IBS – Institut für Brandschutztechnik und Classification Report No.

: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 2 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

1. Introduction

This Classification Report defines the fire resistance class assigned to the construction
product "PROMASTOP®-CC" CC" in compliance with the procedures given in EN 13501-2:2007
13501
+ A1:2009.

2. Details of the classified product

2.1. Function:

The construction product "PROMASTOP®-CC" CC" is suitable for application in combination with
mineral wool boards (class A1 in accordance with EN 13501-1, melting point ≥ 1000 °C)
and is designated as a soft penetration seal for installation in horizontal and vertical
orientation in lightweight and rigid constructions. PROMASTOP®-CC is applicable as
firestop coating in combination
combination with cable trays, cable conductors, electrical cables,
combustible/non-combustible
combustible pipes with combustible/non-combustible
combustible/non combustible insulations as well as
linear joints/gap
/gap penetration seal.
seal. The function of the product is to resist fire in accordance
with typicall product reactions as described in clause 5 of EN 13501--2:2007+A1:2009.

2.2. Description:

The construction product "PROMASTOP®-CC" CC" is fully described in the test reports provided
in support of this Classification listed in clause 3.

The installation guideline related to construction product "PROMASTOP®-CC" is available


upon request and is not attached to this Classification Report.

Due to the possibility of combination


combin with other penetration seals, the installation guidelines
® ®
of "PROMASTOP -FC" FC" and "PROMASTOP
" -W"
W" are separately available.
available

2.2.1. Details:

The construction product "PROMASTOP®-CC" is a water-based based endothermic intumescent


firestop coating.. When "PROMASTOP®-CC" CC" is exposed to fire, its intumescent action
reaction and simultaneous surface ceramisation ensure safe protection against flue gas,
heat transfer and fire spread along building component connections and installations.
installation
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 3 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

"PROMASTOP®-CC"
CC" is available in
in one consistency and is designated as follows:

PROMASTOP®-CC Correspondent to PROMASTOP®-CC


CC for brush/paintable
brush application

The technical data can be taken from the technical data sheet (Promat Fire stopping
handbook or please contact your local Promat office) and from the attachments to this
Classification Report.

2.2.2. General test specimen description:

General test specimen description from Test Report No. Pr-10-2.098


Pr

Test setup: Rigid floor


floor construction from aerated concrete; thickness 150 mm; density
Test date: 30.11.2011 ≥ 450
50 kg/m³.
Test date: 14.10.2010
Test date: 14.05.2010

No. 10 Square opening (1200 x 1200 mm) with cable assignment in compliance with EN
CG1-5 EI90 1366-3:2009
3:2009 (table A.1), cable groups 1-5.
1 Sealed with two mineral wool boards
coated with PROMASTOP®-CC CC (class A1, 50 mm, 150 kg/m³, melting point ≥ 1000
°C). Coating of overlapping cable, cable bundles an d cable trays with PROMASTOP®-
CC, length 100 mm, symmetrical to the supporting construction. Circumferential
coating of the opening
open of adjacent supporting construction:: 10 mm
No. 14 Square opening (1200 x 1200 mm) Sealed with two mineral wool boards coated with
EI120 PROMASTOP®-CC CC (class A1, 30 mm, 150 kg/m³, melting point ≥ 1000 °C).
Circumferential coating of the opening of adjacent supporting construction:
construction 10 mm
No. 34 Square opening (1200 x 1200 mm) with cable assignment in compliance with EN
CG1 E90 EI60
CG2 E90 EI60
1366-3:2009
3:2009 (table A.1). Sealed with two mineral wool boards coated with
CG3 E90 EI60 PROMASTOP®-CC CC (class A1, 30 mm, 150 kg/m³, melting point ≥ 1000 °C). Coating of
CG4 EI90
CG5 E90 EI60 overlapping cable, cable bundles and cable trays with PROMASTOP®-CC, length 100
mm, symmetrical to the supporting construction. Circumferential coating of the
opening of adjacent supporting construction: 10 mm
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 4 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test setup: Flexible wall


wall construction; with a thickness of 100 mm; two layers of gypsum
Test date: 04.12.2009 plaster boards of 12.5 mm in acc. with EN 520; with backfilling from 50 mm
mineral wool acc. to class A1 (density 100 kg/m³).

No. 10 Square opening (1200


( x 1200 mm) with cable assignment in compliance with EN 1366-
1366
CG1-5 EI90 3:2009 (table A.1). Sealed with two mineral wool boards coated with PROMASTOP®-
CC (class A1, 50 mm, 150 kg/m³, melting point ≥ 1000 °C). Coating of overlapping
cable, cable bundles and cable trays with PROMASTOP®-CC, length 100 mm,
symmetrical to the supporting construction.
Circumferential coating of the opening of adjacent supporting construction: 10 mm
No. 11 Square opening (1200 x 1200 mm) Sealed with two mineral wool boards coated with
EI90 PROMASTOP®-CC CC (class A1, 30 0 mm, 150 kg/m³, melting point ≥ 1000 °C).
Circumferential coating of the opening of adjacent supporting construction: 10 mm

General test specimen description from Test Report No. Pr-10-2.099


Pr

Test setup: Rigid floor construction from aerated concrete; thickness 150 mm; density ≥
Test date: 27.07.2010 450 kg/m³.

No. 31 Asymmetrical linear joint with a width of 50 mm. Backfilling from 1K-PU
1K foam (class E):
E120 Top coating with PROMASTOP®-CC, CC, approx. 1 mm. Circumferential coating of joints to
EI60
adjacent supporting construction:
construction 10 mm
No. 32 Asymmetrical linear joint with a width of 50 mm. Backfilling from 1K-PU
1K foam (class E):
EI120 Bottom coating with PROMASTOP®-CC, CC, approx. 1 mm. Circumferential coating of joints
to adjacent supporting construction:
construction 10 mm

Test setup: Rigid wall construction from aerated concrete; thickness


thicknes 150 mm; density ≥
Test date: 29.07.2010 450 kg/m³.

No. 31 Vertical, asymmetrical linear joint with a width of 50 mm. Backfilling from 1K-PU foam
EI90 (class E): Coating of fire-exposed
fire side with PROMASTOP®-CC, approx. 1 mm.
Circumferential coating of joints to adjacent supporting construction:
construction 10 mm
No. 32 Vertical, asymmetrical linear joint with a width of 50 mm. Backfilling from 1K-PU foam
EI90 (class E): Coating of fire-unexposed side with PROMASTOP®-CC, approx. 1 mm.
Circumferential coating of joints to adjacent supporting construction:
construction 10 mm
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 5 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

General test specimen description from Test Report No. Pr-12-2.101


Pr

Test setup: Rigid floor construction from aerated concrete; thickness 150 mm; density ≥
Test date: 11.01.2012 450 kg/m³.

No. 102 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 80 mm with copper pipe Ø 18 / s 1.0 mm u/c and mineral wool insulation
(class A2,
40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total centred
penetration length of 600 mm.
No. 103 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 105 mm with copper pipe Ø 42 / s 1.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 800 mm.
No. 104 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 105 mm with copper pipe Ø 88.9 / s 2.0 mm u/c and mineral wool
insulation (class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with
a total centred penetration length of 800 mm.
No. 105 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 80 mm withwith steel pipe Ø 17 / s 2.0 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 106 ration seal (PROMASTOP®-CC, 2
Metal pipe penetration seal: Opening in the soft penetration
EI90 x 50 mm) Ø 105 mm with steel pipe Ø 42 / s 2.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 107 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 180 mm with steel pipe Ø 114 / s 3.6 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred
entred penetration length of 1000 mm.
No. 108 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 280 mm with steel pipe Ø 220 / s 4.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 2500 mm.
No. 109 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 220 mm with copper pipe Ø 18 / s 1.0 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 600 mm.
No. 110 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 245 mm with copper pipe Ø 42 / s 1.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 800 mm.
No. 111 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 280 mm with copper pipe Ø 88.9 / s 2.0 mm u/c and mineral wool
insulation (class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration
with a total centred penetration length of 2000 mm.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 6 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

No. 112 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 220 mm with steel pipe Ø 17 / s 2.0 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 113 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 245 mm with steel pipe Ø 42 / s 2.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point
po ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 114 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 315 mm with steel pipe Ø 114 / s 3.6 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 1000 mm.
No. 115 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm)) Ø 420 mm with steel pipe Ø 220 / s 4.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 2500 mm.
No. 146 Metal pipe penetration seal: Opening in n the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 150 mm with copper pipe Ø 88.9 / s 2.0 mm u/c and mineral wool
insulation (class A2, 100 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration
with a total centred penetration length of 2000 mm.
mm
No. 149 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 175 mm with steel pipe Ø 114 / s 3.6 mm u/c and mineral
mine wool insulation
(class A2, 100 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 1000 mm.
No. 150 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 220 mm with steel pipe Ø 159 / s 4.0 mm u/c and mineral
mine wool insulation
(class A2, 100 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 2500 mm.
No. 154 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 315 mm with steel pipe Ø 114 / s 3.6 mm u/c and mineral wool insulation
(class A2, 100 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 1000 mm.
No. 155 Metal pipe penetration seal: Opening in the e soft penetration seal (PROMASTOP®-CC, 2
EI90 x 50 mm) Ø 360 mm with steel pipe Ø 159 / s 4.0 mm u/c and mineral
mine wool insulation
(class A2, 100 kg/m³, melting point ≥ 1000 °C, 100mm) in LS configuration with a total
centred penetration length of 2500 mm.
No. 200 Rectangular opening 1500 x 2800 mm with cable assignment in compliance with EN
CG1 EI90 1366-3:2009
3:2009 (table A.1). Sealed with two mineral wool boards coated with
CG2 EI90
CG3 EI90 PROMASTOP®-CC CC (class A1, 50 mm, 150 kg/m³, melting point. ≥ 1000 °C). Coating of
CG4 EI90 overlapping cables, cable bundles and cable trays with PROMASTOP®-CC, length 100
CG5 EI90 mm, symmetrical to the supporting construction. No circumferential coating of the
CG6 EI90
opening of the adjacent supporting construction.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 7 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test setup: Flexible wall construction; with a thickness of 100 mm; two layers of gypsum
Test date: 23.01.2012 plaster boards of 12.5 mm in acc. with EN 520; with backfilling from 40 mm
mineral wool acc. to class A1 (density 100 kg/m³).

No. 102 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI120 x 50 mm) Ø 80 mm with copper pipe Ø 18 / s 1.0 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred
ntred penetration length of 600 mm.
No. 103 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
E120 x 50 mm) Ø 105 mm with copper pipe Ø 42 / s 1.5 mm u/c and mineral wool insulation
EI90
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 800 mm.
No. 104 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
E120 x 50 mm) Ø 150 mm with copper pipe Ø 88.9 / s 2.0 mm u/c and mineral wool
EI90
insulation (class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with
a total centred penetration length of 2000 mm.
No. 105 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI120 x 50
0 mm) Ø 80 mm with steel pipe Ø 17 / s 2.0 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 106 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI120 x 50 mm) Ø 100 mm with steel pipe Ø 42 / s 2.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 107 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
E120 x 50 mm) Ø 175 mm with steel pipe Ø 114 / s 3.6 mm u/c and mineral
mine wool insulation
EI90
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configurat ion with a total
centred penetration length of 1000 mm.
No. 108 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
E120 x 50 mm) Ø 280 mm with steel pipe Ø 220 / s 4.5 mm u/c and mineral
mine wool insulation
EI90
(class A2, 400 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 2500 mm.
No. 109 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI120 x 50 mm) Ø 220 mm with copper pipe Ø 18 / s 1.0 mm u/c and mineral wool insulation
ins
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 600 mm.
No. 110 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
E120 x 50 mm) Ø 245 mm with copper pipe Ø 42 / s 1.5 mm u/c and mineralmine wool insulation
EI90
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 800 mm.
No. 111 enetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
Metal pipe penetration
E120 x 50 mm) Ø 290 mm with copper pipe Ø 88.9 / s 2.0 mm u/c and mineral wool
EI90
insulation (class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration
with a total centred penetration
pen length of 2000 mm.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 8 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

No. 112 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI120 x 50 mm) Ø 215 mm with steel pipe Ø 17 / s 2.0 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 113 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI120 x 50 mm) Ø 245 mm with steel pipe Ø 42 / s 2.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 114 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
EI120 x 50 mm) Ø 315 mm with steel pipe Ø 114 / s 3.6 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 1000 mm.
No. 115 Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 2
E120 x 50 mm) Ø 420 mm with steel pipe Ø 220 / s 4.5 mm u/c and mineral
mine wool insulation
EI90
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 100 mm) in LS configuration with a total
centred penetration length of 2500 mm.
No. 200 Rectangular opening 1500 x 2800 mm with cable assignment in compliance with EN
CG1 EI120
CG2 E120 EI90
1366-3:2009
3:2009 (table A.1). Sealed with two mineral wool boards coated with
CG3 E120 EI90 PROMASTOP®-CC CC (class A1, 50 mm, 150 kg/m³, melting point ≥ 1000 °C). Coating of
CG4 EI120
CG5 E120 EI90 overlapping cable, cable bundles and cable trays with PROMASTOP®-CC, length 100
CG6 E120 EI90 mm, symmetrical to the supporting construction. No circumferential coating of the
opening of the adjacent supporting construction.

Test setup: Rigid floor construction from aerated concrete; thickness 150 mm; density ≥
Test date: 30.07.2012 450 kg/m³.

