You are on page 1of 26

EE3420E – Power Supply Systems - Printed 2021

Chapter 7

EE3420E - Power Supply Systems

Chapter 7.
Equipment sizing

Assoc. Prof. Bach Quoc Khanh, Ph.D


Electric Power Systems dept.
Hanoi University of Science and Technology

Content

1. Generality
2. Conductor sizing
3. Dimensioning of bar conductors
4. Switching device selection
5. Instrument transformer selection

Bach Quoc Khanh/EPS dept./HUST 1


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

1. Generality
1.1. Criteria for steady-state operation
 Steady state operation (permanent): Full load current is checked. Operational
equipment’s utilization factor should be less than or equal to unit.

 Criteria:
‒ Rated voltage (insulation):
‒ Rated current (normal ratings):

 Considerations: Ambient temperature, installation.

1. Generality
1.2. Criteria for short-time operation
 Overloading:
‒ Loads in excess of normal rating. Overload operation for safety reasons or
overload for reliability requirement.
‒ Overloading capacity (permissible loading, Kol = overload current/rated current)
is a function of the overloading duration and depends on cooling conditions.
‒ In design stage, the overloading duration is assumed (for reliability
requirement) to be the mean-time to repair (MTTR).
In USSR, for transformers, Kol = 1.4 (outdoor); 1.3 (indoor) as overloading duration is less
than 5 days, 6 hours per day, initial utilization factor is less 0.93.

‒ Considerations on the co-ordination with overload protection.

Bach Quoc Khanh/EPS dept./HUST 2


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

1. Generality
1.2. Criteria for short-time operation
 Short-circuits:
‒ Requirement for equipment stability against mechanical and thermal
stresses have to be satisfied.
‒ Criteria:
• Thermal short circuit withstand capacity (Ithz):

• Mechanical short circuit withstand capacity (Im):


Ith: Thermal equivalent short-circuit current
t k: Short-circuit duration
tthz: Rated short-circuit duration
iP: Peak short-circuit current

1. Generality
1.3. Economic optimization
 Cost function (C):
‒ Capital cost (CP).
Total Cost

‒ O&M cost (COM):


C = CP + COM
CP

COM

Optimal Size
size F (mm2); STr (kVA)

Bach Quoc Khanh/EPS dept./HUST 3


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

2. Conductor sizing
2.1. Standards
0.5mm2 0.75 1 1.5 2.5 4
6 10 16 25 35 50
 IEC 60228: 70 95 120 150 185 240

 American wire gauge (AWG) 300 400 500 630 800 1000

AWG kcmil
1 kcmil = 0,5067 mm² Cỡ dây F (mm2) Cỡ dây F (mm2) Cỡ dây F (mm2) Cỡ dây F (mm2)
- - - - 250 127 750 380
- - - - 300 152 800 405
20 0,519 4 21,2 350 177 900 456
18 0,823 3 26,7 400 203 1000 507
16 1,31 2 33,6 450 228 1200 608
14 2,08 1 42,4 500 253 1250 633
12 3,31 1/0 53,5 550 279 1500 760
10 5,26 2/0 67,4 600 304 1750 887
8 8,37 3/0 85 650 329 2000 1010
6 13,3 4/0 107 700 355 - -

2. Conductor sizing
2.2. Current carrying capacity

 Current carrying capacity (Ampacity), Ref. IEC60050: The maximum current which
can be carried continuously by the conductor(s) (of the cable) under specified
conditions, without its steady-state temperature exceeding a specified value.

 Ampacity calculation:

Bach Quoc Khanh/EPS dept./HUST 4


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

2. Conductor sizing
2.2. Current carrying capacity
 Reference ampacity Ir for overhead line bare-conductor
qc : Convected heat loss, W/m
qr : Radiated heat loss, W/m
‒ Ref. IEEE Std. 738-1993: qs : Solar heat gain, W/m
Rac : Nominal AC resistance at
operating temperature t, /m

‒ Main factors influencing the conductor ampacity


• Ambient temperature
• Wind speed
• Solar heating

2. Conductor sizing
2.2. Current carrying capacity

10

Bach Quoc Khanh/EPS dept./HUST 5


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

2. Conductor sizing
2.2. Current carrying capacity Ambient
 For cables: Maximum temperature
Installation
temperature rise methods
IEC60364-4-52:2001 Insulation
material

Line
material

11

2. Conductor sizing
2.2. Loading capacity under normal operating condition
 Criteria for selecting the conductor size:
Iz: Current carrying capacity in real operations, A
Ir : Current carrying capacity in reference (specified) operation, A
f: Correction factor for real operations
Ib: Max. continuous current in normal operation, A (possibly
regard to n-1 reliability requirement)

