Professional Documents
Culture Documents
Volume 2
Note to Users
This Service Manual is constructed using a system of issue letters (alphas) immediately
following the reference number, eg. 5943A denotes A as being the first issue. This rule
applies both to the overall volume reference and to its individual chapters, but is applied
to each, separately, whenever important amendments are made. Therefore, the increment
issue letter of any given chapter may not match that of the main volume.
SERVICE MANUAL R8605B
M301, M302 Volume 2
Contents
SAFETY SECTION
CHAPTER 1 INTRODUCTION
CHAPTER 2 INSTALLATION
CHAPTER 3 COMMISSIONING
CHAPTER 4 PROBLEM ANALYSIS
CHAPTER 5 SCADA INFORMATION
SERVICE MANUAL R8605B
M301, M302 Volume 2
Contents
SERVICE MANUAL R8605B
M301, M302 Volume 2
Contents
SAFETY SECTION
This Safety Section should be read before commencing any work on the equipment.
*Note: The term earth used throughout the product documentation is the direct
equivalent of the North American term ground.
Before energising the equipment it must be earthed using the protective earth
terminal, or the appropriate termination of the supply plug in the case of plug
connected equipment. Omitting or disconnecting the equipment earth may cause a
safety hazard.
The recommended minimum earth wire size is 2.5 mm2, unless otherwise stated in
the technical data section of the product documentation.
Before energising the equipment, the following should be checked:
Voltage rating and polarity;
CT circuit rating and integrity of connections;
Protective fuse rating;
Integrity of earth connection (where applicable)
Older Products
Electrical adjustments
Equipments which require direct physical adjustments to their operating mechanism
to change current or voltage settings, should have the electrical power removed
before making the change, to avoid any risk of electric shock.
Mechanical adjustments
The electrical power to the relay contacts should be removed before checking any
mechanical settings, to avoid any risk of electric shock.
Draw out case relays
Removal of the cover on equipment incorporating electromechanical operating
elements, may expose hazardous live parts such as relay contacts.
Insertion and withdrawal of extender cards
When using an extender card, this should not be inserted or withdrawn from the
equipment whilst it is energised. This is to avoid possible shock or damage
hazards. Hazardous live voltages may be accessible on the extender card.
Insertion and withdrawal of heavy current test plugs
When using a heavy current test plug, CT shorting links must be in place before
insertion or removal, to avoid potentially lethal voltages.
Technical Specifications
Protective fuse rating
The recommended maximum rating of the external protective fuse for this
equipment is 6A, Red Spot type or equivalent, unless otherwise stated in the
technical data section of the product documentation.
Chapter 1
Introduction
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 1
Contents
This service manual provides a functional and technical description of the MiCOM
M300 System Analysis and Measurement Centre range and a comprehensive set
of instructions for the use and application of the unit. The generic description used
for the product range in this manual is M300. There are two main product
variants; one panel mounted and referred to throughout as M301, and the other
DIN rail mounted and referred to as M302.
The service manual is split into two volumes as follows:
Volume 1 includes information on the application of the measurement centre and
a technical description of its features. It is mainly intended for
application engineers concerned with the selection and application of
the product for measuring power system parameters.
Volume 2 contains information on the installation and commissioning of the
product, and also a section on fault finding. This volume is intended
for test and commissioning engineers who are responsible for the
installation and maintenance of the unit.
The introductory chapter is common to both volumes and includes:
• An introduction to the MiCOM range of products and the features and facilities
which the range offers.
• A description of the user interface of the M301 to enable the user to start using
the product. This concentrates on the menu structure and how to navigate it from
the front of the unit.
• General technical statements.
The chapter content within each volume is summarised below:
Volume 1 Engineering Volume
Chapter 1 Introduction
Introduction to the MiCOM products and a guide to the user
interface of the M300.
Chapter 2 Applications
Comprehensive and detailed description of the features of the
product, the power system applications for which it is intended, and
how to calculate and apply suitable settings to the unit.
Chapter 3 Description
Overview of the hardware and software in the unit along with a
description of the internal operation of the unit. This chapter includes
information on the self checking features and diagnostics of the
product.
Chapter 4 Specification
Technical specifications of the product giving details of accuracy
limits, recommended operating conditions, technical ratings and
performance etc. Where appropriate the technical specifications are
quoted in relation to the relevant technical standard(s).
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 1
Page 2 of 28
MiCOM is the new range of substation protection and control products from
ALSTOM T&D Protection & Control. Central to the concept of MiCOM is
communication; communication between the different products in the range and
between the MiCOM products and substation control and SCADA systems. This
enables MiCOM to provide a comprehensive range of integrated protection and
control equipment which is capable of fulfilling all substation requirements.
The MiCOM range includes a wide selection of protection relays (the P series),
measurement products for accurate metering and monitoring (the M series) and
versatile communication support packages for personal computer interrogation of
the products (the S series).
All MiCOM products include facilities for recording a multitude of information on
the state and behaviour of the power system through disturbance and fault records,
but also can provide measurements of the system at regular intervals to a control
centre to enable remote monitoring and control to take place.
There are several personal computer based support software packages in the
MiCOM range which are custom designed for use with the other MiCOM
products:
• MiCOM M300 setting software is designed for local control of a single
measurement centre and provides facilities for changing product settings and
viewing measurands. This package communicates via the ModBus protocol.
• MiCOM S1 is designed for local control of a single relay and provides
facilities for operations such as changing the relay settings, programming the
protection scheme logic and extracting disturbance and fault records. This
package communicates via the Courier protocol.
• MiCOM S10 provides substation-wide communication with many MiCOM
products and is capable of extracting and displaying measurements from an
entire substation. Also MiCOM S1 can be combined with MiCOM S10 to
allow control of the relay settings for all MiCOM devices within a substation.
The range of measurement products in the MiCOM range presently includes the
following products:
M100 panel mounted energy meters
M210 system measurement centre
M300 system analysis and measurement centre
For up-to-date information on any of the products in the MiCOM range see the
latest MiCOM publications.
2.1 User interface and menu structure
The settings and functions of the M300 can be accessed from either the front panel
or rear communications port. The M302 has only communications ports and no
local user interface.
2.1.1 Menu structure and password protection
The front panel user interface is arranged in a hierarchical structure which is
designed to provide an intuitive interface eliminating the need for constant
recourse to the service manual. There are three main layers to the menu. Layer 0 of
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 1
Page 4 of 28
the menu allows access to the measured parameters. Layer 1 allows access to the
different setting groups. Once the appropriate setting group that requires changing
is located then access can be gained to the actual setting.
Different password access levels are allotted according to the security criteria of
individual settings.
2.1.1.1 Access level 0
Layer 0 menu
Layer 1 menu
Level 0
or
Level 1
System data
Level 2
Layer 2 menu
or
Password control
or
Access level 0
Figure 1
With this access level set only level 0 settings can be changed without the entrance
of a password. The only setting that can be changed is that of the Real Time Clock.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 1
Page 5 of 28
Layer 1 menu
Device settings
or
Level 0
System data
Level 1
or
Password control
or
Access level 1
Figure 2
With this access level set only level 0 and 1 settings can be changed without the
entry of a password. The settings available include:
Real Time Clock
Clear all event records
Clear waveform capture and all disturbance records
All other reset commands
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 1
Page 6 of 28
Layer 0 menu
Device settings
Level 1 or
Level 2
System data
Layer 2 menu
or
Password control
or
Access level 2
Figure 3
All settings are now available to the operator without entering passwords.
If a setting requires a password to be entered then the following procedure should
be followed:
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 1
Page 7 of 28
Password setting
Enter Level 1 or 2
Password: ****
Z, Y, X etc. or A, B, C etc.
then
or
Enter Level 1 or 2
Password: P***
Z, Y, X etc. or A, B, C etc.
then
Enter Level 1 or 2
Password: P1**
Z, Y, X etc. or A, B, C etc.
then
Enter Level 1 or 2
Password: P1A*
Z, Y, X etc. or A, B, C etc.
then
Figure 4
The three menu layers of the unit can be navigated using the key presses shown in
Figure 5 below. Pressing and holding a key will cause the unit to automatically
step around the layer (auto repeat function).
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 1
Page 8 of 28
Layer 0 menu
Current Power
displays displays
Voltage
displays Power
factor
C
Energy
MiCOM M300 displays
Measurement
Centre
anti-clockwise clockwise
rotation rotation
Maximum
Pulsed
demand
input
displays
displays
DC input System
frequency
System
commands Communications
settings
C
Demand
System data settings
anti-clockwise clockwise
rotation rotation
Analogue
Setpoints
outputs
and tariffs
Layer 2 menu
anti-clockwise clockwise
rotation rotation
Opto input 2
Opto input 1
No effect
Rotate right
pulsed input 1 Real power
Ph B
C
dc input Real power
Ph C
MD PF Reactive power
Go to next Ph A
MD export kW MD import kW Leading energy Lagging energy Export energy Import energy PF = Apparent power Apparent power Apparent power
Total Ph C Ph B
R8605A
Chapter 1
Page 9 of 28
Volume 2
Setpoint Disturbance
group 4 recorder
Go to next
Rotate left menu level
No effect settings
Setpoint Communications
group 3 settings
Chapter 1
Page 10 of 28
Volume 2
More detail
Rotate left where needed
Enter setting change menu
Chapter 1
Page 11 of 28
Volume 2
Rotate right
Chapter 1
Page 12 of 28
Volume 2
Rotate right
No effect
Rotate left
Enter setting change menu
Chapter 1
Page 13 of 28
Volume 2
Rotate right
No effect
Rotate left
Enter setting change menu
Chapter 1
Page 14 of 28
Volume 2
Rotate right
day 7
C day 1
More detail
Rotate left where Maximum demands
Enter setting change menu necessary
Maximum demands day 2
day 6
Chapter 1
Page 15 of 28
Volume 2
Rotate right
More detail
Rotate left where Rate register 3
Enter setting change menu necessary
Rate register 7
Chapter 1
Page 16 of 28
Volume 2
Rotate right
More detail
Rotate left where 2: <error>
Enter setting change menu necessary
6: <error>
Chapter 1
Page 17 of 28
Volume 2
Rotate right
Post trigger cycle
C
Clear to
clear wave cap &
Dist rec
More detail
Rotate left where Set point triggers
Enter setting change menu necessary
disturbance recorder
R8605A
Chapter 1
Page 18 of 28
Volume 2
Rotate right
No effect
Rotate left
Enter setting change menu
Chapter 1
Page 19 of 28
Volume 2
Rotate right
No effect
Rotate left
Enter setting change menu
Demand period
R8605A
Chapter 1
Page 20 of 28
Volume 2
Rotate right
No effect
Rotate left
Enter setting change menu
Chapter 1
Page 21 of 28
Volume 2
Rotate right
No effect
Rotate left
Enter setting change menu
Chapter 1
Page 22 of 28
Volume 2
Rotate right
No effect
Rotate left
Enter setting change menu
Opto input 2:
<assignment>
R8605A
Chapter 1
Page 23 of 28
Volume 2
Setpoint group 1 is used in the example but all other groups are available in the
same format.
Rotate right
More detail
Rotate left where
Enter setting change menu necessary
Setpoint G1, E7:
<assignment>
Rotate right
Rate switching
events 37 - 48
More detail
Rotate left where
Enter setting change menu necessary
Fixed date
exlusions
The front panel will return to a default display if the front panel interface is inactive
for more than 15 minutes. If this happens any setting changes which have not been
confirmed will be lost and the original setting values maintained. The default
display is the layer 0 menu position last displayed by the unit.
A set of screw terminals for connection via twisted pair wiring and RS485
communication to a master terminal at a more distant location (up to 1000m).
This is designed for use with a permanently wired communication system covering,
for example, a whole substation, and can connect a number of units to a single
master station for monitoring and control purposes. This port can be configured as
a either a K-BUS COURIER port or RS 485 ModBus port.
2.4 Courier communication interface
Courier is the communication language developed by ALSTOM T&D Protection &
Control to allow remote interrogation of its range of protection relays and is fully
supported by the MiCOM range. Courier works on a master/slave basis where the
slave units contain information in the form of a database, and respond with
information from the database when it is requested by a master unit.
The Measurement Centre is a slave unit which is designed to be used with a
Courier master unit such as MiCOM S1, PAS&T, ACCESS or a SCADA system.
