You are on page 1of 41

5/14/2021

FX Fire Alarm System


Configuration Sheet

Put together a system in 5 steps:


1. Select initiating devices
2. Select panel
3. Select options for panel
4. Select signals
5. Do battery calculations

Note: Macros must be enabled for all features to work.

Instructions

Before you begin you should have a good idea of what type of system is being quoted (conventional or
addressable), and what / how many devices are being connected to it. The Fire Alarm System FA System
Questions to Ask form is a good place to start if you are not sure. To open a copy of the form, double Questions to Ask
click on the .pdf icon to the right.

The FX Configuration Spreadsheet is a quick way to put together the parts for a conventional or
addressable fire alarm system in 5 easy steps. It was created using an Excel spreadsheet, but can be
printed out and used as a check list that can be filled in by hand. Note that you may have to manually
clarify some part numbers to specify options, such as colors, if using this in its printed form. Yellow
highlighted cells are where you make entries if using this in its electronic spreadsheet form.
Information in other cells will then be filled in automatically as needed.

Step 1 is to select the initiating devices. For a conventional system, these would be on the Conv
Devices (1) tab. For an addressable system, you would start on the Addr Devices (1) tab. Steps 2
and 3 would be to select the panel size and options, either on the Conv Panel (2 & 3) or Addr Panel
(2 & 3) tabs.

Step 4 is to select the signals (horns, strobes) on the Signals (4) tab and calculate the signal load. If
using the printed sheet, you'll have to calculate the signal load manually. If using the electronic
spreadsheet, you can enter the quantities of each device type in the section that shows device currents
and it will total the currents for you.

The final step (step 5) is to determine the proper battery size for the panel using either the Conv Panel
Batts (5) or Addr Panel Batts (5) tab. You can either fill these out manually on the printed page, or by
entering the values in the spreadsheet. If using it in it's electronic form, some of the selections from the
previous sheets automatically carry over to these sheets (other values such as signal loads and battery
back up time will have to be entered manually). The calculations will then be done for you. If booster
power supplies are needed, you will also have to fill out the BPS Batteries (5a) tab to determine proper
batteries.

If your system includes speakers for audio evacuation (paging and/or pre-recorded message), fill out
the Speakers (4a), Audio Panel (4b), and Audio Panel Batts (5b) sheets.

The Misc. sheet includes other available Kidde - Edwards fire alarm products that are less commonly
used. Because of this, there are no "checks and balances" when you select these items (no "too many
devices" or current load checks, for example). Selected devices will be included on the Summary
sheet, however, and be part of the final BOM.

When finished with your selections, you can go the the Summary sheet to review (only in electronic
the Speakers (4a), Audio Panel (4b), and Audio Panel Batts (5b) sheets.

The Misc. sheet includes other available Kidde - Edwards fire alarm products that are less commonly
used. Because of this, there are no "checks and balances" when you select these items (no "too many
devices" or current load checks, for example). Selected devices will be included on the Summary
sheet, however, and be part of the final BOM.

When finished with your selections, you can go the the Summary sheet to review (only in electronic
form). The Summary sheet will summarize your selections and give you the option to print a BOM (be
sure to follow the instructions).

When using this configuration sheet in its electronic form, there are red tags ( ) throughout with
additional information (some tags also mark hidden calculations and pop-up warnings). To view, place
the mouse pointer over the tag. For more detailed product information, refer to catalog and/or
installation sheets

Always double check selections for mistakes. Although there are some warnings for wrong or missing
entries, the user is ultimately responsible for the correct bill of material.

This Configuration Sheet includes most, but no all, the fire alarm products Kidde - Edwards offer. You
can contact Kidde - Edwards if you need something not shown on these sheets. Note: 230V and
foreign versions of panels are not available to U.S. customers.

It is suggested that you keep an original copy of this spreadsheet and save any changes you might
make as another file name to ensure you have a clean starting point each time.
FA System
Questions to Ask
7/19/2011

8/9/2011
8/22/2011
2/1/2012
6/15/2012

1/9/2013
2/20/2013

3/4/2013
3/6/2013
3/19/2013
5/6/2013
6/18/2013
7/9/2013
9/20/2013
9/23/2013
1/16/2014
1/17/2014

6/24/2014
3/25/2015
4/21/2015
5/7/2015
9/8/2015

9/11/2015

1/13/2016

1/19/2016
1/27/2016

7/1/2016
7/18/2016

10/24/2016
11/29/2016
1/5/2017
1/9/2017
1/24/2017
2/3/2017

4/18/2017

4/19/2017
5/3/2017
5/11/2017
6/7/2017
6/23/2017
7/25/2017
8/24/2017
9/6/2017
9/19/2017
1/9/2018
1/23/2018
4/16/2018
4/17/2018
4/24/2018
5/9/2018
6/26/2018
7/3/2018
8/8/2018
8/20/2018
8/22/2018

9/7/2018

10/3/2018
10/16/2018
11/13/2018

6/5/2019
6/12/2019
6/20/2019
9/10/2019
9/24/2019

9/25/2019
10/4/2019
10/8/2019

11/4/2019

11/5/2019
12/10/2019
12/18/2019
3/30/2020
4/3/2020
4/6/2020
7/20/2020
9/3/2020
3/26/2021
5/5/2021
5/14/2021
v10b Updated data sheet links

Updated 24Vdc current of 116DEGEX


v10c Added Genesis w.p. speakers
Split color choice for signals
V10d Fixed calculation on Signals Tab (row 61, 62)
V11 draft Re-did BPS battery calc
Added option to change battery time for BPS and ANS
v11a draft Add W.P. Genesis H/S.
ADI_V1 draft Started to create ADI version with ADI part numbes.
Added Misc. tab.
Changed data sheet links to web. Added FAQ to own tab.
ADI_V1 Released V1 for ADI
v11a draft Converted ADI version back to non-ADI
v11a Released v11a
v11b draft Added 260-CO to Addr. Dev sheet
v11b Released
v11c draft Fix BPS battery calc (total alarm curr, cell F41)
v11c draft Updated hyperlinks
v11c Released
v11d draft Added notes to FSA Batts tab re Aux Power
v11e draft Added low freq Genesis to Signals
Added 5553 haz loc speakers
Removed (hid) TS7 smokes
Removed 24AH battery from ANS Batt tab
v12 Released
v1 draft Began converting to FX
v1 draft Added red annun. Option
v1 draft Added low freq sounder base
v1 draft Removed gray panels
Hid ANS panel and speakers
v1 draft Added SD-4WJ option in place of E-PDD
Hid RPM module
Added hidden warning/counts for future 1000 point panel
v1 FX1000draft Adding FX1000 panel
Adding RZI16-2RS module
Hid SD-4WJ option
Added haz loc pull to Addr. Dev. sheet
v1aFX1000draft Reconfigured Panel Batteries calc (combined Aux powers)
v1a draft Added option on Dev sheet to add BPS for RZI
Changed device CD warnings on Signals sheet.
Changed 116DEG to be powered from booster.
Removed ReadySet
Changed to K- annunciator part numbers
Removed SD-4WJ option
v1b draft Started to add back ANS updated version
Added HF speakers
Addr and Conv v1c draft Started to combine conv. and addr.
Added more warnings to ANS tab
Moved Conv Init. tab to front
Added questions to ask form
Changed to K- pull stations
v2 Released
v2a Removed RZI-MPL (included with RZI16)
Corrected switch mod count (to 1 max) on ANS sheet.
Corrected alarm currents for FX addr. loop cards on batt calc.
Corrected FSRA10 qty calc on ConvBatts tab
Added extra aux load warning on Addr. Panel Batts sheet
Added warning that ANS2 not listed for 520Hz.
v2c draft Added R-LED to Addr Dev sheet
Changed 12V10A batteries to equal 10AH (Leoch LP12-10H)
v2c Released
v2c Updated parts on Misc. sheet
v2d Corrected battery cabinet selection on Addr batt calc
v2d Unlocked cell C17 on BPS Batts sheet
v2d Corrected speaker warning (C50) on Speakers sheet
v2e draft Corrected red annunciator description on Summary sheet
v2e draft Added D16L-FA count warning on Addr Panel sheet
v2f draft Fixed run time error when exporting summary
v3 Int draft Started to add panels for International
Hid 511C detector
v3 Released
v4 draft Added KI detectors
v4 Released
v4a draft Changed R-LED to GSA-LED
Removed 520Hz warning from ANS tab
Added note that ANS50 is not listed for 520Hz
Corrected FX-2WIRE currents on batt calc
Added 74347U boxes (red 449)
v4aa Updated Addr. Panel Batt Calcs and RZI currents
Added KIR- carbon monoxide detectors
Updated 116DEGEX current
v4ab draft Hid KIR COs. Started to add Genesis LED
Added/changed 521NC, 521NCXT
Changed Addr Batt calcs back to previous version.
v5 Released
v5a Fixed Addr Batt Calc (did not remove 1.25 mult.)
v5b draft Fixed 116DEG current and calc on Signals page
Changed F-DACT to F-DACT1
Hid 283B heats
v6 draft Unhide KIR-COs. Added back 1.25 mult. In Addr. Batt Calc.
Added EGC low current LED devices, but hid them for now.
Added EG4 LED devices, but hid them for now.
Corrected CS405-7A-T current. Added -8A currents.
Un-hid EGC LED devices.
Hid KIR COs
Un-hid 260-CO on Addr Dev sheet
Removed 284B-PL, added 302-135, -194
v6 Released
v6a draft Some minor clean up on Signals sheet
Added 731U and 702U
Unhide 260-CO on Summary sheet under Conv. Dev.
Changed 541NCSRXT to 541NCRXT (no sounder)
v7 draft Un-hid KIR COs.
Added another FX-NAC line for riser sup for sounder bases
v7 Released
v7a draft Changed FX-NAC / sounder base note
Added speaker LED devices (will hide 'til release)
Disc. / hid EG1, EGC xenon devices (except 177cd)
Unhid EG4 LED horn strobe devices
v8 Released
v8a draft Unhid EG4 LED speaker devices
v8a Released
v9 draft Started to add SA-USB, SA-FSB. Hid G4 / GCHF speakers
v9 Released
v9a Added EG4*SB surface boxes
Step 1 Conventional - Select the initiating devices

