTR
LIMITS CONTROLLER 8
1K3 C-113.5
10 SECOND
11 4 16 3 5 INTERRUPTED
PILOT/IGNITION
M4A M6B 3
12 PREIGNITION RUNNING C-60 C-50 O-80
INTERLOCKS INTERLOCKS 2K1 O-85 9
(INCLUDING 15 SECOND
13 6 INTERRUPTED
1K1 1K2 AIRFLOW SWITCH) PILOT/IGNITION
M2A
14 C-70
M5B 7
O-109.5
15 O-104 MAIN FUEL
7
M3A TEST C-108 VALVES (S) 4
M1B O-52 C-66 NORM
16 C-4
B 13
LOW FIRE TIMER SWITCH 5
O-120 SWITCH TIMER MOTOR BURNER
17 MOTOR
18
LS1
19 9 ALARM
20
HIGH FIRE
21 10 B B
M10A C-4 O-41 COMMON
22 11 R R
M10B O-4 C-45
MODULATE
23 12 W W
M8A C-100 O-112 M8B O-100 C-116
LOW FIRE
24 14 FIRING SERIES 90
RATE CONTROLLER
MOTOR 6
1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED 5 TIMER SWITCH IS SHOWN IN "NORM" POSITION; IT IS OPEN IN "TEST"
POSITION.
2 TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F 6 USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.
PURPLE PEPPER ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17
7 FOR DIRECT SPARK IGNITION (OIL OR GAS), A JUMPER IS INSTALLED
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C
BETWEEN TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK
DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK DIAGRAM
DIAGRAM OF FIELD WIRING FOR HOOKUP.
OF FIELD WIRING.
8 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
3 FOR DIRECT SPARK IGNITION OR OIL, REFER TO SAMPLE BLOCK DIAGRAM
OF FIELD WIRING FOR HOOKUP OF IGNITION AND MAIN OIL VALVE SOLENOID.
9 15 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
4 SOME AUTHORITIES HAVING JURISDICTION PROHIBIT THE WIRING OF ANY LIMIT
OR OPERATING CONTACTS IN SERIES WITH THE MAIN FUEL VALVE(S). M10044
9 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
PREIGNITION INTERLOCKS 6
RUN
RUNNING INTERLOCKS (PROVEN AIRFLOW) PERIOD
IGN MAIN
TIMER DIAL PREPURGE PURGE
PILOT
START
START
START
STOP
STOP
STOP
TIMER
MOTOR 3 5
BURNER
MOTOR 8 1
(BLOWER)
5 10 SECONDS
INTERRUPTED
PILOT/IGNITION
6 15 SECONDS
MAIN FUEL
VALVE(S) 7
(GAS OR OIL)
2 2 2
2
ACTUAL MOTOR 4
DAMPER
OPERATION MOTOR DRIVES
DRIVES DAMPER 3
MOTOR DRIVES
DAMPER CLOSED
DAMPER CLOSED
OPEN
1 TERMINAL NUMBERS (CIRCLED). 4 FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN
2 SLOPE DEPENDS ON MOTOR TIMING. PERIOD WHILE BURNER IS FIRING).
3 TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES. 5 TIMER STOPS AT 164 SECONDS FOR THE RUN PERIOD WITH
THE BURNER FIRING.
60-2337—3 10
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
11 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
120V, 60 HZ
R4140G1049 SCHEMATIC POWER SUPPLY
(WITH/WITHOUT HEAVY DUTY COVER) L1 L2
(HOT) 1
INTERNAL EXTERNAL
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.
O—OPENING TIME A TIMER CONTACTS SNAP CLOSED.
C—CLOSING TIME
B CONTACTS SNAP OPEN.
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER
MASTER
SWITCH
1 L1 L2
2 NUMBERS BELOW
DESIGNATE LINE
3 9 13 5 8 12 10 LOCATIONS OF
3
RELAY CONTACTS.