The operations and functions supported by Courier communications are as follows:
display and modification of all settings
extraction of digital status
extraction of measurements
extraction of fault records
extraction of event and alarm records
manual extraction of disturbance records
reset of alarm conditions
clearing of event records
time synchronisation
automatic extraction of event and disturbance records
2.5 ModBus communication interface
ModBus is another master/slave communication protocol which can be used for
network control. In a similar fashion to Courier, the system works by the master
device initiating all actions and the slave devices (the Measurement Centres)
responding to the master by supplying the requested data or by taking the
requested action. ModBus communication can be held over the RS232 or RS485
links provided (but not at the same time). Using the RS485 port up to 32 slave
devices can be connected together over a distance of up to 1000m.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 1
Page 27 of 28
M 3 0 0 0 0 0 A
Numeric instrumentation
Application
Variant:
Vx Aux rating:
24...70V dc L
70...250V ac or dc H
In/Vn Rating:
1A, up to 440V 1
5A, up to 440V 5
Hardware
Product
No dc input 0
DC input 0...200mV 1
DC input 0...5V 2
DC input 0...250V 3
DC input 0...20mA 4
Protocol options:
Mounting:
Panel P
DIN rail D
Language:
Multilingual 0
Spare:
Design suffix:
For example, a Measurement Centre with display, and fully equipped with output relays, status inputs, 4 analogue outputs, a 4...20mA DC input, the RS485 set to
MODBUS protocol and the RS232 set to Courier, with a 5A input and a 220V Auxilliary requirement would have the model number M301H5344P0000A
M301, M302
System Analysis and Measurement Centre
Service Manual
Chapter 2
Installation
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 2
Contents
1. GENERAL CONSIDERATIONS 1
1.1 Receipt of M300 1
1.2 Electrostatic discharge 1
2. HANDLING OF ELECTRONIC EQUIPMENT 1
3. UNIT MOUNTING AND CONNECTION 2
4. UNPACKING 4
5. STORAGE 4
FIGURE 1 M301 CASE OUTLINE AND DIMENSIONS 2
FIGURE 2 M302 CASE OUTLINE AND DIMENSIONS 2
FIGURE 3 EXTERNAL WIRING DIAGRAM 3
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 2
Page 1 of 4
Units are dispatched individually for panel (M301) or DIN rail (M302) mounting.
Mounting details are shown in Figures 1 and 2.
MiCOM M300
SETPOINT
TRIP
ALARM
CLEAR
READ
ENTER
119.5
136.4
193.5 186 + 1.1
138 + 1.0
239.5
COM1 COM2
MiCOM M300
12 B A SCN 13
11 14
10 15
9 16
8 17
7 18 142.5
6 19
5 20
4 21
3 CURRENT 22
2 MA LA MB LB MC LC 23 RESET
1 24
145.0
DC RL2 8
analogue
input Relay
– 3 9 outputs
10
SERVICE MANUAL
RL3
19
S1 11
Opto 20 RL4 12
inputs
S2
18
14
22 A01
15
A02
A B C N
23 16 Analogue
A03 outputs
17
A04
24
13
21
A
connection diagram shown in Figure 3.
M
Options
La B COM2
Load
1 Relay outputs and opto unputs
Lb
1 DCD
2 Analogue outputs and DC analogue inputs
2 Rx
M 3 Relay outputs, opto inputs, analogue outputs
3 Tx and DC analogue inputs
P1
S1
S1
S1
Lc 4 DTR COM1
5 Signal Ground
6 DSR
P2
S2
S2
S2
7 RTS
Case earth
connection 8 CTS
The electrical connections should be made in accordance with the external
R8605A
Chapter 2
Page 3 of 4
Volume 2
Section 4. UNPACKING
Care must be taken when unpacking and installing the units so that none of the
parts is damaged. Units must only be handled by skilled persons. The installation
should be clean, dry and reasonably free from dust and excessive vibration.
The site should be well lit to facilitate inspection. Prior to installation, units should
not be left in situations where they are exposed to dust or damp. This particularly
applies to instalations which are being carried out at the same time as construction
work.
Section 5. STORAGE
If units are not to be installed immediately upon receipt they should be stored in a
place free from dust and moisture in their original cartons. Where de-humidifier
bags have been included in the packing they should be retained. The action of the
de-humidifier crystals will be impaired if the bag has been exposed to ambient
conditions and may be restored by gently heating the bag for about an hour, prior
to replacing it in the carton.
Dust which collects on a carton may, on subsequent unpacking, find its way into
the unit; in damp conditions the carton and packing may become impregnated
with moisture and the de-humidifier will lose its efficiency.
Storage temperature –25ºC to +70ºC.
M301, M302
System Analysis and Measurement Centre
Service Manual
Chapter 3
Commissioning
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Contents
1. INTRODUCTION 1
2. PRODUCT MENU FAMILIARISATION 2
3. EQUIPMENT REQUIRED FOR TESTING 3
3.1 Minimum equipment required 3
3.2 Additional equipment 3
4. PRODUCT VERIFICATION TESTS 3
4.1 With the unit de-energised 3
4.1.1 PVI: Visual inspection 3
4.1.2 PVS: Insulation 4
4.1.3 PV3: External wiring 4
4.2 With the unit energised 4
4.2.1 PV4: Light emitting diodes (M301 only) 5
4.2.2 PV4: Set the real-time clock 5
4.2.3 PV4: Reset alarms 5
4.2.4 PV4: Test the "Set point" and "Trip" LEDs (M301 only) 5
4.2.5 PV5: Liquid crystal display (M301 only) 5
4.2.6 PV6: Establish local communications 6
4.2.7 PV7: Set the real-time clock (M302 only) 6
4.2.8 PV8: Relay outputs (when fitted) 6
4.2.9 PV8: Testing alarm outputs 7
4.2.10 PV9: Opto inputs (when fitted) 7
4.2.11 PV10: Settings 8
4.2.12 PV10: Apply settings 8
4.2.13 PV10: Verify settings 8
4.2.14 PV11: Voltage and current inputs 8
4.2.15 PV11: Voltage inputs 9
4.2.16 PV11: Current inputs 9
4.2.17 PV12: Analogue outputs (when fitted) 10
4.2.18 PV13: Communication ports for remote communications 10
4.2.19 PV14: DC input (when fitted) 11
5. WIRING VERIFICATION TEST 11
5.1 Voltage connections 11
5.2 Current connections 12
6. FINAL CHECKS 12
7 MAINTENANCE 12
7.1 Remote testing 12
7.1.1 Alarms 13
7.1.2 Measurement accuracy 13
7.2 Local testing 13
7.2.1 Alarms 13
7.2.2 Measurement accuracy 13
7.2.3 Check output contacts 13
7.2.4 Analogue outputs 13
7.2.5 Additional tests 13
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Contents
Section 1. INTRODUCTION
The M300 products are fully numerical in their design, implementing all functions
in software. They employ a high degree of self checking so that, for the majority of
failures that could occur within the product, all functions will cease to operate and
an error will be flagged. As a result of this, the commissioning tests do not need to
be as thorough as with products using electromechanical and discrete electronic
components. To commission the M300, it is only necessary to verify that the
hardware is functioning correctly and the application-specific software settings
have been applied to the unit.
It is also considered unnecessary to test every function of the unit if the settings
have been verified by one of the following methods:
• Extracting the settings applied to the M300 unit using appropriate setting
software (preferred method)
• Via the operator interface (M301 Measurement Centre only).
The number of tests to be performed will depend on the hardware option that has
been installed in the unit. The hardware option installed can be found from the
“Fitted Hardware” window under the “SYSTEM CONFIGURATION” heading or
directly from the seventh character in the unit’s model number. Table 1 details the
tests that need to be performed for each hardware option.
Unless previously agreed to the contrary, the customer will be responsible for the
correct selection of settings and any interwiring between units.
Blank commissioning test and setting records are provided at the end of this
chapter for completion as required.
BEFORE COMMISSIONING THE M300, REFER TO THE SAFETY AND
INSTALLATION SECTIONS OF THE MANUAL.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 2 of 38
0 1 2 3
No options Relay outputs Analogue Relay outputs
Outputs
Status inputs DC input Status inputs
Analogue
Outputs
DC input
PV1 • • • •
PV2 • • • •
PV3 • • • •
PV4 • • • •
PV5 • • • •
PV6 • • • •
PV7 • • • •
PV8 • •
PV9 • •
PV10 • • • •
PV11 • • • •
PV12 • •
PV13 • • • •
PV14 • •
When commissioning an M301 for the first time, an hour should be allowed to
become familiar with the menu. Chapter 1 contains a description of the menu
structure.
Similarly, if a portable PC with appropriate software is being used to set the unit,
time should be allowed to become familiar with the associated setting software.
This software is essential for setting the M302 because it does not have an integral
user interface. For details of the operation of this software, please refer to the
associated software user manual.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 3 of 38
It should be noted that the unit can withstand ac ripple of up to 12% of rated
voltage on the dc auxiliary supply.
The M300 units are protected against overloads created when batteries are
removed and the charger is left in place. However, this mode of operation is not
recommended as other units, such as protective relays, powered from the same
supply may not have this overload protection.
Energise the unit if the auxiliary supply is within the operating range.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 5 of 38
2 7 and 9
3 9 and 10
4 11 and 12
To check the operation of the status inputs when configured as pulsed input
counters, the counts for each pulsed input can be viewed from the measurement
display for the M301 model, and using the communications and a PC running the
appropriate software for the M302. Apply then remove the dc voltage to the
input, the pulse counter should increase by one.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 8 of 38
0 Single phase • •
6 2 phase, 3 wire • • • •
Terminals MA MB MC 22 23 24 22 23 24
LA LB LC 21 21 21 23 24 22
Otherwise, if the “Display Mode” setting is “Primary”, the measured current values
on the unit should equal the applied current multiplied by the current transformer
ratio set using the “CT Primary” and “CT Secondary” settings under the
“SYSTEM MODES” column heading.
The current can be read directly from the LCD display on the M301 and via the
communications interface and a PC running the appropriate software on the
M302.
The acceptable tolerance is ±0.2% ± digital multi-meter accuracy.
4.2.17 PV12: Analogue outputs (when fitted)
This test checks the operation and accuracy of the analogue outputs.
The assignments of each of the four analogue outputs should have been
determined by the customer and installed as part of the settings of the unit.
The customer should also have calculations which give the expected values of each
analogue output for a given input condition, these should be referred to when
testing the analogue outputs. (In the absence of this information the expected
values of the analogue outputs should be calculated for a definite value of applied
voltage and current, given the settings applied to the unit).
Apply the definite voltage and current values as detailed in the calculations and
check the dc output current for each assigned analogue output with a multimeter,
the terminal allocations are given in Table 6. Check these values against the
expected values.
The acceptable tolerance is ±0.2% ± digital multi-meter accuracy.
Analogue output Reference Terminal
1 AO1 14
2 AO2 15
3 AO3 16
4 AO4 17
Common AOC 13
4 0 to 20mA
Remove all test leads, temporary shorting leads, etc. and replace any external
wiring that has been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the unit in
order to perform any of the above tests, it should be ensured that all connections
are replaced in accordance with the relevant external connection or scheme
diagram.
The following on-load measuring test ensures that the external (customer) wiring to
the current and voltage inputs is correct but can only be carried out if there are no
restrictions preventing the energisation of the plant being monitored.
Note: The following tests alone are not conclusive that the phase connections to
the unit are correct. A phase angle measurement is required for conclusive
testing.
5.1 Voltage connections
Measure the voltage transformer secondary voltages to ensure they are correctly
rated and, if possible, check that the system phase rotation is correct using a
phase rotation meter.
Compare the values of the secondary phase voltages with the unit’s measured
values, which can be found under the “MEASUREMENT” column heading.
The unit’s reading can either be in primary or secondary volts depending on the
setting of “Display Mode” under the “SYSTEM CONFIGURATION” heading.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 12 of 38
If the “Display Mode” setting is “Secondary”, the measured voltage values on the
unit should equal the applied voltage.
Otherwise, if the “Display Mode” setting is “Primary”, the measured voltage values
on the unit should equal the applied voltage multiplied by the voltage transformer
ratio set using the “VT Primary” and “VT Secondary” settings under the “SYSTEM
MODES” column heading.
The acceptable tolerance is ±0.2%, ± digital multi-meter accuracy.
