Kitchen Kitchen
S2
Guard House
S1
Entry Entry
Unit 1
S2
Dining Dining
S1
1
Closet
Bedroom
Closet
2
Bedroom
S1
S1
Unit 2 Bathroom
Bathroom 4
ACU
LIGHTING LAYOUT FOR UNIT 1,2,3 & 4 POWER LAYOUT FOR UNIT 1,2,3 & 4
Unit 3
Entry
Entry
S2
1
S1
S1
Kitchen Kitchen
Dining Dining
3
S2 R
S1 Closet
4
1
Bedroom Living Bedroom Living
2
S2
Power 3
House WP LIGHTING LAYOUT FOR UNIT 5, 6, & 7 POWER LAYOUT FOR UNIT 5, 6, & 7
Schedule of Loads for Outside Branch Circuit 8. ALL WORKS HEREIN WAS UNDER THE DIRECT SUPERVISION OF
THE DULY LICENSED ELECTRICAL ENGINEER.
RATING PROTECTION
CKT NO. LOAD DESCRIPTION QUANTITY CURRENT CONDUCTOR CONDUIT
PHASE VOLTS WATTS POLE FRAME TRIP
1
2
Lighting outlet
Convenience outlet
13
4
1
1
230
230
1300
720
5.65
3.13
2
2
100
100
15
20
2-2.0 mm sq. THHN 20 mm Ø uPVC
2-2.5 mm sq. THHN 20 mm Ø uPVC
LEGEND
3 Water Pump 1 1 230 2237 9.73 2 100 30 2-3.5 mm sq. THHN 20 mm Ø uPVC 2 GANG CONVENIENCE OUTLET
4 Spare 20 PANEL BOARD
TOTAL 230 4257 18.51
ACU OUTLET
Total Connected Load = 18.51 A
Total Computed Load at 80% Demand Factor LED BULB
100 AT
It = (D.F. × Total Connected Loads) + (0.25 × HRM)
It = (0.8 × 18.51 A) + (0.25 × 9.73) s SWITCH
It = 17.2405 A 60 AT 15 AT
Service Entrance Conductor: Use 2-8.0 mm. sq. THHN Copper Wire on a 20 mm. dia. PVC Conduit Pipe
1
20 AT 30 AT
SERVICE ENTRANCE
2 3
30 AT 20 AT
4 5
Protection: Use 60 AT / 100 AF, 230, 2P, MCB Bolt on Type with 7 branch circuit
SUB FEEDER Typical Layout
Service Entrance Conductor: Use 2-6.0 mm. sq. THHN Copper Wire on a 50 mm. dia. PVC Conduit Pipe
Unit 4
POWER LINE
Protection: Use 100 AT / 100 AF, 230, 2P, MCB Bolt on Type with 7 branch circuit Typical Layout
Unit 5 CIRCUIT HOMERUN
Typical Layout
60 AT 15 AT
Unit 6 R
RANGE OUTLET
1
20 AT 30 AT
2 3
Typical Layout
Unit 7
WP
WEATHERPROOF OUTLET