FLAME SIGNAL (UNDERLINE
4 G F
METER JACK INDICATES A
PLUG-IN AMPLIFIER NORMALLY CLOSED
5 CONTACT.)
FLAME
6 DETECTOR 7 M11B
11 16
17 C-15 O-70
7 M9A 1K
17 TO C-57.5 O-111
TIP JACK 2K 2K - 16, 10, 8
8 2 TERMINAL
8 1K - 17, 17, 12
BURNER START 2K3
9 LIMITS CONTROLLER 3 INTERLOCK(S) 4
10 16 4 LS - 22, 8
M7B
O-9.5 C-116 2K2
11 LS HTR
12 5 SECOND
3 18
M2B IGNITION
1K3 M9B
13 RUNNING INTERLOCKS O-70 C-30
(INCLUDING AIRFLOW SWITCH) C-113.5 O-65 10 SECOND 5
14 5 INTERRUPTED
M4A PILOT/IGNITION
M6B
15 C-60 C-50 O-80
2K1 O-85 6
30 SECOND
16 6 INTERRUPTED
1K1 1K2 PILOT/IGNITION
M2A
17 C-70 7
M5B
O-104 O-109.5
18 7 MAIN FUEL
M3A TEST C-108 VALVES (S)
M1B O-52 C-66 NORM
19 C-4
8 13
LOW FIRE TIMER SWITCH
O-120 SWITCH TIMER MOTOR BURNER MOTOR
20
(BLOWER)
21
LS1
22 9 120 V ALARM
23
HIGH FIRE
24 10 B B
M10A C-4 O-41 COMMON
25 11 R R
M10B O-4 C-45
MODULATE
26 12 W W
M8A C-100 O-112 M8B O-100 C-116
LOW FIRE
27 14 FIRING SERIES 90
RATE CONTROLLER
MOTOR 8
1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION 4 IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED
AS REQUIRED. BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE.
2 TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F 5 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17 6 30 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK 7 FOR DIRECT SPARK IGNITION (GAS OR OIL), A JUMPER IS INSTALLED
DIAGRAM OF FIELD WIRING. BETWEEN TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM
OF FIELD WIRING FOR HOOKUP.
3 TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT.
8 USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.
M10155
60-2337—3 12
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
6
RUN 5
RUNNING INTERLOCKS (PROVEN AIRFLOW) PERIOD
IGN MAIN
TIMER DIAL PREPURGE PURGE
PILOT
START
START
START
STOP
STOP
STOP
TIMER
MOTOR 3 5
BURNER
MOTOR 8 1
(BLOWER)
5 SECOND 18
IGNITION
5 10 SECONDS
INTERRUPTED
PILOT/IGNITION
6 30 SECONDS
MAIN FUEL
VALVE(S) 7
(GAS OR OIL)
2 2 2
2
ACTUAL MOTOR 4
DAMPER
OPERATION MOTOR DRIVES
DRIVES DAMPER 3
MOTOR DRIVES
DAMPER CLOSED
DAMPER CLOSED
OPEN
1 TERMINAL NUMBERS (CIRCLED). 4 FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN
2 SLOPE DEPENDS ON MOTOR TIMING. PERIOD WHILE BURNER IS FIRING).
3 TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES. 5 TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE
BURNER FIRING.
13 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
60-2337—3 14
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
120V, 60 HZ
R4140G1056/G1064 SCHEMATIC POWER SUPPLY
(WITH/WITHOUT HEAVY DUTY COVER) L1 L2
(HOT) 1
INTERNAL EXTERNAL
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.
O—OPENING TIME A TIMER CONTACTS SNAP CLOSED.
C—CLOSING TIME
B CONTACTS SNAP OPEN.
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER
MASTER
SWITCH
1 L1 L2
2 NUMBERS BELOW
DESIGNATE LINE
3 9 13 5 8 12 10 LOCATIONS OF
3
RELAY CONTACTS.
FLAME SIGNAL (UNDERLINE
4 G F
METER JACK INDICATES A
PLUG-IN AMPLIFIER NORMALLY CLOSED
5 CONTACT.)
FLAME
6 DETECTOR 7 M11B
11 16
17 C-15 O-70
7 M7A 1K
2K - 16, 10, 8
17 TO C-57.5 O-111
TIP JACK 2K
8 2 TERMINAL 1K - 17, 17, 12
8
BURNER START 2K3 LS2
9 LIMITS CONTROLLER 3 INTERLOCK(S) 4
10 16 4 LS - 22, 8
M7B
O-9.5 C-116 2K2
11 LS HTR
12 5 SECOND
3 18
M2B IGNITION
1K3 M9B
13 RUNNING INTERLOCKS O-70 C-30
(INCLUDING AIRFLOW SWITCH) C-113.5 O-65 10 SECOND 5
14 5 INTERRUPTED
M4A PILOT/IGNITION
M6B
15 C-60 C-50 O-80 6
2K1 O-110
16 6 INTERMITTENT
1K1 1K2 PILOT/IGNITION
M2A
17 C-70
M5B
O-104 O-109.5
18 7 MAIN FUEL
M3A TEST C-108 VALVES (S)
M1B O-52 C-66 NORM
19 C-4
8 13
LOW FIRE TIMER SWITCH
O-120 SWITCH TIMER MOTOR BURNER MOTOR
20
(BLOWER)
21
LS1
22 9 120V ALARM
23
HIGH FIRE
24 10 B B
M10A C-4 O-41 COMMON
25 11 R R
M10B O-4 C-45
MODULATE
26 12 W W
M8A C-100 O-112 M8B O-100 C-116
LOW FIRE
27 14 FIRING SERIES 90
RATE CONTROLLER
MOTOR 7
1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION 4 IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED
AS REQUIRED. BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE.
2 TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F 5 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17 6 FOR DIRECT SPARK IGNITION (GAS OR OIL), REFER TO SAMPLE
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C BLOCK DIAGRAM OF FIELD WIRING FOR HOOKUP.
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK
DIAGRAM OF FIELD WIRING. 7 USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.
M10156
3 TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT.
15 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
6
RUN 5
RUNNING INTERLOCKS (PROVEN AIRFLOW) PERIOD
IGN MAIN
TIMER DIAL PREPURGE PURGE
PILOT
START
START
START
STOP
STOP
STOP
TIMER
MOTOR 3 5
BURNER
MOTOR 8 1
(BLOWER)
5 SECOND
IGNITION 18
10 SECOND
INTERRUPTED 5
PILOT/IGNITION
INTERMITTENT PILOT
OR 1ST STAGE 6
FUEL VALVE
MAIN FUEL
VALVE(S) 7
(GAS OR OIL)
2 2 2
2
ACTUAL 4
DAMPER MOTOR
OPERATION MOTOR
DRIVES
DRIVES 3
DAMPER MOTOR DRIVES
DAMPER
CLOSED DAMPER CLOSED
OPEN
1 TERMINAL NUMBERS (CIRCLED). 4 FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN
2 SLOPE DEPENDS ON MOTOR TIMING. PERIOD WHILE BURNER IS FIRING).
3 TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES. 5 TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE
BURNER FIRING.
Step-By-Step Operation
(R4140G1056 and R4140G1064) opens, and ignition trials cannot be started. Running
Start and Prepurge interlocks must remain closed through the Run period
0 seconds—On a call for heat, the burner controller or the system shuts down; the timer completes its
contacts close. If the limits and start interlock(s) are revolution and recycles the programmer.
closed and flame relay 2K is not holding in, relay 1K 15 seconds—M11B closes; flame relay 2K can pull in if a
pulls in through M7B, 2K2, the LS HTR (lockout switch flame (or a condition simulating a flame) is detected If
heater—thus proving its continuity), and LS2. detected during prepurge (until 57.5 seconds), 2K pulls
— 1K1 closes and 1K2 opens; timer motor starts in, 2K2 opens, 1K drops out, and the system shuts
(through 1K1, M3A, and M5B); power is applied to down; the timer completes its revolution and recycles
terminal 8, starting the burner motor (blower); 1K3 the programmer (if 2K dropped out).
closes. 45 seconds—M10B closes; firing rate motor drives toward
— Prepurge begins. low fire position (closed).
4 seconds—M10A closes, M10B opens; firing rate motor 52 seconds—M3A opens; timer stops until the low fire
drives toward high fire position (open). proving switch closes; timer can be stopped by opening
— M1B closes, bypassing 1K1; the timer can the timer switch (until 66 seconds when M3A closes
complete its revolution if shutdown occurs. again).
9.5 seconds—M7B opens; running interlocks must be 57.5 seconds—M7A closes; the LS HTR (lockout switch
closed (airflow must be proven) or 1K drops out, 1K3 heater) begins heating in preparation for ignition trials.
60-2337—3 16
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
17 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
120V, 60 HZ
POWER SUPPLY
L1 L2
(HOT) 1
INTERNAL EXTERNAL
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.
O—OPENING TIME A TIMER CONTACTS SNAP CLOSED.
C—CLOSING TIME B CONTACTS SNAP OPEN.
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER
MASTER
SWITCH
1 L1 L2
2 NUMBERS BELOW
DESIGNATE LINE
3 9 13 5 8 12 10 LOCATIONS OF
3
RELAY CONTACTS.
FLAME SIGNAL (UNDERLINE
4 G F
METER JACK INDICATES A
PLUG-IN AMPLIFIER NORMALLY CLOSED
5 CONTACT.)
FLAME
6 DETECTOR 7 M11B
11 16
17 C-15 O-70
7 M7A 1K
2K - 8, 10, 16
17 TO C-67 O-168
TIP JACK 2K
8 2 TERMINAL 1K - 12, 17, 17
8
BURNER 2K3 LS2
9 START
LIMITS CONTROLLER 3 INTERLOCK(S) 4
10 16 4 LS - 8, 22,
M7B
O-13.5 C-174 2K2
11 LS HTR
12 5 SECOND
3 18
M2B IGNITION
1K3 M9B
13 RUNNING INTERLOCKS O-80 C-40 O-75
(INCLUDING AIRFLOW SWITCH) C-169
10 SECOND
14 5 INTERRUPTED
M6B PILOT/IGNITION
M4A C-60 O-90
15 C-70
2K1 O-110 30 OR 60 SECOND
16 6 INTERRUPTED
1K1 1K2 PILOT/IGNITION 5
5 M12B
17 C-90 6
M5B
O-140
18 O-155 MAIN FUEL
7
M3A TEST C-164 M2A C-80 VALVES (S) 7
M1B O-60 C-76 NORM O-163
19 C-6
8 13
LOW FIRE TIMER SWITCH
O-180 SWITCH 8 TIMER MOTOR
20 BURNER MOTOR
(BLOWER)
21
LS1
22 9 120V ALARM
23
HIGH FIRE
24 10 B B
M10A C-5 O-34 COMMON
25 11 R R
M10B O-5 C-40
MODULATE
26 12 W W
M8A C-148 O-168 M8B O-148 C-174
LOW FIRE
27 14 FIRING SERIES 90
RATE CONTROLLER
MOTOR 9
1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION 5 A JUMPER IS INSTALLED ON THE BACK OF THE PROGRAMMER TO OBTAIN 60
AS REQUIRED. SECOND INTERRUPTED PILOT/IGNITION AT TERMINAL 6; WITHOUT JUMPER,
IT IS 30 SECONDS.