5.2 Current connections
Measure the current transformer secondary values and check that their polarities
are correct by measuring the phase angle between the current and voltage.
If the unit is connected to a balanced system, ensure the current flowing in the
neutral circuit of the current transformers is negligible.
Compare the values of the secondary phase currents with the unit’s measured
values, which can be found under the “MEASUREMENT” column heading.
The unit’s reading can either be in primary or secondary amperes depending on
the setting of “Display Mode” under the “SYSTEM CONFIGURATION” heading.
If the “Display Mode” setting is “Secondary”, the measured current values on the
unit should equal the applied current.
Otherwise, if the “Display Mode” setting is “Primary”, the measured current values
on the unit should equal the applied current multiplied by the current transformer
ratio set using the “CT Primary” and “CT Secondary” settings under the “SYSTEM
MODES” column heading.
The acceptable tolerance is ±0.2%, ± digital multi-meter accuracy.
Section 7. MAINTENANCE
The M300 units are fully numerical in their design, implementing all functions in
software. They employ a high degree of self-checking so that, for the majority of
failures that can occur within the unit, all functions will cease to operate and an
error will be flagged. Depending on the failure and the hardware options fitted to
the unit, the error will be seen as an alarm that can be accessed over the
communication channel or by the operation of a watchdog contact.
7.1 Remote testing
The M300 units are self-supervising and so require negligible maintenance.
Most problems will result in an alarm so that remedial action can be taken.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 13 of 38
However, some periodic tests could be done to ensure that the unit is functioning
correctly. If the M300 can be communicated with from a remote point, via its
communication port, then some testing can be carried out without actually visiting
site.
7.1.1 Alarms
The alarm status should first be checked to identify if any alarm conditions exist.
The alarm records can then be read to identify the nature of any alarm that may
exist.
7.1.2 Measurement accuracy
The values measured by the unit can be compared with known system values to
check that they are in the approximate range that is expected. If they are, then the
analogue/digital conversion and calculations are being performed correctly.
7.2 Local testing
When testing locally, similar tests to those for remote testing may be carried out to
check for correct functioning of the unit.
7.2.1 Alarms
The alarm status LED should first be checked to identify if any alarm conditions
exist. The alarm records can then be read to identify the nature of any alarm that
may exist.
7.2.2 Measurement accuracy
The values measured by the unit can be checked against known values injected
into the unit via its terminal block. Suitable test methods will be found in Section 8
of this chapter which deals with commissioning. These tests will prove the
calibration accuracy is being maintained.
7.2.3 Check output contacts
Check that the output contacts are giving the correct output state.
7.2.4 Analogue outputs
Check that each analogue output is giving out the expected value using a
multimeter.
7.2.5 Additional tests
Additional tests can be selected from the Commissioning Instructions as required.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 14 of 38
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 15 of 38
Date
Station Circuit
System Frequency
Rating label information
System Analysis and Measurement Centre M30_
Model number
Serial number
Rated current Ιn
Rated voltage Vn
Auxiliary voltage Vx
*Delete as appropriate
Product verification tests
With the device de-energised
PV1 Visual inspection
Is the device damaged? Yes/No*
Rating information correct? Yes/No*
Case earth installed? Yes/No*
PV2 Insulation tested? Yes/No/NA*
PV3 External wiring checked against
diagram? Yes/No/NA*
With the Device Energised
Auxiliary voltage to device V ac/dc*
Polarity checked ? Yes/No/NA*
PV4 Light Emitting Diodes (M301 only) Fitted/Not fitted*
Real-time clock set via user interface? Yes/No/NA*
“Out of Service” LED working? Yes/No*
“Alarm” LED working? Yes/No*
“Set Point” LED working? Yes/No*
“Trip” LED working? Yes/No*
PV5 Liquid Crystal Display (M301 only) Fitted/Not fitted*
All pixels working? Yes/No*
Backlight switches on and off? Yes/No*
PV6 Communications Ports Used/Not used*
Port Tested RS232/RS485
Communications working? Yes/No*
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 16 of 38
Date Date
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 19 of 38
Date Engineer
Station Date
Circuit System Frequency
Rating label information
The following information should be recorded from the rating label of the device.
System Analysis and Measurement Centre M30_
Model number
Serial number
Rated current Ιn
Rated voltage Vn
Auxiliary Voltage Vx
Software installed
The software issues or references used in the device should be recorded in the
following table, these references are contained within the SYSTEM DATA menu.
Software Ref 1
Software Ref 2
Settings
The following sections list the settings that can be applied to the device in the
relevant menus, these should be recorded where applicable.
Each section and sub section refers to a specific menu heading and sub menu
heading where applicable.
System data
Language
Password
Description
Plant Reference
Frequency
Password Control
Level 1 Password
Level 2 Password
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 20 of 38
System configuration
Comms Protocol
Display Mode
LCD Backlight
Real Time Clock
Clock Synch
Max Clock Synch Interval
System Modes
Connection Mode
Power Flow Mode
CT Primary
CT Secondary
VT Primary
VT Secondary
System Commands
“ENTER” to Capture A ph Fast Wform Data
“ENTER” to Capture B ph Fast Wform Data
“ENTER” to Capture C ph Fast Wform Data
Disturbance Recorder
Samples per cycle
Record Config
Post Trigger Cycle
Setpoint Triggers
Opto Input Triggers
Communications Settings
Modem Control Lines
Modbus Address
Modbus Baud Rate
Modbus Framing
Courier Address
IEC870 Baud Rate
IEC870 Framing
Demand Calculation
Function
Demand Period
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 21 of 38
Analogue outputs
These settings only apply to devices with hardware options 2 & 3 installed.
ANALOGUE OUTPUT 1
Analogue Output 1 Parameter
Analogue Output 1 Full Scale
Analogue Output 1 Slope
Analogue Output 1 X-Breakpoint 1
Analogue Output 1 Y-Breakpoint 1
Analogue Output 1 Span
ANALOGUE OUTPUT 2
Analogue Output 2 Parameter
Analogue Output 2 Full Scale
Analogue Output 2 Slope
Analogue Output 2 X-Breakpoint 1
Analogue Output 2 Y-Breakpoint 1
Analogue Output 2 Span
ANALOGUE OUTPUT 3
Analogue Output 3 Parameter
Analogue Output 3 Full Scale
Analogue Output 3 Slope
Analogue Output 3 X-Breakpoint 1
Analogue Output 3 Y-Breakpoint 1
Analogue Output 3 Span
ANALOGUE OUTPUT 4
Analogue Output 4 Parameter
Analogue Output 4 Full Scale
Analogue Output 4 Slope
Analogue Output 4 X-Breakpoint 1
Analogue Output 4 Y-Breakpoint 1
Analogue Output 4 Span
Note1 Setting is only applicable when dual slope is selected.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 22 of 38
Relay outputs
These settings only apply to devices with hardware options 1 & 3 installed.
RELAY OUTPUT 1
Relay 1 Assignment
Relay 1 Label 1
Relay 1 Contacts 1
Import/Export kWh Full Scale 2
Import/Export kWh Pulse Rate 2
Import/Export kWh Pulse Duration 2
Import/export kVArh Full Scale 3
Import/export kVArh Pulse Rate 3
Import/export kVArh Pulse Duration 3
RELAY OUTPUT 2
Relay 2 Assignment
Relay 2 Label 1
Relay 2 Contacts 1
Import/Export kWh Full Scale 2
Import/Export kWh Pulse Rate 2
Import/Export kWh Pulse Duration 2
Import/export kVArh Full Scale 3
Import/export kVArh Pulse Rate 3
Import/export kVArh Pulse Duration 3
RELAY OUTPUT 3
Relay 3 Assignment
Relay 3 Label 1
Relay 3 Contacts 1
Import/Export kWh Full Scale 2
Import/Export kWh Pulse Rate 2
Import/Export kWh Pulse Duration 2
Import/export kvarh Full Scale 3
Import/export kvarh Pulse Rate 3
Import/export kvarh Pulse Duration 3
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 23 of 38
RELAY OUTPUT 4
Relay 4 Assignment
Relay 4 Label 1
Relay 4 Contacts 1
Import/Export kWh Full Scale 2
Import/Export kWh Pulse Rate 2
Import/Export kWh Pulse Duration 2
Import/export kVArh Full Scale 3
Import/export kVArh Pulse Rate 3
Import/export kVArh Pulse Duration 3
Notes
1 Setting is only applicable when relay assignment is set to Setpoint Group.
2 Setting is only applicable when relay assignment is set to Pulsed Import
kWh or Pulsed Export kWh.
3 Setting is only applicable when relay assignment is set to Pulsed import
kVArh or Pulsed export kvarh.
Opto inputs
These settings only apply to devices with hardware options 1 & 3 installed.
OPTO INPUT 1
Opto Input 1 Assignment
Opto Input 1 Label 1
OPTO INPUT 2
Opto Input 2 Assignment
Opto Input 2 Label 1
Notes
1 Setting is only applicable when opto inputs are configured as Pulse
Counters.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 24 of 38
Setpoint Group 1
Setpoint Group 1 Delay
Setpoint G1,E1 (Assignment)
Setpoint G1,E1 High Level
Setpoint G1,E1 Low Level
Setpoint G1,E2 (Assignment)
Setpoint G1,E2 High Level
Setpoint G1,E2 Low Level
Setpoint G1,E3 (Assignment)
Setpoint G1,E3 High Level
Setpoint G1,E3 Low Level
Setpoint G1,E4 (Assignment)
Setpoint G1,E4 High Level
Setpoint G1,E4 Low Level
Setpoint G1,E5 (Assignment)
Setpoint G1,E5 High Level
Setpoint G1,E5 Low Level
Setpoint G1,E6 (Assignment)
Setpoint G1,E6 High Level
Setpoint G1,E6 Low Level
Setpoint G1,E7 (Assignment)
Setpoint G1,E7 High Level
Setpoint G1,E7 Low Level
Setpoint G1,E8 (Assignment)
Setpoint G1,E8 High Level
Setpoint G1,E8 Low Level
Setpoint Group 2
Setpoint Group 2 Delay
Setpoint G2,E1 (Assignment)
Setpoint G2,E1 High Level
Setpoint G2,E1 Low Level
Setpoint G2,E2 (Assignment)
Setpoint G2,E2 High Level
Setpoint G2,E2 Low Level
Setpoint G2,E3 (Assignment)
Setpoint G2,E3 High Level
Setpoint G2,E3 Low Level
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 25 of 38
Tariff Settings
The following sections detail the menus and tabulate the settings within each menu.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 27 of 38
EXCLUSION 6 Week
Day
Season To Use
Day to Use
EXCLUSION 7 Week
Day
Season To Use
Day to Use
EXCLUSION 8 Week
Day
Season To Use
Day to Use
Fixed Date Exclusions
EXCLUSION 1 Month
Day Of Month
Season To Use
Day to Use
EXCLUSION 2 Month
Day Of Month
Season To Use
Day to Use
EXCLUSION 3 Month
Day Of Month
Season To Use
Day to Use
EXCLUSION 4 Month
Day Of Month
Season To Use
Day to Use
EXCLUSION 5 Month
Day Of Month
Season To Use
Day to Use
EXCLUSION 6 Month
Day Of Month
Season To Use
Day to Use
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 3
Page 38 of 38
EXCLUSION 7 Month
Day Of Month
Season To Use
Day to Use
EXCLUSION 8 Month
Day Of Month
Season To Use
Day to Use
Rate Register Data Source
Rate Register 1
Rate Register 2
Rate Register 3
Rate Register 4
Rate Register 5
Rate Register 6
Rate Register 7
Rate Register 8
M301, M302
System Analysis and Measurement Centre
Service Manual
Chapter 4
Problem Analysis
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 4
Contents
flowing. If so, check the continuity of the current loop connected to the unit.
This can be done by using either a continuity device or by feeding a current into
the circuit from a dc constant current source. If there is continuity, then reconnect
the current loop to the unit and measure the voltage at the terminals using an
appropriate voltmeter. If the voltage exceeds 10V then the current loop has too
much resistance around it.
1.5 Output relays (when fitted)
Check that the model has this option fitted via the user interface.
Check that the voltage across the relay contacts falls to zero when the relay
operates.
1.6 Opto inputs (when fitted)
Check that the unit has this option fitted via the user interface.
Check for presence of a voltage at the terminals of the status inputs with an
appropriately rated voltmeter.