No. 16c Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 80 mm) Ø 80 mm with copper pipe Ø 18 / s 1.0 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 600 mm.
No. 17c Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 80 mm) Ø 105 mm with copper pipe Ø 42 / s 1.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 800 mm.
No. 18c Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 80 mm) Ø 150 mm with copper pipe Ø 88.9 / s 2.0 mm u/c and mineral wool
insulation (class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with
a total centred penetration length of 2000 mm.
No. 19c Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 80 mm) Ø 80 mm with steel pipe Ø 17 / s 2.0 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 20c Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 80 mm) Ø 100 mm with steel pipe Ø 42 / s 2.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 500 mm.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 9 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

No. 21c Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 80 mm) Ø 175 mm with steel pipe Ø 114 / s 3.6 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 1000 mm.
No. 34c Rectangular opening 650 x 3000 mm with cable assignment in compliance with EN
CG1 EI90
CG2 EI90
1366-3:2009
3:2009 (table A.1). Sealed with one mineral wool board coated with
CG3 EI90 PROMASTOP®-CC CC (class A1, 80 mm, 150 kg/m³, melting point ≥ 1000 °C). Coating of
CG4 EI90
CG5 E90 EI60 overlapping cable, cable bundles and cable trays with PROMASTOP®-CC, length 100
CG6 E90 EI60 mm, symmetrical to the supporting construction. No circumferential coating of the
opening of the adjacent supporting construction.
No. 16d Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 50 mm) Ø 80 mm with copper pipe Ø 18 / s 1.0 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 600 mm.
No. 17d Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 50 mm) Ø 100 mm with copper pipe Ø 42 / s 1.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a to tal
centred penetration length of 800 mm.
No. 18d Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 50 mm) Ø 150 mm with copper pipe Ø 88.9 / s 2.0 mm u/c and mineral wool
insulation (class A2, 40 kg/m³, melting point
p ≥ 1000 °C, 30 mm) in LS configuration with
a total centred penetration length of 1700 mm.
No. 19d Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 50 mm) Ø 80 mm with steel pipe Ø 17 / s 2.0 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 20d Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 50 mm) Ø 105 mm with steel pipe Ø 42 / s 2.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 21d Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 50 mm) Ø 175 mm with steel pipe Ø 114 / s 3.6 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 1000 mm.
No. 34d
CG1 EI90
Rectangular opening 650 x 3000 mm with cable assignment in compliance with EN
CG2 E90 EI60 1366-3:2009
3:2009 (table A.1). Sealed with one mineral wool board coated with
CG3 E90 EI60
CG4 EI90 PROMASTOP®-CC CC (class A1, 50 mm, 150 kg/m³, melting point ≥ 1000 °C). Coating of
CG5 E90 EI60 overlapping cable, cable bundles and cable trays with PROMASTOP®-CC, length 100
CG6 E90 EI45
mm, symmetrical to the supporting construction. No circumferential coating of the
opening of the adjacent supporting construction.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 10 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test setup: Flexible wall construction; with a thickness of 100 mm; two layers of gypsum
Test date: 14.08.2012 plaster boards of 12.5 mm in acc. with EN 520; with backfilling from 40 mm
mineral wool acc. to class A1 (density 100 kg/m³).

No. 16c Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 80 mm) Ø 80 mm with copper pipe Ø 18 / s 1.0 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a tota l
centred penetration length of 600 mm.
No. 17c Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 80 mm) Ø 105 mm with copper pipe Ø 42 / s 1.5 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 800 mm.
No. 18c Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 80 mm) Ø 145 mm with copper pipe Ø 88.9 / s 2.0 mm u/c and mineral wool
insulation (class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with
a total centred penetration length of 2000 mm.
No. 19c Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 80 mm) Ø 80 mm with steel pipe Ø 17 / s 2.0 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 20c oft penetration seal (PROMASTOP®-CC, 1
Metal pipe penetration seal: Opening in the soft
EI90 x 80 mm) Ø 100 mm with steel pipe Ø 42 / s 2.5 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 21c Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 80 mm) Ø 175 mm with steel pipe Ø 114 / s 3.6 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 1000 mm.
No. 34c Rectangular opening 650 x 3000 mm with cable assignment in compliance with EN
CG1 EI90
CG2 E90 EI60
1366-3:2009
3:2009 (table A.1). Sealed with one mineral wool board coated with
CG3 E90 EI60 PROMASTOP®-CC CC (class A1, 80 mm, 150 kg/m³, melting point ≥ 1000 °C). Coating of
CG4 EI90
CG5 E90 EI60 overlapping cable, cable bundles and cable trays with PROMASTOP®-CC, length 100
CG6 E90 EI60 mm, symmetrical to the supporting construction.
Circumferential coating of the opening of adjacent supporting construction:
construction 10 mm
No. 16d Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 50 mm) Ø 70 mm with copper pipe Ø 18 / s 1.0 mm u/c and mineralmine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 600 mm.
No. 17d Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
E90 x 50 mm) Ø 105 mm with copper pipe Ø 42 / s 1.5 mm u/c and mineralmine wool insulation
EI60
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 800 mm.
No. 18d Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
E90 x 50 mm) Ø 145 mm with copper pipe Ø 88.9 / s 2.0 mm u/c and mineral wool
EI60
insulation (class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with
a total centred penetration length of 2000 mm.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 11 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

No. 19d sea Opening in the soft penetration seal (PROMASTOP®-CC, 1


Metal pipe penetration seal:
EI90 x 50 mm) Ø 80 mm with steel pipe Ø 17 / s 2.0 mm u/c and mineral wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 20d Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 50 mm) Ø 105 mm with steel pipe Ø 42 / s 2.5 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 500 mm.
No. 21d Metal pipe penetration seal: Opening in the soft penetration seal (PROMASTOP®-CC, 1
EI90 x 50 mm) Ø 175 mm with steel pipe Ø 114 / s 3.6 mm u/c and mineral
mine wool insulation
(class A2, 40 kg/m³, melting point ≥ 1000 °C, 30 mm) in LS configuration with a total
centred penetration length of 1000 mm.
No. 34d Rectangular opening 650 x 3000 mm with cable assignment in compliance with EN
CG1 E90 EI60
CG2 E90 EI60
1366-3:2009
3:2009 (table A.1). Sealed with one mineral wool board coated with
CG3 E90 EI60 PROMASTOP®-CC CC (class A1, 50 mm, 150 kg/m³, melting point ≥ 1000 °C). Coating of
CG4 E90 EI60
CG5 E90 EI45 overlapping cable, cable bundles and cable trays with PROMASTOP®-CC, length 100
CG6 E90 EI45 mm, symmetrical to the supporting construction.
Circumferential coating of the opening of adjacent supporting construction:
construction 25 mm

General test specimen description from Test report No. Pr-12-2.059


Pr

Test setup: Rigid floor construction from aerated concrete; thickness 150 mm; density ≥
Test date: 11.01.2012 450 kg/m³.

No. 51 Plastic pipe penetration: Opening in the soft penetration seal (PROMASTOP®-CC, 2 x
EI90 50 mm) Ø 160 mm with PP-HPP pipe Ø 160 / s 4.0 mm u/u. PROMASTOP®-FC3/160
(crit.)
surface-mounted
mounted on bottom side of the soft penetration seal in acc. with the installation
guideline.
No. 52 Plastic pipe penetration: Opening in the soft penetration seal (PROMASTOP®-CC, 2 x
EI90 50 mm) Ø 125 mm with Poloplast PoloKal NG Ø 125 / s 3.9 mm u/u. PROMASTOP®-
(crit.)
FC3/125 surface--mounted on bottom side of the soft penetration seal in acc. with the
installation guideline.
guideline
No. 53 (PROMAST ®-CC, 2 x
Plastic pipe penetration: Opening in the soft penetration seal (PROMASTOP
EI90 50 mm) Ø 160 mm with Poloplast PoloKal NG Ø 160 / s 4.9 mm u/u. PROMASTOP®-
(crit.)
FC3/160 surface--mounted on bottom side of the soft penetration seal in acc. with the
installation guideline.
guideline

Test setup: Flexible wall construction; with a thickness of 100 mm; two layers of gypsum
Test date: 23.01.2012 plaster boards of 12.5 mm in acc. with EN 520; with backfilling from 40 mm
mineral wool acc. to class A1 (density 100 kg/m³).

No. 51 Plastic pipe penetration: Opening in the soft penetration seal (PROMASTOP®-CC, 2 x
EI120 50 mm) Ø 160 mm with PP-HPP H pipe Ø 160 / s 4.0 mm u/u. PROMASTOP®-FC3/160
surface-mounted
mounted on both sides in acc. with the installation guidelines.
guidelines
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 12 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

No. 53 Plastic pipe penetration: Opening in the soft penetration seal (PROMASTOP®-CC, 2 x
EI120 50 mm) Ø 160 mm with Poloplast PoloKal NG Ø 160 / s 4.9 mm u/u. PROMASTOP®-
FC3/160 surface--mounted on both sides in acc. with the installation guidelines.
guidelines
No. 52 Plastic pipe penetration: Opening in the soft penetration seal (PROMASTOP®-CC, 2 x
EI120 50 mm) Ø 125 mm with Poloplast PoloKal NG Ø 125 / s 3.9 mm u/u. PROMASTOP®-
FC3/125 surface--mounted on both sides in acc. with the installation guidelines.
guidelines
No. 66 Composite pipe (plastic and metal) penetration: Opening in the softso penetration seal
EI120 (PROMASTOP®-CC, -CC, 2 x 50 mm) Ø 24 mm with aluminium composite pipe (Geberit
Mepla)) Ø 16 / s 2.25 mm u/u. With insulation (class E, s 4 mm) in LS configuration with
a total centred penetration length of 200 mm. PROMASTOP®-FC3/32 surface-mounted
on both sides in acc. with the installation guidelines.
No. 67 Composite pipe (plastic and metal) penetration: Opening in the soft penetration seal
E120 (PROMASTOP®-CC, -CC, 2 x 50 mm) Ø 40 mm with aluminium composite pipe (Geberit
EI45
Mepla)) Ø 32 / s 3.0 mm u/u. With insulation (class E, s 4 mm) in LS configuration with a
total centred penetration length of 200 mm. PROMASTOP®-FC3/32 FC3/32 surface-mounted
surface
on both sides in acc. with the installation guidelines.
No. 68 Composite pipe (plastic and metal) penetration: Opening in the soft penetration seal
E120 (PROMASTOP®-CC, -CC, 2 x 50 mm) Ø 71 mm with aluminium composite pipe (Geberit
EI45
Mepla)) Ø 63 / s 4.5 mm u/u. With insulation (class
(class E, s 4 mm) in LS configuration with a
total centred penetration length of 200 mm. PROMASTOP®-FC3/63 FC3/63 surface-mounted
surface
on both sides in acc. with the installation guidelines.
No. 69 Composite pipe (plastic and metal) penetration: Opening in the soft penetration seal
E120 (PROMASTOP®-CC, -CC, 2 x 50 mm) Ø 83 mm with aluminium composite pipe (Geberit
EI45
Mepla)) Ø 75 / s 4.7 mm u/u. With insulation (class E, s 4 mm) in LS configuration with a
total centred penetration length of 200 mm. PROMASTOP®-FC3/75 surface-mounted
on both sides in acc. with the installation guidelines.
No. 85 Composite pipe (plastic and metal) penetration: Opening in the soft penetration seal
EI120 (PROMASTOP®-CC, -CC, 2 x 50 mm) Ø 28 mm with aluminium composite pipe (Geberit
Mepla)) Ø 16 /s 2.25 mm u/c. With insulation (class B-s3,d0;
s3,d0; s 6 mm) in LS configuration
with a total centred penetration length of 500 mm. PROMASTOP®-FC3/32 surface-
mounted on both sides in acc. with the installation guidelines..
No. 86 Composite pipe (plastic and metal) penetration: Opening in the soft penetration seal
EI90 (PROMASTOP®-CC, -CC, 2 x 50 mm) Ø 38 mm with aluminium composite pipe (Geberit
Mepla)) Ø 26 / s 3.0 mm u/u. With insulation (class B-s3,d0;
B s3,d0; s 6 mm) in LS configuration
with a total centred penetration length of 500 mm. PROMASTOP®-FC3/32 surface-
mounted on both sides in acc. with the installation guidelines..
No. 87 Composite pipe (plastic and metal) penetration: Opening in the soft penetration seal
E120 (PROMASTOP®-CC, -CC, 2 x 50 mm) Ø 87 mm with aluminium composite
compo pipe (Geberit
EI60
Mepla)) Ø 75 / s 4.7 mm u/u. With insulation (class B-s3,d0;
B s3,d0; s 6 mm) in LS configuration
with a total centred penetration length of 500 mm. PROMASTOP®-FC3/75 surface-
mounted on both sides in acc. with the installation guidelines..
No. 88 Composite pipe (plastic and metal) penetration: Opening in the soft penetration seal
EI90 (PROMASTOP®-CC, -CC, 2 x 50 mm) Ø 80 mm with aluminium composite pipe (Geberit
Mepla)) Ø 16 /s 2.25 mm u/c. With insulation (class B-s3,d0;
B s3,d0; s 32 mm) in LS
configuration with a total centred penetration length of 500 mm. PROMASTOP®-FC3/75
surface-mounted
mounted on both sides in acc. with the installation guidelines.
guidelines
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 13 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

No. 89 Composite pipe (plastic and metal) penetration: Opening in the soft penetration seal
EI90 (PROMASTOP®-CC, -CC, 2 x 50 mm) Ø 139 mm with aluminium composite pipe (Geberit
Mepla)) Ø 75 /s 4.7 mm u/c. With insulation (class B-s3,d0;
B s3,d0; s 32 mm) in LS configuration
with a total centred penetration length of 500 mm. PROMASTOP®-FC3/140 surface-
mounted on both sides in acc.
a with the installation guidelines..

