Professional Documents
Culture Documents
Chapter 7
Chapter 7.
Equipment sizing
Content
1. Generality
2. Conductor sizing
3. Dimensioning of bar conductors
4. Switching device selection
5. Instrument transformer selection
1. Generality
1.1. Criteria for steady-state operation
Steady state operation (permanent): Full load current is checked. Operational
equipment’s utilization factor should be less than or equal to unit.
Criteria:
‒ Rated voltage (insulation):
‒ Rated current (normal ratings):
1. Generality
1.2. Criteria for short-time operation
Overloading:
‒ Loads in excess of normal rating. Overload operation for safety reasons or
overload for reliability requirement.
‒ Overloading capacity (permissible loading, Kol = overload current/rated current)
is a function of the overloading duration and depends on cooling conditions.
‒ In design stage, the overloading duration is assumed (for reliability
requirement) to be the mean-time to repair (MTTR).
In USSR, for transformers, Kol = 1.4 (outdoor); 1.3 (indoor) as overloading duration is less
than 5 days, 6 hours per day, initial utilization factor is less 0.93.
1. Generality
1.2. Criteria for short-time operation
Short-circuits:
‒ Requirement for equipment stability against mechanical and thermal
stresses have to be satisfied.
‒ Criteria:
• Thermal short circuit withstand capacity (Ithz):
1. Generality
1.3. Economic optimization
Cost function (C):
‒ Capital cost (CP).
Total Cost
COM
Optimal Size
size F (mm2); STr (kVA)
2. Conductor sizing
2.1. Standards
0.5mm2 0.75 1 1.5 2.5 4
6 10 16 25 35 50
IEC 60228: 70 95 120 150 185 240
American wire gauge (AWG) 300 400 500 630 800 1000
AWG kcmil
1 kcmil = 0,5067 mm² Cỡ dây F (mm2) Cỡ dây F (mm2) Cỡ dây F (mm2) Cỡ dây F (mm2)
- - - - 250 127 750 380
- - - - 300 152 800 405
20 0,519 4 21,2 350 177 900 456
18 0,823 3 26,7 400 203 1000 507
16 1,31 2 33,6 450 228 1200 608
14 2,08 1 42,4 500 253 1250 633
12 3,31 1/0 53,5 550 279 1500 760
10 5,26 2/0 67,4 600 304 1750 887
8 8,37 3/0 85 650 329 2000 1010
6 13,3 4/0 107 700 355 - -
2. Conductor sizing
2.2. Current carrying capacity
Current carrying capacity (Ampacity), Ref. IEC60050: The maximum current which
can be carried continuously by the conductor(s) (of the cable) under specified
conditions, without its steady-state temperature exceeding a specified value.
Ampacity calculation:
2. Conductor sizing
2.2. Current carrying capacity
Reference ampacity Ir for overhead line bare-conductor
qc : Convected heat loss, W/m
qr : Radiated heat loss, W/m
‒ Ref. IEEE Std. 738-1993: qs : Solar heat gain, W/m
Rac : Nominal AC resistance at
operating temperature t, /m
2. Conductor sizing
2.2. Current carrying capacity
10
2. Conductor sizing
2.2. Current carrying capacity Ambient
For cables: Maximum temperature
Installation
temperature rise methods
IEC60364-4-52:2001 Insulation
material
Line
material
11
2. Conductor sizing
2.2. Loading capacity under normal operating condition
Criteria for selecting the conductor size:
Iz: Current carrying capacity in real operations, A
Ir : Current carrying capacity in reference (specified) operation, A
f: Correction factor for real operations
Ib: Max. continuous current in normal operation, A (possibly
regard to n-1 reliability requirement)
Example 9.1: Sizing CADIVI’s underground 10kV 3-core cable for Ib = 120A
Ib = 120A
F (mm2) … 16 25 35 …
12
2. Conductor sizing
2.2. Loading capacity under normal operating condition
Correction factor f (IEC60364):
‒ On in the air or underground (f1, f2)
13
2. Conductor sizing
2.2. Loading capacity under normal operating condition
Correction factor f (IEC60364):
‒ For groups of more than one circuit or of more than one multi-core cable (f4)
14
2. Conductor sizing
2.2. Loading capacity under normal operating condition
Overload protection co-ordination
Load Cable
for low voltage cable
In I2
Ib Iz 1,45Iz I
15
2. Conductor sizing
2.2. Loading capacity under normal operating condition
Overload protection co-ordination for low voltage cable
t t
t(I) fuse I2t cable
t(I) LV CB
<1g
I I
Ib In Iz I2 Ib In Iz I2 Im
When the protective device is a circuit breaker: Only consider (1) In Iz because I2 = 1.3ln
for CB complying with IEC 60947-2 (for industrial use) and I2 = 1,45In for CB complying with
IEC 60898 (for household and similar installations) if In ≤ Iz, (2) will also be satisfied.