1.7 DC input (when fitted)
Check that the unit has this option fitted via the user interface.
Check for the presence of the correct signal at the terminals using an appropriately
rated multimeter.
1.8 Password lost or not accepted
The Measurement Centre is supplied with the password set to AAAA.
Only upper case letters are acceptable.
The password can be changed by the user. See Chapter 1.
There is an additional unique recovery password associated with the unit which
can be supplied by the factory, or service agent, if they are given details of the
unit serial number. The serial number will be found in the system data column of
the menu and should correspond to the number on the label located on the rear of
the unit. If they differ, quote the one in the system data column.
1.9 Sub assembly fault finding
If the unit continues to operate incorrectly having completed the above tests then it
will have to be returned to the factory for fault finding and repair. It is not practical
to repair the unit on site. If any PCBs are replaced the unit will need to be
recalibrated with equipment having a traceable accuracy of better than 0.05% of
reading. This level of equipment specification is not available for site working.
1.10 Recommended spares
A complete unit can be used to back up several Measurement Centres. In the very
unlikely event that one unit fails it can then be replaced with a complete new unit
and the faulty unit returned to the factory for repair. This will then become the new
spare unit once repaired.
M301, M302
System Analysis and Measurement Centre
Service Manual
Chapter 5
SCADA Information
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Contents
1.1 Introduction
The M301 has two principle means of allowing the user to interact with it; the front
panel interface and a remote communications access interface. This manual
specifies the data available to the user and the method by which the user can
interact with the database via the front panel interface. Also contained within the
document are the associated text strings that appear at the Courier remote
communications interface. The ModBus remote communications interface is more
basic and is described in the SCADA section. These systems implement a broad
range of standard facilities which allow the user to:
• View measurements
• View and change settings
• View (and reset where appropriate) alarm records
• View (and reset where appropriate) event records
• View (and reset where appropriate) alarm/error messages
Access to the unit’s database is provided by means of an intuitive menu system.
Human interaction is provided by means of a twenty character by two line LCD,
seven button keypad, and four LEDs.
The user interface provides textual information in one of four languages:
English
French
German
Spanish
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 2 of 160
Layer 0 Default
Layer 3
Data 2.1.1 Data 2.1.2 Data 2.1.3
Pressing the “down” arrow key at any time returns the user to the display that they
left prior to entering the scan alarms menu.
If an alarm clears itself whilst it is being viewed by the user the alarm message will
be removed and the next alarm message displayed. If this happens when there are
no other alarm messages present, the display returns to that which it left on entry to
the Scan Alarms menu via a temporary intermediate display indicating that there
are no more alarms present.
Key Description of Function
[READ] Steps through present alarm messages and the
reset alarms message in a cyclic manner.
[CLEAR] Resets/clears the alarm messages at the ‘CLEAR to
Clear Alarms’ prompt.
Down arrow Returns the user to the display that they were in
before entering the scan alarms layer.
Other arrow keys No effect whilst in the scan alarms layer.
Pressing the [ENTER] key initiates the password prompt. If no password is required
or the password for the required level of protection has already been entered this
stage is be omitted.
1.4.2 Password protection
The password protection is described in the introduction. The procedure outlined in
that section should be followed to allow the correct password access to be set.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 6 of 160
Again the leading character flashes between its present value and an underscore
to prompt the user that the field may be changed. The numeric value or text string
will be varied by means of the Up and Down arrow keys. (If more than one field is
present eg. register bits, selection of the individual fields is provided by means of
the left and right arrow keys.
Pressing the [ENTER] key accepts the change and the menu returns to normal
browsing mode but the new data value is displayed.
Pressing the [CLEAR] key at any point aborts the setting change and the menu shall
return to browsing mode via a temporary intermediate screen that states “Setting
Aborted”. Time-out of the keypad inactivity timer aborts the whole process and the
menu returns to the default position.
1.4.4 Group settings
If the setting cell is a member of a group setting, the setting change is not
implemented until the user moves up to a primary column heading. This is because
the user may wish to change several related settings that should be implemented
together. Time-out of the keypad inactivity timer, at any stage of this process,
causes all the amended settings within that group to revert to their original values
prior to the change.
After making all the required group setting changes the user returns up the column
headings by pressing the Up arrow key. If any of the group settings have changed
the user shall be prompted by the following display. If no settings were actually
changed the prompt is bypassed.
Update Settings?
ENTER=Yes CLEAR=No
Pressing the [DOWN] key returns the user to the first data cell of the column
heading, with any previous changes still visible.
Pressing the [ENTER] key implements the settings and the menu moves to the
column heading via an intermediate message.
Pressing the [CLEAR] key discards the group settings change and the menu moves
up to the column heading via a temporary intermediate message.
1.4.5 Immediate settings
If an immediate setting has been altered and the [ENTER] key pressed the setting is
updated immediately.
Pressing the [ENTER] key implements the setting change immediately and returns
the menu to normal browse mode.
1.5 Menu Contents
The following sections depict the format of data that is displayed at the front panel
and remote access point in order to view the data base of the unit.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 7 of 160
MEASUREMENTS
Vbn=0.000 kV
Vcn=0.000 kV
Vbc=0.000 kV
Vca=0.000 kV
Vbn(THD)=0.000 %
Vcn(THD)=0.000 %
Vbc(THD)=0.000 %
Vca(THD)=0.000 %
Ιb=0.000 kA
Ιc=0.000 kA
Ιb(THD)=0.000 %
Ιc(THD)=0.000 %
Ιb(MD)=0.000 kA
Ιc(MD)=0.000 kA
Real Power:
Reactive Power:
Apparent Power:
MD Import= MD Import=00.00000 kW
00.00000 kW
MD Export= MD Export=00.00000 kW
00.00000 kW
MD PF=0.000 MD PF=0.000
DC Input=0.000 % DC Input=0.000 %
Communication Level: 1
Courier Address: 1
Opto 1: 1
Opto 2: 0
Relay 1: 0
Relay 2: 1
Relay 3: 0
Relay 4: 1
1.6.1 Language
This setting cell allows the user to select the required interface language. The table
below shows the possible states of the language cell.
Front Panel Remote Access
1.6.2 Password
This setting cell allows the user to enter the password for the desired security level.
The password shall be entered as described in the introduction to the two volumes.
1.6.3 Description
This data cell is a data cell containing a character string describing the device,
namely “Measurement Centre”.
1.6.4 Plant reference
A setting cell containing a 16 character string. Its principal application is to
identify the location of the unit when viewed over a remote access system.
1.6.5 Model number
A data cell containing the unit’s model number.
1.6.6 Serial number
This data cell identifies the serial number of the unit.
1.6.7 Communication level
This data cell indicates the capability of the communications interface to a remote
system. The measurement centre implements level 1 Courier Communications.
1.6.8 Courier address
This setting cell contains the address of the unit.
1.6.9 Software Ref 1
This data cell contains the version of the boot loader software.
1.6.10 Software Ref 2
This data cell contains the version of the main software.
1.6.11 Opto input status (where fitted)
This data cell enables the user to view the status of the opto inputs. When an input
is energised its flag is shown as a ‘1’, otherwise as a ‘0’. Opto 1 status is defined
in bit 1 and Opto 2 is in bit 2.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 15 of 160
1.8.3 CT Primary
This setting cell allows the user to set the CT primary value. The cell’s contents are
variable from 0-9999A in 1A steps.
1.8.4 CT Secondary
This setting cell allows the user to set the CT secondary value. The cell’s contents
are variable from 1.000-9.000A in 0.001A steps.
1.8.5 VT Primary
This setting cell allows the user to set the VT primary value. The cell’s contents are
variable from 0-999999V in 1V steps.
1.8.6 VT Secondary
This setting cell enables the user to set the desired VT secondary value. The cell’s
contents are variable from 1.00V to 500.00V in 0.01V steps.
1.9 System commands menu
The System Commands menu is presented to the user as shown in the table.
The menu basically allows the user to initiate various commands. Pressing the front
panel button referred to in the quotation marks carries out the command (M301
only). Once the command has been completed a message is temporarily displayed
to inform the user. All of these commands are accessed via the communications on
an M302.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 19 of 160
‘ENTER’ to Capture
B ph Fast Wform Data
‘ENTER’ to Capture
C ph Fast Wform Data
MD Day 1: Import=00.00000 kW
Import=00.00000 kW ↓ 06-Jan-1997 11:33:31.087
MD Day 1: Export=00.00000 kW
Export=00.00000 kW ↓ 06-Jan-1997 11:33:31.087
MD Day 1: PF=0.000
PF=0.000 ↓ 06-Jan-1997 11:33:31.087
MD Day 1: Ιa=0.000 A
Ιa=0.000 A ↓ 06-Jan-1997 11:33:31.087
MD Day 1: Ιb=0.000 A
Ιb=0.000 A ↓ 06-Jan-1997 11:33:31.087
MD Day 1: Ιc=0.000 A
Ιc=0.000 A ↓ 06-Jan-1997 11:33:31.087
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 23 of 160
↑←→
Dup Season Events: 1
↑←→
Invalid Season: 1
↑←→
Events In season: 1
↑←→
Rate Register 1: 0
↑←→
Rate Register 2: 1
↑←→
Rate Register 8: 1
Group 1, Element 1: 0
Group 1, Element 2: 1
Group 1, Element 3: 0
Group 1, Element 4: 1
Group 2, Element 1: 0
Group 4, Element 8: 1
Opto I/P 1: 1
Opto I/P 2: 0
Group 4 Group 3
Bit
32
1 0 0 0 0 0 1 0 0 0 0 1 1 0 0 0 ↑
0 0 0 1 0 0 0 0 0 0 0 0 0 1 0 0 ↓
Bit
0
Group 2 Group 1
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 27 of 160
The ‘↑‘ and ‘↓‘ symbols indicate that pressing the Up arrow key returns the user to
the main setting cell, whilst pressing the Down arrow key expands the first flag.
The flag’s expanded information is displayed as in the table below.
The ‘←‘ and ‘→‘ symbols indicate that the user can scroll left or right through the
cells in a cyclic manner using the Left arrrow and Right arrow keys respectively.
↑←→
Group 1,Element 1: 0
↑←→
Group 1,Element 2: 0
↑←→
Group 1,Element 3: 1
↑←→
Group 1,Element 4: 0
↑←→
Group 1,Element 5: 0
↑←→
Group 1,Element 6: 0
↑←→
Group 1,Element 7: 0
↑←→
Group 1,Element 8: 0
↑←→
Group 2,Element 1: 0
↑←→
Group 2,Element 2: 0
↑←→
Group 2,Element 3: 0
↑←→
Group 2,Element 4: 0
↑←→
Group 2,Element 5: 1
↑←→
Group 2,Element 6: 0
↑←→
Group 2,Element 7: 0
↑←→
Group 2,Element 8: 0
↑←→
Group 3,Element 1: 0
↑←→
Group 3,Element 2: 0
↑←→
Group 3,Element 3: 0
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 28 of 160
↑←→
Group 3,Element 4: 1
↑←→
Group 3,Element 5: 1
↑←→
Group 3,Element 6: 0
↑←→
Group 3,Element 7: 0
↑←→
Group 3,Element 8: 0
↑←→
Group 4,Element 1: 0
↑←→
Group 4,Element 2: 1
↑←→
Group 4,Element 3: 0
↑←→
Group 4,Element 4: 0
↑←→
Group 4,Element 5: 0
↑←→
Group 4,Element 6:0
↑←→
Group 4,Element 7:0
↑←→
Group 4,Element 8:1
↑←→
Opto Input Trig 2:0
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 29 of 160
Modbus Framing: 1St, Modbus Framing: 1 Start Bit, 8 Data Bits, Even Parity
8Dt, Even Par, 2Stp Bit, 2 Stop Bits
Modbus Framing: 1St, Modbus Framing: 1 Start Bit, 8 Data Bits, No Parity
8Dt, No Par, 2Stp Bit, 2 Stop Bits
Modbus Framing: 1St, Modbus Framing: 1 Start Bit, 8 Data Bits, Even Parity
8 Dt, Even Par, 1Stp Bit, 1 Stop Bit
Modbus Framing: 1St, Modbus Framing: 1 Start Bit, 8 Data Bits, Odd Parity
8 Dt, Odd Par, 1Stp Bit, 1 Stop Bit
1.11.9 Function
The function setting cell determines the type of demand calculation used as
described in the table.
