Size of M.

S Plate (Spreader
2
C.Compressive strength of 100 mm existing Brick wall = 2.9 N/mm
Partial safety factor of material = 3
* Enter your value in blue cell only.
Allowable stress under bearing plate for masonary= 2.9 / 3 = 0.97 N/mm 2
Maximum Factored S.Force (KN) 129.40 Remarks
Assume length of Plate (LP) (mm) 1,350.00
Assume width of Plate (mm) 100.00
2
Area pf Plate (mm ) 135,000.00
1 Stiff bearing length (mm)
SBL= tw+1.6r+2tf 45.52 203x203 U.C
2 Bearing plate projection (mm)
BPP = (LP-SBL)x 0.5 652.24
2
3 Factor Stress under plate (N/mm )
FSUP = (Maximum Factor S.Fx1000)/AP 0.96 should < 0.97
4 Minimum thickness of plate (mm)
2
t=Sq root (6 x FSUP x (BPP) x 0.5/275 ) 66.70
Assume thickness of plate 70
2
5 Factor Bending stress on plate (N/mm )
2
FBSOP = 6 X SOP x BPPxBPP x 0.5)/(t ) 249.66 < 275