Write-up for Fire Alarm System
DOC. NO. WͲsϬͲϯϲϮͲϱϮϮͲϬϵϯ REV ϭ PAGES 8
Compliance sheet – Write-up for Fire Alarm System - Rev.01-DOC No: PE-V0-362-522-A093.
DRAWING
S. No. GMW DRG.NO BHEL Comments GMW Reply
TITLE
Write up for
PE-V0-362-522- Incorporated in the drawing and submitted for
1 Fire Alarm Page-1 : Title Sheet: Rev is mentioned as A
A093 Approval
System
Fire alarm control panels will have built in battery
charger and this charger will charge Maintenance
free Lead Acid Battery only. As the built in Power
supply is microprocessor based type and
interconnected to Panel CPU and it will control the
charging, healthiness and troubles of all parameters
of Battery and indicate through LCD display. The
built in battery charger will not charge the Ni-Cd
batteries.
Page-5: Ni-Cd type Battery to be provided as If we use the Ni-Cd batteries with separate battery
mentioned in the Design philosophy. Please charger, we will not get any charging, healthiness
cross check and correct. and troubles indication through the display. Due to
this reason we have requested to use the Maintenance
free Lead acid batteries in our fire alarm control
panels
CONTENTS
1.0 GENERAL
1.0 GENERAL
This technical specification covers the Fire Alarm System, which is a part of
Fire Protection system provided for the 2 x 800 MW YERAMARUS STPS to
be set up by Raichur Power Corporation Limited at Yeramarus, Raichur
district Karnataka.
The design & installation of Fire Alarm & Detection system for the subject
project has been designed as per the specification requirements & comply
with the latest applicable Indian/British/American standards/codes. The
following standards/codes shall be followed in particular:
All the systems are designed in such a way so as to make the system
complete and acceptable to TAC/nominated agency of insurance companies.
The Fire Detection and Alarm System will provide instantaneous Audio Alarm
when Fire is detected, in order to prevent loss of life, property and valuables
etc by warning inhabitants in the affected premises immediately, so as to
obtain necessary help from Fire Fighting and Salvage Staff.
The Fire Detection & Alarm System for this project is provided for the
following areas as indicated below:
strategic locations in the plant. All the detectors and detection devices are
connected with the Fire Alarm Panel. The Fire Alarm Panel will be equipped
with Lead Acid type Sealed maintenance-free batteries backup.
1 No. Three Phase 400/440 V AC, 50Hz Operational Siren of 5 Kms range
(diametrical) has been provided on the top of T.G. Building for general alert in
the plant and in vicinity.
The Fire Alarm Panel shows the exact location and status of all detection
devices connected, on the 5.7” TFT display Card. Each Detector has a
definite address, a custom built message, which will be displayed on the
panel, in case of trouble or alarm. The Fire Detection and Alarm Panel have
also been interfaced with the Fire Protection System to annunciate the status
of Fire Water Pump House, operation of MVW & HVW Spray System using
interface units.
All the detectors and detection devices are connected with Fire Alarm Panel.
All the 04 Panels FAP#1, FAP#2, RP#1 & RP#2 are connected in a network.
FAP#1 and FAP#2 are connected with Operator cum engineering station with
Graphic Software for Graphic visualization of Fire.
GENERAL MECHANICAL WORKS (PVT) LTD., VADODARA.
Title WRITE UP OF FIRE ALARM SYSTEM
Project Fire Detection and Protection System for 2 x 800 MW YERAMARUS
STPS
Repeater Panel repeats all the Fire Signals appearing in the Fire Alarm
Panel. Through Repeater Panel we can silence or can pass evacuation
command to any of the Main Fire Alarm Panel as all the Fire Alarm Panels
and Repeater Panels are in Networking.
In the event of fire inside any of the protected area, the detectors will sense
the fire and give signal to the Fire alarm panel which then actuates the
corresponding output devices (Sounder & Relays) as programmed to operate
the fire extinguishing systems or provide necessary audio alarms. The exact
location where the fire / fault generate will be displayed on 5.7” TFT display
Card LCD display of Fire Alarm Panel.
Manual call points are provided floor-wise near exit/staircase for the various
buildings provided with fire alarm system. The addressable Manual call points
are provided for the manual operation of output devices as programmed
All the CABLE GALLERIES are protected by MVW spray system and are
provided with both digital type LHS cable & combination of intelligent Multi-
sensor & Photo-electric smoke detectors. On detection of any abnormal
change in Smoke, heat level by detector, the Fire alarm panel gives the
location of the area on the TFT. The FAP then actuate the corresponding
output devices (Sounder) as programmed. When the fire has been confirmed
by the operation of two detectors (cross zoned) and from LHS Cables, then
Fire Alarm Panel operates the designated deluge Valve. After actuation of the
deluge valve, the “DELUGE VALVE OPERATED“ signal will appears at Fire
alarm panel.
The LHS cables installed in the galleries detects the overheating generated
due to the burning of cable & send the signal to the Fire Alarm Panel, which
then actuate the designated deluge valve for extinguishing the fire. Deluge
Valve Operated signal appears at Fire Alarm Panel with the help of pressure
switches mounted on the deluge valve.
The CONVEYORS are protected by MVW Spray System and are provided
with digital type LHS cable & I.R. Detector as per the specification. The I.R
detector mounted on the specified conveyor detects the moving fire. On
detection of the fire it stops the conveyor, thereafter the LHS cable detects
the overheating generated due to the burning of coal & sends the signal to the
fire alarm panel, which then actuates the designated deluge valve for
GENERAL MECHANICAL WORKS (PVT) LTD., VADODARA.
Title WRITE UP OF FIRE ALARM SYSTEM
Project Fire Detection and Protection System for 2 x 800 MW YERAMARUS
STPS
extinguishing the fire. Deluge Valve Operated signal appears at Fire Alarm
Panel with the help of pressure switches mounted on the deluge valve.
The Fire Alarm Panel FAP#1 in TG Building Common control room unit-1 and
Fire Alarm Panel FAP#2 in CHP Control Room will be provided with
computer, Monitor & all accessories such as video display unit, keyboard and
printer for the Graphical Display & monitoring of all the areas which are
protected by the Fire Alarm System. It gives us the detail of the sensitivity
level of the detectors & the record of Fire & trouble conditions stored in the
VDU. The Monitor will Display the Graphical representation of all the areas
protected by Fire Alarm System. When any of the Detector, MCP, Monitor
Module, Control Relay Module, LHS (Connected with Monitor Module), and
I.R. Detector (connected with Monitor Module) operates the indication of the
corresponding device and the area will flash on the Graphics of the PC.
The system is designed as per TAC & NFPA codes. Following salient
features/ parameters are considered for design of fire alarm system.
1) The Multisensor, Optical & Heat detectors are provided in the protected
areas as per the specification.
2) The spacing of detectors is decided as per IS: 2189 & as per the
specifications in each protected area, considering the construction features
like beam depth, roof height etc. of each protected area.
4) Manual Pull Stations are provided near exit points & as per the
specifications in each protected area.
6) The fire alarm loop cable inside & outside building between detector to
detector, detector to modules & detector to Panel is 2Cx1.5mm2 (Cu)
FRLS, Armoured, and PVC insulated as per IS: 1554.
9) All detectors & modules provided in the loop are of intelligent addressable
type.
GENERAL MECHANICAL WORKS (PVT) LTD., VADODARA.
Title WRITE UP OF FIRE ALARM SYSTEM
Project Fire Detection and Protection System for 2 x 800 MW YERAMARUS
STPS