Designation : PANEL ''C'' Mounting: SURFACE MOUNTED

System : Enclosure: NEMA - 12


Location : ELECTRICAL ROOM Feed: TOP

CONNECTED LOAD OVERCURRENT CONDUCTORS


CKT. PROTECTION (CU. WIRE) RACEWAY QUANTITY REMARKS
LOAD DESCRIPTION AMPERE
NO. VA
AT AF P SIZE (MM2) TYPE SIZE TYPE CO LIGHT MOTOR
1 138894 354.8 300 400 3 PVC SEE REMARKS ON
PANEL C1 3-50 + 1-14 (G) THHN
PANEL "C1"
2 ECB-C2 28391 59.9 35.3 44.8 50 100 3 3-22 + 1-8.0 (G) THHN PVC

TOTAL 167287 354.8 59.9 35.3 44.8

UPGRADE MAIN
I
T DEMANDED LINE CURRENT: = [ 354.8+(1.732 X 59.9) A ] X 0.8DF + (0.25 X 10.6) EXISTING PROTECTION: 300AT/400AF, 3P,500V, 60HZ BOLT-ON, MCCB PROTECTION TO
= 369.5 AMPS EXISTING SUB-FEEDER: 2 SETS 3 - 100MM2 THHN + 1 - 14MM2 THHN (G) IN 50MM DIA. CONDUIT 400A, 3P

NOTE: PANEL C1 PRIMARY LINE CURRENT IS MULTIPLIED BY


SECONDARY TO PRIMARY VOLTAGE RATIO OF DRY TYPE
TRANSFORMER (380V/220V) (Vs/Vp = Ip/Is)