ATEX Instruction Sheet 8 Wide VerticalPLUS I/O Carrier

Part Number: ATEX1


Publication date: May 2018 Left/Right

KJ4003X1-BA1 8-W VerticalPLUS I/O Carrier Left


KJ4003X1-BB1 8-W VerticalPLUS I/O Carrier Right
Hazardous Atmosphere Removal and Insertion
Do not remove or insert this unit with system power
energized.
II 3G Ex nA IIC Gc
FM16ATEX0056U Power must be de-energized before disconnecting
any carriers or LocalBus Extender cables.

Bussed field power must not be connected to a


supply that generates or contains a source of
Power Specifications potential in excess of 30 VDC.
Local Bus Power 12.6 VDC at 15 A
Field power supplied to this device either at the field
Field Circuit Power 30 VDC at 13 A terminal or as bussed field power via the I/O carrier
must be removed before removing or connecting this
device.
Environmental Specifications
A module cover (KJ4001X1-FA1) must be fitted to
Ambient -40 °C to +70 °C any permanently unoccupied location on an I/O
Temperature module carrier. (Permanently unoccupied means no
Shock 10 g half-sine wave for 11 ms I/O module or terminal block is intended for that
location.)
Vibration 1 mm peak to peak from 2 to 13.2 Hz;
0.7 g from 13.2 to 150 Hz This product must not be unplugged unless either
the system has been de-energized or the area is
Airborne ISA-S71.04 –1985 Airborne
Contaminants Contaminants Class G3 known to be safe. No combination of I/O carriers and
LocalBus Extenders may exceed a length of 6.5 m.
Relative Humidity 5 to 95% non-condensing IP 20 rating Interconnecting cable between enclosures must be
in conduit.

Note: Refer to the product label for serial number


and location and date of manufacture.
Maintenance and Adjustment
This unit contains no user-serviceable parts and
Warning: This product has specific instructions for should not be disassembled for any reason.
installation, removal and operation in hazardous Calibration is not required.
areas. Refer to document 12P2046, DeltaV™
Scalable Process System Zone 2 Installation
Instructions. Other installation instructions are Other Safety Approvals
available in the DeltaV™ M-Series Hardware
Installation and Reference manual.

Emerson
Round Rock, Texas