Part Number Qty


Smoke detectors
Photoelectric with CleanMe Use: 521NC Direct wires to detector (base included)
Photo/heat combination w/CleanMe Use: 521NCXT Direct wires to detector (base included)
Photoelectric Use: 711U Wires connect to base (base separate)
Photo/heat combination Use: 721UT Wires connect to base (base separate)
Photoelectric with aux relay Use: 731U Wires connect to base (base separate)
Base for 711U/721U Use: 701U Required for 711U & 721U
Base for 731U Use: 702U Required for 731U
Photo/heat with relay, 4 wire Use: 541NCRXT Direct wires to detector (base included)

Carbon monoxide detector The 260-CO has a built in temporal 4


sounder that operates on a per detector
Carbon monoxide detector, 4 wire Use: 260-CO basis when connected to an FX panel (panel
cannot generate T4).
Heat detectors
135F rate compensation, indoor Use: 302-135
194F rate compensaton, indoor Use: 302-194
Indoor/outdoor, rate compenstion, 135F Use: 302-AW-135
Indoor/outdoor, rate compenstion, 194F Use: 302-AW-194
Ex-proof, rate compenstion, 135F Use: 302-EPM-135 Backbox not included
Ex-proof, rate compenstion, 194F Use: 302-EPM-194 Backbox not included
Mounting box for ex-proof detector Use: JALX11

Pull stations
Single action, 1 N.O. contact Use: K-270-SPO
Single action, 2 N.O. contacts Use: K-270-DPO
Double action, 1 N.O. contact Use: K-278B-1110
Double action w/key reset Use: K-278B-1420
Explosion proof, 1 N.O. contact Use: MPSR1-D45WX-GE Includes backbox
Weatherproof, 1 N.O. contact Use: MPSR1-SHTW-GE Includes backbox
Duct detectors
The SD-2W and -4WJ both include
2 wire Use: SD-2W form C alarm relays. The -4WJ also
4 wire (2 wires for power, 2 wires Use: SD-4WJ includes 2 additional aux relays.
The SD-4WJ can be powered from
for initiation) 24Vac/dc or 120Vac.

Each duct detector requires a sampling tube. Choose a length

8" Use: SD-T8


18" Use: SD-T18
Choose a tube that will cover at
24" Use: SD-T24 least two thirds of the way across
36" Use: SD-T36 the duct. All sampling tube holes
must be within the duct. Also cannot
42" Use: SD-T42 cut sampling tube if it means cutting
60" Use: SD-T60 off a sampling hole.
78" Use: SD-T78
120" Use: SD-T120

Each duct detector should also have a test/reset station.

For the 2 wire SD-2W Use: SD-TRK It is recommended with the 4


wire duct that each have its
For the 4 wire SD-4WJ Use: SD-TRK4 own test/reset station.
FX conventional panels include:
5 class B or 2 class A Initiating Device Circuits (IDCs), or zones, on FX-5.
10 class B or 5 class A IDCs on FX-10.
3.5 amps fwr of signal power on FX-5; 7A on FX-10.
Separate resettable and constant aux power, 500mA total.
2 class B or 1 class A Notification Appliance Circiuts (NACs), or signal circuits, on 5 zone.
4 class B or 2 class A NACs on 10 zone panel, rated at 2A each.
Form C common alarm, trouble & supervisory relay contacts rated for 1A at 30Vdc.

Step 2 Conventional - Choose base panel


Part Number Qty
Panels without dialers
Five zone Use: FX-5R For French Canadian version, add letter F
to end of panel part number.
Ten zone Use: FX-10R
Panels with dialers (F-DACT1)
Five zone Use: FX-5RD If French Canadian version of panel requires a dialer, will have
Ten zone Use: FX-10RD to order French Canadian panel and F-DACT1F separately.

Step 3 Conventional - Next choose options for panel


Option modules
City Tie Module Use: CTM Requires dedicated NAC
Dialer (DACT) module Use: F-DACT1 Select if not included with panel above
Programmable Relays Use: FSRRM24 Includes 5 form C relays rated for 1A @ 30Vdc
Cabinet for relay module Use: MFC-A Can fit up to two FSRRM24 relay modules

Remote annunciators
General system indicator Use: FSRSI Indicates power, common alarm, trouble, supervisory, grnd fault.
Individual zone alarm Use: FSRZI-A Indicates alarms per zones, 5 red LEDs per module.
Individual zone alarm or Use: FSRZI-SA Indicates an alarm or supervisory condition per zone,
zone supervisory 5 selectable red or amber LEDs per module.
1 gang trim Use: FSAT1 Used with 1 FSR zone annunciator module
2 gang trim Use: FSAT2 Used with 2 FSR zone annunciator modules
3 gang trim Use: FSAT3 Used with 3 FSR zone annunciator modules
Individual zone active & trouble Use: K-FSRA10 Indicates active and trouble events per zone, 10 bicolor
indications and 10 amber LEDs. For 10 zone panel only.
Individual zone active & trouble Use: K-FSRA10C Same as above but with reset, signal silence
indications with CC and trouble silence switches.
Remote graphic ann. interface Use: FSUIM Used for driving graphic annunciator LEDs and switches.
Remote enable key switch Use: RKEY Used to enable common control switches on K-FSRA10C
Step 1 Addressable - Select the addressable devices
Part Number Qty
Smoke, heat, and CO detectors
Photoelectric smoke Use: KIR-PD
Photoelectric smoke w/ heat Use: KIR-PHD Each detector requires its own base.
Heat only, ROR or 135F Fixed Use: KIR-HD
With CO detectors, sounder bases
Carbon monoxide (CO) Use: KIR-COD should be used, plus the system should
Heat with CO Use: KIR-HCD include at least one FX-T3T4 module to
produce Temporal 4 CO alarm signal.
Smoke with CO Use: KIR-PCD
Smoke with heat and CO Use: KIR-PHCD
Standard base Use: KI-SB4
Remote LED (for KI-SB4 base only) Use: GSA-LED Only used with KI-SB4 base
Relay base Use: KI-RB4 Rated for 2A @ 30Vdc
Isolator base Use: KI-IB4 Used on class A circuits only
Sounder base (not for CO detectors) Use: KI-ABST Requires separate 24Vdc
Sounder base Use: KI-ABDT Requires separate 24Vdc
Sounder base, low freq (sleeping rms) Use: KI-ABLT Requires separate 24Vdc
Surface mount box for sounder base Use: AB4G-SB

Input / output modules

Single input mini module, class B Use: FX-IDC1B Used for N.O. contact devices
Single input module, class A Use: FX-IDC1A Used for N.O. contact devices
Dual input module, class B Use: FX-IDC2B Used for N.O. contact devices
Combo waterflow/supervisory Use: FX-IDCWS Used for N.O. contact devices
Signal (NAC) module Use: FX-NAC 2 amps max
Signal (NAC) / power riser sup. module Use: FX-NAC Used just for sounder base power sup.
Relay module (form C contacts) Use: FX-RLY 2A @ 30Vdc; .5A @ 120Vac
Isolator module Use: FX-ISO Used on class A circuits only
2 wire smoke module Use: FX-2WIRE Used for conventional smokes
Temporal 3 / 4 generator Use: FX-T3T4 Used with sounder bases
Remote zone module, 16 input, 2 output Use: RZI16-2RS 16 inputs and 2 NAC or relay outputs
Mounting cabinet for RZI16-2RS Use: MFC-A Can fit 1 RZI16-2RS
UL listed EOL resistor (for input & NAC mods) Use: EOL-47
UL listed EOL resistor (for FX-2WIRE & RZI16) Use: EOL-4.7
UL listed EOL resistor (for sig ckts on RZI16) Use: EOL-15
For 230Vac version of booster supply (non-U.S. customers only), enter 230
Booster supply, 6 amp, for RZI16-2RS Use: APS6A You can only power one RZI16-2RS module
Batteries for APS6A (need 2 per APS) Use: 12V17A from panel, and only if not using the NACs
on the module. Otherwise each will require
its own booster supply.

Pull stations
Single action Use: FX-270
Double action (w/key reset) Use: FX-278
Surface box for FX-270 or FX-278 Use: 27193-11
Weatherproof single action* Use: MPSR1-SHTW-GE * MPSR pull stations require
Weatherproof double action* Use: MPSR2-SHTW-GE separate addressable input
Hazardous location* Use: MPSR1-D45WX-GE module(s).
Duct detector
Photoelectric type Use: FX-PDD Includes form C alarm contacts

Total addresses used = 0

Each duct detector requires a sampling tube. Choose a length

8" Use: SD-T8


18" Use: SD-T18 Choose a tube that will cover
24" Use: SD-T24 at least two thirds of the way
across the duct. All sampling
36" Use: SD-T36 tube holes must be within the
42" Use: SD-T42 duct. Also cannot cut
sampling tube if it means
60" Use: SD-T60 cutting off a sampling hole.
78" Use: SD-T78
120" Use: SD-T120

Remote indicator/test station

Key operated Use: SD-TRK


Magnet operated Use: SD-TRM
FX panels include:
-64 module or detector capacity (any combination) for FX-64.
-125 module plus 125 detector capacity for FX-1000, expandable to 500 + 500.
-Up to 3.75 amps of signal power for FX-64 or 6.0 w/ FX-1000 (60Hz operation).
-Up to 1000mA of auxilliary power (divided into 2 separate outputs).
-2 class B signal circuits for FX-64 (4 with FX-1000).
-Common alarm, trouble & supervisory relay contacts.
Step 2 Addressable - Choose base panel
Part Number Qty

Panels without dialers


64 point (any combination) Use: FX-64R Add -F for French Candian, -CA for Canada, -PG for
Portuguese, or -SP for Spanish to end of panel part number.
Up to 500 det. + 500 modules Use: FX-1000
Panels without dialers, 230Vac (not for U.S. customers)
64 point (any combination) Use: FX-64R-2 Add -PG for Portuguese or -SP for Spanish
Up to 500 det. + 500 modules Use: FX-1000-2 to end of panel part number.

