Cutler-Hammer: 1 Moulded Case Circuit Breakers 15-800 Amperes For IEC-947-2 and NEMA Applications
Cutler-Hammer: 1 Moulded Case Circuit Breakers 15-800 Amperes For IEC-947-2 and NEMA Applications
Cutler-Hammer Back
Moulded Case Circuit Breakers 15-800 Amperes 1
July 1998 for IEC-947-2 and NEMA Applications
DS 29-170i AD 29-167i Universal Frame Sizes Gi through Li
Universal Moulded Case For NEMA and IEC Trip Units and Terminals
Standard Voltage Systems Universal Breakers are provided
Circuit Breakers… with factory sealed thermal-
These breakers have been desig-
When Higher nated Universal because they can be magnetic trip units.
Interrupting Ratings applied to both NEMA and IEC stand-
The Gi-Frame Breaker (15-125
Are Not Required ard voltage systems: 277/480 volts
amperes) includes line and load ter-
AC, 220/380 volts AC, and 240/415
Gi-, Fi, Ji-, Ki-, Li-Frames minals with breaker mounting hard-
volts AC at 60 or 50 Hz.
15-800 Amperes ware. Frames Fi (15-225 amperes),
IEC 947-2 440 Volts AC Cutler-Hammer Universal Breakers Ji (250 amperes), Ki (300-400
NEMA 480 Volts AC are rated from 15 through 800 amperes), and Li (500-630 amperes)
amperes and are available in five include line and load end caps with
Cutler-Hammer Universal Moulded
frame sizes. Each frame size has the termination hardware installed. The
Case Circuit Breakers, in one-, two-,
same compact outside dimensions Li-Frame (700-800 amperes) is fitted
and three-pole configurations, are
as Series C Breakers. with both line and load bus bar
designed to provide an economical
extensions that utilize standard
alternative for applications that do Additionally, Universal Breakers are hardware. A full complement of
not require the higher interrupting suitable for 50°C applications and terminals is available to customize
ratings and internal accessories have been rigorously tested to the Universal Breakers as required.
provided by Series CT Breakers. IEC 947-2 standard and are assem-
bled in an ISO certified facility. External Accessories
As with other members of the Cutler-
Hammer family of moulded case Universal Breakers use the same
circuit breakers, Universal Breakers external accessories as Series C
provide high quality, reliability, Breakers: handle mechanisms,
unmatched performance, and out- motor operators, lock-off devices,
standing value. bus bar extensions, and multiple
terminal arrangements.
PG.29.02.T.U
UK PG.29.02.T.U A4 Page 2 Friday, March 12, 1999 3:41 PM
Electrical Characteristics
Frames Gi125 Fi100, Fi160, Fi225 Ji250
Cutler-Hammer
Universal
Moulded Case
Circuit Breakers
Electrical Characteristics
Frame (690V) / Maximum Rated Amperes Gi125 Fi100 Fi160 Fi225 Ji250
Interrupting Rating
IEC 220-240 VAC Icu/Ics 18/5 25/7 25/13 35/18 35/18 35/18
947-2
380-415 VAC Icu/Ics – 18/5 18/9 25/13 25/13 25/13
440 VAC Icu/Ics – – 14/7 20/10 20/10 20/10
NEMA 240 VAC 18 25 25 25 25 35
277/480 VAC 14 14 14 14 14 20
Number of Poles 1 2, 3 2, 3 2, 3 2, 3 3
Continuous Ampere Rating 15, 20, 30, 40, 60, 15, 20, 30, 125, 150, 175, 200, 250
(40°C) 70, 80, 100, 125 40, 60, 70, 160 225
80, 100
Dimensions H W D H W D H W D
PG.29.02.T.U
UK PG.29.02.T.U A4 Page 3 Friday, March 12, 1999 3:41 PM
Cutler-Hammer Back
Moulded Case Circuit Breakers 15-800 Amperes 3
July 1998 for IEC-947-2 and NEMA Applications
Universal Frame Sizes Ki through Li
Electrical Characteristics
Frames Ki400 Li630 Li800
Cutler-Hammer
Universal
Moulded Case
Circuit Breakers
Electrical Characteristics
Frame (690V) / Maximum Rated Amperes Ki400 Li630 Li800
Interrupting Rating
Dimensions H W D H W D H W D
PG.29.02.T.U
UK PG.29.02.T.U A4 Page 4 Friday, March 12, 1999 3:41 PM
➀ Package of 3 terminals.
➁ Base mounting hardware, applicable to both NEMA and IEC applica-
tions, is included with Gi-Frame Breakers. A separate catalogue number
is not required.