Front Panel Remote Access
Relay 1
Event 1
Event 2
Event 12
↑←→
Event 2 Rate Reg 2:0
etc.
The user is able to enter setting mode in the normal manner from any of the
displays. When in setting mode the user shall see the display shown below (the
particular Rate Reg number displayed depends on where the setting mode was
entered from). The Left and Right arrow keys can be used to scroll through the Rate
Registers in a cyclic manner and the Up and Down arrow keys used to toggle the
setting value between ‘0’ and ‘1’. The setting changes is accepted in the normal
manner.
↑←→
Event 1 Rate Reg 1:1
Event 1
Event 12
1.17.1 Month
This setting cell enables the user to select from ‘Disabled’, ‘January’, ‘February’,
‘March’, ‘April’, ‘May’, ‘June’, ‘July’, ‘August’, ‘September’, ‘October’,
‘November’, and ‘December’.
1.17.2 Day of month
This setting cell allows the user to select in steps of 1 day from 1 to 31 days.
1.17.3 New season
This setting cell has a range of 0 to 11 in steps of one.
1.18 Switching events in season menu
Front Panel Remote Access
Exclusion 1:
Exclusion 1 Week: 1
Week: 1
Exclusion 8:
Exclusion 8 Week: 1
Week: 1
Exclusion 1:
Exclusion 8:
1 Francais
SERVICE MANUAL
2 Deutsch
3 Espanol
00 02 Password Ascii Password(4) Password: ****
00 04 Description Ascii Text(16) 20 Characters + NULL Description: Measurement Centre
00 05 Plant Reference Ascii Text (16) 20 Characters + NULL Plant Reference: <User Defined>
00 06 Model Number Ascii Text(16) 15 Characters + NULL Model Number: H100A1100120CEA
00 08 Serial Number Ascii Text(7) 6 Digits + 1 Alpha Serial Number: 123456A
00 09 Frequency (Hz) Unsigned Integer (16) Frequency (Hz): 50
00 0A Communication Level Unsigned Integer (16) Communication Level: 1
00 0B Address Unsigned Integer (16) Address: 1
00 11 Software Ref 1 Ascii Text (16) Software Ref 1: <To be defined>
00 12 Software Ref 2 Ascii Text (16) Software Ref 2: <To be defined>
00 20 Opto Input Status Binary Flags (2) Opto Input Status: 00
00 21 Relay Output Status Binary Flags (4) Relay Output Status: 0000
Page 44 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
00000008h Serial communication controller channel B test 2
00000010h Serial communication controller channel B test 2
M301, M302
Page 45 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
00000008h Group 1 Setpoint 4 Group 1 Setpoint 4: 0
00000010h Group 1 Setpoint 5 Group 1 Setpoint 5: 0
00000020h Group 1 Setpoint 6 Group 1 Setpoint 6: 0
M301, M302
Page 46 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
08000000h Group 4 Setpoint 4 Group 4 Setpoint 4: 0
10000000h Group 4 Setpoint 5 Group 4 Setpoint 5: 0
20000000h Group 4 Setpoint 6 Group 4 Setpoint 6: 0
M301, M302
Page 47 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
01 06 Clock Synch Indexed String 0 Disabled Clock Synchronisation: Disabled
1 30 s
2 1 min
M301, M302
3 5 min
SERVICE MANUAL
4 10 min
5 15 min
6 30 min
7 60 min
01 07 Max Clock Synch Indexed String 0 Disabled
1 to 31 Days
02 00 SYSTEM MODES
02 01 Connection Mode Indexed String 0 Single Phase (L, N)
1 3 phase 4 wire balanced (1 volts, 1 current)
2 3 phase 3 wire balanced (3 volts, 1 current)
3 3 phase 3 wire unbalanced (3 volts, 2 currents)
4 3 phase 4 wire unbalanced (2 volts, 3 currents)
5 3 phase 4 wire unbalanced (3 volts, 3 currents)
6 2 phase 3 wire system (2 volts, 2 currents)
7 3 phase 3 wire balanced (2 volts, 2 currents)
02 02 Power Flow Mode Indexed String 0 Mode 1
1 Mode 2
2 Mode 3
3 Mode 4
Chapter 5
Volume 2
Page 48 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
02 03 C.T. Primary Unsigned Integer(32) 0 No Primary Circuit
1 - 9999 (A)
02 04 C.T. Secondary IEEE Float Value entered = nominal value of I/P current
M301, M302
1 - 99,999 (V)
(V)
02 06 V.T. Secondary IEEE Float Value entered = nominal value of I/P voltage
02 07 Save Settings Indexed String 0 Settings OK
1 Settings Changed
2 Accept New Settings
3 Abort Setting Changes
03 00 SYSTEM COMMANDS
03 01 Reset Energy Meter Indexed String 0 NO
1 YES - RESETS TO 0
03 02 Reset Demand Indexed String 0 NO
1 YES - RESETS TO 0
03 03 Reset Energy Meter and Demand Indexed String 0 NO
1 YES - RESETS TO 0
03 04 Reset Pulse Counts Indexed String 0 NO
1 YES - RESETS TO 0
03 05 Reset Local LEDs Indexed String 0 NO
1 YES - RESETS TO 0
03 06 Restore Password Protection Indexed String 0 NO
Chapter 5
Volume 2
Page 49 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
1 YES - RESETS TO 0
03 07 Start Fast Waveform Capture Indexed String 0 Capture Off
1 Capture A-ph Data
M301, M302
04 00 MEASUREMENTS
04 01 Van Courier Voltage
04 02 Vbn Courier Voltage
04 03 Vcn Courier Voltage
04 04 Vab Courier Voltage
04 05 Vbc Courier Voltage
04 06 Vca Courier Voltage
04 07 Ia Courier Current
04 08 Ib Courier Current
04 09 Ic Courier Current
04 0A In Courier Current
04 0B Frequency Courier Frequency
04 0C dc Input IEEE Float
04 0D Pulse Count 1 Unsigned Integer (16)
04 0E Pulse Count 2 Unsigned Integer (16)
04 0F V %NPS Courier Percentage
04 10 I %NPS Courier Percentage
Chapter 5
Volume 2
Page 50 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
05 01 REAL POWER
05 02 A Phase Real Power Courier Power
SERVICE MANUAL
06 00 DEMAND VALUES
Chapter 5
Volume 2
Page 51 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
06 01 DYNAMIC DEMAND VALUES
06 02 Time Into Period (min) Unsigned Integer(16)
06 03 Import Real Power Courier Power
M301, M302
Page 52 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
06 19 Import Real Power Courier Power
06 1A Time Stamp IEC870 Time & Date
06 1B Export Real Power Courier Power
M301, M302
Page 53 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
06 31 Time Stamp IEC870 Time & Date
06 32 Import Reactive Power Courier var
06 33 Time Stamp IEC870 Time & Date
M301, M302
Page 54 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
07 06 Import Reactive Power Courier var
07 07 Time Stamp IEC870 Time & Date
07 08 Export Reactive Power Courier var
M301, M302
08 00 TARIFF METER
Chapter 5
Volume 2
Page 55 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
08 01 Active Rate Registers Binary Flags (8) 1 Rate Register 1 Active (bit-mask)
2 Rate Register 2 Active (bit-mask)
4 Rate Register 3 Active (bit-mask)
M301, M302
Page 56 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
09 02 Vbn THD Courier Percentage
09 03 Vcn THD Courier Percentage
09 04 Vab THD Courier Percentage
M301, M302
Page 57 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
0A 0F 15th Harmonic Courier Percentage
0A 10 VB HARMONIC DATA SAME AS VA HARMONIC DATA
0A XX VC HARMONIC DATA SAME AS VA HARMONIC DATA
M301, M302
SERVICE MANUAL
Page 58 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
0C 01 IA HARMONIC DATA
0C 02 2nd Harmonic Courier Percentage
0C 03 3rd Harmonic Courier Percentage
M301, M302
10 00 VIEW RECORDS
10 01 No of Records Unsigned Integer (16) 1 1, 2 Alarm Records.
10 02 Record Number Unsigned Integer (16)
10 03 Time Stamp Unsigned Integer (16)
Chapter 5
Volume 2
Page 59 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
10 04 ALARM EVENT (depends on Event Type) Indexed Sting 0 Watchdog Time-Out Reset
1 Serial Communication Controller Channel A Test 1 Fail
2 Serial Communication Controller Channel A Test 2 Fail
M301, M302
Page 60 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
24 EEPROM Error: Configuration Settings
25 EEPROM Error: Calibration Values
26 Frequency Tracking Fail
M301, M302
Page 61 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
2 Element 2
3 Element 3
4 Element 4
M301, M302
5 Element 5
SERVICE MANUAL
6 Element 6
7 Element 7
8 Element 8
10 0A Parameter Indexed String 0 No Input
1 Frequency
2 Total Real Power
3 Total Reactive Power
4 Total Apparent Power
5 Total Power Factor
6 Import Total Watts Demand
7 Export Total Watts Demand
8 Import Total VAr Demand
9 Export Total VAr Demand
10 Positive Total VA Demand
11 Negative Total VA Demand
12 Total Power Factor Demand
13 Ia
14 Ib
15 Ic
16 In
Chapter 5
Volume 2
Page 62 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
17 Ia Demand
18 Ib Demand
19 Ic Demand
M301, M302
20 Ia THD
SERVICE MANUAL
21 Ib THD
22 Ic THD
23 INPS
24 Van
25 Vbn
26 Vcn
27 Vab
28 Vbc
29 Vca
30 Van THD
31 Vbn THD
32 Vcn THD
33 Vab THD
34 Vbc THD
35 Vca THD
36 VNPS
37 dc
10 0B Value Courier Reserved
10 0C Low / High Indexed String 0 Low Alarm
1 High Alarm
Chapter 5
Volume 2
Page 63 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
10 0D Reset / Trip Indexed String 0 Alarm Reset
1 Alarm Trip
10 0E Clear All Event Records Indexed String 0 No
M301, M302
1 Yes - Resets to 0
SERVICE MANUAL
11 00 DISTURBANCE RECORDER
11 01 Recorder Status Indexed String 0 Stopped
1 Triggered
2 Running
11 02 Data Source Indexed String 0 ADC Samples
11 03 Samples per cycle Indexed String 0 24
1 48
11 04 Record Configuration Indexed String 0 1 Record, 36 Cycles
1 2 Record, 18 Cycles
2 3 Record, 12 Cycles
3 4 Record, 9 Cycles
0 1 Record, 72 Cycles
1 2 Record, 36 Cycles
2 3 Record, 24 Cycles
3 4 Record, 18 Cycles
11 05 Post Trigger Cycle: 36 Unsigned Integer (32)
11 06 Setpoint Trigger Binary Flags (32) 2exp0 Group 1, Element 1
Chapter 5
Volume 2
Page 64 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
20 00 COMMS SETTINGS
20 01 Modem Control Indexed String 0 Disabled
1 Enabled
20 02 Modbus Address Unsigned Integer(16)
20 03 Modbus Baud Rate Indexed String 0 1200
1 2400
2 4800
3 9600
Chapter 5
Volume 2
Page 65 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
4 19200
20 04 Modbus Framing Indexed String 0 1 start, 8 data, no parity, 1 stop
1 1 start, 8 data, even parity, 1 stop bit
M301, M302
21 00 DEMAND CALCULATION
21 01 Function Indexed String 0 Fixed Window
1 Sliding Window
2 Thermal
21 02 Demand Subperiods (min) Unsigned Integer (16) Minutes
21 03 Demand Period (subperiods) Unsigned Integer (16) Number of Subperiods
21 04 Save Settings Indexed String 0 Settings OK
Chapter 5
Volume 2
Page 66 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
1 Settings Changed
2 Accept New Settings
3 Abort Setting Changes
M301, M302
SERVICE MANUAL
22 00 ANALOGUE OUTPUTS
22 01 ANALOGUE OUTPUT 1
22 02 Parameter Indexed String 0 Disabled
1 Frequency
2 Total Real Power
3 Total Reactive Power
4 Total Apparent Power
5 Total Power Factor
6 Ia
7 Ib
8 Ic
9 In
10 Van
11 Vbn
12 Vcn
13 Vab
14 Vbc
15 Vca
22 03 Full Scale Courier Percent %
22 04 Slope Indexed String 0 Single
Chapter 5
Volume 2
Page 67 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
1 Dual
22 05 X-Breakpoint Courier Percent %
22 06 Y-Breakpoint Courier Percent %
M301, M302
23 00 RELAY OUTPUTS
23 01 OUTPUT 1
23 02 Assignment Indexed String 0 Disabled
1 Setpoint Group 1
2 Setpoint Group 2
3 Setpoint Group 3
4 Setpoint Group 4
Chapter 5
Volume 2
Page 68 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
5 Pulsed Import Total kWh
6 Pulsed Export Total kWh
7 Pulsed Import Total kvarh
M301, M302
9 Watchdog
23 03 Label Ascii Text 14 Characters - “Relay O/P 1”
23 04 Default State Indexed String 0 Normally Open
1 Normally Closed
23 05 OUTPUT 2
23 09 OUTPUT 3
23 0D OUTPUT 4
23 11 PULSED OUTPUTS
23 12 Import kWh
23 13 Pulse Duration Indexed String 0 100ms
1 200ms
2 400ms
23 14 Pulse Rate (pph) Unsigned Integer (16) Pulses per hour
