Installation Guide
Models Include:
• ACM8 • ACM8E
- Fused Outputs - Fused Outputs
• ACM8CBE • ACM8CB
- PTC Outputs - PTC Outputs
Rev. 092503
Overview:
These units convert one (1) 12 to 24 volt AC or DC input into eight (8) independently controlled fused or PTC protected
outputs. These power outputs can be converted to dry form “C” contacts (ACM8 & ACM8E only). Outputs are activated
by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad,
Push Button, PIR, etc. The units will route power to a variety of access control hardware devices including Mag Locks,
Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. Units are
designed to be powered by one common power source which will provide power for both the board operation and locking
devices, or two (2) totally independent power sources, one (1) providing power for board operation and the other for lock
/ accessory power. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other aux-
iliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.
be d
ng
cy ted
gs
m an
s d
Ag r Li ted
PT ts ted
rs
ut te
tin
sti
en mi
Nu gs
tp tec
we Ra
tp tec
Li
re
Ra
le in
su
Ou Pro
Ou Pro
Fi List
Po s 2
ut
u
clo
Altronix
tp
as
C
se
UL
En
Ou
Cl
Model Number
Fu
-3-
Jumper J3 must be cut (Fig. 3, pg. 6).
6. FACP Dry form “C” output (Fig. 1A, pg. 4):
Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NO] and [C]
FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output.
NO C NC
NC
FACP
+ INP --- T + RET -
J3
INTERFACE
IN GND IN GND IN GND IN GND IN GND IN GND IN GND IN GND TRG
1 2 3 4 5 6 7 8
F1 F2 F3 F4 F5 F6 F7 F8
NO C NC
FACP
SW1-SW8
SW5
3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V
SW2
SW3
SW4
SW6
SW7
SW8
MAIN
10A 250V
FACP Interface Disabled
LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8
MAG. J2
Power Control
--- + --- +
J1
LOCK
UL Listed AC or DC AC or DC
POWER SUPPLY POWER POWER
For this application SUPPLY SUPPLY
ELECTRIC (optional) (req'd.)
STRIKE corresponding
fuse F8 must be
removed. MAG.
LOCK
ELECTROMAGNETIC
DOOR HOLDERS
ACM8/ACM8E ACM8CB/ACM8CBE
F1 F2 F1 F2
SW2
SW1
SW2
-4-
LED Diagnostics:
ACM8 & ACM8CB Access Power Controller
LED ON OFF
LED 1- LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized.
Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition).
-5-
Hook-up Diagrams:
Fig. 2 Optional hook-up using two (2) isolated Fig. 3 Polarity reversal input from FACP signaling circuit
power supply inputs: output (polarity is referenced in alarm condition):
CUT JUMPERS CUT
J1 AND J2 JUMPER J3
J3
FACP
OUTPUT EOL
J2
INTERFACE
ISOLATED POWER INPUT
J1 12 OR 24 VAC OR VDC TRG
(ACM8 POWER)
-- FROM FACP
ISOLATED POWER INPUT + OUTPUT
CIRCUIT
12 OR 24 VAC OR VDC
(LOCK POWER)
NO C NC
FACP
Fig. 4 Normally Open - Non-Latching FACP Fig. 5 Normally Open FACP Latching trigger input
trigger input: with reset:
(This output has not been evaluated by UL)
J3 J3
INTERFACE
TRG TRG
NC
JUMPER
FACP
NO C
Fig. 6 Normally Closed - Non-Latching FACP Fig. 7 Normally Closed - Latching FACP trigger input
trigger input: with reset:
(This output has not been evaluated by UL)
J3 J3
INTERFACE
N.C. RESET
TRG TRG SWITCH
N.C. DRY
TRIGGER
INPUT
N.C. TRIGGER
JUMPER JUMPER INPUT
NO C NC
FACP
-6-
Enclosure Dimensions (ACM8E/ACM8CBE):
15.5”H x 12”W x 4.5”D
1.285
1.285
-7-
Notes: