i JINDAL POWER LIMITED, TAMINAR RAIGARH
meg | 4X 600 MW POWER PLANT
‘SOP FOR FD FAN
STANDARED OPERATION PROCEDURE.
FOR
FD FAN
[JPL/600/SOP/22]
|
|
Issue Date: | 01.04.15 Revision No: 00 | Date: 01.04.15 NoofPages | 05
Prepared by: Lokpal Patel | Reviewed by: Naushag Hassan | Approved by: RK Choudhary, |
Signature: (unr Signature: ier ® Signature:
Designation: Dy. Manager Designation: Asst“General Manager | Designation: General Manager
OC
JPL 4x600 MW SOP Page 1A JINDAL POWER LIMITED, TAMNAR RAIGARH
Jing 4X 600 MW POWER PLANT
ie fi ‘SOP FOR FD FAN in
‘Amendment Record
‘Amendment ‘Amendment Description ‘Acknowledge
Rev No, | Page No. Date by Reviewer
JPL4X600 MW SOP
Page 2JINDAL POWER LIMITED, TAMINAR RAIGARH
| 4X 600 MW POWER PLANT
‘SOP FOR FD FAN
PURPOSE: This procedure is used as work instruction for starting/stopping FD Fan.
‘SCOPE: This procedure is applicable to FD Fan located in JPL 4X600 MW.
RESPONSIBILITY: Boiler Operator, Desk Engineer and Shift In charge.
SPECIFICATION:
GENERAL
Type FAF 24.5 /11.8-1
No, OFF / BOILER 2
Medium Atmospheric Air
Location Outdoor
FAN DESIGN RATING
Capacity (m°/s) 260
Total Head developed (mmwe) 410
Temp of medium (°C) 50
Density (ke/m?) 1.033
Speed (rpm) 390
FAN RESERVE
Flow (%) 50.3
Pressure (96) 723
FAN DRIVE COUPLING .
Type SPACER
DRIVE MOTOR
Make BHEL BHOPAL
Type 11A7802-6P
Rating (kW) 1425
Speed (rpm) 990
Volts (V) 3300
LUBRICATION OF EQUIPMENT
Fan 25 LPM / 35 BAR FOLS (OIL. ISO - VG68)
Motor GREASE LUBRICATED (SERVOGEM3)
Lubrication off Servo prime 68
Oil quantity required 315 litre
TYPE OF FAN REGULATION Blade Pitch Control
BEARINGS
Fixed bearing 7236
Free bearing NU 236 C3,
LUBE OIL SYSTEM
General
Oil type 1S0-V6-68
Required Flow 25 LPM @ 35 Barg
Oil Cooler In / Outlet temperature 60/45 °C
Heat exchanged capacity 3250 Keal/h
Filter mesh rating / Material 25 microns / SS 304
Suction strainer mesh rating / 149 microns / Stainless Stee!
JPL 4X60 MW SOP Page 34)
5)
9)
1)
2)
3)
] JINDAL POWER LIMITED, TAMAR RAIGARH
rT a 4X 600 MW POWER PLANT
[ere | SOP FOR FD FAN
Utilities
Motor type & Rating TEFC & 3.7 kW, 1440 rpm, 415 V, 50 Hz, 3 Phase, [P55
Materials of Construction
Tank capacity / Material 350 liters / IS 2062
Pipe / Fittings Material A106 Gr. B
PROCEDURE: :
LINE UP PROCEDURE:
1) No PTWis pending
2) All manholes in secondary air duct are closed.
3) Ensure FD Fan breaker is normalized and is in Remote condition,
DMCW (SG) pump is in service.
Line-up cooling water to Lube oil cooler ( DMCW Supply, return valves are open )
6) Fan Outlet gate is closed.
7) Lube oil level is normal.
8) All instruments are lined up.
Ensure Air heater is lined up.
10) Ensure APH & 1D Fan is running.
11) Motor protection relay is healthy.
12) Ensure EPB is released.
13) Both lube oil pumps modules are ON and inremote. *
14) Fan discharge damper module is ON and in remote.
‘START UP:
Start lube oll pump. Ensure lube oil pressure is normal (>4 kg/cm’) and control oil pressure normal
(>10 kg/cm’).
Keep the Blade pitch is in minimum position.
Ensure all FD fans start permissive are healthy,
4) Start the FD fan and Ensure lischarge gate is full open in Auto.
5) Ensure furnace pressure is within the permissible range.
6) Ensure bearing vibrations and bearing temp are within the permissible range.
SHUTDOWN:
1) Reduce the unit load less than 50% if first FD fan is stopping.
2) Unload the fan by reducing the blade pitch to min.
3) Stop the fan. x
4) Close discharge gate.
ISOLATION PROCEDURE:
1) Ensure fan is OFF.
| 2) Isolate DC supply and rack out the break
JPL4X600 MW SOP
Page 4| JINDAL POWER LIMITED, TAMNAR RAIGARH
smog 4X 600 MW POWER PLANT
‘SOP FOR FD FAN
3) Isolate discharge gate module.
4) Isolate Lube oil pumps (A, B) modules. (After lube oil system was stopped.)
|CROSS REFERENCE: FD Fan Manual
RECORDS: The records are maintained in field Engineer log book and in CCR log book.
—————_—_
JPL 4X60 MW SOP Page 5