23 15 Full Scale Courier Percent %
23 16 Export kWh
23 1A Import kvarh
23 1E Export kvarh
23 22 Save Settings Indexed String 0 Settings OK
1 Settings Changed
2 Accept New Settings
Chapter 5
Volume 2
Page 69 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
3 Abort Setting Changes
24 00 OPTO INPUTS
M301, M302
24 01 INPUT 1
SERVICE MANUAL
25 00 SETPOINT GROUP 1
25 01 Delay (seconds) Unsigned Integer (32) Seconds
25 02 ELEMENT 1
25 03 Parameter Indexed String 0 Disabled
Chapter 5
Volume 2
Page 70 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
1 Frequency
2 Total Real Power
3 Total Reactive Power
M301, M302
Page 71 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
25 Vbn
26 Vcn
27 Vab
M301, M302
28 Vbc
SERVICE MANUAL
29 Vca
30 Van THD
31 Vbn THD
32 Vcn THD
33 Vab THD
34 Vbc THD
35 Vca THD
36 VNPS
37 dc
25 04 High Set Courier Percent
25 05 Low Set Courier Percent
25 06 ELEMENT 2
25 0A ELEMENT 3
25 0E ELEMENT 4
25 12 ELEMENT 5
25 16 ELEMENT 6
25 1A ELEMENT 7
25 1E ELEMENT 8
25 22 Save Settings Indexed String 0 Settings OK
1 Settings Changed
Chapter 5
Volume 2
Page 72 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
2 Accept New Settings
3 Abort Setting Changes
M301, M302
26 00 SETPOINT GROUP 2
SERVICE MANUAL
27 00 SETPOINT GROUP 3
28 00 SETPOINT GROUP 4
Page 73 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
128 Rate Register 7
30 06 EVENT 2
M301, M302
30 0B EVENT 3
30 10 EVENT 4
SERVICE MANUAL
30 15 EVENT 5
30 1A EVENT 6
30 1F EVENT 7
30 24 EVENT 8
30 29 EVENT 9
30 2E EVENT 10
30 33 EVENT 11
30 38 EVENT 12
Page 74 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
31 33 EVENT 23
31 38 EVENT 24
M301, M302
32 01 EVENT 25
32 06 EVENT 26
32 0B EVENT 27
32 10 EVENT 28
32 15 EVENT 29
32 1A EVENT 30
32 1F EVENT 31
32 24 EVENT 32
32 29 EVENT 33
32 2E EVENT 34
32 33 EVENT 35
32 38 EVENT 36
Page 75 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
33 1F EVENT 43
33 24 EVENT 44
33 29 EVENT 45
M301, M302
33 2E EVENT 46
SERVICE MANUAL
33 33 EVENT 47
33 38 EVENT 48
Page 76 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
Page 77 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
36 10 EXCLUSION 4
36 15 EXCLUSION 5
36 1A EXCLUSION 6
M301, M302
36 1F EXCLUSION 7
SERVICE MANUAL
36 24 EXCLUSION 8
Page 78 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
2 Export Watts
3 Import vars
4 Export vars
M301, M302
40 00 DISTURBANCE RECORDS
40 01 Record Number Unsigned Integer (16)
40 02 Trigger Time IEC Time & Date Disturbance Record Time Stamp
40 03 Channels Available Binary Flags (10) Available Channels in Disturbance Record
40 04 Channel Type Binary Flags (10) Channel Type (Analogue / Digital)
Chapter 5
Volume 2
Page 79 of 160
R8605A
Col Row Menu Text Data Type Ind Values Cell Format String with default value
40 05 Channel Offset Courier Reserved Data offset for Analog Channels
40 06 Channel Scaling Courier Reserved Analogue Channel Scaling Factors
40 10 Record Length Signed Integer (16) Number of samples in Record
M301, M302
40 11 Trigger Position Signed Integer (16) Sample number when trigger occurred
SERVICE MANUAL
Page 80 of 160
R8605A
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 81 of 160
3.3 Framing
There are two types of message framing for the serial communications, ASCII or
RTU. The Measurement Centre will only support RTU framing.
3.3.1 RTU framing
In RTU mode, messages start and end with a silent interval of at least 3.5 character
times (t1-t2-t3-t4 as shown below).
The advantage of this mode of framing is that it enables a greater character
density and a better data throughput. However, each message must be transmitted
in a continuous stream. If a silent interval of more than 1.5 character times occurs
before completion of the frame, the device flushes the incomplete message and
assumes that the next byte will be the address field of a new message.
Start Address Function Data CRC Check End
The Cyclical Redundancy Check (CRC) field is two bytes, containing a 16 bit
binary value. The CRC value is calculated by the transmitting device, which
appends the CRC to the message. The receiving device recalculates a CRC during
receipt of the message, and compares the calculated value to the actual value it
received in the CRC field. If the two values are not equal an error results. The CRC-
16 calculation is an industry standard method used for error detection.
One frame is transmitted as 1 start bit, 8 data bits and 1 stop bits. If parity is
selected then the frame is transmitted as 1 start bit, 8 data bits, 1 parity bit and 1
stop bit.
Where n > 1 data is transmitted most significant byte first.
The CRC check is transmitted least significant byte first.
3.4 Supported functions and usage
Code Function References
Transmissions received from the master with CRC errors will be ignored by the
slave. The number of re-tries needs to be set in the master station software.
An example of an illegal request and the corresponding exception response is
shown below. The request in this example is to read registers 0201H to 0209H. If
these addresses are not supported in the slave then the following occurs:
3.6.1 Request message
Starting Register Register Count
Address Function Code HI LO HI LO CRC
01 01 02 01 00 08 6D B4
02 ILLEGAL DATA ADDRESS The data address received in the request is not an
allowable value for the slave
03 ILLEGAL DATA VALUE The value referenced in the data field transmitted by
the master is not within range for the selected data
address
If the event type is 0 - Alarm event, then the following registers contain the record
information:
Register 30037: Time stamp
Register 30043: Alarm type
Note: Other registers not listed above within the range 30043 ... 30052 are not
available.
If the event type is 1-Setpoint event, then the following registers contain the record
information:
Register 30037: Time stamp
Register 30046: Setpoint group
Register 30047: Setpoint element
Register 30046: Setpoint parameter
Register 30049
/30050: Setpoint value when the setpoint
exceeded alarm threshold.
Register 30051: Setpoint level indicates whether the
setpoint is operated on the high or low alarm.
Register 30052: Setpoint trip/reset indicates whether the
record is logged during the setpoint trip or reset
operation.
Note: Other registers not listed above within the range 30043 ... 30052 are not
available.
If the event type is 2-Output contact change, then the following registers contain
the record information:
Register 30044: The first 4 bits represent the status of the 4 relay outputs of the
unit. Logical ‘1’ means that the output has ‘operated’. However, it does not mean
that the contact has ‘closed’ or ‘opened’. The actual state of the contacts depends
on the setting ‘Relay # Default State’. The unit logs this type of event only when the
setting ‘Relay # Assignment’ is set to Setpoint or Watchdog.
Note: Other registers not listed above within the range 30043 ... 30052 are not
available.
If the event type is 3 - Opto input change, then the following registers contain the
record information:
Register 30045: The first 2 bits represent the status of the 2 opto inputs of
the unit. Logical ‘1’ means the opto is ‘ON’. The unit
logs this type of events only when the setting ‘Opto Input
# Configuration’ is set to Logic Level.
Note: Other registers not listed above within the range 30043 - 30052 are not
available.
3.8.2 Disturbance record extraction
To read a disturbance or a waveform analysis record, the user must first check that
there are records available by reading the register 30054 which gives the total
number of records stored in the unit. The unit can store 1 waveform analysis record
and up to 4 disturbance records depending on the setting ‘Record Configuration’.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 86 of 160
Register 30054 gives the total number of records stored in the unit including both
disturbance and waveform analysis records.
Then set the register 40567 to determine the type of record you want to read. ‘0’
is to read waveform analysis record, and ‘1’ disturbance record. If the disturbance
record is selected, the register 40568 must be set to select the record number.
Record number 0 selects the latest, and 1 the previous one, and so on.
Register 40568 is not available if the waveform analysis is selected because there
is only one waveform analysis record.
Registers 30055 ... 30067 contain information about the record to be extracted.
Register 30055 ... 30060: Time stamp of the record
Register 30061: Available channels. The unit can stored up to 10
channels of data. The total number of bits set
indicates the number of channels stored in the
record.
Register 30062: Channel types. Indicates whether the valid channel
shown in register 30061 is an analogue or digital
channel.
Register 30063: Total number of samples stored per channel.
Register 30065: Number of samples of the selected page which is set
via register 40570.
Register 30066: Trigger position of the record.
Register 30067: Time base. A scaling factor used to convert the
samples of timer channel (channel 0) to a real time
value in seconds.
Register 30068
to30081: Individual scaling factor per analogue channel. It is
used to multiply with the samples read from the
corresponding analogue channel.
Register 30082
to 30151: Analogue channel names.
Register 30152
to 30389: Digital channel names.
The data of a record is extracted on a per channel basis. First select the channel to
be read by setting register 40569 to the correct channel number. Channel number
0 is the timer channel which is excluded from bit value shown in register 30061,
Available Channels (it is always there). Channel number 1 is bit-0 (right to left)
shown in Available Channels and so on.
Each channel of data is extracted on per page basis. The total number of pages of
a selected channel is shown by register 30064. Each page can contain up to 64
samples of data. To read a page of data, first set register 40570 to the required
page number, and from the value read back from register 30065 determine the
number of samples available in the page. The availability of registers 30390 ...
30453 depends on the number of samples of the selected page.
The information presented in the Disturbance/Waveform Analysis Menu is
sufficient to construct a record based on the COMTRADE format (both
COMTRADE: 1991 and COMTRADE: 1996 specifications are supported).
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 87 of 160
T1 Unsigned Value
m15..m8
m15..m8
T39 Voltage
The read only voltage value indicated will depend on
whether ModBus Display Mode is selected to show
primary or secondary values. Data will be scaled by VT
in Primary mode. Data will be formatted as T10 (Base
unit volts) and T11 (Base unit volts) for the primary and
secondary display modes respectively.
SERVICE MANUAL R8605A
M301, M302 Volume 2
Chapter 5
Page 91 of 160
T40 Current
The read only current value indicated will depend on
whether ModBus Display Mode is selected to show
primary or secondary values. Data will be scaled by CT
in primary mode. Data will be formatted as T10(Base
unit amps) and T11 (Base unit amps) for the primary
and secondary display modes respectively.