Panels with dialers


64 point (any combination) Use: FX-64RD Panel with dialer package only available in English (U.S.),
Up to 500 det. + 500 modules Use: FX-1000D 120Vac versions. Could select SA-DACT separately below.

Step 3 Addressable - Next choose options for panel


Option modules

Single loop expansion module Use: FX-SLC1 Supports additional 125 det. + 125 mods (FX1000 only)
Two loop expansion module Use: FX-SLC2 Supports additional 250 det. + 250 mods (FX1000 only)
Dialer (DACT) module Use: SA-DACT Select if not included with panel above
City tie module Use: CTM Requires a dedicated NAC
USB interface module Use: SA-USB For direct connect to laptop and/or printer
RS232 interface module Use: SA-232 For direct connect to laptop and/or printer
Ethernet interface card Use: SA-ETH Used for Ethernet 10/100 Base-T newtork connection
Class A converter Use: SA-CLA Required for class A NACs and annunciator on FX64 panel
LED expander module Use: D16L-FA Provides 16 alarm & trouble zone LEDs (FX1000 panel only)
UL listed, EOL resistors for NACs Use: EOL-15 There are 2 NACs on FX64; 4 on FX1000
Field Server Bridge Use: SA-FSB Requires FSB-BRKT2 mounting bracket and SA-232 module
Mounting bracket for FSB Use: FSB-BRKT2 Used to mount SA-FSB
Mounting cabinet for FSB Use: MFC-A Enclosure for SA-FSB

Remote annunciator
8 remote annunciators max per panel
LCD type Use: K-RLCD 80 character Liquid Crystal Display
LCD type w/ common controls Use: K-RLCD-C 80 character Liquid Crystal Display w/ CC
LED type w/ common controls Use: K-RLED-C 16 zone, red & yellow LED per zone, w/ CC
LED expander, 24 zones Use: K-RLED24 24 zone, red & yellow LED per zone (use w/RLCD or RLED)
Surface mount box Use: LSRA-SB
Single space enclosure Use: RA-ENC1 Optional RA-ENC enclosures provide protection behind a
Two space enclosure Use: RA-ENC2 locked plexiglass door (if flush mounting).
Three space enclosure Use: RA-ENC3
Enable key switch Use: Rkey Used to enable CC on RLED-C. Optional for RLCD-C

Programming cable
The FX panels can be programmed through the front panel
Upload/download cable Use: 260097 keypad. You can also use the FX-CU configuration utility
program if programming via a laptop, or if connecting to
panel from a remote location using the SA-DACT or SA-
ETH module. The 260097 cable is needed for connecting
pc to panel using the SA-232 module. The SA-USB would
use a standard USB cable. The FX-CU can be downloaded
from the kiddefx.kidde.com website.
Step 4 - Select the signaling devices (horns and strobes)
Part Number Qty

Indoor wall mount, single gang, low current LED


Wall mount horn only Use: EG1A__ __ Add letter W for white or R for red followed by F for
Wall mount LED only, 15 - 75cd Use: EG1V__ __ FIRE marking or N for no markings.
(EG1AWF would be white with "FIRE" on it)
Wall mount horn LED, 15 - 75cd Use: EG1AV__ __
Trim for above Use: EG1T__ Trim is for mounting EG1A(V) devices to 4" sq. bx

Indoor wall mount, full size, low current LED


Wall mount horn only Use: EG4A__ __ Add letter W for white or R for red followed by F for
FIRE marking or N for no markings.
Wall mount LED only, 15 - 110cd Use: EG4V__ __ (EG4AWF would be white with "FIRE" on it).
Wall mount horn LED, 15 - 110cd Use: EG4AV__ __ For trim and box, just add W or R.
All EG4s include mounting/wiring plate.
Trim for above Use: EG4T__
Surface mount box Use: EG4__SB
Indoor ceiling mount, high output
Ceiling strobe only, 15 - 95cd Use: EGC__ __-VM Add letter F after the C for "FIRE" markings.
Ceiling strobe only, 95 - 177cd Use: EGC__ __-VMH Add letter R after F for red device with "FIRE" (otherwise it's
white).
Ceiling horn strobe, 15 - 95cd Use: EGC__ __-HDVM Red ceiling devices only available with "FIRE".
Ceiling horn strobe, 95 - 177cd Use: EGC__ __-HDVMH 95-177 cd devices only available in white.
Indoor ceiling mount, low current LED
Add letter W for white or R for red followed by F for FIRE
Ceiling horn only EGCA__ __ marking or N for no markings.
Ceiling LED only, 15 - 115cd EGCV__ __ (EGCAWF would be white with "FIRE" on it)
Horn only version only available with "FIRE".
Ceiling horn LED, 15 - 115cd EGCAV__ __ All EGCs including mounting/wiring plate.
Trim for above EGCT__
Low frequency (520Hz) for sleeping areas
Wall mount horn only Use: G4LF__ __-H Add letter R for red or W for white after F, and F for "FIRE"
or N for no markings after color (G4LFRF-H would be red
Wall mount horn strobe, 15 - 110cd Use: G4LF__ __-HVM with "FIRE" printed on it).
Surface mount box Use: EG4__B For box, add R for red, otherwise it's white.
Indoor / outdoor Genesis (2 wire)
Weatherproof horn Use: WG4__ __-H Add letter R for red or W for white after 4, and F for "FIRE"
Weatherproof h/s, 15 - 87cd Use: WG4__ __-HVMC or N for no markings after color (WG4RF-H would be red
with "FIRE" printed on it)
Weatherproof h/s, 102 - 161cd Use: WG4__ __-HVMHC
Surface mount trim skirt Use: WG4__TS Add R for red or W for white
Weatherproof box Use: 449
Indoor / outdoor Integrity (4 wire)
Weatherproof horn Use: 2447TH-__
Add letter R for red or W for white to end of part
Weatherproof horn with strobe Use: 2452THS-15/75-__ number
WP box for horn(/strobe) Use: 2459-WPB-__
Weatherproof strobe, 15/75cd Use: CS405-7A-T
Weatherproof strobe, 110cd Use: CS405-8A-T
Weatherproof box for strobe Use: 449
Hazardous location
Explosion proof horn Use: 889D-AW Must be powered from booster power supply
Transient protector for 889D Use: 235196P One required for each NAC where 889D is connected
Explosion proof strobe Use: 116DEGEX-FJ Must be powered from booster power supply
Pendant bracket for 116 Use: 116EX-P You must order the mounting for the 116 beacon
Ceiling box for 116 Use: 116EX-C separately. Wall mount requires both 116EX-C
Wall bracket for 116 Use: 116EX-B and 116EX-B.
To accurately size power supplies, enter quantities below for each strobe and horn strobe candela (cd) setting used and total up device currents for both fwr (full
wave rectified) and dc. The FX-5 has 3.5 amps of fwr power, the FX-10 has 7.0 amps of fwr power, the FX-64 panel has 3.75 amps of fwr power, and the FX-
1000 has 6 amps of fwr power. If fwr total exceeds panel's supply, you will need booster power supply(ies). Use dc current values to determine booster power
supply load.
Note: If using the FX-5 or FX-64 panel, and the total fwr signal load exceeds that panel's power supply rating, it may be more cost effective to use the larger
panel (FX-10 or FX-1000 respectively) then to add a booster supply (assuming the signal load does not exceed the larger panel's supply capacity).

Current (mA) Qty Strb Qty Horn


Strobe / Horn Strobe Only & H/S Total (fwr) Total (dc)
EG1 wall horn only x
69fwr, 36dc 0 =
EG1A wall horn only 29fwr, 23dc x =
EG1V wall LED only 32fwr, 24dc x =
EG1AV wall horn LED 55fwr, 45dc x =
EGC ceiling horn only 40fwr, 30dc x =
EGC low current ceiling LED only 45fwr, 35dc x =
EGC low current ceiling horn LED 75fwr, 60dc x =
EG4A wall horn only 38fwr, 28dc x =
EG4V wall LED only 36fwr, 28dc x =
EG4AV wall horn LED 60fwr, 50dc x =
G4LF low frequency horn only 215fwr, 166vdc x =
2447TH w.p. horn only 82fwr, 35dc x 0 =
2452THS w.p. horn strobe 265fwr, 190dc x 0 =
CS405 w.p. strobe only, 15/75cd 210fwr, 162dc x 0 =
CS405 w.p. strobe only, 110cd 420fwr, 329dc x 0
EGC ceiling (horn) strobe - 95cd 432fwr, 330dc / 487fwr, 341dc x =
EGC ceiling (horn) strobe - 115cd 518fwr, 392dc / 578fwr, 399dc x =
EGC ceiling (horn) strobe - 150cd 643fwr, 502dc / 670fwr, 505dc x =
EGC ceiling (horn) strobe - 177cd 693fwr, 565dc / 711fwr, 570dc x =
G4LF low freq. horn strobe - 15cd 308fwr, 219vdc x =
G4LF low freq. horn strobe - 30cd 362fwr, 266vdc x =
G4LF low freq. horn strobe - 75cd 510fwr, 381vdc x =
G4LF low freq. horn strobe - 110cd 579fwr, 437vde x =
WG4 weatherproof horn only 135fwr, 69dc x 0 =
WG4 w.p. h/s, 15cd 218fwr, 127dc x =
WG4 w.p. h/s, 29cd 239fwr, 168dc x =
WG4 w.p. h/s, 70cd 393fwr, 297dc x =
WG4 w.p. h/s, 87cd 422fwr, 351dc x =
WG4 w.p. h/s 102cd 447fwr, 324dc x =
WG4 w.p. h/s 123cd 502fwr, 408dc x =
WG4 w.p. h/s 147cd 614fwr, 517dc x =
WG4 w.p. h/s 161cd 679fwr, 526dc x =
Horn(strobe) totals (mA) fwr = dc =
Currents from Speakers sheet (mA) fwr = dc =
Subtotal fwr = dc =
Ex-proof horn (889D-AW) 160dc x 0 =
Ex-proof strobe (116DEGEX-FJ) 540dc x 0 =
Enter fwr load to be connected to panel mA fwr
Ratio of dc to fwr load = Divide subtotal dc current by subtotal fwr current.
Y = Multiply ratio x fwr load connected to panel.
Remaining load for booster power supplies = dc Subtract Y from subtotal dc current, then add
889D and/or 116DEGEX current (if used).
Enter CA for Canadian version of BPS Enter 230 for 230Vac version
Booster power supplies Qty
6 amp booster supply Use: EBPS6A 0
10 amp booster supply Use: EBPS10A 0
Go to BPS Batteries sheet to calculate battery size. 0