PG.29.02.T.U
UK PG.29.02.T.U A4 Page 5 Friday, March 12, 1999 3:41 PM
Cutler-Hammer Back
Moulded Case Circuit Breakers 15-800 Amperes 5
July 1998 for IEC-947-2 and NEMA Applications
Universal Frame Sizes Gi through Li
Dimensions, mm (inches)
Gi
Front Cover Cutout Front View 3-Pole Side View
Fi
Front Cover Cutout Front View 3-Pole Side View
CL
Breaker
6.35 (.25) R
33.65
(1.32) 73.81 101.60
(2.90) 152.40
CL (4.00) (6.00)
Handle
Ji
Front Cover Cutout Front View 3-Pole Side View
CL
Breaker 39.67 (1.56)
Ki
Front Cover Cutout Front View 3-Pole Side View
CL
Breaker
8.74 (.344) R 151.55
(5.96)
95.25
(3.75) 21.03 (.82) 257.17
CL (10.12)
Handle
31.75 (1.25) 41.66 (1.64)
4.77 (.18) R
33.35 (1.31)
66.67 (2.62) 139.45 109.55
60.73 (4.31)
(2.39) 121.46 (5.49)
(4.78)
43.66 (1.71)
87.32
63.50 (2.50) R (3.43) 142.60
(5.61)
33.65
83.34 (1.32) 273.10 406.40
4.77 (3.28) CL (10.75) (16.00)
(.18) R 58.22 Handle
(2.29)
38.10
(1.50)
92.48
(3.64)
184.94
(7.28)
10.00
139.70 44.50 (.39)
(5.50) (1.75)
All dimensions are provided for guidance and should not be used for construction purposes unless approved.
Contact Cutler-Hammer for detailed outline drawings.
PG.29.02.T.U
UK PG.29.02.T.U A4 Page 6 Friday, March 12, 1999 3:41 PM
30 Electromagnetic
TIME IN SECONDS
30
20 Electromagnetic 20
Release Release
10 10
5 Total
Total 5
3 3
Clearing
2 Clearing Time
2
Time
1 1
.5 .5
.3 .3
.2 .2
.1 .1 Interrupting
Interrupting Rating
.05 .05
Rating determines
.03 .03
.02 determines end of curve
.02
end of curve
.01 .01
.005 .005
.003 .003
.002 .002
.001 .001
10 0 2 4 6 8 10 1 2 4 6 8 10 2 2 4 6 8 10 3 100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103
Type Fi160 Molded Case Circuit Breakers Type Fi225 Molded Case Circuit Breakers
Thermal Magnetic Trip, Fixed Thermal-Fixed Magnetic Thermal Magnetic Trip, Fixed Thermal-Fixed Magnetic
Maximum Volts AC: 440 at 50/60 Hz Maximum Volts DC: 250 Poles: 2 and 3 Maximum Volts AC: 440 at 50/60 Hz Maximum Volts DC: 250 Poles: 2 and 3
NEMA Interrupting Ratings 14 kA @ 480 Volts AC NEMA Interrupting Ratings 14 kA @ 480 Volts AC
Breaker Rating Interrupting Ratings (IEC 947-2) Breaker Rating Interrupting Ratings (IEC 947-2)
Continuous Instantaneous RMS Symmetrical Amperes (kA) Continuous Instantaneous RMS Symmetrical Amperes (kA)
Amperes Trip Amperes Volts Icu Ics Amperes Trip Amperes Volts Icu Ics
125, 150, 160 8 x ln 220-240 AC 25 13 175, 200, 225 10 x ln 220-240 AC 25 13
380-415 AC 18 9 380-415 AC 18 9
440 AC 14 7 440 AC 14 7
250 DC 10 5 250 DC 10 5
10000 10000
5000 5000
3000 Fixed Inverse-Time 3000 Fixed Inverse-Time
2000 2000
Overcurrent Release Overcurrent Release
1000 1000
500 500
300 300
200 200
100 100 Fixed
50 50 Electromagnetic
Fixed Release
TIME IN SECONDS
30 30
TIME IN SECONDS
20
Electromagnetic 20
Release
10 10
Total 5
Total
5
3 Clearing 3 Clearing
2 Time 2 Time
1 1
.5 .5
.3 .3
.2 .2
.1 Interrupting .1
.05 Rating .05
determines Interrupting
.03 .03 Rating
.02 end of curve .02
determines
.01 .01 end of curve
.005 .005
.003 .003
.002 .002
.001 .001
100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103 100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103
PG.29.02.T.U
UK PG.29.02.T.U A4 Page 7 Friday, March 12, 1999 3:41 PM
Cutler-Hammer Back
Moulded Case Circuit Breakers 15-800 Amperes 7
July 1998 for IEC-947-2 and NEMA Applications
Universal Frame Sizes Ji through Li
30
TIME IN SECONDS
30
20 20
10 10
5 Total 5 Total
3 Clearing 3
2 2
Clearing
Time Time
1 1
.5 .5
.3 .3
.2 .2
.1 .1
.05 Interrupting Interrupting
.05
.03 Rating Rating
.03
.02 determines .02 determines
end of curve end of curve
.01 .01
.005 .005
.003 .003
.002 .002
.001 .001
100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103 100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103
Type Li630 Molded Case Circuit Breakers Type Li800 Molded Case Circuit Breakers
Thermal Magnetic Trip, Fixed Thermal-Adjustable Magnetic Thermal Magnetic Trip, Fixed Thermal-Adjustable Magnetic
Maximum Volts AC: 440 at 50/60 Hz Maximum Volts DC: 250 Poles: 3 Maximum Volts AC: 440 at 50/60 Hz Maximum Volts DC: 250 Poles: 3
NEMA Interrupting Ratings 20 kA @ 480 Volts AC NEMA Interrupting Ratings 30 kA @ 480 Volts AC
Breaker Rating Interrupting Ratings (IEC 947-2) Breaker Rating Interrupting Ratings (IEC 947-2)
Continuous Instantaneous RMS Symmetrical Amperes (kA) Continuous Instantaneous RMS Symmetrical Amperes (kA)
