Write-up for Fire Alarm System
DOC. NO. WͲsϬͲϯϲϮͲϱϮϮͲϬϵϯ REV ϭ PAGES 8
Compliance sheet – Write-up for Fire Alarm System - Rev.01-DOC No: PE-V0-362-522-A093.

DRAWING
S. No. GMW DRG.NO BHEL Comments GMW Reply
TITLE
Write up for
PE-V0-362-522- Incorporated in the drawing and submitted for
1 Fire Alarm Page-1 : Title Sheet: Rev is mentioned as A
A093 Approval
System
Fire alarm control panels will have built in battery
charger and this charger will charge Maintenance
free Lead Acid Battery only. As the built in Power
supply is microprocessor based type and
interconnected to Panel CPU and it will control the
charging, healthiness and troubles of all parameters
of Battery and indicate through LCD display. The
built in battery charger will not charge the Ni-Cd
batteries.

Page-5: Ni-Cd type Battery to be provided as If we use the Ni-Cd batteries with separate battery
mentioned in the Design philosophy. Please charger, we will not get any charging, healthiness
cross check and correct. and troubles indication through the display. Due to
this reason we have requested to use the Maintenance
free Lead acid batteries in our fire alarm control
panels

ESSER Honeywell Fire Alarm System’s Power


supply has been designed and tested to charge and
operate only Lead Acid Batteries. The manufacturers
recommend the using of “Sealed Maintenance Free
Lead-Acid Batteries” only. The letter from ESSER
Honeywell is enclosed for your reference.
Page-5: The system shall be supplied as
finalized in the Design philosophy. Vendor to
cross check and update the document
accordingly.
Included all the Fire alarm system components in the
write up and submitted for Approval.
Monitor (PC) - ?
Printers - ?
Hooter -?
UPS - ?


GENERAL MECHANICAL WORKS (PVT) LTD., VADODARA.


Title WRITE UP OF FIRE ALARM SYSTEM
Project Fire Detection and Protection System for 2 x 800 MW YERAMARUS
STPS

CONTENTS

1.0 GENERAL

2.0 INTRODUCTION OF FIRE ALARM SYSTEM

3.0 SCOPE OF FIRE ALARM SYSTEM

4.0 SYSTEM DESCRIPTION

5.0 SYSTEM OPERATION

6.0 DESIGN CRITERIA

7.0 SAILENT FEATURES OF THE FIRE ALARM PANEL


GENERAL MECHANICAL WORKS (PVT) LTD., VADODARA.
Title WRITE UP OF FIRE ALARM SYSTEM
Project Fire Detection and Protection System for 2 x 800 MW YERAMARUS
STPS

1.0 GENERAL

This technical specification covers the Fire Alarm System, which is a part of
Fire Protection system provided for the 2 x 800 MW YERAMARUS STPS to
be set up by Raichur Power Corporation Limited at Yeramarus, Raichur
district Karnataka.
The design & installation of Fire Alarm & Detection system for the subject
project has been designed as per the specification requirements & comply
with the latest applicable Indian/British/American standards/codes. The
following standards/codes shall be followed in particular:

a. TAC Manual - Manual of Tariff Advisory Committee of Insurance Cos. of


(India)

b. NFPA Codes - National Fire Protection Association Codes (U.S.A.)

All the systems are designed in such a way so as to make the system
complete and acceptable to TAC/nominated agency of insurance companies.

2.0 INTRODUCTION OF FIRE ALARM SYSTEM

A Common concern is shared by all Automatic Fire Detectors/Detection


methods. The criteria is to detect a hostile fire early enough to allow for
effective counter actions i.e. evacuation of persons or extinguishment of Fire.

The Fire Detection and Alarm System will provide instantaneous Audio Alarm
when Fire is detected, in order to prevent loss of life, property and valuables
etc by warning inhabitants in the affected premises immediately, so as to
obtain necessary help from Fire Fighting and Salvage Staff.

The Fire Alarm System may be activated by automatic detection devices or


by manual operation. Fire Detection and Alarm System performs the function
of monitoring the areas from Fire continuously and giving an Audible Alarm in
case of sensing of “Fire”. The sensing of the Fire is accomplished through
various types of detector/LHS Cable/I.R. Detector etc. “Fault” is the detection
of short circuit or open circuit in the Detector loop. Various areas are provided
with the adequate number of Detectors for continuous monitoring.
GENERAL MECHANICAL WORKS (PVT) LTD., VADODARA.
Title WRITE UP OF FIRE ALARM SYSTEM
Project Fire Detection and Protection System for 2 x 800 MW YERAMARUS
STPS

3.0 SCOPE OF FIRE ALARM SYSTEM

The Fire Detection & Alarm System for this project is provided for the
following areas as indicated below:

1. TG Building MCC, UPS, Battery, Battery Charger & Control Room.


2. TG Building Cable Galleries.
3. ESP Building Control & SWGR Room.
4. Administrative Building
5. Service Building
6. Fuel Oil Pump House MCC/Control Room
7. C.W.P.H. MCC/Control Room
8. ASH Handling Plant Control & SWGR Room.
9. CHP Control/SWGR Room
10. Conveyors Area
11. DG Building MCC/Control Room
12. WT/ETP Control/SWGR Room.
13. Switchyard Building.
14. Compressor Building MCC/Control Room.
15. RWPH Control/SWGR Room.
16. HFO/LDO Tank.
17. Hydrogen Storage Area.
18. Pantry Rooms etc.