When the protective device is a fuse : IEC60269-2-1 I2 = 1,6.In (In reality, I2 =
(1.61.9).In) (2) becomes 1.6 In ≤ 1,45 Iz or In 0.9 Iz
16
2. Conductor sizing
2.3. Loading capacity under fault conditions
Protection against thermal stress of short-circuit current
tsc, Isc The short-circuit duration (s) and effective short-circuit current (A)
F The cross-sectional area (mm2);
k Factor taking account of the resistivity, temperature coefficient and heat capacity of the
conductor material, and the appropriate initial and final temperatures.
IEC60364-4-43,
the value of k for
phase conductor
17
2. Conductor sizing
2.4. Voltage drop
For a line segment feeding a lumped load at the end
18
2. Conductor sizing
2.4. Voltage drop Source P1,Q1 Pn,Qn
For a line feeder with distributed lumped loads
F1, l1 Fn, ln
‒ With the same conductor size:
19
2. Conductor sizing
2.5. Economical optimization
Economic load ranges:
‒ Conductor’s annual cost function per km: ZL F1 F2 F3
IL
IL1 IL2
20
2. Conductor sizing
2.5. Economical optimization
Kelvin’s law: Economical size of conductors
21
2. Conductor sizing
2.5. Economical optimization
Economic load density Je
‒ Economic size of conductor: C
Fopt = 75mm2
22
23
24
‒ Correction factor k:
Takes account of the
conductor spacing
and shapes.
Example 9.3:
a = 5mm, b = 80mm, d = 100mm, l = 1m
k=0,91. If iP = 35kA Fm= 224daN Dwight’s chart
25
26
‒ Dimensions:
• Main conductor spacing: a
(between two phase centers)
• Sub-conductor spacing: a12, …
• Support spacing: l
• Two adjacent sub-conductor
spacers: ls
27
28
29
where:
: Factor depending on the type and number of supports
Vd : Factor takes account of mechanical natural frequency for supports.
For DC system: Vd = 2;
For AC single phase system: Vd 2;
For AC threee phase system: Vd 2,7
FrB: Rated force of the support insulator given by Manufacturer
30
31
‒ Classifications
Arc extinction by SF6 gas
• Principles of Arc extinction: Vacuum
and SF6 (Sulphur hexafluoride) gas
(1) (2)
32
Medium voltage circuit breaker: Rated current Ir (IEC60694): With the circuit breaker always
closed, the load current must pass through it in compliance with a
‒ Parameters maximum temperature value as a function of the materials and the
type of connections
33
34
35
36
‒ Parameters:
Rated Impulse withstand
Rated Insulation Voltage (Ui): the voltage (Uimp) for 1.2/50s
voltage on which the dielectric impulse voltage test
properties are based.
37
38
39
Limiting isc by • High contact acceleration: Modified the fixed contact to increase the impulsion force,
increase of Ua use double rotating contacts.
40
41
42
‒ Contactor’s Ratings:
IL: Full load current, A
Ir : Rated normal current, A
Us: Maximum system operating voltage, V
Ui: Rated insulation voltage, V
Thermal overload relay selection:
Referred to Chapter 8
43
44
• In
• I2
• I1
45
‒ Breaking capacity:
46
ip Without
CL fuse
with
CL fuse
Isc
47
48
Ratings selection:
‒ Insulation:
35kV outdoor VT
Us: Maximum system operating voltage, V
Ui: Rated insulation voltage, V
49
Parameters:
Parameter definition
50
Ratings selection:
‒ Normal operation:
51
52