General test specimen description from Test report No. Pr-14-2.075-En


Pr En

Test setup: Rigid floor construction from aerated concrete; thickness 150 mm; density ≥
450 kg/m³.

No. 60 Rectangular opening 600 x 1400


1400 mm with cable assignment in compliance with EN
CG1 EI120 1366-3:2009
3:2009 (table A.1). Sealed with two mineral wool boards coated with
CG2 E120
EI90 PROMASTOP®-CC CC (class A1, 50 mm, 150 kg/m³, melting point ≥ 1000 °C). Coating of
CG3 E120 g cable, cable bundles and cable trays with PROMASTOP®-CC, length 100
overlapping
EI90
CG4 EI120
mm, symmetrical to the supporting construction.

General test specimen description from Test report No. Pr-13-2.045-En


Pr En

Test setup: Flexible wall construction; with a thickness of 100 mm; two layers of gypsum
plaster boards of 12.5 mm in acc. with EN 520; with no backfilling.

No. A Blank seal with 3 m² seal size. Sealed with two mineral wool boards coated with
EI120 PROMASTOP®-CC CC (class A1, 50 mm, 150 kg/m³, melting point ≥ 1000 °C). No
circumferential coating on the adjacent supporting construction.

General test specimen description from Test report No. Pr-13-2.047-En


Pr En

Test setup: Flexible wall construction; with a thickness of 100 mm; two layers of gypsum
plaster boards of 12.5 mm in acc. with EN 520; with no backfilling.

No. A Blank seal with 3 m² seal size. Sealed with one mineral wool board coated with
EI120 PROMASTOP®-CC CC (class A1, 80 mm, 150 kg/m³, melting point ≥ 1000 °C). No
circumferential coating on the adjacent supporting construction.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 14 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

General test specimen description from Test report No. Pr-13-2.052-En


Pr En

Test setup: Flexible wall construction; with a thickness of 100 mm; two layers of gypsum
plaster boards of 12.5 mm in acc. with EN 520; with backfilling from 40 mm
mineral wool acc. to class A1 (density 40 kg/m³).

No. B Blank seal with 3 m² seal size. Sealed with one mineral wool board coated with
E90 EI60 PROMASTOP®-CC CC (class A1, 500 mm, 150 kg/m³, melting point ≥ 1000 °C). No
circumferential coating on the adjacent supporting construction.

General test specimen description from Test report No. Pr-13-2.051-En


Pr En

Test setup: Rigid floor construction from aerated concrete; thickness 150 mm; density ≥
450 kg/m³.

No. A Blank seal with 3 m² seal size. Sealed with two mineral wool boards coated with
EI120 PROMASTOP®-CC CC (class A1, 50 mm, 150 kg/m³, melting point ≥ 1000 °C). No
circumferential coating on the adjacent supporting construction.

General test specimen description from Test report No. Pr-13-2.093-En


En

Test setup: Rigid floor construction from aerated concrete; thickness 150 mm; density ≥
450 kg/m³.

No. A Blank seal with 3 m² seal size. Sealed with one mineral wool board coated with
EI120 PROMASTOP®-CC CC (class A1, 80 mm, 150 kg/m³, melting point ≥ 1000 °C). No
circumferential coating on the adjacent supporting construction.

General test specimen description from Test report No. Pr-16-2.061-En


Pr En

Test setup: Rigid floor construction from aerated concrete; thickness 150 mm; density ≥
450 kg/m³.

No. R Blank seal with 1,74 m² seal size. Sealed with one mineral wool board coated with
EI60 PROMASTOP®-CC CC (class A1, 50
50 mm, 150 kg/m³, melting point ≥ 1000 °C). No
circumferential coating on the adjacent supporting construction.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 15 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

3. Test reports and test results in support of the classification:

3.1 Test reports:

Name of testing Sponsor Test Report No. Test method


institute
Pavus a.s. Promat GmbH,
Pr-10-2.098 of EN 1363-1: 2000-01
J. Hybese 879, St.
St.-Peter-Str. 25,
22.09.2010 EN 1366-3: 2009
CZ-39181 Veseli A-4021 Linz
Pavus a.s. Promat GmbH,
Pr-10-2.099 of EN 1363-1: 2000-01
J. Hybese 879, St.
St.-Peter-Str. 25,
22.09.2010 EN 1366-4: 2006
CZ-39181 Veseli A-4021 Linz
Pavus a.s. Promat GmbH,
Pr-12-2.101 of EN 1363-1: 2000-01
J. Hybese 879, St.
St.-Peter-Str. 25,
06.09.2012 EN 1366-3: 2009
CZ-39181 Veseli A-4021 Linz
Pavus a.s. Promat GmbH,
Pr-12-2.059 of EN 1363-1: 2000-01
J. Hybese 879, St.
St.-Peter-Str. 25,
02.07.2012 EN 1366-3: 2009
CZ-39181 Veseli A-4021 Linz
Pavus a.s. Promat GmbH,
Pr-14-2.075 of EN 1363-1: 2012
J. Hybese 879, St.
St.-Peter-Str. 25,
18.11.2015 EN 1366-3: 2009
CZ-39181 Veseli A-4021 Linz
Pavus a.s. Promat GmbH,
Pr-13-2.045 of EN 1363-1: 2012
J. Hybese 879, St.
St.-Peter-Str. 25,
05.09.2014 EN 1366-3: 2009
CZ-39181 Veseli A-4021 Linz
Pavus a.s. Promat GmbH,
Pr-13-2.047 of EN 1363-1: 2012
J. Hybese 879, St.
St.-Peter-Str. 25,
08.09.2014 EN 1366-3: 2009
CZ-39181 Veseli A-4021 Linz
Pavus a.s. Promat GmbH,
Pr-13-2.052 of EN 1363-1: 2012
J. Hybese 879, St.
St.-Peter-Str. 25,
15.07.2014 EN 1366-3: 2009
CZ-39181 Veseli A-4021 Linz
Pavus a.s. Promat GmbH,
Pr-13-2.051 of EN 1363-1: 2012
J. Hybese 879, St.
St.-Peter-Str. 25,
15.07.2014 EN 1366-3: 2009
CZ-39181 Veseli A-4021 Linz
Pavus a.s. Promat GmbH,
Pr-13-2.093 of EN 1363-1: 2012
J. Hybese 879, St.
St.-Peter-Str. 25,
09.04.2014 EN 1366-3: 2009
CZ-39181 Veseli A-4021 Linz
Pavus a.s. Promat GmbH,
Pr-13-2.103 of EN 1363-1: 2012
J. Hybese 879, St.
St.-Peter-Str. 25,
09.09.2014 EN 1366-3: 2009
CZ-39181 Veseli A-4021 Linz
Pavus a.s. Promat GmbH,
Pr-14-2.074 of EN 1363-1: 2012
J. Hybese 879, St.
St.-Peter-Str. 25,
25.09.2014 EN 1366-3: 2009
CZ-39181 Veseli A-4021 Linz
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 16 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Pavus a.s. Promat GmbH,


Pr-16-2.061 of EN 1363-1: 2012
J. Hybese 879, St.-Peter-Str. 25,
St.
10.06.2016 EN 1366-3: 2009
CZ-39181 Veseli A-4021 Linz

3.2 Resistance to fire performance:

Table 1: Terms of conditions

Standard time temperature


emperature curve: Standard time temperature curve (STTC)
as specified in EN 1363--1: 2000, clause
5.1.1
Direction of exposure: horizontal penetration sealing (floor)
vertical penetration sealing (wall)

Table 2: Test results

Test method Parameter Result


Test Report No.
Date
Test specimen 10, cable groups 1-5
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-10-2.098 Time until occurrence of sustained ≥ 90
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 30.11.2009
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]
Test specimen 14
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-10-2.098 Time until occurrence of sustained ≥ 120
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 30.11.2009
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 17 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 34, cable group 1


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-10-2.098 Time until occurrence of sustained ≥ 90
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 14.05.2010 Time of exceeding the maximum ≥ 60
temperature increase above 180 K
 CC on the unexposed side [min.]

Test specimen 34, cable group 2


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-10-2.098 Time until occurrence of sustained ≥ 90
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 14.05.2010 Time of exceeding the maximum ≥ 60
temperature increase above 180 K
 CC on the unexposed side [min.]

Test specimen 34, cable group 3


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-10-2.098 Time until occurrence of sustained ≥ 90
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 14.05.2010 Time of exceeding the maximum ≥ 60
temperature increase above 180 K
 CC on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 18 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 34, cable group 4


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-10-2.098 Time until occurrence of sustained ≥ 90
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 14.05.2010
Time of exceeding the maximum ≥ 90
temperature increase above 180 K
 CC on the unexposed side [min.]

Test specimen 34, cable group 5


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-10-2.098 Time until occurrence of sustained ≥ 90
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 14.05.2010 Time of exceeding the maximum ≥ 60
temperature increase above 180 K
 CC on the unexposed side [min.]

Test specimen 10, cable groups 1-5


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-10-2.098 Time until occurrence of sustained ≥ 90
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 04.12.2009 Time of exceeding the maximum ≥ 90
temperature increase above 180 K
 CC on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 19 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 11
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-10-2.098 Time until occurrence of sustained ≥ 90
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 04.12.2009 Time of exceeding the maximum ≥ 90
temperature increase above 180 K
 CC on the unexposed side [min.]

Test specimen 31
EN 1366-4: 2006 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-10-2.099 Time until occurrence of sustained ≥ 120
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 27.07.2010 Time of exceeding the maximum ≥ 60
temperature increase above 180 K
 CC joint on the unexposed side [min.]

Test specimen 32
EN 1366-4: 2006 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-10-2.099 Time until occurrence of sustained ≥ 120
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 27.07.2010 Time of exceeding the maximum ≥ 120
temperature increase above 180 K
 CC joint on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 20 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 31
EN 1366-4: 2006 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-10-2.099 Time until occurrence of sustained ≥ 90
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 29.07.2010 Time of exceeding the maximum ≥ 90
temperature increase above 180 K
 CC joint on the unexposed side [min.]

Test specimen 32
EN 1366-4: 2006 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-10-2.099 Time until occurrence of sustained ≥ 90
flaming [min.]
of 22.09.2010 Thermal insulation (I)
Test date: 29.07.2010 Time of exceeding the maximum ≥ 90
temperature increase above 180 K
 CC joint on the unexposed side [min.]

Test specimen 102, 103, 104, 105, 106, 107, 108, 109, 110,
111, 112, 113, 114, 115, 146, 149, 150, 154, 155
EN 1366-3: 2009 Pipe end configuration u/c
in conjunction with Fire integrity (E)
EN 1363-1: 2000 Time until cotton pad ignition [min.] ≥ 90
Time until failure of gap gauge ≥ 90
Pr-12-2.101 criteria [min.]
Time until occurrence of sustained ≥ 90
of 06.09.2012 flaming [min.]
Test date: 11.01.2012 Thermal insulation (I)
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 21 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 200, cable groups 1-6


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 11.01.2012 Time of exceeding the maximum ≥ 90
temperature increase above 180 K
 CC cable on the unexposed side [min.]

Test specimen 102


EN 1366-3: 2009 Pipe end configuration u/c
in conjunction with Fire integrity (E)
EN 1363-1: 2000 Time until cotton pad ignition [min.] ≥ 120
Time until failure of gap gauge ≥ 120
Pr-12-2.101 criteria [min.]
Time until occurrence of sustained ≥ 120
of 06.09.2012 flaming [min.]
Test date: 23.01.2012 Thermal insulation (I)
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]
Test specimen 103 & 104
Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 120
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 23.01.2012
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 22 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 105 & 106


Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 120
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 23.01.2012
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]

Test specimen 107 & 108


EN 1366-3: 2009 Pipe end configuration u/c
in conjunction with Fire integrity (E)
EN 1363-1: 2000 Time until cotton pad ignition [min.] ≥ 120
Time until failure of gap gauge ≥ 120
Pr-12-2.101 criteria [min.]
Time until occurrence of sustained ≥ 120
of 06.09.2012 flaming [min.]
Test date: 23.01.2012 Thermal insulation (I)
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]
Test specimen 109
Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 120
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 23.01.2012
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 23 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 110 & 111


Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 120
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 23.01.2012
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]

Test specimen 112, 113, 114


EN 1366-3: 2009 Pipe end configuration u/c
in conjunction with Fire integrity (E)
EN 1363-1: 2000 Time until cotton pad ignition [min.] ≥ 120
Time until failure of gap gauge ≥ 120
Pr-12-2.101 criteria [min.]
Time until occurrence of sustained ≥ 120
of 06.09.2012 flaming [min.]
Test date: 23.01.2012 Thermal insulation (I)
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]
Test specimen 115
Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 120
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 23.01.2012
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 24 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 200, cable groups 2, 3, 5, 6


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 120
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 23.01.2012 Time of exceeding the maximum ≥ 90
temperature increase above 180 K
 CC cable on the unexposed side [min.]

Test specimen 200, cable groups 1 & 4


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 120
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 23.01.2012 Time of exceeding the maximum ≥ 120
temperature increase above 180 K
 CC cable on the unexposed side [min.]

Test specimen 16c, 17c, 18c, 19c, 20c, 21c


Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 30.07.2012
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 25 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 34c, cable groups 1-4


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 30.07.2012 Time of exceeding the maximum ≥ 90
temperature increase above 180 K
 CC cable on the unexposed side [min.]