4.0 SYSTEM DESCRIPTION

The proposed Fire Detection and Alarm System is Intelligent, Analogue


Addressable, Microprocessor type. The System consists of addressable
Multi-sensor, Photoelectric Smoke Detector & Heat Detector which
checks/detect any abnormal change in Smoke, heat level. These detector
then give signal back to the Fire alarm panel which then actuate the
corresponding output devices (Sounder & Relays) as programmed to take
appropriate extinguishing measures.

The System consists of addressable Multisensor Detector, Photoelectric


Smoke Detector, Heat Detector & addressable Manual Call Points. In addition
to these, Response Indicators and Loop Sounders have been provided at
GENERAL MECHANICAL WORKS (PVT) LTD., VADODARA.
Title WRITE UP OF FIRE ALARM SYSTEM
Project Fire Detection and Protection System for 2 x 800 MW YERAMARUS
STPS

strategic locations in the plant. All the detectors and detection devices are
connected with the Fire Alarm Panel. The Fire Alarm Panel will be equipped
with Lead Acid type Sealed maintenance-free batteries backup.

1 No. Three Phase 400/440 V AC, 50Hz Operational Siren of 5 Kms range
(diametrical) has been provided on the top of T.G. Building for general alert in
the plant and in vicinity.

The Fire Alarm Panel shows the exact location and status of all detection
devices connected, on the 5.7” TFT display Card. Each Detector has a
definite address, a custom built message, which will be displayed on the
panel, in case of trouble or alarm. The Fire Detection and Alarm Panel have
also been interfaced with the Fire Protection System to annunciate the status
of Fire Water Pump House, operation of MVW & HVW Spray System using
interface units.

4.1 The Fire Alarm System consists of following:-

1) Intelligent, Analogue Addressable type Microprocessor based Fire Alarm


Panel – 02 Nos.
2) Intelligent, Microprocessor based Repeater Panel – 02 Nos.
3) Intelligent Detectors of Multi-sensor, Photo-electric & Heat Detector.
4) Intelligent Manual Call Point (MCP).
5) Intelligent Monitor Module (Interface Unit)
6) Intelligent Control Relay Module.
7) Loop Sounders (Electronic Hooters)
8) Response Indicator.
9) Infrared Detector.
10) Linear Heat Sensing Cable (LHSC) – Digital type.
11) Probe Type Heat Detector
12) SIREN
13) Probe Type Heat Detector
14) Personal Computer installed with Graphic Software.
15) Monitor
16) Printer
17) Un-irrupted Power Supply

All the detectors and detection devices are connected with Fire Alarm Panel.
All the 04 Panels FAP#1, FAP#2, RP#1 & RP#2 are connected in a network.

4.1.1 FIRE ALARM PANEL

The Fire alarm panels are located at the following locations:

Description Location of FAP Tag No.


Fire Alarm Panel Common Control Room TG Building FAP#1
Fire Alarm Panel CHP Control Room FAP#2

FAP#1 and FAP#2 are connected with Operator cum engineering station with
Graphic Software for Graphic visualization of Fire.
GENERAL MECHANICAL WORKS (PVT) LTD., VADODARA.
Title WRITE UP OF FIRE ALARM SYSTEM
Project Fire Detection and Protection System for 2 x 800 MW YERAMARUS
STPS

4.1.2 REPEATER PANEL

Repeater Panel repeats all the Fire Signals appearing in the Fire Alarm
Panel. Through Repeater Panel we can silence or can pass evacuation
command to any of the Main Fire Alarm Panel as all the Fire Alarm Panels
and Repeater Panels are in Networking.

Description Location of FAP Tag No.


Repeater Panel Fire Station RP#1
Repeater Panel Security house RP#2

5.0 SYSTEM OPERATION

In the event of fire inside any of the protected area, the detectors will sense
the fire and give signal to the Fire alarm panel which then actuates the
corresponding output devices (Sounder & Relays) as programmed to operate
the fire extinguishing systems or provide necessary audio alarms. The exact
location where the fire / fault generate will be displayed on 5.7” TFT display
Card LCD display of Fire Alarm Panel.

