ATEX Instruction Sheet VerticalPLUS Power/Controller

Part Number: ATEX2


Publication date: May 2018 Carrier

KJ4003X1-BC1 VerticalPLUS Power/Controller


Carrier
Hazardous Atmosphere
Power must be de-energized before disconnecting
any carriers or LocalBus Extender cables.

II 3G Ex nA IIC Gc A module cover (KJ4001X1-FA1) must be fitted to


FM16ATEX0056U any permanently unoccupied location on an I/O
module carrier. (Permanently unoccupied means no
I/O module or terminal block is intended for that
location.)
Power Specifications This product must not be unplugged unless either
the system has been de-energized or the area is
Local Bus Power 12.6 VDC at 15 A
known to be safe. No combination of I/O carriers and
LocalBus Extenders may exceed a length of 6.5 m.
Interconnecting cable between enclosures must be
Environmental Specifications in conduit.
Ambient -40 °C to +70 °C
Temperature Maintenance and Adjustment
Shock 10 g half-sine wave for 11 ms This unit contains no user-serviceable parts and
should not be disassembled for any reason.
Vibration 1 mm peak to peak from 2 to 13.2 Hz; Calibration is not required.
0.7 g from 13.2 to 150 Hz

Airborne ISA-S71.04 –1985 Airborne


Contaminants Contaminants Class G3 Other Safety Approvals
Relative Humidity 5 to 95% non-condensing IP 20 rating

Note: Refer to the product label for serial number


and location and date of manufacture.

Warning: This product has specific instructions for


installation, removal and operation in hazardous
areas. Refer to document 12P2046, DeltaV™
Scalable Process System Zone 2 Installation
Instructions. Other installation instructions are
available in the DeltaV™ M-Series Hardware
Installation and Reference manual.

Removal and Insertion


Do not remove or insert this unit with system power
energized.

Emerson
Round Rock, Texas