Test specimen 34c, cable groups 5-6


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 30.07.2012 Time of exceeding the maximum ≥ 60
temperature increase above 180 K
 CC cable on the unexposed side [min.]

Test specimen 16d, 17d, 18d, 19d, 20d, 21d


Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 30.07.2012
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 26 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 34d, cable groups 2, 3, 5


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 30.07.2012 Time of exceeding the maximum ≥ 60
temperature increase above 180 K
 CC cable on the unexposed side [min.]

Test specimen 34d, cable group 1, 4


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 30.07.2012 Time of exceeding the maximum ≥ 90
temperature increase above 180 K
 CC cable on the unexposed side [min.]

Test specimen 34d, cable group 6


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 30.07.2012 Time of exceeding the maximum ≥ 45
temperature increase above 180 K
 CC cable on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 27 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 16c, 17c, 18c, 19c, 20c, 21c


Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 14.08.2012
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]

Test specimen 34c, cable groups 1, 4


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 14.08.2012 Time of exceeding the maximum ≥ 90
temperature increase above 180 K
 CC cable on the unexposed side [min.]

Test specimen 34c, cable groups 2, 3, 5, 6


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 14.08.2012 Time of exceeding the maximum ≥ 60
temperature increase above 180 K
 CC cable on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 28 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 16d


Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 14.08.2012
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]

Test specimen 17d, 18d


Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 14.08.2012
Time of exceeding the maximum ≥ 60
 CC temperature increase above 180 K
on the unexposed side [min.]

Test specimen 19d, 20d, 21d


Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 14.08.2012
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 29 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 34d, cable groups 1-4


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 14.08.2012 Time of exceeding the maximum ≥ 60
temperature increase above 180 K
 CC cable on the unexposed side [min.]

Test specimen 34d, cable groups 5, 6


EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.101 Time until occurrence of sustained ≥ 90
flaming [min.]
of 06.09.2012 Thermal insulation (I)
Test date: 14.08.2012 Time of exceeding the maximum ≥ 45
temperature increase above 180 K
 CC cable on the unexposed side [min.]

Test specimen 51, 52, 53


Pipe end configuration u/u
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.059 Time until occurrence of sustained ≥ 90
flaming [min.]
of 02.07.2012 Thermal insulation (I)
Test date: 11.01.2012
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 30 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 51, 53, 52


Pipe end configuration u/u
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-12-2.059 Time until occurrence of sustained ≥ 120
flaming [min.]
of 02.07.2012 Thermal insulation (I)
Test date: 23.01.2012
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]

Test specimen 66
Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-12-2.059 Time until occurrence of sustained ≥ 120
flaming [min.]
of 02.07.2012 Thermal insulation (I)
Test date: 23.01.2012
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]

Test specimen 67, 68, 69


Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-12-2.059 Time until occurrence of sustained ≥ 120
flaming [min.]
of 02.07.2012 Thermal insulation (I)
Test date: 23.01.2012
Time of exceeding the maximum ≥ 45
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 31 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 85
EN 1366-3: 2009 Pipe end configuration u/c
in conjunction with Fire integrity (E)
EN 1363-1: 2000 Time until cotton pad ignition [min.] ≥ 120
Time until failure of gap gauge ≥ 120
Pr-12-2.059 criteria [min.]
Time until occurrence of sustained ≥ 120
of 02.07.2012 flaming [min.]
Test date: 23.01.2012 Thermal insulation (I)
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]
Test specimen 86
Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2000 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-12-2.059 Time until occurrence of sustained ≥ 90
flaming [min.]
of 02.07.2012 Thermal insulation (I)
Test date: 23.01.2012
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]

Test specimen 87
Pipe end configuration u/c
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2000 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-12-2.059 Time until occurrence of sustained ≥ 120
flaming [min.]
of 02.07.2012 Thermal insulation (I)
Test date: 23.01.2012
Time of exceeding the maximum ≥ 60
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 32 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen 88, 89


EN 1366-3: 2009 Pipe end configuration u/c
in conjunction with Fire integrity (E)
EN 1363-1: 2000 Time until cotton pad ignition [min.] ≥ 90
Time until failure of gap gauge ≥ 90
Pr-12-2.059 criteria [min.]
Time until occurrence of sustained ≥ 90
of 02.07.2012 flaming [min.]
Test date: 23.01.2012 Thermal insulation (I)
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]
Test specimen 60 cable group 1, 4
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2012 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-14-2.075 Time until occurrence of sustained ≥ 120
flaming [min.]
of 18.11.2015 Thermal insulation (I)
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]
Test specimen 60 cable groups 2, 3
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2012 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-14-2.075 Time until occurrence of sustained ≥ 120
flaming [min.]
of 18.11.2015 Thermal insulation (I)
Time of exceeding the maximum ≥ 90
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 33 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen A
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2012 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-13-2.045 Time until occurrence of sustained ≥ 120
flaming [min.]
of 05.09.2014 Thermal insulation (I)
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]
Test specimen A
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2012 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-13-2.047 Time until occurrence of sustained ≥ 120
flaming [min.]
of 08.09.2014 Thermal insulation (I)
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]
Test specimen B
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 90
EN 1363-1: 2012 Time until failure of gap gauge ≥ 90
criteria [min.]
Pr-13-2.052 Time until occurrence of sustained ≥ 90
flaming [min.]
of 15.07.2014 Thermal insulation (I)
Time of exceeding the maximum ≥ 60
 CC temperature increase above 180 K
on the unexposed side [min.]
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 34 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Test specimen A
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2012 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-13-2.051 Time until occurrence of sustained ≥ 120
flaming [min.]
of 15.07.2014 Thermal insulation (I)
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]
Test specimen A
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 120
EN 1363-1: 2012 Time until failure of gap gauge ≥ 120
criteria [min.]
Pr-13-2.093 Time until occurrence of sustained ≥ 120
flaming [min.]
of 09.04.2014 Thermal insulation (I)
Time of exceeding the maximum ≥ 120
 CC temperature increase above 180 K
on the unexposed side [min.]
Test specimen R
EN 1366-3: 2009 Fire integrity (E)
in conjunction with Time until cotton pad ignition [min.] ≥ 60
EN 1363-1: 2012 Time until failure of gap gauge ≥ 60
criteria [min.]
Pr-16-2.061 Time until occurrence of sustained ≥ 60
flaming [min.]
of 10.06.2016 Thermal insulation (I)
Time of exceeding the maximum ≥ 60
 CC temperature increase above 180 K
on the unexposed side [min.]

4. Classification and direct field of application:

4.1 Reference of Classification:

This classification has been carried out in accordance with clause 7 of EN 13501-2:2007
and A1:2009.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 35 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

4.2 Classification

The construction product “PROMASTOP®-CC” CC” is classified according to following


combinations of performance parameters and classes as appropriate.

 Pr-10-2.098 – Test specimen 10,


10 cable groups 1-5  CC
of 30.11.2009
R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90

 Pr-10-2.098 – Test specimen 14 of 30.11.2009  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90, E 120
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90, EI 120

 Pr-10-2.098 – Test specimen 34 CG1, CG2, CG3 of 14.05.2010 CC


R E I W t t - M S C IncSlow sn ef r
- E - - 90 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 60 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90
EI 15, EI 20, EI 30, EI 45, EI 60

 Pr-10-2.098 – Test specimen 34 CG4 of 14.05.2010  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 36 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-10-2.098 – Test specimen 34 CG5 of 14.05.2010  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 90 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 60 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90
EI 15, EI 20, EI 30, EI 45, EI 60

 Pr-10-2.098 – Test specimen 10 CG1, CG2, CG3, CG4, CG5 of 04.12.2009  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90

 Pr-10-2.098 – Test specimen 11 of 04.12.2009  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90

 Pr-10-2.098 – Test specimen 31 of 27.07.2010  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 120 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 60 - - - - - - - - -

Fire resistance classification:


EI 60 – H – M 7.5 – F – W 5 to 50
However, on a small scale it can be replaced by:
E 15, E 30, E 45, E 60, E 90, E 120
EI 15, EI 20, EI 30, EI 45, EI 60
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 37 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-10-2.098 – Test specimen 32 of 27.07.2010  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


EI 120 – H – M 7.5 – F – W 5 to 50
However, on a small scale it can be replaced by:
E 15, E 30, E 45, E 60, E 90, E 120
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90, E 120

 Pr-10-2.098 – Test specimen 31 of 29.07.2010  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


EI 90 – V – M 7.5 – F – W 5 to 50
However, on a small scale it can be replaced by:
E 15, E 30, E 45, E 60, E 90
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90

 Pr-10-2.098 – Test specimen 32 of 29.07.2010  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


EI 90 – V – M 7.5 – F – W 5 to 50
However, on a small scale it can be replaced by:
E 15, E 30, E 45, E 60, E 90
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90

 Pr-12-2.101 – Test specimen 102, 103, 104, 105, 106, 107, 108, 109, 110, 111, 112,
113, 114, 115, 146, 149, 150, 154, 155 of 11.01.2012  CC
R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 38 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-12-2.101 – Test specimen 200 CG1, CG2, CG3, CG4, CG5, CG6 of 11.01.2012 CC
R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90

 Pr-12-2.101 – Test specimen 102 of 23.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c, E 120 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c, EI 120 – u/c

 Pr-12-2.101 – Test specimen 103, 104 of 23.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 120 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c, E 120 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c

 Pr-12-2.101 – Test specimen 105, 106 CC


of 23.01.2012 
R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c, E 120 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c, EI 120 – u/c
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 39 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-12-2.101 – Test specimen 107, 108 of 23.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 120 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c, E 120 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c

 Pr-12-2.101 – Test specimen 109 of 23.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c, E 120 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c, EI 120 – u/c

 Pr-12-2.101 – Test specimen 110, 111 CC


of 23.01.2012 
R E I W t t - M S C IncSlow sn ef r
- E - - 120 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c, E 120 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c

 Pr-12-2.101 – Test specimen 112, 113, 114 of 23.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c, E 120 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c, EI 120 – u/c
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 40 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-12-2.101 – Test specimen 115 of 23.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 120 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c, E 120 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c

 Pr-12-2.101 – Test specimen 200 CG2, CG3, CG5, CG6 of 23.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 120 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90,
90 E 120
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90

 Pr-12-2.101 – Test specimen 200 CG1,


CG CG4 of 23.01.2012  CC
R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90, E 120
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90, EI 120

 Pr-12-2.101 – Test specimen 16c, 17c, 18c, 19c, 20c, 21c of 30.07.2012  CC
R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 41 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-12-2.101 – Test specimen 34c CG1, CG2, CG3, CG4 of 30.07.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90

 Pr-12-2.101 – Test specimen 34c CG5, CG6 of 30.07.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 90 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 60 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60,, E 90
EI 15, EI 20, EI 30, EI 45, EI 60

 Pr-12-2.101 – Test specimen 16d, 17d, 18d, 19d, 20d, 21d CC


of 30.07.2012 
R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c

 Pr-12-2.101 – Test specimen 34d CG2, CG3, CG5 of 30.07.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 90 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 60 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60,, E 90
EI 15, EI 20, EI 30, EI 45, EI 60
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 42 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-12-2.101 – Test specimen 34d CG1, CG4 of 30.07.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90

 Pr-12-2.101 – Test specimen 34d CG6 of 30.07.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 90 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 45 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45,, E 60, E 90
EI 15, EI 20, EI 30, EI 45

 Pr-12-2.101 – Test specimen 16c, 17c, 18c, 19c, 20c, 21c of 30.07.2012  CC
R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c

 Pr-12-2.101 – Test specimen 34c CG1, CG4 of 14.08.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E90
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 43 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-12-2.101 – Test specimen 34c CG2, CG3, CG5, CG6 of 14.08.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 90 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 60 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60,, E 90
EI 15, EI 20, EI 30, EI 45, EI 60

 Pr-12-2.101 – Test specimen 16d of 14.08.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c

 Pr-12-2.101 – Test specimen 17d, 18d of 14.08.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 90 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 60 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c

 Pr-12-2.101 – Test specimen 19d, 20d, 21d of 14.08.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 44 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-12-2.101 – Test specimen 34d CG1, CG2, CG3, CG4 of 14.08.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 90 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 60 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60,, E 90
EI 15, EI 20, EI 30, EI 45, EI 60

 Pr-12-2.101 – Test specimen 34d CG5, CG6 of 14.08.2012 CC


R E I W t t - M S C IncSlow sn ef r
- E - - 90 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 45 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45,, E 60, E 90
EI 15, EI 20, EI 30, EI 45

 Pr-12-2.059 – Test specimen 51, 52, 53 of 11.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/u, E 30 – u/u, E 45 – u/u, E 60 – u/u, E 90 – u/u
EI 15 – u/u, EI 20 – u/u, EI 30 – u/u, EI 45 – u/u, EI 60 – u/u, EI 90 – u/u

 Pr-12-2.059 – Test specimen 51, 53, 52 of 23.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15 – u/u, E 30 – u/u, E 45 – u/u, E 60 – u/u, E 90 – u/u, E 120 – u/u
EI 15 – u/u, EI 20 – u/u, EI 30 – u/u, EI 45 – u/u, EI 60 – u/u, EI 90 – u/u, EI 120 – u/u
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 45 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-12-2.059 – Test specimen 66 of 23.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c, E 120 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c, EI 120 – u/c

 Pr-12-2.059 – Test specimen 67, 68, 69 of 23.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 120 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 45 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c, E 120 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c

 Pr-12-2.059 – Test specimen 85 CC


of 23.01.2012 
R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c, E 120 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c, EI 120 – u/c

 Pr-12-2.059 – Test specimen 86 CC


of 23.01.2012 
R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 46 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-12-2.059 – Test specimen 87 of 23.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 120 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 60 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c, E 120 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c

 Pr-12-2.059 – Test specimen 88, 89 of 23.01.2012  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15 – u/c, E 30 – u/c, E 45 – u/c, E 60 – u/c, E 90 – u/c
EI 15 – u/c, EI 20 – u/c, EI 30 – u/c, EI 45 – u/c, EI 60 – u/c, EI 90 – u/c

 Pr-14-2.075 – Test specimen 60 CG1,


CG1 CG 4  CC
R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90,
90 E 120
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90, EI 120

 Pr-14-2.075 – Test specimen 60 CG2, CG3  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 120 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 90 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90,
90 E 120
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 47 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-13-2.045 – Test specimen A  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90,
90 E 120
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90, EI 120

 Pr-13-2.047 – Test specimen A  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90, E 120
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90, EI 120

 Pr-13-2.052 – Test specimen B  CC


R E I W t t - M S C IncSlow sn ef r
- E - - 90 - - - - - - - - -

R E I W t t - M S C IncSlow sn ef r
- E I - 60 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90
EI 15, EI 20, EI 30, EI 45, EI 60

 Pr-13-2.051 – Test specimen A  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90, E 120
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90, EI 120
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 48 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

 Pr-13-2.093 – Test specimen A  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 120 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60, E 90, E 120
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90, EI 120

 Pr-16-2.061 – Test specimen R  CC


R E I W t t - M S C IncSlow sn ef r
- E I - 60 - - - - - - - - -

Fire resistance classification:


E 15, E 30, E 45, E 60
EI 15, EI 20, EI 30, EI 45, EI 60

No other classifications are permitted.


IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 49 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

4.3 Field of application:

4.3.1 Orientation of penetration seal

The test results are only applicable to the orientation in which the penetration seals were
tested, i.e. in a wall or floor.

4.3.2 Pipe end configuration

Pipe end configuration tests performed u/u shall also cover the configurations u/u, c/u, u/c
and c/c.

Pipe end configuration tests performed u/c shall also cover the configuration u/c and c/c.

4.3.3 Supporting construction (wall/floor)


(wall/

Rigid floor constructions::


The floor must have a minimum thickness of ≥ 150 mm and a minimum density of ≥ 450
kg/m³.

Rigid wall constructions::


The wall must either have a minimum thickness of ≥ 100 mm or ≥ 150 mm and a density of
≥ 450 kg/m³.
(See clause 4.3.10 on specifications of walls for linear joint/gap
/gap seals).
seal
The results achieved using a rigid standard supporting construction shall be valid for
separating construction products
products of concrete or masonry having a similar or higher
thickness and density as the tested ones.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 50 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Flexible wall constructions:


constructions
The wall must have a thickness of ≥ 100 mm and be made from wooden or metal studs st
which are lined on both sides with minimum 2 layers of minimum 12.5 mm thick boards
(other board thicknesses shall be permissible,
permissible, please note minimum thickness). For timber
stud walls, a minimum distance of 100 mm must be kept from each of the wooden stud to
the sealing and the cavity between studs and sealing must be filled with at least 100 mm
insulation material compliant to class A1 or A2 (in acc. with EN 13501-1).
13501 An additional
framing with boards of the opening is not necessary.

The classification results from flexible wall constructionss may also apply to rigid wall
constructions in case the thickness and density is higher than those of the tested
construction.

The supporting construction must be classified in accordance to EN 13501-2


13501 for the
required fire resistance period.

4.3.4 PROMASTOP®-CC
CC soft
s penetration seals

When installing soft penetration seals, the following parameters must be observed:
The boards
oards must be of non-combustible
non combustible mineral wool (A1 in acc. with EN 13501-1)
13501 with a
melting point of ≥ 1000°C and a density of ≥ 140 kg/m³, ³, unless otherwise defined.
The distance between the mineral wool boards must be ≥ 0 mm.

The PROMASTOP®-CC CC firestop coating


co must be applied on all cutting edges, board joints
and outer surfaces. The dry film thickness on the outside surface of the mineral wool boards
must be ≥ 0.7 mm.
The required coating thickness can be taken from the cable classifications; however,
basically the surface requires 1 mm;
mm except for cable group 6 which takes 3 mm.
The overlapping coating of penetration seals on the supporting construction
co (wall/floor)
takes 0 mm.

The necessary thickness and number of mineral wool boards is relatedrel to the specific use
and the required classification (see table with penetration seal sizes below).
It is not necessary to use an additional framing with boards in the opening in the flexible wall
construction, the soft penetration seal can be directly mount into the metal studs.

Penetration seal versions:

Mineral wool board with PROMASTOP®-


1 x 50 mm 1 x 80 mm 2 x 50 mm
CC
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 51 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Penetration seal sizes:

Soft penetration seal versions and areas


Installation / Supporting construction
1 x 50 mm 1 x 80 mm 2 x 50 mm
Flexible wall ≥ 100 mm 1.80 m² 1.80 m² 3.75 m²
Rigid wall ≥ 100 mm 1.80 m² 1.80 m² 3.75 m²
Rigid floor ≥ 150 mm 1.95 m² 1.95 m² 3.75 m²

Mounting possibilities of the soft penetration seals:

Shortcuts used in drawings:

Shortcut Description

A Building element (floor, wall)


B Firestop product (Coating)
C Backfilling material
D Penetrating installations
E Pipe insulation
F Soft penetration seal
G Framing in flexible walls (see figures 6-8)
6
tA Thickness of the building element (floor, wall)
tB Thickness of firestop product (PROMASTOP®-CC CC coating)
tC Thickness of the backfilling material
tD Thickness of the installation (e.g. pipe wall…)
tE Thickness of Insulation
tF Thickness of the soft penetration seal
TG Thickness of aperture framing (see figures 6-8)
wF Width of soft penetration seal
dD Diameter of the installation (e.g. pipe, cable, cable bundle…)

Figure 1 – 3:

A… Flexible wall
B… PROMASTOP®-CC firestop coating
tA ≥ 100 mm
tB ≥ 0,7 mm PROMASTOP®-CC
wF depends on the soft penetration seal sizes, see
above.
F… see clause 4.3.4

Figure 1:

Single board soft penetration seal


tf = min. 50 mm
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 52 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Figure 1 Figure 2 Figure 3 Figure 2:

Single board soft penetration seal


tf = min. 80 mm

Figure 3:

Double board soft penetration seal


tf = min. 2 x 50 mm

Figure 4 – 5:

Possible arrangement of the soft


penetration seals in flexible walls
A… Flexible wall
B… PROMASTOP®-CC firestop coating
tA ≥ 100 mm
tB ≥ 0,7 mm PROMASTOP®-CC
wF depends on the soft penetration seal
sizes, see above.
F… see clause 4.3.4

Figure 4 Figure 5

Figure 6 – 8:

Possible structural connection detail


for soft penetration seals in flexible
walls
A… Flexible wall
G… Aperture framing, 1 layer
tA ≥ 100 mm
tG… thickness ≥ 1 layer of the wall
lining
F… see clause 4.3.4
Figure 6:

Without additional aperture framing,


but with the metal stud
Figure 7:

Without the metal stud but with


minimum 1 layer of the flexible wall
lining in the aperture
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 53 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Figure 6 Figure 7 Figure 8 Figure 8:

With the metal stud and minimum 1


layer of the flexible wall lining in the
aperture

Figure 9 – 11:

A… Rigid wall
B… PROMASTOP®-CC firestop coating
tA ≥ 100 mm
tB ≥ 0,7 mm PROMASTOP®-CC
wF depends on the soft penetration seal sizes, see
above.
F… see clause 4.3.4

Figure 9:

Single board soft penetration seal


tf = min. 50 mm

Figure 10:

Single board soft penetration seal


tf = min. 80 mm

Figure 11:

Double board soft penetration seal


tf = min. 2 x 50 mm

Figure 9 Figure 10 Figure 11


Figure 12 – 13:

Possible arrangement of the soft


penetration seals in rigid walls
A… Rigid wall
B… PROMASTOP®-CC firestop coating
tA ≥ 100 mm
tB ≥ 0,7 mm PROMASTOP®-CC
wF depends on the soft penetration seal
sizes, see above.
F… see clause 4.3.4
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 54 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Figure 12 Figure 13

Figure 14 – 16:

Soft penetration seals in rigid floor


A… Rigid floor
B… PROMASTOP®-CC firestop coating
tA ≥ 150 mm
tB ≥ 0,7 mm PROMASTOP®-CC
wF depends on the soft penetration seal sizes, see
above.
F… see clause 4.3.4
Figure 14:

Single board soft penetration seal


tf = min. 50 mm
Figure 14

Figure 15:

Single board soft penetration seal


tf = min. 80 mm

Figure 15

Figure 16:

Double board soft penetration seal


tf = min. 2 x 50 mm

Figure 16
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 55 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

4.3.5 Overpaintability of PROMASTOP®-CC penetration seals

PROMASTOP®-CC CC penetration seals can be overpainted with coatings and paints based on
emulsion, polyurethane, acrylic or their mixtures for decorative or environmental protection purposes
(Test Report No. Pr-13-2.103--En, issued 09.09.2014).

PROMASTOP®-CC
CC penetration seals can be overpainted with fire stop coatings PROMASTOP®-I or
®
PROMASTOP -E (Test
st Report No. Pr-14-2.074-En,
Pr issued 25.09.2014).

There was now negative influce for the fire resistance regarding Integrity (E) and Insulation (I)
recorded.

4.3.6 Cable penetration seals

Depending on the soft penetration seal version, the following classifications can be assigned:
Soft penetration seal versions and
orientation
Electrical installation
1 x 50 mm 1 x 80 mm 2 x 50 mm
Wall Floor Wall Floor Wall Floor
All sheated cable types
E90
Ø ≤ 21 mm EI90 EI90 EI90 EI120 EI120
EI60
(CG 1)
All sheated cable types
E90 E90 E90 E120 E120
Ø ≤ 50 mm EI60 EI60 EI60
EI90
EI90 EI90
(CG 2)
All sheated cable types
E90 E90 E90 E120 E120
Ø ≤ 80 mm EI90
EI60 EI60 EI60 EI90 EI90
(CG 3)
Cable bundle
E90
Ø ≤ 100 mm EI90 EI90 EI90 EI120 EI120
EI60
(CG 4)
Non-sheated cable types
E90 E90 E90 E90 E120
Ø ≤ 24 mm EI45 EI60 EI60
EI90
EI60 EI90
(CG 5)
Empty conduits from steel, copper or
plastic; Pipe end configuration U/C E90 E90 E90 E90 E120
EI90
Ø ≤ 16 mm EI45 EI45 EI60 EI60 EI90
(CG 6)
CG...Cable group compliant to EN 1366-3:2009
1366

Coating thickness, coating length of cables,


cables, cable bundles, cable trays, cable groups:
Object Film thickness (mm) Coating length (mm)
Cable groups 1 - 5 1
Cable group 6 3 100
Cable trays, cable ladders,
ladders etc. 1

Cable trays and cable ladders can be lead through the soft penetration seal.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 56 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Figure 17 – 18:

Possible arrangement of
the single or double board
soft penetration seals in
flexible and rigid walls

A1… Rigid wall


A2… Flexible wall
B… PROMASTOP®-CC
firestop coating
D… Cables, cable
bundles, conduits without
cable tray
D1… Cables, cable
bundles, conduits with
cable tray
D2… Cable tray, cable
ladder
tA ≥ 100 mm
lB ≥ 100 mm
tB1 ≥ 1 mm
Figure 17 Figure 18 PROMASTOP®-CC
tB2 ≥ 0,7 mm
Detail: Detail: PROMASTOP®-CC
wF depends on the soft
penetration seal sizes, see
clause 4.3.4.
F… see clause 4.3.4

Thickness of B on cable
group 6 ≥ 3 mm, see
above.

Figure 19:

Possible arrangement of the soft


penetration seals in rigid walls
A… Rigid wall
B… PROMASTOP®-CC firestop
coating
tA ≥ 100 mm
tB1 ≥ 1 mm PROMASTOP®-CC
tB2 ≥ 0,7 mm PROMASTOP®-CC
wF depends on the soft penetration
seal sizes, see above.
F… see clause 4.3.4

Thickness of B on cable group 6 ≥ 3


mm, see above.

Detail:
Detail If there is a space between the boards,
it is not necessary to apply the firestop
coating on the cables, cable tray... .
Figure 19
Cable trays can penetrate also the
seal.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 57 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Figure 20 – 23:

Soft penetration seals in rigid floor


A… Rigid floor
B… PROMASTOP®-CC firestop coating
D… Cables, cable bundles, conduits without cable
tray
D1… Cables, cable bundles, conduits with cable tray
D2… Cable tray, cable ladder
tA ≥ 150 mm
tB ≥ 0,7 mm PROMASTOP®-CC
lB ≥ 100 mm
tB1 ≥ 1 mm PROMASTOP®-CC
tB2 ≥ 0,7 mm PROMASTOP®-CC
tF … see clause 4.3.5
wF depends on the soft penetration seal sizes, see
clause 4.3.4.
F… see clause 4.3.4

Thickness of B on cable group 6 ≥ 3 mm, see above.

If there is a space between the boards, it is not


necessary to apply the firestop coating on the cables,
Figure 20 cable tray... .

Figure 21:

Single board soft penetration seal


tf = min. 80 mm

Thickness of B on cable group 6 ≥ 3 mm, see above.