Amperes Trip Amperes Volts Icu Ics Amperes Trip Amperes Volts Icu Ics
500 2500-5000 220-240 AC 35 18 700 2800-5400 220-240 AC 42 21
630 3000-6000 380-415 AC 25 13 800 3200-6400 380-415 AC 35 18
440 AC 20 10 440 AC 30 15
250 DC 10 5 250 DC 10 5
10000 10000
5000 5000 Fixed Inverse-Time
3000 3000 Overcurrent Release
2000 Fixed Inverse-Time
2000
Overcurrent Release
1000 1000
500 Adjustable 500 Adjustable
300 Electromagnetic 300 Electromagnetic
200 Release 200 Release
100 100
50 50
30
TIME IN SECONDS
TIME IN SECONDS
30
20 20
10 10
5 Total 5 Total
3 Clearing 3 Clearing
2 Time 2 Time
1 1
.5 .5
.3 .3
.2 .2
.1 Interrupting .1 Interrupting
.05 Rating .05 Rating
.03 determines .03 determines
.02 end of curve .02 end of curve
.01 .01
.005 .005
.003 .003
.002 .002
.001 .001
100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103 100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103
PG.29.02.T.U
UK PG.29.02.T.U A4 Page 8 Friday, March 12, 1999 3:41 PM
DS 29-170i AD 29-167i
Typical Specifications
for UniversalE Moulded
Case Circuit Breakers
Electrical circuits shall be protected by Moulded Case Circuit breakers shall be completely enclosed in a high
Circuit Breakers as manufactured by Cutler-Hammer. strength glass-polyester case.
Each pole of the one-, two-, and three-pole circuit break- The minimum interrupting ratings of the circuit breakers
ers shall provide complete circuit overcurrrent protection shall be at least equal to the available short circuit cur-
by having inverse time and instantaneous tripping char- rent at the line terminals. The circuit breakers can be
acteristics and, where applicable, be current limiting. applied in series rated applications and subject to test
data verification.
The circuit breakers shall be operated by a toggle-type
handle and have a quick-make, quick-break, over-centre Circuit breakers in frame sizes 100 amperes through
switching mechanism that is mechanically trip-free from 800 amperes shall be equipped with thermal-magnetic
the handle so that the contacts cannot be closed against trip units.
short circuit currents. Tripping due to overload or short
circuits shall be clearly indicated by the position of the Circuit breakers in the 125 ampere frame size shall be
handle. The ON and OFF positions shall be clearly supplied in one-, two-, and three-pole models, as speci-
marked on the cover of the circuit breaker (F-Frame and fied on the drawings. Circuit breakers in ratings of 225
larger) along with the international symbols I for ON and ampere frame size shall be supplied in two-, or three-
O for OFF on the handle, providing positive indication poles as specified on the drawings. The 250 amperes
of the circuit breaker contact position. Additionally, through 800 amperes frame sizes shall be supplied as
a colour-coded indication of the circuit breaker contact three-pole models only as specified on the drawings.
position shall be provided for the F-Frame and have red
for ON, green for OFF, and white for TRIPPED. An easily Electrical operators for circuit breakers of the 400 am-
accessible Push-To-Trip button for mechanically exercis- pere frame size and below shall be of the solenoid type
ing the trip unit shall be provided on the cover of each with maximum five cycle closing characteristics. Electri-
circuit breaker (F-Frame and larger). All poles of a multi- cal operators for circuit breaker frame sizes 630 amperes
pole circuit breaker shall be so constructed as to ensure through 800 amperes shall be of the motor driven type.
simultaneous open, close, and trip operations. All electrical operators shall be cover mounted.
Moulded case circuit breakers shall be of the inverse Circuit breakers shall be provided with uniformly
time and instantaneous trip type as provided by thermal designed nameplates to clearly indicate the type, rating,
magnetic trip elements. listing/recognition/certification marks, accessory details,
and other information defined in IEC 947-2.
Noninterchangeable trip circuit breakers shall be factory
sealed to prevent tampering. Ampere ratings shall be
clearly visible from the front of the circuit breaker. Con-
tacts shall be nonwelding silver alloy. Arc extinction
shall be accomplished by means of DE-ION® arc
extinguishers, consisting of metal grids mounted in
an insulating support.
PG.29.02.T.U