Example 9.1: Sizing CADIVI’s underground 10kV 3-core cable for Ib = 120A

Ib = 120A
F (mm2) … 16 25 35 …

Iz (A) … 109 140 166 …

12

Bach Quoc Khanh/EPS dept./HUST 6


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

2. Conductor sizing
2.2. Loading capacity under normal operating condition
 Correction factor f (IEC60364):
‒ On in the air or underground (f1, f2)

‒ Consider the soil thermal


resistivity (f3)

13

2. Conductor sizing
2.2. Loading capacity under normal operating condition
 Correction factor f (IEC60364):
‒ For groups of more than one circuit or of more than one multi-core cable (f4)

14

Bach Quoc Khanh/EPS dept./HUST 7


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

2. Conductor sizing
2.2. Loading capacity under normal operating condition
 Overload protection co-ordination
Load Cable
for low voltage cable

In I2
Ib Iz 1,45Iz I

In: Nominal current of the protective device Protection


I2: The current ensuring effective operation in
the conventional time of the protective device
(1): For protection selectivity and conductor not to be overloaded.
(2): Permissible overload 45% for a conventional time.

15

2. Conductor sizing
2.2. Loading capacity under normal operating condition
 Overload protection co-ordination for low voltage cable
t t
t(I) fuse I2t cable

t(I) LV CB
<1g

I I
Ib In Iz I2 Ib In Iz I2 Im
 When the protective device is a circuit breaker: Only consider (1) In  Iz because I2 = 1.3ln
for CB complying with IEC 60947-2 (for industrial use) and I2 = 1,45In for CB complying with
IEC 60898 (for household and similar installations)  if In ≤ Iz, (2) will also be satisfied.
 When the protective device is a fuse : IEC60269-2-1  I2 = 1,6.In (In reality, I2 =
(1.61.9).In) (2) becomes 1.6  In ≤ 1,45  Iz or In  0.9  Iz

16

Bach Quoc Khanh/EPS dept./HUST 8


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

2. Conductor sizing
2.3. Loading capacity under fault conditions
 Protection against thermal stress of short-circuit current

tsc, Isc The short-circuit duration (s) and effective short-circuit current (A)
F The cross-sectional area (mm2);

k Factor taking account of the resistivity, temperature coefficient and heat capacity of the
conductor material, and the appropriate initial and final temperatures.

IEC60364-4-43,
the value of k for
phase conductor

17

2. Conductor sizing
2.4. Voltage drop
 For a line segment feeding a lumped load at the end

When UA: Permissible voltage drop.

less dependent on cross-section area


0,30,4(/km) for OHL
as xo =
0,070,1(/km) for cables

18

Bach Quoc Khanh/EPS dept./HUST 9


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

2. Conductor sizing
2.4. Voltage drop Source P1,Q1 Pn,Qn
 For a line feeder with distributed lumped loads
F1, l1 Fn, ln
‒ With the same conductor size:

‒ With the same current density:

19

2. Conductor sizing
2.5. Economical optimization
 Economic load ranges:
‒ Conductor’s annual cost function per km: ZL F1 F2 F3

IL

IL1 IL2

20

Bach Quoc Khanh/EPS dept./HUST 10


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

2. Conductor sizing
2.5. Economical optimization
 Kelvin’s law: Economical size of conductors

‒ Total annual cost:

Economical size: C0 Min

21

2. Conductor sizing
2.5. Economical optimization
 Economic load density Je
‒ Economic size of conductor: C

IL : Normal load current


Je : Economic load density (pre-determined
and given in design handbooks)
F
Example 9.2:
F1 F2 Fopt F3
… 50 70 95 120 …. F(mm2)

Fopt = 75mm2

22

Bach Quoc Khanh/EPS dept./HUST 11


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

3. Dimensioning of bar conductors


3.1. Mechanical short-circuit strength
 Electromagnetic (electrodynamic) force between two parallel rigid conductors
‒ Electromagnetic force:
B: Flux density (T)
I: Current (A)
l: Length (mm)

‒ The force is greatest for N(3) short-circuit,


‒ Application:
• Two-phase or three-phase systems
• For rigid conductors (e.g. bar conductors, tubular conductors…)
• Post insulators (fixing with rigid conductors)

23

3. Dimensioning of bar conductors


3.2. Busbar sizing for mechanical strength
 For parallel solid busbar conductors
‒ Each phase main conductors are single conductors.
‒ For three-phase short-circuit in 3P system,
maximum electromagnetic force on the center main
conductor:
iP2, iP3: Phase-to-phase and 3 phase
short-circuit peak currents
l: Support spacing (cm)
‒ For phase-to-phase short-circuit in 3P
d: Main busbar spacing (cm)
system or single phase system:
0: Permeability constant
(4.10-7 Vs/Am)
k: Correction factor

24

Bach Quoc Khanh/EPS dept./HUST 12


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

3. Busbar sizing and bus supports


3.2. Busbar sizing for mechanical strength
 For parallel solid busbar conductors

‒ Correction factor k:
Takes account of the
conductor spacing
and shapes.

