String Report for: Telmex | Metro | Culh 01f | Bb2 alpha on 02/02/2022 10:18:42 Page: 1

02/02/2022 14:19:02

String Information Test Information


Site Name: Telmex | Metro | Culh 01f Test Start Date: 02/02/2022 10:18:42
String ID: Bb2 alpha Operator:
# of Batteries: 24 Float Voltage:
Float Current:

String Specific Battery Details Battery Definition Test Settings


# of Straps: 0 Manufacturer: Gnb Noise Filtering: Auto
Float: On Model: 100G33 Polarity Correction: On
Voltage Reference/Cell: 2.230 Cell Type: Lead Acid (AGM) Battery Test Start: Auto
Voltage Reference/Battery: 2.230 Capacity: 1600.0 (Ah) Strap Test Start: Auto
# of Cells/Battery: 1 Auto Start Delay: 1
Test Level: Battery

Baseline Information Test Parameters Hardware Settings


Impedance Reference: 0.196 (mΩ) Impedance Serial Number: EC2000-1103496
ACF: 1.444 Voltage MAC Address: 00:0D:15:00:A8:5E
Baseline Type: Auto Generated in EC2000 CELScan Hardware Version: 19333301
(Sulfation/Dryout)
Baselined from Test Date: 02/02/2022 10:18:42 Firmware Version: 2.1.8
Data Origin: EC2000

Applied Alarms

Impedance (%) Voltage (V/Cell) Sulfation (%) Dryout (%) Strap (%)
High Fail 125.0 2.35 20 20 Undefined
High Warn 117.0 2.30 15 15 Undefined
Low Warn 70.0 2.20
Low Fail 50.0 2.15
String Report for: Telmex | Metro | Culh 01f | Bb2 alpha on 02/02/2022 10:18:42 Page: 2
02/02/2022 14:19:02

Impedance (mΩ)
Healthy High Fail: 125.0% High Warn: 117.0% Low Warn: 70.0% Low Fail: 50.0%

14

12
Impedance (mΩ)

10

0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb2 alpha on 02/02/2022 10:18:42 Page: 3
02/02/2022 14:19:02

Voltage (V)
Healthy High Fail: 2.35 V/Cell High Warn: 2.30 V/Cell Low Warn: 2.20 V/Cell Low Fail: 2.15 V/Cell

2.8
2.7
Voltage (V/Battery)

2.6
2.5
2.4
2.3
2.2
2.1
2
1.9

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb2 alpha on 02/02/2022 10:18:42 Page: 4
02/02/2022 14:19:02

Sulfation (%)
Healthy High Fail: 20% High Warn: 15%

80

70

60
Sulfation (%)

50

40

30

20

10

0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb2 alpha on 02/02/2022 10:18:42 Page: 5
02/02/2022 14:19:02

Dryout (%)
Healthy High Fail: 20% High Warn: 15%
200
180
160
140
Dryout (%)

120
100
80
60
40
20
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb2 alpha on 02/02/2022 10:18:42 Page: 6
02/02/2022 14:19:02

Temperature (°C)

100
90
80
Temperature (°C)

70
60
50
40
30
20
10
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb2 alpha on 02/02/2022 10:18:42 Page: 7
02/02/2022 14:19:02

Battery # Result Impedance Impedance (%) Voltage Sulfation Dryout Temperature


(mΩ) (Population Ref.) (V) (%) (%) (°C)
1 Fail 0.343 175.3 2.240 34 0 26.8
2 Warning 0.234 119.4 2.230 10 0 26.8
3 Fail 0.374 191.4 2.256 40 0 26.8
4 Fail 0.246 125.8 2.225 8 0 26.8
5 Fail 7.705 3940.3 2.536 0 100 26.8
6 Pass 0.205 105.0 2.230 2 0 26.8
7 Pass 0.221 113.0 2.230 6 0 26.8
8 Fail 0.552 282.4 2.244 0 42 26.8
9 Warning 0.234 119.5 2.235 8 0 26.8
10 Pass 0.199 101.8 2.230 1 0 26.8
11 Pass 0.196 100.3 2.231 0 0 26.8
12 Warning 0.239 122.4 2.240 9 0 26.8
13 Pass 0.200 102.2 2.238 1 0 26.8
14 Pass 0.219 111.7 2.242 5 0 26.8
15 Pass 0.212 108.4 2.242 3 0 26.8
16 Pass 0.173 88.7 2.242 0 0 26.8
17 Pass 0.196 100.0 2.239 0 0 26.8
18 Fail 0.248 126.6 2.244 10 0 26.8
19 Fail 0.277 141.7 2.238 15 0 26.8
20 Fail 0.589 301.3 2.235 0 42 26.8
21 Fail 0.575 293.9 2.231 0 39 26.8
22 Fail 0.777 397.5 2.229 0 59 26.8
23 Fail 0.355 181.8 2.236 33 0 26.8
24 Fail 0.409 209.1 2.234 41 0 26.8
String Report for: Telmex | Metro | Culh 01f | Bb2 alpha on 02/02/2022 10:18:42 Page: 8
02/02/2022 14:19:02

Battery # Installation Manufactured Replaced


Date Date
1 No
2 No
3 No
4 No
5 No
6 No
7 No
8 No
9 No
10 No
11 No
12 No
13 No
14 No
15 No
16 No
17 No
18 No
19 No
20 No
21 No
22 No
23 No
24 No
String Report for: Telmex | Metro | Culh 01f | Bb2 alpha on 02/02/2022 10:18:42 Page: 9
02/02/2022 14:19:02

Summary
Test Summary
Test Start Date & Time: 02/02/2022 10:18:42
Test End Date & Time: 02/02/2022 10:29:31
Total Number of Batteries Tested: 24
Number of Batteries Passed: 9
Number of Batteries Failed: 12
Number of Batteries Warned: 3

Test Statistics

Coefficient of
Maximum Minimum Mean Std. Deviation Variation %
Impedance (mΩ): 7.705 0.173 0.624 1.485 237.9
Impedance (%) (Population-referenced): 3940.3 88.7 319.1 759.2 237.9
Voltage (V): 2.536 2.225 2.249 0.060 2.7
Temperature (°C): 26.8 26.8 26.8 0.0 0.0
Sulfation (%): 41 0
Dryout (%): 100 0