Basic Compliance Requirement with reference :

1. Fire Hydrant . [ ACCORD Standard ,Part 5 ]

2. Addressable fire alarm [ACCORD Standard, 5.7.2.2 ]

3. PA will be covered to all areas. [NFPA 72 -Clause 24.4.3.2.5.2]

4. Minimum width of aisles: Aisles shall be provided with a minimum unobstructed clear--‐width of 0.9
m (36 inc.) [ACCORD Standard 6.5.1]

5. Exit Door width will be 1.15 meter (45 Inc.), Height 2 meter (78 inc.) [BLR -2015 (54-2)]

6. Dining facility must be provided for 15 % existing worker in the facility. [BLR -2015 (92)]

7. Exit will not be more distance than 50 meter from any workers. [BLR -2015 (54-2)]

8. Toilet facility : Male - First 100 : 1 toilet for 40 [Next 1 for 60 workers ] Female - First 100 : 1 toilet for
25 [Next 1 for 50 workers ] BLR -2015 Schedule -2 .

9. All doors in a means of egress shall be of the side--‐hinged swinging type. Roll--‐down and sliding
gates and shutters shall not be allowed. [ACCORD Standard 6.8.1]

10. Assembly area should be designated [ BNBC Part 4 , Sec. 4.8.11.1 ]

11. A factory having more than 3000 to 7500 workers two registered doctor , Asst. , Nurse is required .
More than 7500 workers 3 registered doctor , Asst. , Nurse is required . [ BLR – 78 ]

12. Automatic sprinkler protection shall be installed throughout all portions of new and existing high--‐
rise buildings with an occupiable floor greater than 23 m (75 ft) above . [ ACCORD Standard 5.3.3.]

13. Extinguishers shall be placed so that maximum travel distance to the nearest unit shall not exceed 30
m (100 ft). [ ACCORD Standard 5.6.1 ]

14. Factory Owner shall ensure that at least one trained professional individual is assigned to each
factory facility to manage and monitor the operational loadings of the building. [ACCORD Standard
13.7.1.1 ]