Door holders
Single door, floor mount Use: 1501-AQN5
1504-AQN5 These are multi-voltage, 24Vac/dc, 120Vac; 15mA.
Flush wall mount Use:
Surface wall mount Use: 1508-AQN5 DH current = 0 mA
Step 4a (optional) - Select speakers
Part Number Qty
High Output Strobe (indoor); 1/4, 1/2, 1, 2 watt taps Add letter W for white or R for red after HF.
Ceiling spkr/strb, 95 - 177cd Use: GCHF__ __-S7VMCH Add letter F for FIRE or N for no markings after color.

High Fidelity, low current LED (indoor); 1/4, 1/2, 1, 2 watt taps
Wall mount speaker only Use: EG4S__ __
Wall mount spkr/LED, 15 - 110cd Use: EG4SV__ __
Surface mount box Use: EG4__SB Add letter W for white or R for red after S(V).
Add letter F for FIRE or N for no markings after color.
Flush mount trim skirt Use: EG4T__ (EG4SRF would be a red speaker with "FIRE" markings).
For trim and box, add add W or R for color.
All EG4s and EGCs include mounting/wiring plate.
Ceiling speaker only Use: EGCS__ __
Ceiling spkr/LED, 15 - 115cd Use: EGCSV__ __
Flush mount trim skirt Use: EGCT__

Indoor/Outdoor; 1/4, 1/2, 1, 2 watt taps


Speaker only Use: WG4__ __-S
Add letter W for white or R for red and F for
Speaker strobe, 15 - 87cd Use: WG4__ __-SVMC FIRE marking or N for no marking.
Speaker strobe, 102 - 161cd Use: WG4__ __-SVMHC (WG4RF-SVMC would be red with FIRE)
Surface mount trim skirt Use: WG4__TS Recommended when surface mounting (add R or W)
Weatherproof box Use: 449 Required when using WG4s outdoors

Indoor/Outdoor high output; 1, 2, 4, 8, 15 watt taps


Double reentrant speaker, gray Use: 5552-15W-G
Double reentrant speaker, red Use: 5552-15W-R

Haz Loc (Div 2); 1, 2, 4, 8, 15 watt taps


Haz loc speaker, gray Use: 5553-25/70-G
Haz loc speaker, red Use: 5553-25/70-R

Enter quantity of speakers below for each wattage tap used.


Use Audio Panel (4b) sheet to select amplifiers.

Qty Wattage Total


Number of speakers tapped at 1/4W x 0.25 =
Number of speakers tapped at 1/2W x 0.5 =
Number of speakers tapped at 1W x 1 =
Number of speakers tapped at 2W x 2 =
Number of speakers tapped at 4W x 4 =
Number of speakers tapped at 8W x 8 =
Number of speakers tapped at 15W x 15 =
Total wattage =
To accurately size power supplies, enter quantities below for each speaker strobe candela (cd) setting used and total up device currents for both fwr
(full wave rectified) and dc. The FX-3 has 3.5 amps of fwr power, the FX-10 has 7.0 amps of fwr power, the FX-64 panel has 3.75 amps of fwr power,
and the FX-1000 has 6 amps of fwr power.

Current (mA)
Speaker Strobe Qty Total (fwr) Total (dc)
EG4SV wall speaker LED 45fwr, 35dc =
EGCSV ceiling speaker LED 45fwr, 35dc =
(E)G4 wall speaker strobe - 15cd 120fwr, 96dc x =
(E)G4 wall speaker strobe - 30cd 169fwr, 130dc x =
(E)G4 wall speaker strobe - 75cd 329fwr, 239dc x =
(E)G4 wall speaker strobe - 110cd 375fwr, 294dc x =
(E)GC ceiling speaker strobe - 15cd 131fwr, 109dc x =
(E)GC ceiling speaker strobe - 30cd 194fwr, 151dc x =
(E)GC ceiling speaker strobe - 75cd 379fwr, 281dc x =
(E)GC ceiling speaker strobe - 95cd 437fwr, 330dc x =
(E)GC ceiling speaker strobe - 115cd 518fwr, 392dc x =
(E)GC ceiling speaker strobe - 150cd 643fwr, 502dc x =
(E)GC ceiling speaker strobe - 177cd 693fwr, 565dc x =
WG4 speaker strobe - 15cd 120fwr, 106dc x =
WG4 speaker strobe - 29cd 178fwr, 144dc x =
WG4 speaker strobe - 70cd 347fwr, 167dc x =
WG4 speaker strobe - 87cd 386fwr, 319dc x =
WG4 speaker strobe - 102cd 412fwr, 324dc x =
WG4 speaker strobe - 123cd 487fwr, 390dc x =
WG4 speaker strobe - 147cd 607fwr, 494dc x =
WG4 speaker strobe - 161cd 646fwr, 495dc x =
Subtotal currents (mA) fwr = dc =

Bring subtotal currents to Signals sheet.


Step 4b (optional) - Select audio panel
Part Number Qty

Primary amplifier Primary amplifier includes 1 speaker circuit, cabinet, power


25 watt main amplifier Use: ANS25MD__2 supply, prerecorded message, microphone, and battery
charger.
50 watt main amplifier Use: ANS50MD__2 Select only one primary amplifier.
100 watt main amplifier Use: ANS100MD__2 Add letter R for red or G for gray cabinet.

Expander amplifiers
25 watt expander Use: ANS25X__ Expander amplifiers include same as primary except for
prerecorded message and microphone.
50 watt expander Use: ANS50X__ Can have up to 15 total amplifiers on a system.
100 watt expander Use: ANS100X__ Add letter R for red or G for gray cabinet.

Backup amplifer(s)
25 watt backup Use: ANS25X__ Backup amplifier should be at least as large as the largest
primary or expander amplifier.
50 watt backup Use: ANS50X__ Can have 1 backup amp covering all other amps, or 1
100 watt backup Use: ANS100X__ backup amp for each primary and expander amp (1:1).

Options cards
Remote micrphone Use: ANSREM__ Includes cabinet (add R or G). Can have up to 5.
Mic supervisory card Use: ANSREMSUP One required for up to 5 remote mics.
Backup amp switching mod. Use: ANSBKUP One required for each backup amplifier.
Zone splitter card Use: ANSZM4B2A Splits circuit to 4 class B or 2 class A (2 max)
8 position zone switch card Use: ANSSW8 Provides 8 switches for zone/paging control (1 max)
8 input interface card Use: ANSDC8 Provides 8 programmable dry contact inputs (2 max)
8 output interface card Use: ANSXM8 Provides 8 programmable dry contact outputs (2 max)

Standard primary message: “Attention Please, there has


been a report of an emergency. Proceed calmly to the
nearest exit and leave the building immediately. Do
not use the elevators, use stairwells where
necessary. All handicapped occupants shall
use the building evacuation plan.”
Step 5 Conventional - Calculate battery size for panel

Standby Alarm
Current Standby Current Alarm
Item Qty (mA) Subtot (mA) Subtot
Assumes all circuits used
FX-5 x 119 224 Assumes all circuits used
FX-10 x 158 242 Assumes all circuits used
F-DACT x 65 107
FSRSI x 17 48
FSRZI-A / FSRZI-SA x 4 56
FSRA10 x 17 98
FSRRM24 (common operation) x 26 70
FSRRM24 (matrix operation) x 10 70
FSUIM x 55 114
Other Aux 500mA total aux (see note 2)
NAC 1 Current 2000mA max per circuit (see note 1). Enter 200 if using CTM
NAC 2 Current 2000mA max per circuit (see note 1)
NAC 3 Current (FX-10 only) 2000mA max per circuit (see note 1)
NAC 4 Current (FX-10 only) 2000mA max per circuit (see note 1)

Note 1: Max total NAC current = Total Current (mA) =


3500mA for 5 zone; 7000mA for 10 zone. x Stdby Hrs. Alarm Min Enter battery time required
/ 60
Note 2: Can use BPSs for additional mA Hours = + = mAH
aux power Multiply Total Standby mA x Stdby Hrs. Multiply x 1.2
Total Alarm mA x Alarm Min. and divde by 60. mAH
Add Standby mAH + Alarm mAH to get Total
mAH. Amp Hours is final battery size
/ 1000
Battery Size = Amp Hours
26 Amp Hour max
Enter quantities of batteries based on above