2 TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR
F OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING 6 FOR DIRECT SPARK IGNITION OF OIL, A JUMPER IS INSTALLED BETWEEN
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17 TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM OF FIELD WIRING FOR
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C HOOKUP OF IGNITION AND MAIN OIL VALVE SOLENOID.
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE 7
BLOCK DIAGRAM OF FIELD WIRING. SOME AUTHORITIES HAVING JURISDICTION PROHIBIT THE WIRING OF ANY LIMIT OR
OPERATING CONTACTS IN SERIES WITH THE MAIN FUEL VALVE(S).
3 TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT. 8
TIMER SWITCH IS SHOWN IN NORM POSITION; IT IS OPEN IN TEST POSITION.
4 IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED 9
BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE. USE A SERIES 90 MODULATING MOTOR. M10158
Fig. 11. Simplified schematic diagram of R4140G1171, R4140G122 and R4140G1114 Programmers.
60-2337—3 18
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
TIMER 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180
SECONDS
IGN MAIN
TIMER DIAL PREPURGE PURGE
PILOT
START
START
START
STOP
STOP
STOP
TIMER MOTOR 3 5
BURNER
MOTOR 8 1
(BLOWER)
5 SECOND
INGITION 18
5 10 SECONDS
INTERRUPTED
PILOT/INGITION 6 30 SECONDS (WITHOUT JUMPER)
MAIN FUEL
VALVE(S) 7
(GAS OR OIL)
1 TERMINAL NUMBERS (CIRCLED). 4 FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 148 TO 168 SECONDS (INCLUDING RUN
2 SLOPE DEPENDS ON MOTOR TIMING. PERIOD WHILE BURNER IS FIRING).
3 TIMER STOPS AT 60 SECONDS UNTIL LOW FIRE PROVING 5 TIMER STOPS FOR THE RUN PERIOD WITH THE BURNER FIRING.
SWITCH CLOSES.
6 RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)
MUST REMAIN CLOSED THROUGH THE RUN PERIOD.
M10057
Fig. 12. Timer sequence for R4140G1171, R4140G1122 and R4140G1114 Programmers.
Step-By-Step Operation
(R4140G1171, R4140G1122 and R4140G1114)
Start and Prepurge
0 seconds—On a call for heat, the burner controller contacts down; the timer completes its revolution and recycles
close. If the limits and start interlock(s) are closed, relay the programmer.
1K pulls in through M7B, 2K2, the LS HTR (lockout 13.5 seconds—M7B opens; running interlocks must be
switch heater—thus proving its continuity), and LS2. closed (airflow must be proven) or 1K drops out, 1K3
— 1K1 closes and 1K2 opens; timer starts (through opens, and ignition trials cannot be started. Running
M3A and M5B); power is applied to terminal 8, interlocks must remain closed through the Run period
starting the burner motor (blower); 1K3 closes. or the system shuts down; the timer completes its
— Prepurge begins. revolution and recycles the programmer.
5 seconds—M10A closes, M10B opens; firing rate motor 40 seconds—M10B closes; firing rate motor drives toward
drives toward high fire position (open). low fire position (closed).
6 seconds—M1B closes, bypassing 1K1; the timer 60 seconds—M3A opens; timer stops until the low fire
completes its revolution if shutdown occurs. proving switch closes; timer can be stopped by opening
10 seconds—M11B closes; flame relay 2K can pull in if a the timer switch (until 76 seconds when M3A closes
flame (or a condition simulating a flame) is detected. If again).
detected during prepurge (until 67 seconds), 2K pulls 67 seconds—M7A closes; the LS HTR (lockout switch
in, 2K2 opens, 1K drops out, and the system shuts heater) begins heating in preparation for ignition trials.
19 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
Ignition Trials 148 seconds—M8A closes, M8B opens; firing rate motor is
70 seconds—M4A closes; power is applied to terminals released to modulate under control of the Series 90
18, 5 and 6, energizing the ignition transformer and Controller.
pilot valve (and terminal 7, main oil valve solenoid, if 155 seconds—M5B opens; timer stops with the system in
using direct spark ignition of oil). the Run condition.