Code Address Contents Data Ind Values / Dependencies Reg. Type Min Max Step Passcode
SYSTEM DATA
SERVICE MANUAL
Page 93 of 160
R8605A
Page 94 of 160
R8605A
Code Address Contents Data Ind Values / Dependencies Reg. Type Min Max Step Passcode
EVENT RECORDS
04 30035 Number of Event records “T44” 1 1...100 Alarm Records Data 0
Chapter 5
Volume 2
Page 95 of 160
R8605A
Code Address Contents Data Ind Values / Dependencies Reg. Type Min Max Step Passcode
Event
04 30036 Event Type “ T1” 0 Alarm event Data 0
1 Setpoint event
M301, M302
04 30037 30042 Calendar Clock Time Stamp “T38” IEC format Data 0
04 30043 Alarm Element Event (depends on Event Type) “ T1” 0 Watchdog Timeout Test Fail Data
0
1 Comms Channel A Test 1 Fail
2 Comms Channel A Test 2 Fail
3 Comms Channel B Test 1 Fail
4 Comms Channel B Test 2 Fail
5 EEPROM Error: Immediate settings
6 EEPROM Error: System Modes settings
7 EEPROM Error: Disturbance Recorder settings
8 EEPROM Error: Communications settings
9 EEPROM Error: Demand settings
10 EEPROM Error: Analogue Output settings
11 EEPROM Error: Relay Output settings
12 EEPROM Error: Opto Input settings
13 EEPROM Error: Alarm Group 1 settings
14 EEPROM Error: Alarm Group 2 settings
15 EEPROM Error: Alarm Group 3 settings
16 EEPROM Error: Alarm Group 4 settings
17 EEPROM Error: Tariff settings
18 EEPROM Error: Metering Data
19 EEPROM Error: Event Records
Chapter 5
Volume 2
Page 96 of 160
R8605A
Code Address Contents Data Ind Values / Dependencies Reg. Type Min Max Step Passcode
Page 97 of 160
R8605A
Code Address Contents Data Ind Values / Dependencies Reg. Type Min Max Step Passcode
4 Element 4
SERVICE MANUAL
5 Element 5
6 Element 6
7 Element 7
8 Element 8
04 30048 Setpoint Parameter “ T1” 0 No Parameter Data 0
1 Frequency
2 Total 3 Phase Active Power
3 Total 3 Phase Reactive Power
4 Total 3 Phase Apparent Power
5 Total Power Factor
6 Import Total Watts Demand
7 Export Total Watts Demand
8 Lagging Total Var Demand
9 Leading Total Var Demand
10 Positive Total VA Demand
11 Negative Total VA Demand
12 Total Power Factor Demand
13 IA
14 IB
15 IC
16 IN
Chapter 5
Volume 2
Page 98 of 160
R8605A
Code Address Contents Data Ind Values / Dependencies Reg. Type Min Max Step Passcode
17 IA Demand
18 IB Demand
19 IC Demand
M301, M302
20 IA THD%
SERVICE MANUAL
21 IB THD%
22 IC THD%
23 Inps
24 VA
25 VB
26 VC
27 VAB
28 VBC
29 VCA
30 VA THD%
31 VB THD%
32 VC THD%
33 VAB THD%
34 VBC THD%
35 VCA THD%
36 Vnps
37 dc Input
04 30049 30050 Setpoint Value “T15” Data 0
04 30051 Setpoint Level “ T1” 0 High Alarm Data 0
1 Low Alarm
04 30052 Setpoint Trip / Reset “ T1” 0 Alarm Trip Data 0
1 Alarm Reset
Chapter 5
Volume 2
Page 99 of 160
R8605A
Code Address Contents Data Ind Values / Dependencies Reg. Type Min Max Step Passcode
DISTURBANCE RECORDS
AND WAVEFORM ANALYSIS
04 30053 Disturbance Recorder Status “T46” 0 Stopped Data 0
M301, M302
1 Triggered
SERVICE MANUAL
2 Running
04 30054 Number of Disturbance &
Waveform Capture Records “T45” Total number of disturbance records and
waveform capture recdord stored Data 0
RECORD DATA
04 30055 30060 Trigger Time “T52” Time and date stamp in IEC 870 format Data 0
04 30061 Available Channels “T49” Bit set indicates channel is available
(1=channel 1 ... 512=channel 10) Data 0
04 30062 Channel Types “T49” Bit set indicates channel is analogue,
reset indicates channel is digital Data 0
04 30063 Record Length “T49” Number of samples stored in a channel. Data 0
04 30064 Number of Sample Pages “ T1” Number of sample pages of the
Select Channel Number Data
04 30065 Number of Samples in
Sample Page “T48” The number of samples of the
Select Sample Page Data
04 30066 Trigger Position “T49” Data 0
04 30067 Time Base “T56” The scaling factor of the timer channel.
It is 50ns. Data 0
MEASUREMENTS
04 30454 30455 VA “T39” Data 0
04 30456 30457 VB “T39” Data 0
04 30458 30459 VC “T39” Data 0
04 30460 30461 VAB “T39” Data 0
04 30462 30463 VBC “T39” Data 0
04 30464 30465 VCA “T39” Data 0
04 30466 30467 IA “T40” Data 0
04 30468 30469 IB “T40” Data 0
Chapter 5
Volume 2
POWER/ENERGY MEASUREMENTS
04 30483 30484 A Phase Real Power “T21” Data 0
04 30485 30486 B Phase Real Power “T21” Data 0
04 30487 30488 C Phase Real Power “T21” Data 0
04 30489 30490 A Phase Reactive Power “T21” Data 0
04 30491 30492 B Phase Reactive Power “T21” Data 0
04 30493 30494 C Phase Reactive Power “T21” Data 0
04 30495 30496 A Phase Apparent Power “T21” Data 0
04 30497 30498 B Phase Apparent Power “T21” Data 0
04 30499 30500 C Phase Apparent Power “T21” Data 0
04 30501 30502 Total Real Power “T21” Data 0
04 30503 30504 Total Reactive Power “T21” Data 0
04 30505 30506 Total Apparent Power “T21” Data 0
04 30507 Total Power Factor “ T8” Data 0
04 30508 30509 Import Real Energy (Wh) “T20” Data 0
04 30510 30511 Export Real Energy (Wh) “T20” Data 0
04 30512 30513 Import Reactive Energy (varh) “T20” Data 0
Chapter 5
Volume 2
VA Harmonic Data
SERVICE MANUAL
VB Harmonic Data
04 31244 VB Second Harmonic % “ T3” Data 0
04 31245 VB Third Harmonic % “ T3” Data 0
04 31246 VB Fourth Harmonic % “ T3” Data 0
04 31247 VB Fifth Harmonic % “ T3” Data 0
04 31248 VB Sixth Harmonic % “ T3” Data 0
04 31249 VB Seventh Harmonic % “ T3” Data 0
Chapter 5
Volume 2
VC Harmonic Data
04 31258 VC Second Harmonic % “ T3” Data 0
04 31259 VC Third Harmonic % “ T3” Data 0
04 31260 VC Fourth Harmonic % “ T3” Data 0
04 31261 VC Fifth Harmonic % “ T3” Data 0
04 31262 VC Sixth Harmonic % “ T3” Data 0
04 31263 VC Seventh Harmonic % “ T3” Data 0
04 31264 VC Eigth Harmonic % “ T3” Data 0
04 31265 VC Ninth Harmonic % “ T3” Data 0
04 31266 VC Tenth Harmonic % “ T3” Data 0
04 31267 VC Eleventh Harmonic % “ T3” Data 0
04 31268 VC Twelfth Harmonic % “ T3” Data 0
04 31269 VC Thirteenth Harmonic % “ T3” Data 0
04 31270 VC Fourteenth Harmonic % “ T3” Data 0
04 31271 VC Fifteenth Harmonic % “ T3” Data 0
Chapter 5
Volume 2
IB Harmonic Data
04 31328 IB Second Harmonic % “ T3” Data 0
04 31329 IB Third Harmonic % “ T3” Data 0
04 31330 IB Fourth Harmonic % “ T3” Data 0
04 31331 IB Fifth Harmonic % “ T3” Data 0
04 31332 IB Sixth Harmonic % “ T3” Data 0
04 31333 IB Seventh Harmonic % “ T3” Data 0
04 31334 IB Eigth Harmonic % “ T3” Data 0
04 31335 IB Ninth Harmonic % “ T3” Data 0
04 31336 IB Tenth Harmonic % “ T3” Data 0
04 31337 IB Eleventh Harmonic % “ T3” Data 0
04 31338 IB Twelfth Harmonic % “ T3” Data 0
04 31339 IB Thirteenth Harmonic % “ T3” Data 0
Chapter 5
Volume 2
IC Harmonic Data
SERVICE MANUAL
CALIBRATION COEFFICIENT
04 32013 32014 Va Calibration Coefficient “T18” Data 0
04 32015 32016 Ia Calibration Coefficient “T18” Data 0
Chapter 5
Volume 2
SYSTEM DATA
03,06,16 40001 Language “ T1” 0 English Setting 0 3 1 2
1 Francais
2 Deutsch
Chapter 5
Volume 2
3 Espanol
03,06,16 40002 40003 User Password “T29” Password to attempt user access level upgrade Setting 41h 5Ah 1 0
03,06,16 40004 40013 Description “T43” Setting 20h 7Eh 1 2
M301, M302
SYSTEM CONFIGURATION
03,06,16 40029 Communication Protocols “ T1” 0 Courier/IEC870 & Modbus/RS485 Setting 0 1 1 2
1 Modbus/RS232 & Courier/KBUS
03,06,16 40030 Modbus Display Mode “ T1” 0 Secondary Setting 0 1 1 2
1 Primary
03,06,16 40031 LCD Back Light “ T1” 0 Off Setting 0 1 1 2
1 On
Clock and Calendar
03,06,16 40032 40037 Time and Date “T19” IEC 870 Time/Date format Setting
SYSTEM COMMANDS
03,06,16 40047 Reset Command Register “T35” Bit-0 Reset Energy Meter Setting 1 255 1
Bit-1 Reset Demand
M301, M302
COMMUNICATION SETTINGS
03,06,16 40049 Modem Control Lines “ T1” 0 Disabled Setting 0 1 1 2
1 Enabled
Courier
03,06,16 40050 Courier Address “ T1” Setting 0 255 1 2
03,06,16 40051 IEC870 Frame “ T1” 0 FT1.2, 11 bits Setting 0 1 1 2
1 10 bits
03,06,16 40052 Baud Rate “ T1” 0 1200 baud Setting 0 4 1 2
1 2400 baud
2 4800 baud
3 9600 baud
4 19200 baud
Chapter 5
Volume 2
Modbus
03,06,16 40053 Modbus Address “ T1” Setting 1 247 1 2
03,06,16 40054 Baud Rate “ T1” 0 1200 baud Setting 0 4 1 2
M301, M302
1 2400 baud
SERVICE MANUAL
2 4800 baud
3 9600 baud
4 19200 baud
03,06,16 40055 Framing “ T1” 0 1 start bit, 8 data bits, no parity, 2 stop bits Setting 0 2 1 2
1 1 start bit, 8 data bits, even parity, 1 stop bits
2 1 start bit, 8 data bits, odd parity, 1 stop bits
DEMAND CALCULATION
03,06,16 40056 Demand function “ T1” 0 Fixed window demand calculation Setting 0 2 1 2
1 Sliding window demand calculation
2 Thermal characteristic demand calculation
03,06,16 40057 Demand Sub-Period
Sliding Window “ T1” Duration of sub-period specified in minutes Setting 1 99 1 2
03,06,16 40058 Demand Period Sliding “ T1” Number of Sub-Intervals in a Demand Period Setting 1 15 1 2
03,06,16 40059 Demand Period Fixed “ T1” Duration of period specified in minutes
(when not Sliding Window) Setting 1 99 1 2
ANALOGUE OUTPUTS
Output 1
03,06,16 40060 Output 1 Parameter “T27” 0 No Parameter Setting 0 15 1 2
1 Frequency
Chapter 5
Volume 2
6 IA
7 IB
8 IC
9 IN
10 VA
11 VB
12 VC
13 VAB
14 VBC
15 VCA
03,06,16 40061 Output 1 Full Scale % “ T2” Setting - - - 2
03,06,16 40062 Output 1 Slope Setting “ T1” 0 Single Slope Setting 0 1 1 2
1 Dual Slope
03,06,16 40063 Output 1 X Breakpoint % “ T2” Setting 0 1000 1 2
03,06,16 40064 Output 1 Y Breakpoint % “ T2” Setting 0 1000 1 2
03,06,16 40065 Output 1 Current Output “T28” 0 0 ...10 mA Uni-directional input Setting 0 5 1 2
1 0 ... 20 mA Uni-directional input
2 4 ... 20 mA Uni-directional input
3 0 ... 10 mA Bi-directional input
4 0 ... 20 mA Bi-directional input
5 4 ... 20 mA Bi-directional input
Chapter 5
Volume 2
Output 2
03,06,16 40066 Output 2 Parameter “T27” see Output 1 Setting 0 15 1 2
03,06,16 40067 Output 2 Full Scale % “ T2” see Output 1 Setting 0 2000 1 2
