You are on page 1of 14

BUILD SIMUL

https://doi.org/10.1007/s12273-020-0692-4

Study on the optimal operation mode of ventilation system during


metro double-island platform fire

Research Article
Zeng Long1,2, Yuxuan Yang1, Chang Liu1, Maohua Zhong1 ()

1. Institute of Public Safety Research, Department of Engineering Physics, Tsinghua University, Beijing 100084, China
2. Beijing Key Laboratory of City Integrated Emergency Response Science, Beijing 100084, China

Abstract Keywords
Large metro transfer stations have been widely constructed in China, among which the double-island metro,
station faces the serious fire safety issues owing to its large passenger flow. In this paper, simulation double-island platform,
cases were carried out to investigate the effectiveness of different ventilation modes by jointly fire,
operating tunnel ventilation fan (TVF) and platform screen doors (PSD) under two typical fire ventilation mode,
scenarios in the platform. The numerical model was established by Fire Dynamics Simulator numerical simulation,
software and verified via reduced-scale model experiments. The results indicate that the TVF model experiment

mode of supplying at the end near fire and exhausting at the other end is superior to that of
exhausting at both ends. Besides, activating more PSD and TVF on the both sides of platform will
Article History
Received: 10 March 2020
restrict smoke in one end to the greater extent. During a fire in the middle of the platform, opening
Revised: 09 July 2020
all PSD near tunnel-2 and TVF in tunnel-2 and tunnel-3 is the most appropriate mode. While
Accepted: 16 July 2020
during a fire at the left end of the platform, activating all PSD and TVF on both sides is the optimal
operation mode. The conclusions can provide guidance for smoke control design and on-site
© Tsinghua University Press and
emergency ventilation operation in double-island platform fire.
Springer-Verlag GmbH Germany,
part of Springer Nature 2020

1 Introduction not only suffocates people owing to its poisonous gas


composition with a high concentration, but also hampers
Recently urban rail traffic has been developed in China, and evacuees from seeking escape routes by reducing visibility
quantities of metro lines and stations have been constructed dramatically, consequently seriously threatening pedestrians
to meet the requirements of passengers, with the quick life safety.
increase of the passenger flow volume per day especially in In order to protect passengers from fire damage,

Indoor/Outdoor Airflow
the metropolis. In 2019, the average daily passenger flow of ventilation system need to be installed to eliminate the
and Air Quality
15 cities exceeded 1 million, of which the volume was over fire-induced smoke and adjust the ambient temperature.
10 million in Beijing and Shanghai metro network (China However, only utilizing the proper ventilation mode can
Urban Rail Transit Association 2020). There may be various control smoke effectively. About the tunnel fire ventilation,
factors that cause fire problems in the subway station, such Ingason et al. (2015) introduced systematically the typical
as cable fire, baggage fire, intentional arson and so on. The ventilation systems, including longitudinal ventilation, single
fire safety is worth paying high attention due to the occurrence point extraction and two point extraction. Besides, the critical
of accidents in King’s Cross Station, Baku Azerbaijan and velocity and back-layering length were discussed. The results
Daegu, with the death of 32, 289 and 192, respectively (Roh could provide solid background information for tunnel fire
et al. 2009; Tsukahara et al. 2011; Gao et al. 2012b). Generally, ventilation research and application. In addition, various
most casualties are from hazardous smoke instead of burning ventilation modes were proposed under metro station
flame in fire accidents. In a relatively restricted space like fire scenarios. Cheng et al. (2001) studied the emergency
an underground subway station, the fire-induced smoke ventilation pattern in case of fire in underground facilities,