— When flame is detected, relay 2K pulls in, 2K2
opens, and the LS HTR stops heating; 2K1 and
2K3 close. Run Period (Burner is Firing)
75 seconds—M9B opens; 5 second ignition (terminals 18) Postpurge and Stop
de-energizes (pilot only until 80 seconds). 155 seconds—When the operating setpoint is reached, the
76 seconds—M3A closes, bypassing the low fire switch burner controller contacts open; relay 1K and the main
and the timer switch. fuel valve(s) (terminal 7) de-energizes.
80 seconds—M2B opens; pilot or ignition trial ends; flame — 1K2 closes; timer motor starts; postpurge begins.
must be detected by this time (2K pulled in and 2K1 — When flame goes out, relay 2K drops out.
closed) or safety shutdown occurs and the lockout 168 seconds—M8A opens; firing rate motor stops
switch trips. modulating under control of the Series 90 Controller.
— M2A closes; power is applied to terminal 7, 174 seconds—M8B closes; firing rate motor drives toward
energizing the main fuel valve(s). low fire position (closed).
— M11B opens; prevents 2K from pulling in after this 180 seconds—M1B opens; timer and burner motor stop;
time. cycle ends.
90 seconds—M6B opens; 10 second interrupted pilot/
ignition (terminal 5) de-energizes. Fig. 13 shows all contacts in the standby position (zero
110 seconds—M4A opens; 30 second interrupted pilot/ seconds). The opening and closing times are shown adjacent
ignition (terminal 6) de-energizes if jumper was not to each timer contact. Refer to Fig. 14 and the Step-by-Step
installed on back of programmer. Operation section.
140 seconds—M12B opens; 60 second interrupted pilot/
ignition (terminal 6) de-energizes if jumper was installed
on back of programmer.
60-2337—3 20
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
120V, 60 HZ
R4140G1148 SCHEMATIC POWER SUPPLY
(WITH/WITHOUT HEAVY DUTY COVER) L1 L2
(HOT) 1
INTERNAL EXTERNAL
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.
O—OPENING TIME A TIMER CONTACTS SNAP CLOSED.
C—CLOSING TIME
B CONTACTS SNAP OPEN.
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER
MASTER
SWITCH
1 L1 L2
2 NUMBERS BELOW
DESIGNATE LINE
3 9 13 5 8 12 10 LOCATIONS OF
3
RELAY CONTACTS.
FLAME SIGNAL (UNDERLINE
4 G F
METER JACK INDICATES A
PLUG-IN AMPLIFIER NORMALLY CLOSED
5 CONTACT.)
FLAME
6 DETECTOR 7 M11B
11 16
17 C-15 O-70
7 M9A 1K
2K - 16, 10, 8
17 TO C-57.5 O-111
TIP JACK 2K
8 2 TERMINAL 1K - 17, 17, 12
8
BURNER 2K3 LS2
9 START
LIMITS CONTROLLER 3 INTERLOCK(S) 4
10 16 4 LS - 22, 8
M7B
O-9.5 C-116 2K2
11 LS HTR
12 5 SECOND
3 18
M2B IGNITION
1K3 M9B
13 RUNNING INTERLOCKS O-70 C-30 O-65
(INCLUDING AIRFLOW SWITCH) C-113.5
10 SECOND 5
14 5 INTERRUPTED
M4A PILOT/IGNITION
M6B
15 C-60 C-50 O-80
2K1 O-85 6
15 SECOND
16 6 INTERRUPTED
1K1 1K2 PILOT/IGNITION
M2A
17 C-70 7
M5B
O-104 O-109.5
18 7 MAIN FUEL
M3A TEST C-108 VALVES (S)
M1B O-52 C-66 NORM
19 C-4
8 13
LOW FIRE TIMER SWITCH
O-120 SWITCH TIMER MOTOR BURNER MOTOR
20
(BLOWER)
21
LS1
22 9 120V ALARM
23
HIGH FIRE
24 10 B B
M10A C-4 O-41 COMMON
25 11 R R
M10B O-4 C-45
MODULATE
26 12 W W
M8A C-100 O-112 M8B O-100 C-116
LOW FIRE
27 14 FIRING SERIES 90
RATE CONTROLLER
MOTOR 8
1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION 4 IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED
AS REQUIRED. BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE.
2 TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F 5 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17 6 15 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK 7 FOR DIRECT SPARK IGNITION (GAS OR OIL), A JUMPER IS INSTALLED
DIAGRAM OF FIELD WIRING. BETWEEN TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM
OF FIELD WIRING FOR HOOKUP.