Manual call points are provided floor-wise near exit/staircase for the various
buildings provided with fire alarm system. The addressable Manual call points
are provided for the manual operation of output devices as programmed

All the CABLE GALLERIES are protected by MVW spray system and are
provided with both digital type LHS cable & combination of intelligent Multi-
sensor & Photo-electric smoke detectors. On detection of any abnormal
change in Smoke, heat level by detector, the Fire alarm panel gives the
location of the area on the TFT. The FAP then actuate the corresponding
output devices (Sounder) as programmed. When the fire has been confirmed
by the operation of two detectors (cross zoned) and from LHS Cables, then
Fire Alarm Panel operates the designated deluge Valve. After actuation of the
deluge valve, the “DELUGE VALVE OPERATED“ signal will appears at Fire
alarm panel.

The LHS cables installed in the galleries detects the overheating generated
due to the burning of cable & send the signal to the Fire Alarm Panel, which
then actuate the designated deluge valve for extinguishing the fire. Deluge
Valve Operated signal appears at Fire Alarm Panel with the help of pressure
switches mounted on the deluge valve.

The CONVEYORS are protected by MVW Spray System and are provided
with digital type LHS cable & I.R. Detector as per the specification. The I.R
detector mounted on the specified conveyor detects the moving fire. On
detection of the fire it stops the conveyor, thereafter the LHS cable detects
the overheating generated due to the burning of coal & sends the signal to the
fire alarm panel, which then actuates the designated deluge valve for
GENERAL MECHANICAL WORKS (PVT) LTD., VADODARA.
Title WRITE UP OF FIRE ALARM SYSTEM
Project Fire Detection and Protection System for 2 x 800 MW YERAMARUS
STPS

extinguishing the fire. Deluge Valve Operated signal appears at Fire Alarm
Panel with the help of pressure switches mounted on the deluge valve.

The Fire Alarm Panel FAP#1 in TG Building Common control room unit-1 and
Fire Alarm Panel FAP#2 in CHP Control Room will be provided with
computer, Monitor & all accessories such as video display unit, keyboard and
printer for the Graphical Display & monitoring of all the areas which are
protected by the Fire Alarm System. It gives us the detail of the sensitivity
level of the detectors & the record of Fire & trouble conditions stored in the
VDU. The Monitor will Display the Graphical representation of all the areas
protected by Fire Alarm System. When any of the Detector, MCP, Monitor
Module, Control Relay Module, LHS (Connected with Monitor Module), and
I.R. Detector (connected with Monitor Module) operates the indication of the
corresponding device and the area will flash on the Graphics of the PC.

The PC based Central Monitoring Station with printer will be provided at TG


Building Common Control Room and also CHP Control Room.

6.0 Design Criteria

The system is designed as per TAC & NFPA codes. Following salient
features/ parameters are considered for design of fire alarm system.

1) The Multisensor, Optical & Heat detectors are provided in the protected
areas as per the specification.

2) The spacing of detectors is decided as per IS: 2189 & as per the
specifications in each protected area, considering the construction features
like beam depth, roof height etc. of each protected area.

3) Response indicators are provided for above false ceiling detectors.

4) Manual Pull Stations are provided near exit points & as per the
specifications in each protected area.

5) Loop Sounders are provided in each protected area.

6) The fire alarm loop cable inside & outside building between detector to
detector, detector to modules & detector to Panel is 2Cx1.5mm2 (Cu)
FRLS, Armoured, and PVC insulated as per IS: 1554.

7) Networking Cable between Fire Alarm Panels is 2C X1.5 Sq.mm. Control


Cable.

8) Monitor Modules are provided in the system for monitoring switching


contacts of Pressure & Limit Switch for MVW & HVW System.

9) All detectors & modules provided in the loop are of intelligent addressable
type.
GENERAL MECHANICAL WORKS (PVT) LTD., VADODARA.
Title WRITE UP OF FIRE ALARM SYSTEM
Project Fire Detection and Protection System for 2 x 800 MW YERAMARUS
STPS

7.0 SALIENT FEATURES OF THE FIRE ALARM PANEL

1) Intelligent, Analogue Addressable, Microprocessor based.


2) 5.7” TFT display Card.
• Displays information important to user first.
• First & Last alarm display hands free.
3) Exceptional Alarm Response Times.
• 3 Seconds alarm response time over any size Network.
• 750ms loop alarm response time.
4) 3.5 KM Loop Lengths

5) Modbus connectivity with DCS

6) Up to 32 powered loop per panel.


7) Automatic Device & Panel Addressing (Electronic).
8) 127 Devices per Loop in any combination..
9) 31 Nodes can be connected.
10) Electronic Device Circuit Mapping.
11) Exceptional History Log Capacity (10000).
12) Redundant CPU
13) System Status LED.