Kitchen

3
Kitchen
s1

Living

Living
s1 2

s1
s3

Entry

Entry
s2

Dining

Dining
Guard House

s2
Unit 1 1
2

Bedroom

Bedroom
s1

s1
Unit 2 4
ACU

LIGHTING LAYOUT FOR UNIT 1,2,3 & 4 POWER LAYOUT FOR UNIT 1,2,3 & 4

Unit 3

Entry Entry
s2
Unit 4

s1
s1 Kitchen Kitchen

3
2
Dining Dining R

s1

s2
Unit 7 Unit 6 Unit 5 s2 s1 2
1

4
Bedroom Living Bedroom Living
Power

ACU
House
LIGHTING LAYOUT FOR UNIT 5, 6, & 7 POWER LAYOUT FOR UNIT 5, 6, & 7

SUBMITTED BY: SUBMITTED TO: SHEET CONTENT: DRAWING NO:


HOUSE PLAN LIGHTING
ACTIVITY NO. 4 ANIEKEN Q. AYO ENGR. VINYL OQUINO
ELECTRICAL ENGINEER AND
POWER LAYOUT
E-1
BSEE - 4A
GENERAL NOTES
1. ALL ELECTRICAL WORKS HEREIN INCLUDED WERE EXECUTED
Schedule of Loads for Unit 1 to 7
ACCORDING TO THE REQUIREMENTS OF THE FOLLOWING
RATING PROTECTION
A. PHILIPPINE ELECTRICAL CODE (PEC-1-2009) CKT NO. LOAD DESCRIPTION QUANTITY CURRENT CONDUCTOR CONDUIT
B. RULES AND REGULATION OF THE MUNICIPALITY PHASE VOLTS WATTS POLE FRAME TRIP
C. LEYTE ELECTRIC COOPERATIVE
1 Lighting outlet 7 1 230 700 3.04 2 100 15 2-2.0 mm sq. THHN 20 mm Ø uPVC
2. COORDINATED TO OTHER TRADE AND SPECIALTY WORK 2 Convenience outlet 6 1 230 1080 6.26 2 100 20 2-2.5 mm sq. THHN 20 mm Ø uPVC
CONTRACTORS FOR UP TO DATE REQUIREMENTS ON 2 2-2.5 mm sq. THHN 20 mm Ø uPVC
RELATED ELECTRICAL WORKS HEREIN EXECUTED.
3 Convenience outlet 6 1 230 1080 6.26 100 20
4 ACU 1 1 230 1398.75 6.08 2 100 30 2-5.5 mm sq. THHN 20 mm Ø uPVC
3. ALL METAL FRAMES OF EQUIPMENT WERE GROUNDED BY 5 Spare 20
CONNECTING TO GROUNDING CONDUCTORS
TOTAL 230 4258.75 18.52
4. SERVICE ENTRANCE AND BRANCH CIRCUIT ARE INSTALLED AS
INDICATED ON PLANS, INDIVIDUAL BRANCH CIRCUIT Total Connected Load = 18.52 A
HOMERUNS WERE NOT BE COMBINED IN THE SAME RACEWAY Total Computed Load at 80% Demand Factor
It = (D.F. × Total Connected Loads) + (0.25 × HRM)
5. MINIMUM SIZE OF WIRE WAS 2.0 mm2 THHN FOR LIGHTING It = (0.8 × 18.52) + (0.25 × 4.87)
AND 3.5 mm FOR CONVENIENCE OUTLET AND POWER. It = 16.0335 A
Service Entrance Conductor: Use 2-8.0 mm. sq. THHN Copper Wire on a 20 mm. dia. PVC Conduit Pipe
6. ALL WIRING FOR LIGHTING POWER AND CONVENIENCE OUTLET Protection: Use 60 AT / 100 AF, 230, 2P, MCB Bolt on Type with 7 branch circuit
WERE POLYVINYLCHLORIDE CONDUIT PVC
For total Current for 7 dwelling units:
7. MOUNTING HEIGHT OF DEVICES ARE AS FOLLOWS:
It = (Total Current at 80% *7) × 44%
A. SWITCHES = 1400 mm ABOVE FLOOR FINISHED
B. CONVENIENCE OUTLET = 300 mm ABOVE FLOOR FINISHED
It= (16.0335 A *7) × 44%
C. CEILING FAN OUTLET = 3000 mm ABOVE FLOOR FINISHED It= 49.38 A

8. ALL WORKS HEREIN WAS UNDER THE DIRECT SUPERVISION OF


THE DULY LICENSED ELECTRICAL ENGINEER.

Schedule of Loads for Outside Branch Circuit


RATING PROTECTION
CKT NO. LOAD DESCRIPTION QUANTITY CURRENT CONDUCTOR CONDUIT
PHASE VOLTS WATTS POLE FRAME TRIP
1 Lighting outlet 14 1 230 1400 6.08 2 100 15 2-2.0 mm sq. THHN 20 mm Ø uPVC

100 AT
2 Convenience outlet 8 1 230 1440 6.21 2 100 20 2-2.5 mm sq. THHN 20 mm Ø uPVC

3 Spare 20

60 AT 15 AT
20 AT 20 AT
1
TOTAL 230 2840 12.29
2 3
30 AT 20 AT
4 5

SUB FEEDER Typical Layout


Total Connected Load = 12.29 A
2-6.0 mm. sq. Unit 2 Total Computed Load at 80% Demand Factor
THHN Copper It = (D.F. × Total Connected Loads) + (0.25 × HRM)
Wire M M M M M M M M Typical Layout It = (0.8 × 12.29 A) + (0.25 × 9.73)
Unit 3
It = 12.2645 A
Service Entrance Conductor: Use 2-10.0 mm. sq. THHN Copper Wire on a 20 mm. dia. PVC Conduit Pipe
Typical Layout
Unit 4 Protection: Use 30 AT / 100 AF, 230, 2P, MCB Bolt on Type with 7 branch circuit

For main feeder:


Typical Layout
Unit 5 It= (It for 7 dwelling units) + (It for outside circuit)
It= 49.38 + 12.2645
It= 61.6445 A
Service Entrance Conductor: Use 2-6.0 mm. sq. THHN Copper Wire on a 50 mm. dia. PVC Conduit Pipe
Typical Layout
Unit 6
Protection: Use 100 AT / 100 AF, 230, 2P, MCB Bolt on Type with 7 branch circuit
30 AT 15 AT
1
20 AT 20 AT
2 3

Typical Layout
Unit 7

SUBMITTED BY: SUBMITTED TO: SHEET CONTENT: DRAWING NO:


HOUSE PLAN LIGHTING
ACTIVITY NO. 4 ANIEKEN Q. AYO ENGR. VINYL OQUINO
ELECTRICAL ENGINEER AND
POWER LAYOUT
E-2
BSEE - 4A