KJ4003X1-BB1 8-W VerticalPLUS I/O Carrier Right Hazardous Atmosphere Removal and Insertion Do not remove or insert this unit with system power energized. II 3G Ex nA IIC Gc FM16ATEX0056U Power must be de-energized before disconnecting any carriers or LocalBus Extender cables.
Bussed field power must not be connected to a
supply that generates or contains a source of Power Specifications potential in excess of 30 VDC. Local Bus Power 12.6 VDC at 15 A Field power supplied to this device either at the field Field Circuit Power 30 VDC at 13 A terminal or as bussed field power via the I/O carrier must be removed before removing or connecting this device. Environmental Specifications A module cover (KJ4001X1-FA1) must be fitted to Ambient -40 °C to +70 °C any permanently unoccupied location on an I/O Temperature module carrier. (Permanently unoccupied means no Shock 10 g half-sine wave for 11 ms I/O module or terminal block is intended for that location.) Vibration 1 mm peak to peak from 2 to 13.2 Hz; 0.7 g from 13.2 to 150 Hz This product must not be unplugged unless either the system has been de-energized or the area is Airborne ISA-S71.04 –1985 Airborne Contaminants Contaminants Class G3 known to be safe. No combination of I/O carriers and LocalBus Extenders may exceed a length of 6.5 m. Relative Humidity 5 to 95% non-condensing IP 20 rating Interconnecting cable between enclosures must be in conduit.
Note: Refer to the product label for serial number
and location and date of manufacture. Maintenance and Adjustment This unit contains no user-serviceable parts and Warning: This product has specific instructions for should not be disassembled for any reason. installation, removal and operation in hazardous Calibration is not required. areas. Refer to document 12P2046, DeltaV™ Scalable Process System Zone 2 Installation Instructions. Other installation instructions are Other Safety Approvals available in the DeltaV™ M-Series Hardware Installation and Reference manual.