Part # Qty
12 volt, 4.5 amp hour Use: 12V4A For the 5 zone panel, batteries larger than
12 volt, 7.2 amp hour Use: 12V6A5 12V6A5 require a separate battery cabinet.
With the 10 zone panel, batteries larger than
12 volt, 10 amp hour Use: 12V10A 12V10A require a separate cabinet.
12 volt, 18 amp hour Use: 12V17A
Each panel requires 2 of selected battery.
12 volt, 26 amp hour Use: 12V24A
18AH battery cabinet Use: BC-2
26AH battery cabinet Use: BC-1
Step 5 Addressable - Calculate battery size for panel
Control Panel
Standby Total Alarm Total
Current Standby Current Alarm
Item Qty ea. (mA) (mA) ea. (mA) (mA)
FX-64 x 155 204 Base panel numbers do NOT include primary loop
FX-1000 x 172 267
1st card, 1st loop x 55 80 Assumes fully loaded loop
1st card, 2nd loop (FX-1000) x 45 70 Assumes fully loaded loop
2nd card, 1st loop (FX-1000) x 55 80 Assumes fully loaded loop
2nd card, 2nd loop (FX-1000) x 45 70 Assumes fully loaded loop
D16L-FA (FX-1000 only) x 4 48 2 max
SA-CLA (FX-64 only) x 3 60
SA-232 x 13 13
SA-DACT x 41 41
SA-ETH x 34 34
SA-USB x 14 20

Sub Totals
x 1.25 1.25
Totals Carry to Battery Calc section below

Smoke/Acc (Aux output)


Standby Total Alarm Total
Current Standby Current Alarm
Item Qty ea. (mA) (mA) ea. (mA) (mA)
FX-2WIRE x 2 0 17 0 If used, only enter 1, even if more than 1 installed
RZI16-2RS x 200 0 800 0 Can only power 1 RZI from panel. Must be from Aux 1.
K-RLCD x 98 0 113 0
K-RLCD-C x 99 0 115 0 8 remote annunciators
K-RLED-C x 28 0 62 0 max per panel
K-RLED24 x 6 0 34 0
Other (sounder bases, etc.) Manually enter currents for items not covered above

Sub Totals 500mA max sup, 1000mA max alarm


x 1.25 x 1.25
Totals = Carry to Battery Calc section below

Battery Calc
Total Total
Standby Alarm
Item (mA) (mA)
Control Panel From above
Smoke/Acc From above
Aux Power (Aux out 1)
NAC1* 2500mA max per circuit. Enter 200 if using CTM
NAC2* 2500mA max per circuit
NAC3 (FX-1000 only)* 2500mA max per circuit
NAC4 (FX-1000 only)* 2500mA max per circuit

Multiply Total Standby mA x Stdby Hrs. Totals = mA mA


Multiply Total Alarm mA x Alarm Min. and x Stdby Hrs Alarm Min Enter battery time required
divde by 60. Add Standby mAH + Alarm /60
mAH to get Total mAH. Amp Hours is final
= + = Total mAH
battery size.
x 1.2
*Total available NAC current for FX-64 is 3750mA
(3000mA for 50Hz operation). /1000
Total available NAC current for FX-1000 is 6000mA Battery Size = Amp Hours
(5000mA for 50Hz operation).
(26 amp hour max)

Enter Quantity of Batteries Based on Above

Part # Qty
12 volt, 4.5 amp hour Use: 12V4A For FX-64, batteries larger than 12V10A will
12 volt, 7.2 amp hour Use: 12V6A5 require a separate battery cabinet. For the FX-
1000, batteries larger than 12V17A require a
For FX-64, batteries larger than 12V10A will
require a separate battery cabinet. For the FX-
1000, batteries larger than 12V17A require a
12 volt, 10 amp hour Use: 12V10A separate battery cabinet.
12 volt, 18 amp hour Use: 12V17A
Panels require 2 of selected size.
12 volt, 26 amp hour Use: 12V24A
18AH battery cabinet Use: BC-2
26AH battery cabinet Use: BC-1
Step 5a - Detailed booster bower supply battery calculations
Supervisory (AUX1, AUX2, AUX3, AUX4) This is for supervisory current from devices such as remote annunciators
Note: Only add auxiliary current if aux output stays on after AC power failure. and sounder bases connected to signal circuits that have been
Circuit Current (mA) configured as AUX outputs (not supervised) and will stay powered if loss
Aux 1 of AC (battery backed up).
Aux 2 3000mA
max per
Aux 3 ckt
Aux 4 Remaining annunciator supervisory load not assigned to panel = 0 mA
Number of ckts set to AUX: 0 x 35 = 0 Total sounder base supervisory load = 0 mA
Total AUX current (if switch SW2-7 is off): 0 mA (A) Total 260-CO detector supervisory load = 0 mA
Total sup. cur. is limited to 6 amps for EBPS6A, 8 amps for EBPS10A.

200 mA AUX This is the dedicated 200mA AUX output that is typically used
Current (mA) for low current devices, such as 4 wire smokes, that do
require battery backup.
Total 200 mA AUX current: 0 mA (B)

Rated base BPS supervisory current: 70 mA (C)


Total supervisory current (A+B+C): 0 mA (D)
Hours of standby supervisory time: Hrs (E) Enter battery time required
Supervisory mAH required (DxE): 0 mAH (F)

Alarm (NAC1, NAC2, NAC3, NAC4) This is for signal loads as well as alarm currents for devices such as
Circuit Current (mA) remote annunciators and sounder bases .
NAC 1 / Aux 1 Use Vdc, RMS current ratings of devices.
3000mA
NAC 2 / Aux 2 max per
NAC 3 / Aux3 ckt
NAC 4 / Aux 4 Remaining signal load (dc) not assigned to panel = mA
Remaining annunciator alarm load not assigned to panel = 0 mA
Total NAC / Aux alarm current: 0 mA (G) Total sounder base alarm load = 0 mA
Total 260-CO detector alarm load = 0 mA
Rated base BPS alarm current: 270 mA (H)
Total alarm current (D+G+H): 0 mA (J)
Minutes of alarm time: Min (K) Enter battery time required
Hours of alarm (K/60): 0 Hr (L)
Alarm mAH required (JxL): 0 mAH (M)

Total battery mAH required (M+F): 0 mAH (N)


Preliminary Total battery AH required (N/1000): 0 AH (O)
Final Battery AH Required (Ox1.2): 0 AH (P)

Enter the number of booster power supplies below requiring the calculated battery size. Total
batteries will be that number x 2 (2 batteries per booster).
Total
Part # # of BPS Batts
12 volt, 7.2 amp hour Use: 12V6A5 x2= 0
12 volt, 10 amp hour Use: 12V10A x2= 0 The size and number of booster power supplies
12 volt, 18 amp hour Use: 12V17A x2= 0 should be selected on the Signals sheet first.
12 volt, 26 amp hour Use: 12V24A x2= 0

Qty
18AH battery cabinet Use: BC-2 0 Batteries larger than 12V10A require BC-1 or BC-2. 2 batteries per
26AH battery cabinet Use: BC-1 0 Batteries larger than 12V17A require BC-1. cabinet
Step 5b - Detailed ANS audio panel battery calculations
Do calculations for 1 amplifier at at time. Only
enter quantities of options installed in / powered
by each amp.

Standby Alarm
Current Total Current Total
Item Qty (Amps) Standby (Amps) Alarm
ANS100 - 100W Amp x 0.16 0.6
ANS50 - 50W Amp x 0.15 0.8
ANS25 - 25W Amp x 0.18 1.1
ANSREMSUP - Remote Mic Sup Module x 0.03 0.05 One max per amp
ANSREM - Remote Mic x 0.02 0.04 Five max per amp
ANSZM4B2A - Zone Splitter x 0.051 0.13
ANSSW8 - Zone switch module x 0.003 0.005
ANSDC8 - Input interface module x 0.003 0.005
ANSXM8 - Output interface module x 0.003 0.028
ANSBKUP - Backup Amp Module x 0.04 0.01 One max per amp

Totals = Amps Amps


Enter battery time required x Stdby Hrs. Alarm Mins.
0 Alarm Hrs.
= + = AH
x 1.2
Battery Size = Amp Hours
Batteries larger than 7.2AH require separate battery cabinet.

Enter the number of ANS amps below requiring the calculated battery size. Total batteries
will be that number x 2 (2 batteries per ANS).

Total
Part # # of ANS Batts
12 volt, 7.2 amp hour battery Use: 12V6A5 x2= 0
12 volt, 10 amp hour battery Use: 12V10A x2= 0
12 volt, 18 amp hour battery Use: 12V17A x2= 0

Qty
18 AH battery cabinet Use: BC-2 0 Batteries larger than 12V6A5 require BC-2 battery cabinet.
This sheet contatins the other less common, but available Kidde - Edwards fire
alarm products not covered in the previous sheets. None of these products
figure into any calculations (device quantity checks, current loads, etc.), but will
get totaled on the Summary sheet as part of the final BOM if you enter
quantities.
None of these devices are addressable, so if you select an initiating device, such
as a weatherprrof MPSR series pull station, you will need to select the
appropriate module on the Addr. Devices sheet if you want to connect it to the
addressable panel.