3 TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT.
8 USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED. M10157
21 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
6
RUN 5
RUNNING INTERLOCKS (PROVEN AIRFLOW) PERIOD
IGN MAIN
TIMER DIAL PREPURGE PURGE
PILOT
START
START
START
STOP
STOP
STOP
TIMER
MOTOR 3 5
BURNER
MOTOR 8 1
(BLOWER)
5 SECOND 18
IGNITION
5 10 SECONDS
INTERRUPTED
PILOT/IGNITION
6 15 SECONDS
MAIN FUEL
VALVE(S) 7
(GAS OR OIL)
2 2 2
2
ACTUAL MOTOR 4
DAMPER
OPERATION MOTOR DRIVES
DRIVES DAMPER 3
MOTOR DRIVES
DAMPER CLOSED
DAMPER CLOSED
OPEN
1 TERMINAL NUMBERS (CIRCLED). 4 FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN
2 SLOPE DEPENDS ON MOTOR TIMING. PERIOD WHILE BURNER IS FIRING).
3 TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING 5 TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE
SWITCH CLOSES. BURNER FIRING.
60-2337—3 22
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
23 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
IGNITION
5
TRANSFORMER
JUMPER
TO 6
L2
MAIN FUEL
VALVE (S) 7
2
WIRING
SUBBASE RUNNING
TERMINAL INTERLOCKS
STRIP (4) (INCLUDING
AIRFLOW SWITCH) 10 SECOND
3 5
INTERRUPTED
3 PILOT/IGNITION
PREIGNITION
INTERLOCK(S) 5
18 30 (OR 15) SECOND
INTERRUPTED 6
BURNER
4 LIMITS L1 PILOT/IGNITION 4
CONTROLLER
17 MAIN FUEL 7
VALVE(S)
L2 9
9 120V ALARM
16
BURNER MOTOR 8
(BLOWER)
HIGH FIRE
10 12
15
LOW FIRE
COMMON SWITCH G
11
13 14
RECTIFYING FLAME
ROD, RECTIFYING
PHOTOCELL, OR
B B INFRARED
F 6 (LEAD SULFIDE)
R R FLAME DETECTOR
MODULATE
OR
LOW FIRE
W W
BLUE C7027A, C7035A, OR WHITE
C7044A ULTRAVIOLET
SERIES 90 SERIES 90 FLAME DETECTOR
CONTROLLER FIRING RATE OR
MOTOR
BLUE C7012A,C,E,F YELLOW
1 OR C7076A 7
120V, 60 HZ L1 (HOT) ULTRAVIOLET
POWER FLAME DETECTOR
L2 WHITE
SUPPLY
MASTER
SWITCH WHITE 10
L2
BLACK
L1
7 BLACK
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD L2
1
PROTECTION AS REQUIRED.
7 C7012 OR C7076 MUST BE RATED FOR 120 V, 60Hz. TWO DETECTORS
2 USE ALL NEC CLASS 1 WIRING. WITH THE SAME MODEL NUMBER CAN BE WIRED IN PARALLEL TO
THE SAME TERMINALS. C7076A DOES NOT HAVE LEADWIRES. (FOR
3 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD. INSTRUCTIONS, SEE FORM NUMBERS: 60-2046 FOR C7012A,C MODELS
WITH ELECTRON TUBES; 60-2044 FOR C7012E,F MODELS WITH ELECTRON
4 30 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD (MBFEP) ON TUBES; 60-2398 FOR C7012A,C,E,F SOLID STATE MODELS; 95-8269 FOR
THE R4140G1007 and R4140G1015 MODELS; 15 SECOND MBFEP ON THE C7076A.)
THE R4140G1106 MODEL.
8 WHITE SHUTTER LEADWIRES ARE ONLY ON THE C7012E OR F PURPLE PEEPER
5 FOR DIRECT SPARK IGNITION (OIL OR GAS) CONNECT THE IGNITION ULTRAVIOLET FLAME DETECTORS WITH SELF-CHECKING FEATURE; C7076A
TRANSFROMER AND FUEL VALVE(S) AS SHOWN IN THE INSET. ADJUSTABLE SENSITIVITY ULTRAVIOLET FLAME DETECTORS DO NOT
HAVE LEADWIRES.
6 FOR THE C7015A INFRARED (LEAD SULFIDE) FLAME DETECTOR, EITHER
LEADWIRE CAN BE CONNECTED TO THE F TERMINAL. RUN THE C7015A 9 TERMINAL 17 IS USED ONLY FOR THE SHUTTER ON SELF-CHECKING
LEADWIRES ALONE IN CONDUIT ALL THE WAY TO THE WIRING SUBBASE C7012E,F OR C7076A FLAME DETECTORS.
AND GROUND THE CONDUIT AT THE SUBBASE. (REFER TO PUBLICATION M10131
60-2306 FOR DETAILED INSTRUCTIONS.)
Fig. 15. Sample block diagram of field wiring for R4140G1007, R4140G1015 and R4140G1106 Programmers.