‒ Calculate k using Dwight’s chart.

Example 9.3:
a = 5mm, b = 80mm, d = 100mm, l = 1m
 k=0,91. If iP = 35kA  Fm= 224daN Dwight’s chart

25

3. Busbar sizing and bus supports


3.2. Busbar sizing for mechanical strength
 For parallel solid busbar conductors
‒ Bending moment M on busbar
(calculated according to the laws of rigidity):
Fm: electromagnetic force (N)
l : Support spacing (cm)

‒ Bending stress on rigid busbars must be less Moment of resistance for


some conductor shapes
than permissible bending stress:
W: Moment of resistance (cm3)
V: Factor takes account of mechanical natural frequency.
IEC60865: VB = 1 (without reclosing), VB=1.8 (with reclosing)
: Factor for loading of the main conductor
per: Permissible stress of the busbar

26

Bach Quoc Khanh/EPS dept./HUST 13


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

3. Busbar sizing and bus supports


3.2. Busbar sizing for mechanical strength
 For parallel attached-elements busbar conductors

‒ Each phase main busbar H is a group of t elements (sub-conductors)

‒ Dimensions:
• Main conductor spacing: a
(between two phase centers)
• Sub-conductor spacing: a12, …
• Support spacing: l
• Two adjacent sub-conductor
spacers: ls

27

3. Busbar sizing and bus supports


3.2. Busbar sizing for mechanical strength
 For parallel attached-elements busbar conductors

‒ The electrodynamic force between the


main conductors
Parameters are similar
to the case of parallel
solid busbar conductors
‒ The electrodynamic force between
the sub-conductors

Where k1s is calculated by Dwight’s chart

28

Bach Quoc Khanh/EPS dept./HUST 14


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

3. Busbar sizing and bus supports


3.2. Busbar sizing for mechanical strength  and  factors

 For parallel attached-elements busbar conductors


‒ Bending stress on main conductors:

‒ Bending stress on sub-conductors:

W s: Moment of resistance of sub-conductors.


Other parameters remain as for the case of solid busbar conductors.

29

3. Busbar sizing and bus supports


3.3. Post insulator selection
 Force on post insulator

where:
: Factor depending on the type and number of supports
Vd : Factor takes account of mechanical natural frequency for supports.
For DC system: Vd = 2;
For AC single phase system: Vd  2;
For AC threee phase system: Vd  2,7
FrB: Rated force of the support insulator given by Manufacturer

30

Bach Quoc Khanh/EPS dept./HUST 15


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

4. Switching device selection


4.1. Circuit breaker (CB)
 Functions:  Operating Principle:
‒ A piece of equipment which
can make or break a circuit
either manually or by remote
control under normal
conditions, Medium voltage CB operation

‒ Break a circuit automatically


under fault condition.

‒ Make a circuit either


manually or by remote under
fault condition.

Low voltage CB operation

31

4. Switching device selection


4.1. Circuit breaker
 Medium voltage circuit breaker:
‒ Standards: IEC60056; IEC60694

‒ Classifications
Arc extinction by SF6 gas
• Principles of Arc extinction: Vacuum
and SF6 (Sulphur hexafluoride) gas

• Installation: Outdoor (1), indoor (2)

(1) (2)

32

Bach Quoc Khanh/EPS dept./HUST 16


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

4. Switching device selection


Rated voltage Ur (IEC60694) The rated voltage is the maximum
4.1. Circuit breaker rms. value of the voltage that the equipment can withstand in
normal service. It is always greater than the operating voltage.