Make entries in yellow highlighted cells

Qty Part Number Description


Door Holders & Accessories
1500-1 DH catch plate ext 3.125 inch
1500-12 DH ctch plt ext 7.5 to 12 inch
1500-2 DH ctch plt ext 3.625 inch
1500-7 DH ctch plt ext 5.25-7.5 inch
CS2595-5 CATCH PLATE
CS2598-5 CATCH PLATE
1502-AQN5 Door Holder Dbl Flr Mnt
1505-AQN5 Door Holder Flsh Wal Shrt Ctch
1509-AQN5 Door Holder Flush Wall Mnt
Pull Stations & Accessories
K-270A-DPO Pull Station Dbl Pole Wire Lds
K-270A-SPO Pull Sta Sgle Pole Wire Lds
K-270-DOC Pull Station opn/clsd contacts
270-GLR Glass Rods for 270 Pull Stations
K-276B-1110 Pull Station Sngle Pole term
K-276B-1120 Pull Sta Sngle pole key term
276B-RSB Surface Back Box - Red Steel
276-GLR Glass Rods for 276 277 278 279
276-K1 Reset Key for Manual Stations
K-277B-1110 Pull Sta SPO single act wire
K-278B-1120 Pull Sta SPO key dbl act term
K-279B-1110 Pull Sta SPO dbl act wire
MPSR1-D45W-GE Pull Sta,WP,SA,Key Reset,DPDT
MPSR1-DHTW-GE Pull Sta,WP,SA,Hex Reset,DPDT
MPSR1-S45W-GE Pull Sta,WP,SA,Key Reset,SPST
MPSR2-D45W-GE Pull Sta,WP,DA,Key Reset,DPDT
MPSR2-DHTW-GE Pull Sta,WP,DA,Hex Reset,DPDT
MPSR2-S45W-GE Pull Sta,WP,DA,Key Reset,SPST
MPSR2-S45W-GE-NYW Pull Sta,WP,DA,Key Reset, NYC
MPSR2-SHTW-GE-NYW Pull Sta,WP,DA,Hex Reset,NYC
MPSRGR10 Repl.glass rods, MPSR 10/pack
MPSRHEX Replace Hex Key for MPSR
MPSR-LP MPSR Pull Dual Action Cover
STI-1100 Pull Sta Cover w/Horn, Flush
STI-1130 Pull Sta Cover w/Horn, Surface
STI-1200 Pull Sta Cover w/o Horn, Flush
STI-1230 Pull Sta Cover w/o Horn, Surf
STI-1250 PullStaCover,WP,w/o Horn,Flush
STI-3002 Pull Sta Cover Gasket
STI-3003 Pull Sta Cover Conduit Gasket
STI-3004 Pull Sta Cover Conduit Plug
STI-3100 Pull Sta Cover Spacer
STI-3150 Pull Sta Cover, WP,w/Horn,Surf
P-027193 Surface Box Cast
P-039250 Surface Box
Heat Detectors & Accessories
302-135 Rate Comp HD Interior - 135F
302-194 Rate Comp HD Interior - 194F
302-ET-135 Rate Comp HD Outdoor 135F
302-ET-194 Rate Comp HD Outdoor 194F
JALX11 Exproof box for 302-EPM
AP-P Heat Det Rate Comp Adptr plt
Bells, Horns, Strobes & Acc.
438D-10N5 BELL 10 INCH 120V 60 HZ DIODE
438D-10N5-R BELL 10 INCH 120Vac RED DIODE
438D-6N5 BELL 6 INCH 120V 60 HZ DIODE
438D-6N5-R BELL 6 INCH 120Vac RED DIODE
438D-8N5 BELL 8 INCH 120V 60 HZ DIODE
438D-8N5-R BELL 8 INCH 120Vac RED DIODE
439D-10AW 10 inch Bell 24 Vdc Gray
439D-10AW-R 10 inch Bell 24 Vdc Red
439D-6AW 6 inch Bell 24 Vdc Gray
439D-6AW-R 6 inch Bell 24 Vdc Red
439D-8AW Bell 8 inch 24 Volts DC Gray
439D-8AW-R Bell 8 inch 24 Volts DC Red
439DEX-10AW Exproof 10 inch Bell 24 Vdc
439DEX-6AW Exproof 6 inch Bell 24 Vdc
439DEX-8AW Exproof 8 inch Bell 24 Vdc
5530MD-24AW Multi-tone Elec FA Signal
888D-N5 HORN EX-PL 120V60HZ
2459-SMB-R SURFACE BOX, RED
2459-SMB-W SURFACE BOX, WHITE
Power Supplies & Battery Cabinets
APS10A Aux/Booster Power Supply 10A
APS6A Aux/Booster Power Supply 6A
APSEQ APS - Seismic Battery hold
BC-1EQ Seismic Batt hold down, BC-1
BC-1R Battery Cabinet - Red
BC-2R Battery Cabinet, Red
Genesis Horns, Strobes & Accessories
EG1-C CHIME,TEMP,HI-LO,WHITE
EG1-CVM CHIME STRB,MULTI-CD,WHITE
EG1F-C CHIME,HI-LO,WHITE,MARKED FIRE
EG1F-CVM CHIME STRB,MULTI-CD,WHITE,FIRE
EG1F-P GENESIS HORN,WHITE,MARKED FIRE
EG1M GENESIS SIGNAL MASTER
EG1M-RM GENESIS SIGNAL MASTER,REM MT
EG1-P GENESIS HORN,WHITE
EG1R-C CHIME,TEMP,HI-LO,RED
EG1R-CVM CHIME STROBE,MULTI-CD,RED
EG1RF-CVM CHIME STRB,MULTI-CD,RED,FIRE
EG1RF-P GENESIS HORN,RED,MARKED FIRE
EG1R-P GENESIS HORN,RED
EG1RT GENESIS 1GANG 4 INCH TRIM RED
EG1RT-FIRE GENESIS TRIM RED MARKED FIRE
EG1T GENESIS 1GANG TRIM WHITE
EG1T-FIRE GENESIS TRIM WHITE MARKED FIRE
WG4GSKT Gasket for WP Speaker(Strobe)
Relays
MR101/C Relay,SPDT w/LED,Metal Encl
MR101/T Relay,SPDT w/LED,Track Mntng
MR104C Relay,4-Pos SPDT w/LED,Encl
MR104T Relay,4-Pos SPDT w/LED,Track
MR199X13 Relay, DPDT 24 Vdc
MR199X13/C Relay, DPDT 24 Vdc w/enclosure
MR199X14 Relay, DPDT, 120Vac
MR199X14/C Relay,DPDT,120Vac w/enclosure
MR201/C Relay,DPDT,120Vac, Track Mnt
MR201/T Single SPDT w/LED Track Mount
MR204/C Rly,4-Pos,SPDT w/LED,Enclosure
MR204/T Rly,4-Pos,SPDT w/LED,Track Mnt
MR601/T Relay,SPDT w/LED, Track Mnt
MR604/T Rly,4-Pos,SPDT w/LED,Track Mnt
MR608/S Rly,8-Pos,SPDT w/LED,Spacers
MR608/T Rly,8-Pos,SPDT w/LED,Track Mnt
MR701/S Rly,SPDT w/LED,Mntng Spacers
MR701/T Rly,SPDT w/LED,Track Mount
MR704/T Rly,4-Pos,SPDT w/LED,Track Mnt
MR708/T Rly,8-Pos,SPDT w/LED,Track Mnt
MR801/S Rly,SPDT w/LED,Mntng Spacers
MR801/T Rly,SPDT w/LED,Track Mount
MR804/T Rly,4-Pos,SPDT w/LED,Track Mnt
MR808/T Rly,8-Pos,SPDT w/LED,Track Mnt
PAM1 Relay,SPDT w/LED,Tape Mounting
Panel Remote Annunciators & Accessories
SA-TRIM1 Trim Kit for FX-64 panel
SA-TRIM2 Trim Kit for FX-1000 panel
R-LED Remote LED, FX- Detectors
GCI Rem graphic interface,addr
MFC-A Multifunction Fire Cabinet
EOL47PK2 EOL Res, 2 PACK,4.7K
EOL47PK7 EOL Res,4.7k Ohm,Pack of 7
Detectors & Accessories
SD-4WPCBT Replacement Sensor PCB, SD-ST
SD-CJ SuperDuct Controller (RJ45)
SD-CT SuperDuct Controller (term)
SD-GSK Cover Gasket, SuperDuct
SD-MAG SuperDuct Test magnet kit
SD-PH SuperDuct Protective Housing
SD-RJ10 SuperDuct RJ45 wir har kt,10ft
SD-RJ15 SuperDuct RJ45 wir har kt,15ft
SD-RJ5 SuperDuct RJ45 wir har kt,5ft
SD-SJ SuperDuct Sensor (RJ45) 4-wire
SD-ST SuperDuct Sensor (terminals)
SD-TRK4 SuperDuctRemTestStaKey, 4-wire
SD-TRM4 SuperDuctRemTestStaMag, 4-wire
SD-VTK SuperDuct Air vel test kit
211-10PKG Replace Opt Chmbrs photo smks
Number of user entries this sheet: 0
Date:
Job Name:
Quoted for (name):
(Company):
Quoted by (name):
(Company):

Qty Part Number Description


Conventional panel and peripherals
FX-5R 5 zone fire panel
FX-10R 10 zone fire panel
FX-5RD 5 zone fire panel w/dialer
FX-10RD 10 zone fire panel w/dialer
CTM City tie module
F-DACT1 Dual line dialer
FSRRM24 Remote relay module