60-2337—3 24
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
FOR DIRECT SPARK IGNITION (OIL OR GAS) FOR DIRECT SPARK IGNITION (OIL OR GAS)
ON MODELS WITH INTERRUPTED ON MODELS WITH INTERMITTENT
PILOT/IGNITION ON TERMINAL 6 PILOT/IGNITION ON TERMINAL 6.
IGNITION IGNITION 5
5
TRANSFORMER TRANSFORMER
JUMPER
1ST STAGE 6
TO 6 TO FUEL VALVE
L2 L2
2 5 SECOND IGNITION
WIRING (EARLY SPARK
SUBBASE 4
RUNNING TERMINATION)
TERMINAL INTERLOCKS
STRIP (4) (INCLUDING
AIRFLOW SWITCH) 10 SECOND
5 5
INTERRUPTED
3 PILOT/IGNITION
START
INTERLOCK(S) 3
7
18
PILOT/IGNITION 6
BURNER LIMITS 6
4 L1
CONTROLLER
17 MAIN FUEL 7
VALVE(S) 4
L2 11
9 ALARM
16
BURNER MOTOR 8
(BLOWER)
12
HIGH FIRE
10 12
15
LOW FIRE
COMMON SWITCH G
11
13 14
RECTIFYING FLAME
ROD, RECTIFYING
PHOTOCELL, OR
B B INFRARED
F 8 (LEAD SULFIDE)
R R FLAME DETECTOR
MODULATE
OR
LOW FIRE
W W
BLUE C7027A, C7035A, OR WHITE
C7044A ULTRAVIOLET
SERIES 90 SERIES 90 FLAME DETECTOR
CONTROLLER FIRING RATE OR
MOTOR
BLUE C7012A,C,E,F YELLOW
1 OR C7076A 9
120V, 60 HZ L1 (HOT) ULTRAVIOLET
POWER FLAME DETECTOR
L2 WHITE
SUPPLY
MASTER
SWITCH WHITE 10
L2
BLACK
L1
9 BLACK
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD L2
1
PROTECTION AS REQUIRED.
8 FOR THE C7015A INFRARED (LEAD SULFIDE) FLAME DETECTOR, EITHER
2 USE ALL NEC CLASS 1 WIRING. LEADWIRE CAN BE CONNECTED TO THE F TERMINAL. RUN THE C7015A
LEADWIRES ALONE IN CONDUIT ALL THE WAY TO THE WIRING SUBBASE
3 IF START INTERLOCK(S) IS NOT USED, INSTALL A JUMPER AND GROUND THE CONDUIT AT THE SUBBASE. (REFER TO PUBLICATION
BETWEEN TERMINALS 4 AND 16. 60-2306 FOR DETAILED INSTRUCTIONS.)
4 5 SECOND IGNITION IS AVAILABLE ONLY ON THE R4140G1049, 9 C7012 OR C7076 MUST BE RATED FOR 120V, 60Hz. TWO DETECTORS
G1056, G1064, G1114, G1122, G1148, AND G1171 MODELS. WITH THE SAME MODEL NUMBER CAN BE WIRED IN PARALLEL TO
THE SAME TERMINALS. C7076A DOES NOT HAVE LEADWIRES. (FOR
5 10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD. ON R4140G114, INSTRUCTIONS SEE FORM NUMBERS; 60-2046 FOR C7012A, C MODELS
G1122, G1171 FOR 60 SECOND INTERRUPTED PILOT IGNITION, INSTALL WITH ELECTRON TUBES; 60-2044 FOR C7012E,F MODELS WITH ELECTRON
JUMPER (IN 4074B2V BAG ASSEMBLY) ON BACK OF PROGRAMMER TUBES; 60-2398 FOR C7012A,C,E,F SOLID STATE MODELS; 95-8269 FOR THE
BETWEEN SCREW TERMINALS LABELED "JUMPER TO EXTEND MAIN C7076A.) C7012E,F UV FLAME DETECTORS WITH SELF CHECKING FEATURE
IGNITION TRIAL." CANNOT BE USED WITH THE R4140G1122 OR R4140G1114.
6 30 SECOND INTERRUPTED PILOT/IGNITION (30 SECOND MAIN BURNER 10 WHITE SHUTTER LEADWIRES ARE ONLY ON THE C7012E OR F PURPLE PEEPER
FLAME-ESTABLISHING PERIOD, MBFEP) ON THE R4140 AND ULTRAVIOLET FLAME DETECTORS WITH SELF-CHECKING FEATURE; C7076A
R4140G1049, G1114, G1122, G1171, 15 SECOND INTERRUPTED PILOT/ ADJUSTABLE SENSITIVITY ULTRAVILOET FLAME DETECTOR DO NOT
IGNITION (15 SECOND MBFEP) ON THE R4140G1148. INTERMITTENT HAVE LEADWIRES.
PILOT/IGNITION ON THE R4140G1056, AND R4140G1064.