M301, M302
RELAY OUTPUTS
03,06,16 40084 Relay 1 Assignment “ T1” 0 Disabled Setting 0 9 1 2
1 Setpoint 1
2 Setpoint 2
Chapter 5
Volume 2
3 Setpoint 3
4 Setpoint 4
5 Pulsed Import kWh
M301, M302
03,06,16 40121 Import Watts Pulse Rate “ T1” See notes 5,6 60008.1210.060 for
dependence of Pulse Rate Setting 1 4000 1 2
03,06,16 40122 Import Watts Full Scale “ T2” See notes 5,6 60008.1210.060 for
M301, M302
Export Watts
03,06,16 40123 Export Watts Pulse Duration “ T1” see Import Watts Setting 0 2 1 2
03,06,16 40124 Export Watts Pulse Rate “ T1” see Import Watts Setting 1 4000 1 2
03,06,16 40125 Export Watts Full Scale “ T2” see Import Watts Setting 10 2000 1 2
Import vars
03,06,16 40126 Import vars Pulse Duration “ T1” see Import Watts Setting 0 2 1 2
03,06,16 40127 Import vars Pulse Rate “ T1” see Import Watts Setting 1 4000 1 2
03,06,16 40128 Import vars Full Scale “ T2” see Import Watts Setting 10 2000 1 2
Export vars
03,06,16 40129 Export vars Pulse Duration “ T1” see Import Watts Setting 0 2 1 2
03,06,16 40130 Export vars Pulse Rate “ T1” see Import Watts Setting 1 4000 1 2
03,06,16 40131 Export vars Full Scale “ T2” see Import Watts Setting 10 2000 1 2
OPTO INPUTS
03,06,16 40132 Opto Input 1 Configuration “ T1” 0 Opto Input Disabled Setting 0 6 1 2
1 Demand Synchronisation
2 Energy Synchronisation
3 Energy & Demand Synchronisation
4 Pulse Counter
5 Clock And Calendar Synchronisation
Chapter 5
Volume 2
6 Logic Level
03,06,16 40133 40139 Opto Input 1 Label “T22” Setting 20h 7Eh 1 2
03,06,16 40140 Opto Input 2 Configuration “ T1” See Opto Input 1 Configuration Setting 0 6 1 2
M301, M302
03,06,16 40141 40147 Opto Input 2 Label “T22” Setting 20h 7Eh 1 2
SERVICE MANUAL
SETPOINT SETTINGS
Setpoint 1
03,06,16 40148 Setpoint 1 Delay On/Off “ T1” Setting 1 60 1 2
Element 1
03,06,16 40149 Setpoint 1 First Setpoint
Parameter “T26” 0 No Parameter Setting 0 37 1 2
1 Frequency
2 Total 3 Phase Active Power
3 Total 3 Phase Reactive Power
4 Total 3 Phase Apparent Power
5 Total Power Factor
6 Import Total Watts Demand
7 Export Total Watts Demand
8 Lagging Total Var Demand
9 Leading Total Var Demand
10 Positive Total VA Demand
11 Negative Total VA Demand
12 Total Power Factor Demand
13 IA
14 IB
15 IC
16 IN
Chapter 5
Volume 2
17 IA Demand
18 IB Demand
19 IC Demand
M301, M302
20 IA THD%
SERVICE MANUAL
21 IB THD%
22 IC THD%
23 Inps
24 VA
25 VB
26 VC
27 VAB
28 VBC
29 VCA
30 VA THD%
31 VB THD%
32 VC THD%
33 VAB THD%
34 VBC THD%
35 VCA THD%
36 Vnps
37 dc Input
03,06,16 40150 Setpoint 1 First Hi Setpoint
Level % “ T6” (lower limit of High Set depends on upper limit of Low Set; Setting - - - 2
03,06,16 40151 Setpoint 1 First Lo Setpoint
Level % “ T6” (upper limit of Low Set depends on lower limit of High Set; Setting - - - 2
Chapter 5
Volume 2
Element 2
03,06,16 40152 Setpoint 1 Second Setpoint
Parameter Group “T26” see Setpoint 1 Element 1 Setting 0 37 1 2
M301, M302
03,06,16 40153 Setpoint 1 Second Hi Setpoint (lower limit of High Set depends on
Level % “ T6” upper limit of Low Set; Setting - - - 2
SERVICE MANUAL
03,06,16 40154 Setpoint 1 Second Lo Setpoint (upper limit of Low Set depends on
Level % “ T6” lower limit of High Set; Setting - - - 2
Element 3
03,06,16 40155 Setpoint 1 Third Setpoint
Parameter Group “T26” see Setpoint 1 Element 1 Setting 0 37 1 2
03,06,16 40156 Setpoint 1 Third Hi Setpoint (lower limit of High Set depends on
Level % “ T6” upper limit of Low Set; Setting - - - 2
03,06,16 40157 Setpoint 1 Third Lo Setpoint (lower limit of High Set depends on
Level % “ T6” lower limit of High Set; Setting - - - 2
Element 4
03,06,16 40158 Setpoint 1 Fourth Setpoint
Parameter Group “T26” see Setpoint 1 Element 1 Setting 0 37 1 2
03,06,16 40159 Setpoint 1 Fourth Hi Setpoint (lower limit of High Set depends on
Level % “ T6” upper limit of Low Set; Setting - - - 2
03,06,16 40160 Setpoint 1 Fourth Lo Setpoint (upper limit of Low Set depends on
Level % “ T6” lower limit of High Set; Setting - - - 2
Element 5
03,06,16 40161 Setpoint 1 Fifth Setpoint
Parameter Group “T26” see Setpoint 1 Element 1 Setting 0 37 1 2
03,06,16 40162 Setpoint 1 Fifth Hi Setpoint (lower limit of High Set depends on
Level % “ T6” upper limit of Low Set; Setting - - - 2
03,06,16 40163 Setpoint 1 Fifth Lo Setpoint (upper limit of Low Set depends on
Level % “ T6” lower limit of High Set; Setting - - - 2
Element 6
03,06,16 40164 Setpoint 1 Sixth Setpoint
Parameter Group “T26” see Setpoint 1 Element 1 Setting 0 37 1 2
Chapter 5
Volume 2
Code Address Contents Data Ind Values / Dependencies Reg. Type Min Max Step Passcode
03,06,16 40181 Setpoint 2 Third Hi (lower limit of High Set depends on
Setpoint Level % “ T6” upper limit of Low Set; Setting - - - 2
03,06,16 40182 Setpoint 2 Third Lo (upper limit of Low Set depends on
Setpoint Level % “ T6” lower limit of High Set; Setting - - - 2
Element 4
03,06,16 40183 Setpoint 2 Fourth Setpoint
Parameter Group “T26” see Setpoint 1 Element 1 Setting 0 37 1 2
03,06,16 40184 Setpoint 2 Fourth Hi Setpoint (lower limit of High Set depends on
Level % “ T6” upper limit of Low Set; Setting - - - 2
03,06,16 40185 Setpoint 2 Fourth Lo Setpoint (upper limit of Low Set depends on
Level % “ T6” lower limit of High Set; Setting - - - 2
Element 5
03,06,16 40186 Setpoint 2 Fifth Setpoint
Parameter Group “T26” see Setpoint 1 Element 1 Setting 0 37 1 2
03,06,16 40187 Setpoint 2 Fifth Hi Setpoint (lower limit of High Set depends on
Level % “ T6” upper limit of Low Set; Setting - - - 2
03,06,16 40188 Setpoint 2 Fifth Lo Setpoint (upper limit of Low Set depends on
Level % “ T6” lower limit of High Set; Setting - - - 2
Element 6
Chapter 5
Volume 2
03,06,16 40215 Setpoint 3 Sixth Hi Setpoint (lower limit of High Set depends on
Level % “ T6” upper limit of Low Set; Setting - - - 2
03,06,16 40216 Setpoint 3 Sixth Lo Setpoint (upper limit of Low Set depends on
M301, M302
03,06,16 40228 Setpoint 4 Second Hi Setpoint (lower limit of High Set depends on
Level % “ T6” upper limit of Low Set; Setting - - - 2
03,06,16 40229 Setpoint 4 Second Lo Setpoint (upper limit of Low Set depends on
M301, M302
03,06,16 40241 Setpoint 4 Sixth Lo Setpoint (upper limit of Low Set depends on
Level % “ T6” lower limit of High Set; Setting - - - 2
Element 7
M301, M302
03,06,16 40243 Setpoint 4 Seventh Hi Setpoint (lower limit of High Set depends on
Level % “ T6” upper limit of Low Set; Setting - - - 2
03,06,16 40244 Setpoint 4 Seventh Lo Setpoint (upper limit of Low Set depends on l
Level % “ T6” ower limit of High Set; Setting - - - 2
Element 8
03,06,16 40245 Setpoint 4 Eighth Setpoint
Parameter Group “T26” see Setpoint 1 Element 1 Setting 0 37 1 2
03,06,16 40246 Setpoint 4 Eighth Hi Setpoint (lower limit of High Set depends on
Level % “ T6” upper limit of Low Set; Setting - - - 2
03,06,16 40247 Setpoint 4 Eighth Lo Setpoint (upper limit of Low Set depends on
Level % “ T6” lower limit of High Set; Setting - - - 2
TARIFF STRUCTURE
RATE SWITCHING EVENTS
Rate Switching Event 1
03,06,16 40248 Activation Day “ T1” 0 Inactive switching event Setting 0 7 1 2
1 .. 7 Monday .. Friday
03,06,16 40249 Activation Hour “ T1” Hour of the switching time Setting 0 23 1 2
03,06,16 40250 Activation Minute “ T1” Minutes of the switching time Setting 0 59 1 2
03,06,16 40251 Active Rates “T57” 0 No rate registers are active Setting 0 255 2
Bit-0 Rate register 1 is active
Bit-1 Rate register 2 is active
Bit-2 Rate register 3 is active
Bit-3 Rate register 4 is active
Chapter 5
Volume 2
03,06,16 40570 Select Sample Page “ T1” Waveform analysis or disturbance record
sample page. Setting 0 269 1 0
M301, M302
SERVICE MANUAL
Calibration Settings
06,16 41017 Calibration Command Register “T31” 1 Calibrate Analogue inputs
(Calibration Mode Only) Setting 1 12 Calib Mode
M301, M302
Calibration success
128 Acknowledge Analogue outputs
SERVICE MANUAL
Calibration Failed
256 Acknowledge Base Temperture
Calibration success
512 Acknowledge Base Temperture
Calibration failed
03,06,16 41019 41020 Va Calibration Actual Value “T13” Setting 0 100 0.00001 Calib Mode
03,06,16 41021 41022 Ia Calibration Actual Value “T13” Setting 0 100 0.00001 Calib Mode
03,06,16 41023 41024 Vb Calibration Actual Value “T13” Setting 0 100 0.00001 Calib Mode
03,06,16 41025 41026 Ib Calibration Actual Value “T13” Setting 0 100 0.00001 Calib Mode
03,06,16 41027 41028 Vc Calibration Actual Value “T13” Setting 0 100 0.00001 Calib Mode
03,06,16 41029 41030 Ic Calibration Actual Value “T13” Setting 0 100 0.00001 Calib Mode
03,06,16 41031 41032 Analogue Output 1
Actual Value “T13” Setting 0 100 0.00001 Calib Mode
03,06,16 41033 41034 Analogue Output 2
Actual Value “T13” Setting 0 100 0.00001 Calib Mode
03,06,16 41035 41036 Analogue Output 3
Actual Value “T13” Setting 0 100 0.00001 Calib Mode
03,06,16 41037 41038 Analogue Output 4
Actual Value “T13” Setting 0 100 0.00001 Calib Mode
Please complete this form and return it to ALSTOM T&D Protection & Control Limited with the
equipment to be repaired. This form may also be used in the case of application queries.
continued overleaf
✁
6. What did happen?
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
______________________________________ _______________________________________
Signature Title
______________________________________ _______________________________________
Name (in capitals) Company name
✁
A L S T O M T & D P r o t e c t i o n & C o n t r o l L t d St Leonards Works, Stafford, ST17 4LX England
Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: pcs.enquiries@tde.alstom.com Internet: www.alstom.com