 Medium voltage circuit breaker: Rated current Ir (IEC60694): With the circuit breaker always
closed, the load current must pass through it in compliance with a
‒ Parameters maximum temperature value as a function of the materials and the
type of connections

Rated short-circuit breaking current Isc (IEC60056) The rated


short-circuit breaking current is the highest value of current that the
circuit breaker must be capable of breaking at its rated voltage

Rated peak withstand current IP (IEC60694) and making


current Ima (IEC60056): The making current is the maximum value
that a circuit breaker is capable of making and maintaining on an
installation in short-circuit. The peak value of the short-time
withstand current is equal to: 2.5Isc for 50 Hz, 2.6Isc for 60 Hz
and 2.7Isc for special applications

Rated short-time withstand current Ithr (IEC60694): the


standardised rms. value of the maximum permissible short-circuit
current on a network for the rated duration tthr of 1 or 3 seconds.
Example: Schneider’s MV circuit breaker SF1

33

4. Switching device selection


4.1. Circuit breaker
 Medium voltage circuit breaker:
‒ Ratings selection:
• Load current condition:

IL: Full load current, A


Ir: Rated normal current, A

• Rated voltage (Ue)

Us: Maximum system operating voltage, V


Ur: Rated voltage, V

34

Bach Quoc Khanh/EPS dept./HUST 17


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

4. Switching device selection


4.1. Circuit breaker
 Medium voltage circuit breaker:
‒ Ratings selection:
• Rated short circuit making current (Ima):.

iP: Peak short-circuit current calculated by I”k (Chapter 6)


I”k: Initial symmetrical short-circuit current

• Thermal short circuit capacity (Ithz):


Ith: Thermal equivalent short-circuit current calculated by I”k (Chapter 6)
Ithr: Rated short-circuit current - the rated short circuit duration tthr
tk : Short-circuit duration

• Rated short circuit breaking current (Isc):

35

4. Switching device selection


4.1. Circuit breaker
 Low voltage circuit breaker:
Miniature circuit breaker (MCB): Molded case circuit breaker Air circuit breaker (ACB)
(MCCB)
• Ref. IEC 60898 • Ref. IEC 60947-2
• Ref. IEC 60947-2
• Typical range: 0.5A to 125A • Typical range: 630A to
• Typical range: 16A to 6300A
• Final circuit protection
1600A (3200A)
(domestic, industry) • Main incoming circuit
• Incoming circuit protection protection (mainly in
(domestic, industry) industry)

36

Bach Quoc Khanh/EPS dept./HUST 18


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

4. Switching device selection


4.1. Circuit breaker Rated Current (In): The current that the
circuit-breaker will carry continuously
under specified conditions and on which
 Low voltage circuit breaker: the time/current characteristics are based

‒ Parameters:
Rated Impulse withstand
Rated Insulation Voltage (Ui): the voltage (Uimp) for 1.2/50s
voltage on which the dielectric impulse voltage test
properties are based.

Rated Operating Voltage (Ue): System


Rated Service Short-Circuit
operating voltage
Breaking Capacity (Ics): in %
of Icu
Rated Ultimate Short-Circuit Breaking
Capacity (Icn or Icu):

Rated Short-time withstand Capacity


(Icw): assumed constant during short- Example: Schneider’s LV circuit
time delay breaker Compact NS range

37

4. Switching device selection


4.1. Circuit breaker
 Low voltage circuit breaker:
‒ Ratings selection:
• Load current condition: IL: Full load current, A
Ir: Rated normal current, A

• Rated insulation voltage (Ui): Us: Maximum system operating voltage, V


Ui: Rated insulation voltage, V

• Rated short-circuit breaking current (Ics):

I”k: Initial symmetrical short-circuit current

38

Bach Quoc Khanh/EPS dept./HUST 19


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

4. Switching device selection


4.1. Circuit breaker
 Low voltage circuit breaker:
‒ The fault-current limitation capacity: preventing the passage of the maximum prospective fault-
current, permitting only a limited amount of current to flow crossing downstream the circuit
breaker  Reduce thermal stress, mechanical stress, electromagnetic-interference effects

‒ Interrupt the short circuit energy in one half cycle or less.

39

4. Switching device selection


4.1. Circuit breaker
 Low voltage circuit breaker:
‒ How to limit the fault-current:

Limiting isc by • High contact acceleration: Modified the fixed contact to increase the impulsion force,
increase of Ua  use double rotating contacts.

• Arc Extinction: Elongation, splitting and cooling the arc.

40

Bach Quoc Khanh/EPS dept./HUST 20


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

4. Switching device selection


4.2. Switches
 Medium voltage switch:
‒ Load break switch (LBS):
Interrupt load currents upto full
load (rated load) value. Including
a mechanism for suppression of
electric arcs. Adopts SF6 gas as
Medium voltage LBS
the medium of arc extinction.

‒ Disconnecting switch (DS):


Intended for safety isolation.
Lack a mechanism for
suppression of electric arcs, Medium voltage DS
when interrupting load current.