Cable trays can penetrate also the seal.

Figure 21
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 58 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Figure 22:

Double board soft penetration seal


tf = min. 2 x 50 mm

Thickness of B on cable group 6 ≥ 3 mm, see above.

Cable trays can penetrate also the seal.

Figure 22

Figure 23:

Single board soft penetration seal


tf = min. 50 mm

Thickness of B on cable group 6 ≥ 3 mm, see above.

Cable trays can penetrate also the seal.

Figure 23
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 59 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

4.3.7 Non-combustible
combustible pipe materials with non-combustible
combustible section insulation of
class A2 / A2L or higher-graded
higher

Applications for non-combustible


combustible pipe materials:
The section insulation can be made of mineral wool (melting point ≥ 1000°C, A2 / A2 L acc.
to EN 13501-1 or higher-graded
graded)) fulfilling the required lengths and thicknesses as can be
taken from the diagrams. The section insulation can be realised as a LS, LI, CS or CI
configuration in compliance with EN 1366-3.
1366

The insulation shall be placed in the center of the supporting construction or soft penetration
seal and fixed
ed with steel wire or the like.

Continued insulation, sustained Continued insulation, interrupted


(CS) (CI)

Local insulation, sustained (LS) Local insulation, interrupted (LI)

Results of copper pipes can be also apply to steel pipes but not vice versa.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 60 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Supporting distances:
The installations must be suspended ≤ 250 mm on both sides from walls or on the top of
floor constructions.

Classification steel pipes and substitutes


Classification:

Density mineral wool: ≥ 40 kg/m³


kg/m to ≤ 150 kg/m³
Insulation thickness: ≥ 30 mm to ≤ 100 mm, or see remark on 4 mm pipe wall thickness

EI 60-u/c EI 90-u/c EI 90-u/c


with non-combustible ® ® ®
PROMASTOP -CC PROMASTOP -CC PROMASTOP -CC
insulation 1 x 50 mm 1 x 80 mm 2 x 50 mm
Wall Floor Wall Floor Wall Floor
Steel pipe OD [mm] ≤ 114 ≤ 114 ≤ 114 ≤ 114 ≤ 220 ≤ 220
Steel pipe s [mm] T ≤ 14.2 T ≤ 14.2 T ≤ 14.2 T ≤ 14.2 T ≤ 14.2 T ≤ 14.2
OD...Outer diameter
s...pipe thickness
T... Table value (see below)

The results can be also applied


appl to metal pipes with a lower thermal conductivity λ ≤ 58
W/mK and a melting point ≥ 1100 °C (e.g. stainless steel, cast iron and nicke l alloys (NiCr,
NiMo, NiCu).
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 61 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Classification copper pipes and substitutes


Classification:

Density mineral wool: ≥ 40 kg/m³


kg/m to ≤ 150 kg/m³
Insulation thickness: ≥ 30 mm to ≤ 100 mm

EI 60-u/c EI 90-u/c EI 90-u/c


® ® ®
with non-combustible PROMASTOP -CC PROMASTOP -CC PROMASTOP -CC
insulation 1 x 50 mm 1 x 80 mm 2 x 50 mm
Wall Floor Wall Floor Wall Floor
Copper pipe OD [mm] ≤ 88.9 ≤ 88.9 ≤ 88.9 ≤ 88.9 ≤ 88.9 ≤ 88.9
Copper pipe s [mm] T ≤ 14.2 T ≤ 14.2 T ≤ 14.2 T ≤ 14.2 T ≤ 14.2 T ≤ 14.2
OD...Outer diameter
s...pipe thickness
T... Table value (see below)

The results from copper pipelines the results can be also applied to steel pipes, however,
not vice versa, and to pipes with λ ≤ 380 W/mK and a melting point of ≥ 1083 °C.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 62 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

4.3.8 Aluminium composite pipes with combustible insulation of class E (acc. to EN


13501-1) or higher-graded
graded (exclusive of class B)

4.3.8.1 Aluminium composite pipes type Geberit Mepla

Aluminium composite pipes (type Geberit Mepla)) with combustible insulation (maximum
thickness 4 mm, class E in acc. with EN 13501-1
13501 or higher-graded
graded (exclusive of class B),
B)
®
e.g. from PE), can be sealed with fire stop collars of type PROMASTOP -FC. The
combustible insulation is placed in the middle-position
position of the soft penetration seal and must
have a minimum length of 200 mm. When used use in walls, fire stop collars must be mounted
on both sides of the soft penetration (with threaded rods through the soft penetration). The
configuration of this insulation is effected as LS (see illustration clause 4.3.7).

Classification

Aluminium composite ®
PROMASTOP -CC
pipes with combustible 2 x 50 mm
insulation and
PROMASTOP -FC
® Wall Floor
Geberit Mepla EI 120-u/c -
Ø 16 mm
Geberit Mepla EI 45-u/c
Ø 20, 26, 32, 40, 50, 63, 75 -
mm E 120-u/c

4.3.8.2 Aluminium composite pipes type Pipelife Radopress

Aluminium composite pipes (type Pipelife Radopress) with combustible insulation (thickness
4 – 9 mm, class E in acc. with EN 13501-1
13501 or higher-graded
graded (exclusive of class B), e.g. from
PE), can be sealed with fire stop wrap PROMASTOP®-W (for wall application on both sides
of the penetration seal, for floor applications on the bottom side of the penetration seal).
seal) The
combustible insulation situation is CS (see illustration clause 4.3.7).
4.3.7 .

Classification

Aluminium composite ®
PROMASTOP -CC
pipes with combustible 2 x 50 mm
insulation and
®
PROMASTOP -W – 1 Wall Floor
Layer
Pipelife Radopress EI 120-u/c EI 120-u/c
Ø 16 – 63 mm
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 63 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

4.3.9 Aluminium composite pipes with combustible insulation of class B-s3,


B d0 (acc.
to EN 13501-1)
1) or higher-graded
higher

4.3.9.1 Aluminium composite pipes type Geberit Mepla

Aluminium composite pipes (type Geberit Mepla)) with combustible insulation (thickness
from ≥ 6 mm to ≤ 32 mm, class B-s3,
B d0 in acc. with EN 13501-1 or higher-graded,
higher e.g. from
®
elastomeric foam), can be sealed with fire stop collars of type PROMASTOP -FC.

The combustible insulation is placed in the middle-position


position of the soft penetration seal and
must have a minimum length of 500 mm. When used in walls, fire stop collars must be
mounted on both sides of the soft penetration seal (with threaded rods through the soft
penetration seal). The configuration of this insulation is effected as LS (see illustration
clause point 4.3.7).

Classification with insulation thickness 6 mm and insulation length 500 mm

Aluminium composite ®
PROMASTOP -CC
pipes with combustible 2 x 50 mm
insulation and
PROMASTOP -FC
® Wall Floor
Geberit Mepla EI 120-u/c -
Ø 16 mm
Geberit Mepla EI 90-u/c -
Ø 20, 26 mm
Geberit Mepla EI 60-u/c
Ø 32, 40, 50, 63, 75 mm -
E 120-u/c

Classification with insulation thickness 32 mm and insulation length 500 mm

Aluminium composite ®
PROMASTOP -CC
pipes with combustible 2 x 50 mm
insulation and
PROMASTOP -FC
® Wall Floor
Geberit Mepla
Ø 16, 20, 26, 32, 40, 50, 63, EI 90-u/c -
75 mm

Combinations of insulation are possible with thicknesses between 6 - 32 mm and pipe


diameters between 16 - 26 mm; EI 90-u/c.
90 u/c. All other possibilities arise from the two tables
above.

4.3.9.2 Aluminium composite pipes type Pipelife Radopress

Aluminium composite pipes (type Pipelife Radopress) with combustible insulation (thickness
6 – 32 mm, class B-s3,
s3, d0 in acc. with EN 13501-1
13501 or higher-graded,
graded, e.g. from elastomeric
®
foam), can be sealed with fire stop wrap PROMASTOP -W (for for wall application on both
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 64 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

sides
ides of the penetration seal, for floor applications on the bottom side of the penetration
seal).. The combustible insulation is placed in the middle-position
middle position of the soft penetration seal
and must have a minimum length of 500 mm, the insulation situation is LS (see illustration
clause 4.3.7).

Classification

Aluminium composite ®
PROMASTOP -CC
pipes with combustible 2 x 50 mm
insulation and
®
PROMASTOP -W – 1 Wall Floor
Layer
Pipelife Radopress EI 120-u/c
u/c
Ø 16 – 63 mm EI 120-u/c
* for Ø 63 mm E120 EI60-u/c*
u/c*
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 65 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

4.3.10 Fire stop wrap PROMASTOP®-W in the PROMASTOP®-CC


CC penetration seal

The fire stop wrap PROMASTOP®-W shall be e wrapped around plastic pipes within the
PROMASTOP®-CC CC penetration seal. For wall application on both sides of the penetration
seal, for floor applications on the bottom side of the penetration seal. PROMASTOP®-W
shall be installed flushed to the surface of the penetration seal (max. 5 mm off the surface)
and shall be fixed with PROMASTOP®-CC, PROMASEAL®-A A or PROMASEAL®-AG.

Classification overview: pipe materials, dimensions, installation situation, classifications

Dimension range Orientation


No. of Layers
Designation Ø…Diameter (mm) F...Floor
Ø (mm)  Layers
Classification
s…pipe wall thickness (mm) W...wall
32 – 63  1
75 – 110  2
PVC-U Ø 32 / s 1.8 - Ø 160 / s 11.8 W EI120-U/C
125  3
140 – 160  4
32 – 63  1
75 – 110  2
PE-HD Ø 32 / s 2.0 - Ø 160 / s 14.6 W EI120-U/C
125  3
140 – 160  4
32 – 63  1
75 – 110  2
PP-H / PP-R Ø 32 / s 1.8 - Ø 160 / s 14.6 W EI120-U/C
125  3
140 – 160  4
Ø 32 / s 1.8
Ø 40 / s 1.8
32  2
Ø 50 / s 2.0
40 – 63  3
Ø 75 / s 2.6
Poloplast PoloKal NG W 75 – 90  4 EI90-U/U
Ø 90 / s 3.0
110 – 125  5
Ø 110 / s 3.4
140 – 160  6
Ø 125 / s 3.9
Ø 160 / s 4.9
Ø 75 / s 3.8
Ø 90 / s 4.5 75 – 90  4
Poloplast PoloKal 3S Ø 110 / s 4.8 W 110 – 125  5 EI90-U/U
Ø 125 / s 5.3 140 – 160  6
Ø 160 / s 7.5
Ø 32 / s 1.8
Ø 40 / s 1.8
32  2
Ø 50 / s 2.0
40 – 63  3
Ø 75 / s 2.6
Poloplast PoloKal XS W 75 – 90  4 EI90-U/U
Ø 90 / s 3.0
110 – 125  5
Ø 110 / s 3.4
140 – 160  6
Ø 125 / s 3.9
Ø 160 / s 4.9
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 66 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Dimension range Orientation


No. of Layers
Designation Ø…Diameter (mm) F...Floor
Ø (mm)  Layers
Classification
s…pipe wall thickness (mm) W...wall
Ø 56 / s 3.2
Ø 63 / s 3.2 32  2
Ø 75 / s 3.6 40 – 63  3
Geberit Silent-db20 Ø 90 / s 5.5 W 75 – 90  4 EI90-U/U
Ø 110 / s 6.0 110 – 125  5
Ø 135 / s 6.0 135 – 160  6
Ø 160 / s 7.0
32 – 63  1
75 – 110  2
PVC-U Ø 32 / s 1.8 - Ø 160 / s 11.8 F EI120-U/C
125  3
140 – 160  4
32 – 63  1
75 – 110  2
PE-HD Ø 32 / s 2.0 - Ø 160 / s 14.6 F EI120-U/C
125  3
140 – 160  4
32 – 63  1
75 – 110  2
PP-H / PP-R Ø 32 / s 1.8 - Ø 160 / s 14.6 F EI120-U/C
125  3
140 – 160  4
Ø 32 / s 1.8
Ø 40 / s 1.8
32  2
Ø 50 / s 2.0
40 – 63  3
Poloplast PoloKal NG Ø 75 / s 2.6 F EI90-U/U
75 – 90  4
Ø 90 / s 3.0
110 – 125  5
Ø 110 / s 3.4
Ø 125 / s 3.9
Ø 32 / s 1.8
Ø 40 / s 1.8 32  2
Ø 50 / s 2.0 40 – 63  3
Poloplast PoloKal NG Ø 75 / s 2.6 F 75 – 90  4 EI90-U/U
Ø 90 / s 3.0 110 – 125  5
Ø 110 / s 3.4
Ø 125 / s 3.9
Ø 56 / s 3.2
32  2
Ø 63 / s 3.2
40 – 63  3
Geberit Silent-db20 Ø 75 / s 3.6 F EI90-U/U
75 – 90  4
Ø 90 / s 5.5
110 – 125  5
Ø 110 / s 6.0

The classifications for PVC-U


U pipes are applicable for pipes acc. to EN 1452-1,
1452 DIN 8061 and DIN
8062.
HD pipes are applicable for pipes acc. to EN 12201-2,
The classifications for PE-HD 12201 DIN 8074, DIN
8075.
The classifications for PP-H
H and PP-R
PP R pipes are applicable for pipes acc. to EN ISO 15494, DIN
8077 and DIN 8078.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 67 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

PVC pipes with PROMASTOP®-W fire stop wrap in the PROMASTOP®-CC


CC penetration seal in wall
wa
and floor application, EI120-U/C
U/C

PE pipes with PROMASTOP®-W fire stop wrap in the PROMASTOP®-CC


CC penetration seal in wall
and floor application, EI120-U/C
U/C
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 68 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

PP pipes with PROMASTOP®-W fire stop wrap in the PROMASTOP®-CC


CC penetration seal in wall
and floor application, EI120-U/C
U/C

4.3.11 Fire stop collar PROMASTOP®-FC


FC on soft penetration PROMASTOP®-CC

The classification results from flexible wall constructions may also apply to rigid wall
constructions in case the thickness and density is equal or higher than those of the tested
construction.
When used in walls, the fire stop collars must be installed on both sides of the wall; but
when used in floor constructions the fire stop collars are only needed on the bottom side.

