Voltage limiting device
HVL 120-0.3
U 1 2 3 3
Product Description:
The HVL 120-0.3 (hybrid voltage limiter) is a voltage limiting Within the defined current range, the HVL is recoverable, i.e.
device (VLD) used primarily in DC traction systems to it returns back to the insulating condition after the current
protect against electric shock. Impermissible touch voltages flow. If, however, the short-time current is too high or active
can occur in DC traction systems between track systems for too long in case a fault occurs, the thyristors will be
(return conductors) and earthed metal structures, as the overloaded, alloy and become very low resistive. In this case,
track systems are laid insulated to limit stray currents. both surge and personal protection are still ensured, but the
The HVL limits touch voltages regardless of whether they measure for limiting stray currents is no longer in effect and
are purely DC or mixed voltages (both DC and AC voltages) the HVL shall be replaced.
to the permissible limit values defined in EN 50122-1.
The HVL is a class 2.2 (bi-directional) voltage limiting device
The HVL consists of the parallel connection of a metal-oxide and is type tested as per EN 50526-2. Mechanically, the
(MO) surge arrester with no spark gaps and two anti-parallel HVL features a very rugged design. As with all high-voltage
connected thyristors. Transient surges caused by lightning arresters from ABB, the active component is directly
and switching operations in the system are limited by the moulded in grey silicone. This well-proven design protects
MO arrester. If overvoltages occur for a longer period of the device from any possible environmental stresses, such
time (milliseconds to hours) due to faults in the system or as UV radiation, vibrations, humidity and pollution. The HVL
for operational reasons, the thyristors fire to limit touch is corrosion resistant and can be used either outdoors or
voltages. As soon as a zero-current transition occurs, the indoors. The HVL does not require a power supply from the
thyristors cut off the current flow and the original condition mains grid.
is restored.
The HVL complies with both VLD-O and VLD-F functionality
in the specified current range.
Voltage limiting device | HVL 120 - 0.3 2
Application
Application
HVL
Voltage limiting device | HVL 120 - 0.3 3
Technical Data
Operating conditions
Ambient temperature Tamb −40 to +60 °C
Altitude unlimited
Weight 4 kg
Degree of protection according to IEC 60529 IPx6, IPx7
Additional certification
Fire and smoke behavior tested and classified according to EN 45545-2
Weather ageing test 1000 h in salt fog chamber
Voltage limiting device | HVL 120 - 0.3 4
Technical Data
800
700
600
Voltage / V
500
400
300
200
100
0
1 10 100
t / ms
7000
6000
5000
I/A
4000
3000
2000
1000
0
0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0 110.0 120.0
t / ms
HVL 120-0.3
900
800
700
600
I/A
500
400
300
200
100
0
0 200 400 600 800 1000 1200 1400 1600 1800
t/s
HVL 120-0.3
Dimensions
2016-12-07 M.Staubli
2016-12-07 P.Dubach
Dimensions with optional standard accessories Structure of type designation with optional accessories
(Example)
HVL-Type
2801
Dimensions (mm)
For more information please contact: Note
We reserve the right to make technical changes or modify
ABB Switzerland Ltd. the contents of this document without prior notice. With
High Voltage Products regard to purchase orders the agreed particulars shall
Surge Arresters prevail. ABB does not accept any responsibility whatsoever
Jurastrasse 45 for potential errors or possible lack of information in this
CH-5430 Wettingen document. We reserve all rights in this document and in the
Phone: +41 58 585 29 11 subject matter and illustrations contained therein. Any
Telefax: +41 58 585 55 70 reproduction, disclosure to third parties or utilization of its
E-Mail: sales.sa@ch.abb.com contents – in whole or in parts – is forbidden without prior
written consent of ABB.
www.abb.com/arrestersonline
Our products are certified according ISO 9001, 14001, 18001
and IRIS