MFC-A Mounting cabinet


FSRSI Remote system indicator
FSRZI-A Remote alarm zone annunciator
FSRZI-SA Remote alarm/sup zone annunciator
FSAT1 1 gang trim
FSAT2 2 gang trim
FSAT3 3 gang trim
K-FSRA10 Remote 10 zone annunciator
K-FSRA10C Remote 10 zone annunciator w/CC
FSUIM Remote graphic ann. driver
RKEY Remote enable key switch
Batteries for panel
12V4A 4.5 amp hour battery
12V6A5 7.2 amp hour battery
12V6A5 7.2 amp hour battery (Default battery selection)
12V10A 10 amp hour battery
12V10A 10 amp hour battery (Default battery selection)
12V17A 18 amp hour battery
12V24A 26 amp hour battery
BC-2 Battery cabinet, up to 18AH
BC-1 Battery cabinet, up to 55AH
Conventional initiating devices
511C Photoelectric smoke
521NC Photoelectric smoke w/CleanMe
521NCXT Photo smoke/heat combination
711U Photo smoke
721UT Photo smoke with heat
731U Photo smoke with aux relay
701U Base for 711U / 721UT
702U Base for 731U
541NCRXT Photo smoke/heat with relay, 4 wire
260-CO Carbon monoxide detector
283B-PL Heat detector, 135F fixed
302-135 Heat detector, 135F rate compensation
302-194 Heat detector, 194F rate compensation
302-AW-135 Heat detector, all weather, 135F
302-AW-194 Heat detector, all weather, 194F
302-EPM-135 Heat detector, ex-proof, 135F
302-EPM-194 Heat detector, ex-proof, 194F
JALX11 Ex-proof mounting box for heat detector
K-270-SPO Single action pull station, SPO
K-270-DPO Single action pull station, DPO
K-278B-1110 Double action pull station, tool reset
K-278B-1420 Double action pull station, key reset
MPSR1-D45WX-GE Ex-proof pull station, key reset
MPSR1-SHTW-GE Weatherproof pull station, tool reset
SD-2W Duct detector, 2 wire
SD-4WJ Duct detector, 4 wire
SD-T8 Sampling tube, 8 inches
SD-T18 Sampling tube, 18 inches
SD-T24 Sampling tube, 24 inches
SD-T36 Sampling tube, 36 inches
SD-T42 Sampling tube, 42 inches
SD-T60 Sampling tube, 60 inches
SD-T78 Sampling tube, 78 inches
SD-T120 Sampling tube, 120 inches
SD-TRK Test station, 2 wire duct
SD-TRK4 Test station, 4 wire duct
Addressable panel and peripherals
FX-64R Addr. panel, up to 64 pts., red
FX-1000 Addr. panel, up to 1000 pts., red
FX-64R-2 Addr. panel, up to 64 pts., red, 230V
FX-1000-2 Addr. panel, up to 1000 pts., red, 230V
FX-64RD Addr. panel, up to 64 pts., red, with dialer
FX-1000D Addr. panel, up to 1000 pts., red, with dialer
FX-SLC1 Single loop expander module
FX-SLC2 Two loop expander module
SA-DACT Dual line dialer
CTM City tie module
SA-USB USB interface module
SA-232 RS232 interface module
SA-ETH Ethernet interface module
SA-CLA Class A converter module
D16L-FA 16 LED zone display
EOL-15 15K ohm EOL resistor
SA-FSB Field Server Bridge
FSB-BRKT2 Mounting bracket for SA-FSB
MFC-A Mounting cabinet
K-RLCD Remote LCD annunciator, white
K-RLCD-C Remote LCD annunciator w/cc, white
K-RLED-C Remote LED annunciator w/cc, white
K-RLED24 24 LED expander annunciator, white
LSRA-SB Annunciator surface box
RA-ENC1 One space ann. enclosure
RA-ENC2 Two space ann. enclosure
RA-ENC3 Three space ann. enclosure
Rkey Remote enable keyswitch
260097 Download cable
Batteries for panel
12V4A 4.5 amp hour battery
12V6A5 7.2 amp hour battery
12V10A 10 amp hour battery
12V10A 10 amp hour battery (Default battery selection)
12V17A 18 amp hour battery
12V17A 18 amp hour battery (Default battery selection)
12V24A 26 amp hour battery
BC-2 Battery cabinet, up to 18 AH
BC-1 Battery cabinet, up to 55 AH
Detectors and modules
KIR-PD Addr. photo smoke detector
KIR-PHD Addr. photo/heat detector
KIR-HD Addr. heat detector, ROR or 135F fixed temp
KIR-COD Carbon monoxide detector
KIR-HCD Heat with CO
KIR-PCD Smoke with CO
KIR-PHCD Smoke with heat and CO
KI-SB4 Standard base
GSA-LED Remote LED
KI-RB4 Relay base
KI-IB4 Isolator base
KI-ABST Sounder base
KI-ABDT Sounder base
KI-ABLT Sounder base, low frequency
AB4G-SB Surface box for sounder base
284B-PL Heat detector, 194F fixed
260-CO Carbon Monoxide detector
FX-IDC1B Single input module
FX-IDC1A Single input module, class A
FX-IDC2B Dual input module
FX-IDCWS Waterflow / supervisory module
FX-NAC Signal circuit / power riser module
FX-NAC Signal circuit / power riser module
FX-RLY Relay module
FX-ISO Isolator module
FX-2WIRE Two wire smoke module
FX-T3T4 Temporal 3 / 4 generator
RZI16-2RS Remote zone module, 16 input, 2 output
MFC-A Mounting cabinet
RZI-MPL Mounting bracket for RZI16-2RS
EOL-47 47K ohm EOL resistor
EOL-4.7 4.7K ohm EOL resistor
EOL-15 15K ohm EOL resistor
APS6A 6 amp booster supply

12V17A 12 volt, 18 amp hour battery


FX-270 Addr. single action pull station
FX-278 Addr. dual action pull station
27193-11 Surface box
MPSR1-SHTW-GE Weatherproof pull station, single action
MPSR2-SHTW-GE Weatherproof pull station, double action
MPSR1-D45WX-GE Hazardous location pull station, single action
FX-PDD Addr. duct detector
SD-T8 Sampling tube, 8"
SD-T18 Sampling tube, 18"
SD-T24 Sampling tube, 24"
SD-T36 Sampling tube, 36"
SD-T42 Sampling tube, 42"
SD-T60 Sampling tube, 60"
SD-T78 Sampling tube, 78"
SD-T120 Sampling tube, 120"
SD-TRK Key test switch
SD-TRM Magnet test switch
Signals and acc.
EG1__ __-HD Temporal horn
EG1__ __-VM Multi-cd strobe
EG1__ __-HDVM Multi-cd horn strobe
EG1__T-____ Trim
EG1A__ __ Temporal horn
EG1V__ __ Multi-cd LED
EG1AV__ __ Multi-cd horn LED
EG1T__ Trim
EG4A__ __ Wall mount horn only
EG4V__ __ Wall mount strobe only
EG4AV__ __ Wall mount horn strobe
EG4T__ Trim for EG4A
EG4__SB Surface box
EGC__ __-VM Ceiling multi-cd strobe
EGC__ __-VMH Ceiling multi-cd strobe, H.O.
EGC__ __-HDVM Ceiling multi-cd h/s
EGC__ __-HDVMH Ceiling multi-cd h/s, H.O.
EGCA__ __ Ceiling mount horn only
EGCV__ __ Ceiling mount low current LED only
EGCAV__ __ Ceiling mount low current LED horn
EGCT__ Trim for ceiling mount horn(strobe)
G4LF__ __-H Low frequency horn
G4LF__ __-HVM Low frequency horn strobe
EG4__B Surface mount box
WG4__ __-H Outdoor rated horn
WG4__ __-HVMC Outdoor horn/strobe, 2 wire
WG4__ __-HVMHC Outdoor horn/strobe, 2 wire, high CD
WG4__TS Trim for WG4 horn(strobe)
449 Weatherproof box
2447TH-__ Outdoor rated horn
2452THS-15/75-__ Outdoor rated horn/strobe
2459-WPB-__ Weatherproof box
CS405-7A-T Outdoor rated strobe, 15/75cd
CS405-8A-T Outdoor rated strobe, 110cd
449 Weatherproof box
889D-AW Explosion proof horn
235196P Transient protector
116DEGEX-FJ Explosion proof strobe
116EX-P Pendant mount
116EX-C Ceiling mount
116EX-B Bracket (wall) mount
EBPS6A Booster power supply, 6A
EBPS10A Booster power supply, 10A
12V6A5 7.2 amp hour battery
12V6A5 7.2 amp hour battery (Default battery selection)
12V10A 10 amp hour battery
12V17A 18 amp hour battery
12V24A 26 amp hour battery
BC-2 Battery cabinet, up to 18 AH
BC-1 Battery cabinet, up to 55 AH
1501-AQN5 Floor mount door holder
1504-AQN5 Flush mount door holder
1508-AQN5 Surface mount door holder
Speaker(strobes)
EG4__ __-S7 Wall mount speaker
EG4__ __-S7VM Wall mount speaker strobe
EG4__B Surface mount box
EGC__ __-S7 Ceiling mount speaker
EGC__ __-S7VM Ceiling mount speaker strobe
EGC__-S7VMH Ceiling mount spkr/strb, H.O.
G4HF__ __-S7 Wall mount speaker
G4HF__ __-S7VMC Wall mount speaker strobe
EG4__B Surface mount box
EG4S__ __ Wall mount speaker
EG4SV__ __ Wall mount speaker LED
EG4__SB Surface box
EG4T__ Flush mount trim
EGCS__ __ Ceiling speaker
EGCSV__ __ Ceiling speaker LED
EGCT__ Trim skirt
GCHF__ __-S7 Ceiling mount speaker
GCHF__ __-S7VMC Ceiling mount speaker strobe
GCHF__ __-S7VMCH Ceiling mount spkr/strb, H.O.
WG4__ __-S W.P speaker
WG4__ __-SVMC W.P speaker strobe
WG4__ __-SVMHC W.P. speaker strobe, high CD
WG4__TS Surface trim skirt
449 Weatherproof box
5552-15W-G Double reentrant speaker, gray
5552-15W-R Double reentrant speaker, red
5553-25/70-G Hazardous location speaker, gray
5553-25/70-R Hazardous location speaker, red
Audio panel and acc.
ANS25MD__2 25 watt amp w/DMR and mic
ANS50MD__2 50 watt amp w/DMR and mic
ANS100MD__2 100 watt amp w/DMR and mic
ANS25X__ 25 watt expander amp
ANS50X__ 50 watt expander amp
ANS100X__ 100 watt expander amp
ANSREM__ Remote microphone
ANSREMSUP Remote mic supervisory card
ANSBKUP Back up amplifier superviory card
ANSZM4B2A Speaker zone splitter card
ANSSW8 8 switch card
ANSDC8 8 dry contact input card
ANSXM8 8 dry contact output card
Batteries for ANS audio panel
12V6A5 7.2 amp hour battery
12V6A5 7.2 amp hour battery (Default battery selection)
12V10A 10 amp hour battery
12V17A 18 amp hour battery