41

4. Switching device selection


4.2. Switches
 Medium voltage switch:
‒ Switch ratings selection

IL: Full load current, A


Ir: Rated normal current, A
Us: Maximum system operating voltage, V
Ur: Rated voltage, V
iP: Peak short-circuit current calculated by I”k (Chapter 6)
I”k: Initial symmetrical short-circuit current
Ith: Thermal equivalent short-circuit current calculated by I”k (Chapter 6)
Ithr: Rated short-circuit current - the rated short circuit duration tthr
tk : Short-circuit duration

42

Bach Quoc Khanh/EPS dept./HUST 21


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

4. Switching device selection


4.2. Switches
 Low voltage switch:
‒ Contactor: an electrically controlled switch
used for switching an electrical power circuit

‒ Functions: Interrupt power circuit upto overload


current. Not intended for short-circuit current
interruption. Thermal overload relay included.

‒ Contactor’s Ratings:
IL: Full load current, A
Ir : Rated normal current, A
Us: Maximum system operating voltage, V
Ui: Rated insulation voltage, V
Thermal overload relay selection:
Referred to Chapter 8

43

4. Switching device selection


4.3. Fuses
 Functions: Overcurrent protection
 Medium voltage fuse (Ref. IEC60282-1)
‒ Construction:
‒ Parameters: In, I3, I2 and I1

44

Bach Quoc Khanh/EPS dept./HUST 22


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

4. Switching device selection


4.3. Fuses
 Low voltage fuse (Ref. IEC60269-1 and 2)
‒ Types:
• g (full-range breaking capacity): Overload and short-circuit
protection.
• a (partial-range breaking capacity): Short-circuit protection.
‒ Parameters:

• In
• I2
• I1

45

4. Switching device selection


4.3. Fuses
 Fuse selection (ratings)
‒ Normal operation:

IL: Full load current, A


Ir : Rated normal current, A
Us: Maximum system operating voltage, V
Ui: Rated insulation voltage, V

‒ Breaking capacity:

I1: Maximum rated breaking current, A


Ik’’: Initial symmetrical short-circuit current, A

46

Bach Quoc Khanh/EPS dept./HUST 23


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

4. Switching device selection


4.3. Fuses
 Current-limiting fuse:
‒ Reduce the peak current (reduce mechanical
stress) and let-through energy (thermal stress)
of the protected circuit.
‒ Reduce the clearing time to less than 1/2cycle.

ip Without
CL fuse

with
CL fuse
Isc

47

4. Switching device selection


4.3. Fuses
 Fuse and Switch combination: Used at sites
where circuit switching is not regular.
‒ Medium voltage applications:
• Distribution transformer protection
LBS-fuse
• Ring-main unit (RMU) combination
• Overcurrent protection combines
with load on/off switching
MV Disconnector-
‒ Low voltage applications:
fuse combination
• Motor protection
• Capacitor protection LV Switch-fuse
combination

48

Bach Quoc Khanh/EPS dept./HUST 24


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

5. Instrument transformer selection


5.1. Voltage transformers
 Functions: Transform the primary high voltage
to secondary 100V or 110V

 Ratings selection:
‒ Insulation:
35kV outdoor VT
Us: Maximum system operating voltage, V
Ui: Rated insulation voltage, V

‒ Voltage ratio, number of secondary windings, class of


accuracy and secondary load: referred to Chapter 8
‒ 3 phase wiring diagram (Star, delta)
22kV indoor VT

49

5. Instrument transformer selection


5.2. Current transformers
 Functions: Transform the primary high current to
secondary current of 1A or 5A
 Types: Outdoor/indoor, ring-type Symbol

Indoor Outdoor Ring-type

 Parameters:
Parameter definition

50

Bach Quoc Khanh/EPS dept./HUST 25


EE3420E – Power Supply Systems - Printed 2021
Chapter 7

5. Instrument transformer selection


5.2. Current transformers ‒ Short-circuit withstand capacity

 Ratings selection:
‒ Normal operation:

I”k: Initial symmetrical short-circuit current


IL: Full load current, A
Ith: Thermal equivalent short-circuit current
Ir : Primary rated current, A
calculated by I”k
Us: Maximum system
Ithr: Rated short-circuit current - the rated short
operating voltage, V
circuit duration tthr
Ur: Rated voltage, V
tk : Short-circuit duration
‒ Voltage ratio, number of secondary iP: Peak short-circuit current calculated by I”k
windings, class of accuracy and Idyn: Maximum current for stability against
secondary load: referred to Chapter 8. mechanical stress under short-circuit current

51

52

Bach Quoc Khanh/EPS dept./HUST 26

You might also like