Sealing of annular gap:


In soft penetrations the annular gap is filled with acrylic sealant PROMASEAL®-A in a depth
of ≥ 5 mm and backfilled with mineral wool of class A1 (in acc. with EN 13501-1). 13501
Alternatively, also the firestop coating PROMASTOP®-CC CC can be used.

Sockets:
The diameter of the socketss may be reduced but not increased.
re the usage of PROMASTOP®-FC6 fire stop collars.
Sockets always require

Sound decoupling:
Any sound decoupling strips based on PE foam and class E (acc. to EN 13501-1)
13501 or higher-
graded with a maximum thickness of 5 mm can be used.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 69 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Supporting distance:
The installations must be suspended ≤ 250 mm on both sides from walls or on the top of
floor constructions.

Pipe end configuration:


Pipe end configuration tests performed u/u shall also cover the configurations u/u, c/u, u/c
and c/c.
Pipe end configuration
on tests performed u/c shall also cover the configuration u/c and c/c.
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 70 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Fire stop collar PROMASTOP®-FC installation "the


the built in situation":
situation

Fire stop collar PROMASTOP®-FC installation "surface-mount":


mount":

When taking the results of the critical pipe method into account the following pipes and
installation types shall apply:

Classification overview: pipe materials,


materia dimensions, installation situation,
situation classifications

Soft
Dimension range penetra
Orientation
Designation Ø…Diameter F...Floor Collar type Classification
s…
…pipe wall thickness
tion W...wall
(mm)
Friatec Friaphon Ø 52 / s 2.8 - Ø 110 / s 5.3 1 x 50 F FC3 EI60-U/U
Friatec Friaphon Ø 52 / s 2.8 - Ø 110 / s 5.3 1 x 80 F FC3 EI90-U/U
Friatec Friaphon Ø 52 / s 2.8 - Ø 110 / s 5.3 2 x 50 F FC3 EI90-U/U
Friatec dBlue Ø 50 / s 1.8 - Ø 125 / s 3.9 1 x 50 F FC3 EI60-U/U
Friatec dBlue Ø 50 / s 1.8 - Ø 125 / s 3.9 1 x 80 F FC3 EI90-U/U
Friatec dBlue Ø 50 / s 1.8 - Ø 125 / s 3.9 2 x 50 F FC3 EI90-U/U
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 71 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Geberit Silent dB 20 Ø 56 / s 3.2 - Ø 160 / s 7.0 1 x 50 F FC3 EI60-U/U


Geberit Silent dB 20 Ø 56 / s 3.2 - Ø 160 / s 7.0 1 x 80 F FC3 EI90-U/U
Geberit Silent dB 20 Ø 56 / s 3.2 - Ø 160 / s 7.0 2 x 50 F FC3 EI90-U/U
Geberit Silent dB 20 Ø 56 / s 3.2 - Ø 135 / s 6.0 1 x 50 W FC3 EI60-U/U
Geberit Silent dB 20 Ø 56 / s 3.2 - Ø 135 / s 6.0 1 x 80 W FC3 EI90-U/U
Geberit Silent dB 20 Ø 56 / s 3.2 - Ø 135 / s 6.0 2 x 50 W FC3 EI90-U/U
Pipelife Master3 Ø 75 / s 2.1 - Ø 125 / s 3.5 1 x 50 F FC3 EI60-U/U
Pipelife Master3 Ø 75 / s 2.1 - Ø 125 / s 3.5 1 x 80 F FC3 EI90-U/U
Pipelife Master3 Ø 75 / s 2.1 - Ø 125 / s 3.5 2 x 50 F FC3 EI90-U/U
Pipelife Master3 Ø 75 / s 2.1 - Ø 125 / s 3.5 1 x 50 W FC3 EI60-U/U
Pipelife Master3 Ø 75 / s 2.1 - Ø 125 / s 3.5 1 x 80 W FC3 EI90-U/U
Pipelife Master3 Ø 75 / s 2.1 - Ø 125 / s 3.5 2 x 50 W FC3 EI120-U/U
PoloKal NG Ø 32 / s 1.8 - Ø 250 / s 8.6 1 x 50 F FC3/FC6 EI60-U/U
PoloKal NG Ø 32 / s 1.8 - Ø 250 / s 8.6 1 x 80 F FC3/FC6 EI90-U/U
PoloKal NG Ø 32 / s 1.8 - Ø 250 / s 8.6 2 x 50 F FC3/FC6 EI90-U/U
PoloKal NG Ø 32 / s 1.8 - Ø 160 / s 4.9 1 x 50 W FC3 EI60-U/U
PoloKal NG Ø 32 / s 1.8 - Ø 250 / s 8.6 1 x 50 W FC3/FC6
FC EI60-U/U
PoloKal NG Ø 32 / s 1.8 - Ø 250 / s 8.6 1 x 80 W FC3/FC6 EI90-U/U
PoloKal NG Ø 32 / s 1.8 - Ø 250 / s 8.6 2 x 50 W FC3/FC6 EI90-U/U
PoloKal XS Ø 32 / s 1.8 - Ø 250 / s 8.6 1 x 50 F FC3/FC6 EI60-U/U
PoloKal XS Ø 32 / s 1.8 - Ø 250 / s 8.6 1 x 80 F FC3/FC6 EI90-U/U
PoloKal XS Ø 32 / s 1.8 - Ø 250 / s 8.6 2 x 50 F FC3/FC6 EI90-U/U
PoloKal XS Ø 32 / s 1.8 - Ø 160 / s 4.9 1 x 50 W FC3 EI60-U/U
PoloKal XS Ø 32 / s 1.8 - Ø 250 / s 8.6 1 x 50 W FC3/FC6 EI60-U/U
PoloKal XS Ø 32 / s 1.8 - Ø 250 / s 8.6 1 x 80 W FC3/FC6 EI90-U/U
PoloKal XS Ø 32 / s 1.8 - Ø 250 / s 8.6 2 x 50 W FC3/FC6 EI90-U/U
PoloKal 3S Ø 75 / s 3.8 - Ø 160 / s 7.5 1 x 50 F FC3 EI60-U/U
PoloKal 3S Ø 75 / s 3.8 - Ø 160 / s 7.5 1 x 80 F FC3 EI90-U/U
PoloKal 3S Ø 75 / s 3.8 - Ø 160 / s 7.5 2 x 50 F FC3 EI90-U/U
PoloKal 3S Ø 75 / s 3.8 - Ø 160 / s 7.5 1 x 50 W FC3 EI60-U/U
PoloKal 3S Ø 75 / s 3.8 - Ø 160 / s 7.5 1 x 80 W FC3 EI60-U/U
PoloKal 3S Ø 75 / s 3.8 - Ø 160 / s 7.5 2 x 50 W FC3 EI120-U/U
PVC-U Ø 32 / s 1.8 - Ø 250 / s 4.9 1 x 50 F FC3/FC6 EI60-U/U
PVC-U Ø 32 / s 1.8 - Ø 250 / s 4.9 1 x 80 F FC3/FC6 EI90-U/U
PVC-U Ø 32 / s 1.8 - Ø 250 / s 4.9 2 x 50 F FC3/FC6 EI90-U/U
PE-HD Ø 32 / s 1.8 - Ø 200 / s 11.4 1 x 50 F FC3/FC6 EI60-U/U
PE-HD Ø 32 / s 1.8 - Ø 200 / s 11.4 1 x 80 F FC3/FC6 EI90-U/U
PE-HD Ø 32 / s 1.8 - Ø 200 / s 11.4 2 x 50 F FC3/FC6 EI90-U/U
PE-HD Ø 40 / s 1.8 - Ø 200 / s 11.4 1 x 50 W FC3/FC6 EI60-U/U
PE-HD Ø 40 / s 1.8 - Ø 200 / s 11.4 1 x 80 W FC3/FC6 EI90-U/U
PE HD Ø 40 / s 1.8 - Ø 200 / s 11.4 2 x 50 W FC3/FC6 EI90-U/U

PE-HD Ø 40 / s 1.8 - Ø 200 / s 11.4 2 x 50 W FC3/FC6 EI90-U/U


(the
the built in situation)
situation
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 72 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

PP-H / PP-R Ø 30 / s 1.8 - Ø 200 / s 11.4 1 x 50 F FC3/FC6 EI60-U/U


PP-H / PP-R Ø 30 / s 1.8 - Ø 200 / s 11.4 1 x 80 F FC3/FC6 EI90-U/U
PP-H / PP-R Ø 30 / s 1.8 - Ø 200 / s 11.4 2 x 50 F FC3/FC6 EI90-U/U
PP-H / PP-R Ø 40 / s 1.8 - Ø 250 / s 14.2 1 x 50 W FC3/FC6 EI60-U/U
PP-H / PP-R Ø 40 / s 1.8 - Ø 250 / s 14.2 1 x 80 W FC3/FC6 EI90-U/U
PP-H / PP-R Ø 40 / s 1.8 - Ø 250 / s 14.2 2 x 50 W FC3/FC6 EI90-U/U
PP-H / PP-R Ø 40 / s 1.8 - Ø 250 / s 14.2 2 x 50 W FC3/FC6 EI120-U/U
Raupiano Plus Ø 40 / s 1.8 - Ø 200 / s 6.2 1 x 50 F FC6 EI60-U/U
Raupiano Plus Ø 40 / s 1.8 - Ø 200 / s 6.2 1 x 80 F FC6 EI90-U/U
Raupiano Plus Ø 40 / s 1.8 - Ø 200 / s 6.2 2 x 50 F FC6 EI90-U/U
Raupiano Plus (+socket) Ø 40 / s 1.8 - Ø 125 / s 3.1 1 x 50 F FC6 EI60-U/U
Raupiano Plus (+socket) Ø 40 / s 1.8 - Ø 125 / s 3.1 1 x 80 F FC6 EI90-U/U
Raupiano Plus (+socket) Ø 40 / s 1.8 - Ø 125 / s 3.1 2 x 50 F FC6 EI90-U/U
Raupiano Plus (+socket) Ø 40 / s 1.8 - Ø 125 / s 3.1 1 x 50 W FC6 EI60-U/U
Raupiano Plus (+socket) Ø 40 / s 1.8 - Ø 125 / s 3.1 1 x 80 W FC6 EI90-U/U
Raupiano Plus (+socket) Ø 40 / s 1.8 - Ø 125 / s 3.1 2 x 50 W FC6 EI120-U/U

Details on the dimensions of combustible pipes can be taken from the following diagrams.

Friatec Friaphon pipe with or without sound decoupling combined with surface-mounted
surface
firestop collar PROMASTOP®-FC FC on soft penetration seal PROMASTOP®-CC with EI60 –
u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 73 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Friatec Friaphon pipe with or without sound decoupling combined with surface-mounted
surface
®
firestop collar PROMASTOP -FC FC on soft penetration seal PROMASTOP®-CC with EI90 –
u/u:

Friatec Friaphon pipe with or without sound decoupling combined with surface-mounted
surface
firestop collar PROMASTOP®-FC FC on soft penetration seal PROMASTOP®-CC with EI90 –
u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 74 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Friatec dBlue pipe with or without sound decoupling combined with surface-mounted
surface
firestop collar PROMASTOP®-FC FC on soft penetration seal PROMASTOP®-CC with EI60 –
u/u:

Friatec dBlue pipe with or without sound decoupling combined with surface-mounted
surface
®
firestop collar PROMASTOP -FC FC on soft penetration seal PROMASTOP®-CC with EI90 –
u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 75 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Friatec dBlue pipe with or without sound decoupling combined with surface-mounted
surface
®
firestop collar PROMASTOP -FC FC on soft penetration seal PROMASTOP®-CC with EI90 –
u/u:

Rehau Raupiano Plus pipe with socket and with/without sound decoupling combined with
surface-mounted firestop collar PROMASTOP®-FCFC on soft penetration seal PROMASTOP®-
CC with EI60 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 76 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Rehau Raupiano Plus pipe with socket and with/without sound decoupling combined with
surface-mounted firestop collar PROMASTOP®-FCFC on soft penetration seal PROMASTOP®-
CC with EI90 – u/u:

Rehau Raupiano Plus pipe with socket and with/without sound decoupling combined with
surface-mounted firestop collar PROMASTOP®-FCFC on soft penetration seal PROMASTOP®-
CC with EI90 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 77 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Rehau Raupiano Plus pipe with or without sound decoupling combined with surface-
surface
mounted firestop collar PROMASTOP -FC on soft penetration seal PROMASTOP®-CC with
®

EI60 – u/u:

Rehau Raupiano Plus pipe with or without sound decoupling combined with surface-
surface
®
mounted firestop collar PROMASTOP -FC FC on soft penetration seal PROMASTOP®-CC with
EI90 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 78 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Rehau Raupiano Plus pipe ipe with or without sound decoupling combined with surface-
surface
®
mounted fire stop collar PROMASTOP -FC FC on soft penetration seal PROMASTOP®-CC
with EI90 – u/u:

