ArresterFacts Riser Pole Arrester
ArresterFacts Riser Pole Arrester
ArresterFacts 015
Prepared by
Jonathan Woodworth
Consulting Engineer
ArresterWorks
Note in the IEEE definition, it is a type of If the underground circuit has an aging
arrester and not a class of arrester. Also cable system, 70kV could easily result in a
there are no special tests prescribed in the failure of the system.
IEEE standard.
For the same reason, arresters are
sometimes installed directly in the
underground circuit at the pad mounted
transformers.
Non-Ganged Hot
Stick Operated
Disconnect Switch
Hot Stick
operable Insulated Guy
Hotline Clamp Wire
Arrester Polymer
Lead Terminator
Riser Pole Head
Arrester Arrester Ground
Lead
System
Neutral
Underground
Cable Clamp
(URD) Cable
Cable Shield
Wire
Pole Ground
Wire
Porcelain Terminator
Hollow Steel
Tower
Tower Ground 115kV
Conductor Underground
Cable
Cable Shield to
Ground
Connection
Cable Support
Three Phase
Underbuild
Distribution circuit
******************************
Installation Considerations
As usual, it is always better to use the shortest ArresterFacts Usage
possible lead lengths when mounting arresters. ArresterFacts are Copyrighted documents intended for
the education of arrester users and stakeholders. If
It is even more important in this case. As you you choose to copy any part of this document for
can see in Figure 4, the top of the terminator teaching purposes you have my permission, however
should be as close as possible to the top of the please give ArresterWorks proper credit.
Jonathan Woodworth