11 TERMINAL 17 IS USED ONLY FOR THE SHUTTER ON SELF-CHECKING
7 FOR DIRECT SPARK IGNITION (OIL OR GAS) CONNECT THE IGNITION C7012E,F OR C7076A FLAME DETECTORS.
TRANSFROMER AND FUEL VALVE(S) AS SHOWN IN THE APPROPRIATE INSET.
12 TERMINAL 16 IS USED ONLY AS A TIE POINT. M10059
Fig. 16. Sample block diagram of field wiring for R4140G1049, R4140G1056, R4140G1064,
R4140G1114, R4140G1122, R4140G1148 and R4140G1171 Programmers.
25 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
a. Connect the intermittent pilot between terminals 6 2 M4A O-85 ON THE R4140G1106, AND R4140G1148; O-110 ON THE
and L2. R4140G1056, R4140G1064, R4140G1114, R4140G1122, AND R4140G1171.
b. Connect the main fuel valve between terminals 3 JUMPER IS NOT NECESSARY TO OBTAIN INTERMITTENT PILOT/IGNITION
12 and L2. ON THE R4140G1056, OR R4140G1064; THESE MODELS PROVIDE
INTERMITTENT PILOT/IGNITION ON TERMINAL 6.
IMPORTANT 4 IF A 2ND STAGE CONTROLLER IS USED, THE 2ND STAGE OIL VALVE
SOLENOID IS NOT ENERGIZED UNTIL THE 2ND STAGE CONTROLLER
The fuel valve or solenoid connected to terminal 12 CONTACTS CLOSE.
must not exceed the electrical rating of terminal 7. M10060
NOTE: The maximum Pilot or First Stage Flame- Fig. 17. Field wiring changes (dashed) to provide
Establishing Period is ten seconds. two-stage switching or intermittent pilot/ignition
for a nonmodulating oil burner.
For a description of the Ignition Trials for this hookup, refer to
Fig. 18 and the Step-by-Step Operation section.
60-2337—3 26
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
20 SECOND
INTERRUPTED 5
PILOT/IGNITION 1
INTERRUPTED
PILOT/IGNITION 6
OR 1ST STAGE
OIL VALVE
2
RUN
PERIOD
MAIN FUEL VALVE
OR 2ND STAGE 12 3
OIL VALVE
1 TERMINAL NUMBERS (CIRCLED). 3 IF A 2ND STAGE CONTROLLER IS USED, THE 2ND STAGE OIL VALVE
IS ENERGIZED ONLY WHEN THERE IS A DEMAND FOR MORE HEAT
2 TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE AND THE 2ND STAGE CONTROLLER CONTACTS CLOSE.
BURNER FIRING.
M10061
Fig. 18. Partial timer sequence for optional hookups of R4140G Programmers.
Step-By-Step Operation
(for Two-Stage Switching or Intermittent Pilot/
Ignition of a Nonmodulating Oil Burner)
Ignition Trials
60 seconds—M4A closes; power is applied to terminals 5 NOTE: If using two-stage switching with a second stage
and 6, energizing the ignition transformer and pilot controller, the second stage oil valve solenoid
valve (or first stage oil valve solenoid when using two- energizes only when there is a demand for more
stage switching). heat and the second stage controller contacts close.
— When a flame is detected, 2K pulls in, 2K2 opens,
and the LS HTR stops heating; 2K1 and 2K3 close. 104 seconds—M5B opens; timer stops with the system in
70 second—M2B opens; pilot or ignition trial ends; a flame the run condition.
must be detected by this time (2K pulled in and 2K1
closed) or safety shutdown occurs and the lockout NOTE: Intermittent pilot/ignition and all fuel valves and
switch trips. solenoids (terminals 6 and 12) de-energize when the
— M2A closes; power is applied to terminal 7, Run period is complete and the main burner
maintaining power at terminals 6 and 11 (through controller contacts open.
the jumpers) until the Run period is completed.
80 seconds—M6B opens: 20 second interrupted pilot/ For complete installation, checkout, troubleshooting, and
ignition (terminal 5) de-energizes. service information, refer to form 60-0770.
100 seconds—M8A closes; power is applied to terminal
12, energizing the main fuel valve (or second stage oil
valve solenoid when using two-stage switching).
27 60-2337—3
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS
Home and Building Control Home and Building Control Honeywell Asia Pacific Inc.
Honeywell Internationsl, Inc. Honeywell Limited-Honeywell Limitée Room 3213-3225
1985 Douglas Drive North 35 Dynamic Drive Sun Hung Kai Centre
Golden Valley, MN 55422 Scarborough, Ontario No. 30 Harbour Road
M1V 4Z9 Wanchai
Hong Kong
Honeywell Latin American Division Honeywell Europe S.A.
Miami Lakes Headquarters 3 Avenue du Bourget
14505 Commerce Way Suite 500 B-1140 Brussels Belgium
Miami Lakes FL 33016