Geberit Silent dB20 pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
al PROMASTOP®-CC with EI60 – u/u:
penetration seal
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 79 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Geberit Silent dB20 pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
®
penetration seal PROMASTOP -CC with EI90 – u/u:

Geberit Silent dB20 pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI90 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 80 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Pipelife Master3 pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI60 – u/u:

Pipelife Master3 pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
®
penetration seal PROMASTOP -CC with EI90 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 81 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Pipelife Master3 pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI90 – u/u:

Poloplast PoloKal 3S pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI60 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 82 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Poloplast PoloKal 3S pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI90 – u/u:

Poloplast PoloKal 3S pipe with surface-mounted firestop collar PROMASTOP®-FC on soft


penetration seal PROMASTOP®-CC with EI90 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 83 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

PoloKal NG and XS pipes with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI60 – u/u:

PoloKal NG and XS pipes with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI90 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 84 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

PoloKal NG and XS pipes with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI90 – u/u:

PVC-U U pipe in conformity with EN 1452-1,


1452 DIN 8061 and DIN 8062 with surface-mounted
surface
firestop collar PROMASTOP®-FC FC on soft penetration seal PROMASTOP®-CC with EI60 –
u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 85 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

The test results of the PVC-U


PVC pipes shall also apply to PVC-U U pipes in accordance with EN
1329-1 and EN 1453-1 1 and to PVC-C
PVC C pipes complying with EN 1566-1.
1566

PVC-U U pipe in conformity with EN 1452-1,


1452 DIN 8061 and DIN 8062 with surface-mounted
surface
®
firestop collar PROMASTOP -FC FC on soft penetration seal PROMASTOP®-CC with EI90 –
u/u:

The test results of the PVC-U


PVC pipes shall also apply to PVC-U U pipes in accordance with EN
1329-1 and EN 1453-1 1 and to PVC-C
PVC C pipes complying with EN 1566-1.
1566

PVC-U U pipe in conformity with EN 1452-1,


1452 DIN 8061 and DIN 8062 with surface-mounted
surface
llar PROMASTOP®-FC
firestop collar FC on soft penetration seal PROMASTOP®-CC with EI90 –
u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 86 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

The test results of PVC-U


U pipes shall also apply to PVC-U
PVC U pipes in accordance with EN
1329-1 and EN 1453-1 1 as well as PVC-C
PVC C pipes complying with EN 1566-1.
1566

PE-HD pipe conforming with EN 12201-2,


12201 EN 1519-1, EN 12666-1,
1, DIN 8074 and DIN 8075
mounted firestop collar PROMASTOP®-FC
with surface-mounted FC on soft penetration seal
PROMASTOP®-CC CC with EI60 – u/u:

The test results of the PE pipes shall also apply to ABS pipes in accordance with EN 1455-1
1455
and SAN and PVC pipes complying with EN 1565-1.
1565

PE-HD
HD pipe conforming with EN 12201-2,
12201 EN 1519-1, EN 12666-1,
1, DIN 8074 and DIN 8075
mounted firestop collar PROMASTOP®-FC
with surface-mounted FC on soft penetration seal
PROMASTOP®-CC with EI90 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 87 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

The test results of the PE pipes shall also apply to ABS pipes in accordance with EN 1455-1
1455
and SAN and PVC pipes complying with EN 1565-1.
1565

PE-HD
HD pipe conforming with EN 12201-2,
12201 EN 1519-1, EN 12666-1,
1, DIN 8074 and DIN 8075
ounted firestop collar PROMASTOP®-FC
with surface-mounted FC on soft penetration seal
PROMASTOP®-CC CC with EI90 – u/u:

The test results of the PE pipes shall also apply to ABS pipes in accordance with EN 1455-1
1455
and SAN and PVC pipes complying with EN 1565-1.
1565

PP-H and PP-R pipes (e.g.


(e.g complying with OENORM B 5174-1, 1, DIN 8077, DIN 8078 (or
equal products)) with surface-mounted
surface firestop collar PROMASTOP®-FC on soft penetration
seal PROMASTOP®-CC CC with EI60 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 88 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

PP-H and PP-R R pipes (e.g.


(e.g complying with OENORM B 5174-1, 1, DIN
DI 8077, DIN 8078 (or
equal products))
)) with surface-mounted
surface firestop collar PROMASTOP®-FC on soft penetration
seal PROMASTOP®-CC CC with EI90 – u/u:

PP-H and PP-R R pipes (e.g.


(e.g complying with OENORM B 5174-1, 1, DIN 8077, DIN 8078 (or
equal products)) with surface-mounted
surface firestop collar PROMASTOP®-FC on soft penetration
seal PROMASTOP®-CC CC with EI90 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 89 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Rehau Raupiano Plus pipe with socket and with/without sound decoupling combined
com with
surface-mounted firestop collar PROMASTOP®-FC penetrati seal PROMASTOP®-
FC on soft penetration
CC with EI60 – u/u:

Rehau Raupiano Plus pipe with socket and with/without sound decoupling combined
com with
surface-mounted firestop collar PROMASTOP®-FC
FC on soft penetration seal PROMASTOP®-
CC with EI90 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 90 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Rehau Raupiano Plus pipe with socket and with/without sound decoupling combined with
surface-mounted firestop collar PROMASTOP®-FC
FC on soft penetration seal PROMASTOP®-
CC with EI120 – u/u:

Geberit Silent dB20 pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI60 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 91 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Geberit Silent dB20 pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI90 – u/u:

Geberit Silent dB20 pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI120 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 92 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Pipelife Master3 pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI60 – u/u:

Pipelife Master3 pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
®
penetration seal PROMASTOP -CC with EI90 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 93 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Pipelife Master3 pipe with


h surface-mounted
surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI120 – u/u:

Poloplast PoloKal 3S pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI60 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 94 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

Poloplast PoloKal 3S pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI90 – u/u:

Poloplast PoloKal 3S pipe with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI120 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 95 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

PoloKal NG and XS pipes with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
®
penetration seal PROMASTOP
ROMASTOP -CC with EI120 – u/u:

PoloKal NG and XS pipes with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
®
penetration seal PROMASTOP -CC with EI60 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 96 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

PoloKal NG and XS pipes with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI90 – u/u:

PoloKal NG and XS pipes with surface-mounted


surface firestop collar PROMASTOP®-FC on soft
®
penetration seal PROMASTOP -CC with EI90 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 97 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

PE-HD pipe conforming with EN 12201-2, EN 1519-1, EN 12666-1, 1, DIN 8074 and DIN 8075
with the built in firestop collar PROMASTOP®-FC
FC on soft penetration seal PROMASTOP®-
CC with EI120 – u/u:

The test results of the PE pipes shall also apply to ABS pipes in accordance with EN 1455-1
and SAN and PVC pipes complying with EN 1565-1.
1565

PE-HD
HD pipe conforming with EN 12201-2,
12201 EN 1519-1, EN 12666-1,
1, DIN 8074 and DIN 8075
mounted firestop collar PROMASTOP®-FC
with surface-mounted FC on soft penetration seal
PROMASTOP®-CC CC with EI60 – u/u:

est results of the PE pipes shall also apply to ABS pipes in accordance with EN 1455-1
The test 1455
and SAN and PVC pipes complying with EN 1565-1.
1565
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 98 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

PE-HD
HD pipe conforming with EN 12201-2,
12201 EN 1519-1, EN 12666-1,
1, DIN 8074 and DIN 8075
mounted firestop collar PROMASTOP®-FC
with surface-mounted FC on soft penetration seal
PROMASTOP®-CC CC with EI90 – u/u:

The test results of the PE pipes shall also apply to ABS pipes in accordance with EN 1455-1
1455
and SAN and PVC pipes complying with EN 1565-1.
1565

PE-HD
HD pipe conforming with EN 12201-2,
122 EN 1519-1, EN 12666-1,
1, DIN 8074 and DIN 8075
mounted firestop collar PROMASTOP®-FC
with surface-mounted FC on soft penetration seal
PROMASTOP®-CC CC with EI90 – u/u:

The test results of the PE pipes shall also apply to ABS pipes in accordance with EN 1455-1
1455
and SAN and PVC pipes complying with EN 1565-1.
1565
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 99 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

PP-H and PP-R R pipes (e.g.


(e.g complying with OENORM B 5174-1, 1, DIN 8077, DIN 8078 (or
equal products)) with surface-mounted
surface firestop collar PROMASTOP®-FC on soft penetration
seal PROMASTOP®-CC CC with EI60 – u/u:

PP-H and PP-R R pipes (e.g.


(e.g complying with OENORM B 5174-1, 1, DIN 8077, DIN 8078 (or
equal products)) with surface-mounted
surface firestop collar PROMASTOP®-FC on soft penetration
seal PROMASTOP®-CC CC with EI90 – u/u:

PP-H and PP-R pipes (e.g. complying with OENORM B 5174-1, 1, DIN 8077, DIN 8078 (or
equal products))
)) with surface-mounted
surface fire stop collar PROMASTOP®-FC on soft
penetration seal PROMASTOP®-CC with EI90 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 100 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

PP-H and PP-R pipes (e.g. complying with OENORM B 5174-1, 1, DIN 8077, DIN 8078 (or
equal products)) with surface-mounted
surface firestop collar PROMASTOP®-FC on soft penetration
seal PROMASTOP®-CC CC with EI120 – u/u:
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 101 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

4.3.12 Distances

Supporting distances:
The installations must be suspended ≤ 250 mm on both sides from walls or on the top of
floor constructions.

Distances in or between products:

Object Minimum distance


(mm)
Non-combustible
combustible insulation – non-combustible insulation 0
Non-combustible insulation – supporting 0
construction/aperture opening
combustible insulation – PROMASTOP®-IM-CJ21
Non-combustible 0
combustible insulation – PROMATECT® duct
Non-combustible 0
combustible insulation – PROMASTOP®-FC
Non-combustible 0
Cable, cable trays – supporting construction/aperture 0
opening
Cable, cable trays – cable, cable trays 0
Cable, cable trays – PROMASTOP®-FC 0
Cable, cable trays – PROMASTOP®-IM-CJ21 0
PROMASTOP®-FC – PROMASTOP®-FC 0
PROMASTOP®-FC – PROMASTOP®-IM-CJ21 0
PROMASTOP®-FC – PROMATECT® duct 0
PROMASTOP®-FC – supporting construction/aperture 0
opening
PROMASTOP®-W – supporting construction/aperture 0
opening
PROMASTOP®-W – non-combustible
non insulation 0
® ®
PROMASTOP -W – PROMASTOP -W 0
PROMASTOP®-W – PROMASTOP®-IM-CJ21 20
PROMASTOP®-W – PROMASTOP®-FC 25
PROMASTOP®-W – PROMATECT® duct 30
PROMASTOP®-IM-CJ21 CJ21 – PROMASTOP®-IM-CJ21 0
®
PROMASTOP -IM-CJ21 CJ21 – PROMASEAL®-AG 0
PROMASTOP®-IM-CJ21 CJ21 – supporting construction/aperture 0
opening
Any other distances 100
IBS – Institut für Brandschutztechnik und Classification Report No.: 316100407-A-en
Sicherheitsforschung Gesellschaft m. b. H. Date: 08.11.2016
A - 4020 Linz, Petzoldstrasse 45 Page 102 of 103
Akkreditierte Prüf-,, Inspektions-
Inspektions und Zertifizierungsstelle Sponsor: PRTC

4.3.13 Linear Joint and Gap seals

Rigid floor constructions::


The floors must have a minimum thickness of ≥ 150 mm and a minimum density of ≥ 450
kg/m³.

Rigid wall constructions::


The walls must have a minimum thickness of ≥ 150 mm and a minimum density of ≥ 450
kg/m³.

The results achieved using a rigid standard supporting construction shall be valid for
separating construction products
products of concrete or masonry having a similar or higher
thickness and density as the tested ones.

Classification of linear joint seals in rigid floor constructions

Thickness of rigid floor: ≥ 150 mm


Linear joint width: > 5 ≤ 50 mm
Backfilling material:: Backfilling class E in accordance to EN 13501--1 (or higher-graded e.g.
glass wool,
ool, mineral wool, ceramic wool etc.) e.g. single-component
component PU foam.
PROMASTOP®-CC (thickness
thickness ≥ 1 mm) is used on top or bottom of the backfilling and a 10
mm coating is applied circumferentially to the adjacent structural component.

Alignment A tested in accordance with EN 1366-4:2010


1366 4:2010 (joint sealing in horizontal test
frame) shall cover A and D in compliance with EN 1366-4:2010
1366 4:2010 (linear
( joint sealing in
horizontal floor construction and horizontal wall joint adjoining a floor
loor, suspended floor or
roof).

Top coating with 1 mm PROMASTOP®-CC (on the unexposed side)


EI 60 – H – M 7.5 – F – W 5 to 50
Classification in the small frame can be replaced by:
E 15, E 30, E 45, E 60, E 90, E 120
EI 15, EI 20, EI 30, EI 45, EI 60

Bottom coating with 1 mm PROMASTOP®-CC (on the exposed side)


EI 120 – H – M 7.5 – F – W 5 to 50
Classification in the small frame can be replaced by:
E 15, E 30, E 45, E 60, E 90, E 120
EI 15, EI 20, EI 30, EI 45, EI 60, EI 90, EI 120

Classification of linear joint seals in rigid wall constructions

Thickness of rigid wall: ≥ 150 mm


Linear joint width: > 5 ≤ 50 mm