BC-2 Battery cabinet, up to 18 AH

Other (manual entries)


Qty Part Number Description

Other Miscellaneous Items


Door Holders & Accessories
1500-1 DH catch plate ext 3.125 inch
1500-12 DH ctch plt ext 7.5 to 12 inch
1500-2 DH ctch plt ext 3.625 inch
1500-7 DH ctch plt ext 5.25-7.5 inch
CS2595-5 CATCH PLATE
CS2598-5 CATCH PLATE
1502-AQN5 Door Holder Dbl Flr Mnt
1505-AQN5 Door Holder Flsh Wal Shrt Ctch
1509-AQN5 Door Holder Flush Wall Mnt
Pull Stations & Accessories
K-270A-DPO Pull Station Dbl Pole Wire Lds
K-270A-SPO Pull Sta Sgle Pole Wire Lds
K-270-DOC Pull Station opn/clsd contacts
270-GLR Glass Rods for 270 Pull Stations
K-276B-1110 Pull Station Sngle Pole term
K-276B-1120 Pull Sta Sngle pole key term
276B-RSB Surface Back Box - Red Steel
276-GLR Glass Rods for 276 277 278 279
276-K1 Reset Key for Manual Stations
K-277B-1110 Pull Sta SPO single act wire
K-278B-1120 Pull Sta SPO key dbl act term
K-279B-1110 Pull Sta SPO dbl act wire
MPSR1-D45W-GE Pull Sta,WP,SA,Key Reset,DPDT
MPSR1-DHTW-GE Pull Sta,WP,SA,Hex Reset,DPDT
MPSR1-S45W-GE Pull Sta,WP,SA,Key Reset,SPST
MPSR2-D45W-GE Pull Sta,WP,DA,Key Reset,DPDT
MPSR2-DHTW-GE Pull Sta,WP,DA,Hex Reset,DPDT
MPSR2-S45W-GE Pull Sta,WP,DA,Key Reset,SPST
MPSR2-S45W-GE-NYW Pull Sta,WP,DA,Key Reset, NYC
MPSR2-SHTW-GE-NYW Pull Sta,WP,DA,Hex Reset,NYC
MPSRGR10 Repl.glass rods, MPSR 10/pack
MPSRHEX Replace Hex Key for MPSR
MPSR-LP MPSR Pull Dual Action Cover
STI-1100 Pull Sta Cover w/Horn, Flush
STI-1130 Pull Sta Cover w/Horn, Surface
STI-1200 Pull Sta Cover w/o Horn, Flush
STI-1230 Pull Sta Cover w/o Horn, Surf
STI-1250 PullStaCover,WP,w/o Horn,Flush
STI-3002 Pull Sta Cover Gasket
STI-3003 Pull Sta Cover Conduit Gasket
STI-3004 Pull Sta Cover Conduit Plug
STI-3100 Pull Sta Cover Spacer
STI-3150 Pull Sta Cover, WP,w/Horn,Surf
P-027193 Surface Box Cast
P-039250 Surface Box
Heat Detectors & Accessories
302-135 Rate Comp HD Interior - 135F
302-194 Rate Comp HD Interior - 194F
302-ET-135 Rate Comp HD Outdoor 135F
302-ET-194 Rate Comp HD Outdoor 194F
JALX11 Exproof box for 302-EPM
AP-P Heat Det Rate Comp Adptr plt
CF135-2 Heat Detector, 135F Fixed
CF200-2 Heat Detector, 200F Fixed
CR135-2 Heat Detector, 135F/ROR
CR200-2 Heat Detector, 200F/ROR
Bells, Horns, Strobes & Acc.
438D-10N5 BELL 10 INCH 120V 60 HZ DIODE
438D-10N5-R BELL 10 INCH 120Vac RED DIODE
438D-6N5 BELL 6 INCH 120V 60 HZ DIODE
438D-6N5-R BELL 6 INCH 120Vac RED DIODE
438D-8N5 BELL 8 INCH 120V 60 HZ DIODE
438D-8N5-R BELL 8 INCH 120Vac RED DIODE
439D-10AW 10 inch Bell 24 Vdc Gray
439D-10AW-R 10 inch Bell 24 Vdc Red
439D-6AW 6 inch Bell 24 Vdc Gray
439D-6AW-R 6 inch Bell 24 Vdc Red
439D-8AW Bell 8 inch 24 Volts DC Gray
439D-8AW-R Bell 8 inch 24 Volts DC Red
439DEX-10AW Exproof 10 inch Bell 24 Vdc
439DEX-6AW Exproof 6 inch Bell 24 Vdc
439DEX-8AW Exproof 8 inch Bell 24 Vdc
5530MD-24AW Multi-tone Elec FA Signal
888D-N5 HORN EX-PL 120V60HZ
2459-SMB-R SURFACE BOX, RED
2459-SMB-W SURFACE BOX, WHITE
Power Supplies & Battery Cabinets
APS10A Aux/Booster Power Supply 10A
APS6A Aux/Booster Power Supply 6A
APSEQ APS - Seismic Battery hold
BC-1EQ Seismic Batt hold down, BC-1
BC-1R Battery Cabinet - Red
BC-2R Battery Cabinet, Red
Genesis Horns, Strobes & Accessories
EG1-C CHIME,TEMP,HI-LO,WHITE
EG1-CVM CHIME STRB,MULTI-CD,WHITE
EG1F-C CHIME,HI-LO,WHITE,MARKED FIRE
EG1F-CVM CHIME STRB,MULTI-CD,WHITE,FIRE
EG1F-P GENESIS HORN,WHITE,MARKED FIRE
EG1M GENESIS SIGNAL MASTER
EG1M-RM GENESIS SIGNAL MASTER,REM MT
EG1-P GENESIS HORN,WHITE
EG1R-C CHIME,TEMP,HI-LO,RED
EG1R-CVM CHIME STROBE,MULTI-CD,RED
EG1RF-CVM CHIME STRB,MULTI-CD,RED,FIRE
EG1RF-P GENESIS HORN,RED,MARKED FIRE
EG1R-P GENESIS HORN,RED
EG1RT GENESIS 1GANG 4 INCH TRIM RED
EG1RT-FIRE GENESIS TRIM RED MARKED FIRE
EG1T GENESIS 1GANG TRIM WHITE
EG1T-FIRE GENESIS TRIM WHITE MARKED FIRE
WG4GSKT Gasket for WP Speaker(Strobe)
Relays
MR101/C Relay,SPDT w/LED,Metal Encl
MR101/T Relay,SPDT w/LED,Track Mntng
MR104C Relay,4-Pos SPDT w/LED,Encl
MR104T Relay,4-Pos SPDT w/LED,Track
MR199X13 Relay, DPDT 24 Vdc
MR199X13/C Relay, DPDT 24 Vdc w/enclosure
MR199X14 Relay, DPDT, 120Vac
MR199X14/C Relay,DPDT,120Vac w/enclosure
MR201/C Relay,DPDT,120Vac, Track Mnt
MR201/T Single SPDT w/LED Track Mount
MR204/C Rly,4-Pos,SPDT w/LED,Enclosure
MR204/T Rly,4-Pos,SPDT w/LED,Track Mnt
MR601/T Relay,SPDT w/LED, Track Mnt
MR604/T Rly,4-Pos,SPDT w/LED,Track Mnt
MR608/S Rly,8-Pos,SPDT w/LED,Spacers
MR608/T Rly,8-Pos,SPDT w/LED,Track Mnt
MR701/S Rly,SPDT w/LED,Mntng Spacers
MR701/T Rly,SPDT w/LED,Track Mount
MR704/T Rly,4-Pos,SPDT w/LED,Track Mnt
MR708/T Rly,8-Pos,SPDT w/LED,Track Mnt
MR801/S Rly,SPDT w/LED,Mntng Spacers
MR801/T Rly,SPDT w/LED,Track Mount
MR804/T Rly,4-Pos,SPDT w/LED,Track Mnt
MR808/T Rly,8-Pos,SPDT w/LED,Track Mnt
PAM1 Relay,SPDT w/LED,Tape Mounting
Panel Remote Annunciators & Accessories
SA-TRIM1 Trim Kit for FX64 panel
SA-TRIM2 Trim Kit for FX1000 panel
PT-1S Desk Printer, FX Panels
R-LED Remote LED, FX- Detectors
GCI Rem graphic interface,addr
MFC-A Multifunction Fire Cabinet
EOL47PK2 EOL Res, 2 PACK,4.7K
EOL47PK7 EOL Res,4.7k Ohm,Pack of 7
Detectors & Accessories
SD-4WPCBT Replacement Sensor PCB, SD-ST
SD-CJ SuperDuct Controller (RJ45)
SD-CT SuperDuct Controller (term)
SD-GSK Cover Gasket, SuperDuct
SD-MAG SuperDuct Test magnet kit
SD-PH SuperDuct Protective Housing
SD-RJ10 SuperDuct RJ45 wir har kt,10ft
SD-RJ15 SuperDuct RJ45 wir har kt,15ft
SD-RJ5 SuperDuct RJ45 wir har kt,5ft
SD-SJ SuperDuct Sensor (RJ45) 4-wire
SD-ST SuperDuct Sensor (terminals)
SD-TRK4 SuperDuctRemTestStaKey, 4-wire
SD-TRM4 SuperDuctRemTestStaMag, 4-wire
SD-VTK SuperDuct Air vel test kit
EC5000R Reflective Beam Det 26-330ft
1206B Detector Wire Guard
211-10PKG Replace Opt Chmbrs photo smks

You might also like