E-mail: mhzhong@tsinghua.edu.cn
2 Long et al. / Building Simulation

and the results showed that the push-pull ventilation system the platform, the best ventilation mode was found to activate
had better smoke control effect. In Chen et al.’s work (2003), the supply system in hall, the exhaust system in platform,
it was concluded through numerical simulation that stack the over track exhaust system (OTE) and TVF system.
effect had a significant influence on smoke control in subway For purpose of passengers’ safety and platforms’
stations. Rie et al. (2006) compared the effects of three comfortable environment, platform screen doors (PSD)
ventilation modes in case of metro station fire, and obtained generally are installed in new-built stations. As a result, the
the best smoke restriction strategy. Park et al. (2006) influence of PSD on ventilation effect has been focused
carried out a numerical prediction to assess the influence of gradually. Roh et al. (2010) investigated the influence of PSD
subway fire, and measured the wind speed at several points on smoke spread and available safe egress time (ASET), and
on the platform. They found out that the larger smoke the results showed that pedestrians owned more available
exhaust capacity would improve the ability to prevent smoke time in the platform with PSD in comparison with the
movement, obtaining the optimal mode of emergency condition of no PSD installed. Li et al. (2009) revealed that
response. Zhong (2007) conducted numerical simulation to the smoke control effect of full-sealed PSD was better than
study smoke extraction strategies in a metro station with that of half-height PSD based on the temperature and
side platform. The results demonstrated that only turning visibility profiles. Therefore, full-sealed PSD were installed
exhaust mode in smoke-proof zone where the fire source abroad in the underground station due to these advantages.
was located and increasing the volume flux of single vent In the study of smoke control, there were still several
could restrict smoke effectively. In Kang’s research (2007), controversies about whether to open and how to open the
a smoke visibility prediction model was used to investigate screen doors or end doors on the platform. Ding et al. (2016)
smoke confinement in an underground station. Wu and You investigated 4 switching modes of end doors, finding that
(2009) proposed a method with using age of air to evaluate opening end doors would accelerate the vertical decent of
the effectiveness of ventilation measurement, which could smoke. Therefore, it was not recommended to open end
be conducive to obtain reasonable smoke restrict strategies. doors in case of platform fire. Li et al. (2016) designed
Gao et al. (2012a) investigated the hybrid ventilation mode 4 kinds of switch modes of PSD and compared the exhaust
of controlling smoke in a large transit metro station; by effect. It was observed that opening front, middle and rear
setting various ventilation modes, it was concluded that PSD on two sides performed best in the developing stage of
changing the ventilation rate had little effect on the smoke fire, and it’s better to open all PSD on one side in the stable
layer height, but it could significantly control the fire- stage. Wang et al. (2018) designed 24 cases of operating PSD,
induced smoke in the horizontal direction. Subsequently, obtaining the optimum modes of smoke confinement under
Luo et al. (2014a) carried out 1:50 scale model experiments three fire source locations. Besides, the results showed that
and computational fluid dynamics (CFD) simulations to it was not appropriate to activate the bottom smoke exhaust
further research the performance of hybrid ventilation under system and open the end door when screen door was opened.
different fire scenarios. Zhou et al. (2018) comparatively In Li and Zhu’s study (2018), opening the PSD on both sides
analyzed three ventilation modes when a fire happened could enhance the efficiency of smoke elimination during a
separately in the lobby, transfer floor and platform of a large fire in the middle of platform.
four-line transfer station. Zhang (2014) carried out numerical The above research involved confinement and elimination
simulation to verify the effectiveness of coordinated smoke of the fire-induced smoke in many scenarios, where the
extraction mode during fire occurring in a double-island platform structures were mostly traditional island type
platform. It was observed that insufficient exhaust volume or side type. Additionally, majority of them just studied
in the platform would hinder personnel evacuation. The separately the effects of different TVF or PSD operations,
hybrid ventilation modes in above research results didn’t and few combined the two systems to investigate the optimal
include the tunnel ventilation fan system (TVF) yet, while ventilation mode. When a fire occurred in a double-island
other scholars studied the effect of combining ventilation platform, smoke diffusion pattern and joint ventilation system
system in station and tunnel. Zhao et al. (2016) conducted effect would be different. In this study, numerical simulations
a study on the optimal TVF operation mode in a T-type were carried out during a fire occurring in the center or the
transfer station, and it was revealed that TVF on the left and left end of platform under various TVF operation modes
right end should be in supply and exhaust mode respectively. and PSD switching modes. After the numerical model was
Hu et al. (2014) investigated the optimal cooperative verified by reduced-scale fire experiments, the optimal smoke
ventilation mode during a train fire in metro station. It was control modes were obtained for different fire scenarios by
suggested that opening the exhaust systems both in the comparing temperature and visibility profiles. The work
tunnel and platform could control smoke better. In Meng could technically support the design of fire emergency plan
et al’s work (2014), when a train with fire stopped beside in an underground subway double-island platform.
Long et al. / Building Simulation 3

2 Numerical simulation which can be defined as:


μLESCp
2.1 Introduction to FDS software kLES = (5)
Pr
Taking into account the huge risk and high cost, the full-scale μLES
( ρD )l ,LES = (6)
fire experiment is not widely used to study fire safety issues. Sc
On the contrary, numerical simulation is a more flexible The Prandtl number and the Schmidt number are
and operable way to set up various fire scenarios and assumed to be constant. In the FDS model, the values of Cs,
examine safety parameters with the characteristics of safe Sc, Pr are acquiescently set to be 0.2, 0.5, 0.5 respectively.
environment and low cost. In this paper, Fire Dynamics The mixture-fraction combustion model is adopted,
Simulator version 6.3.2 (FDS) was adopted to build up a and the mixed fraction is defined as:
double-island station model and analyze the performance
of different ventilation modes. As a kind of computational sYF - ( Yo - Yo¥ )
Z= (7)
fluid dynamics (CFD) tool, the software was developed by sYFI + Yo¥
National Institute of Standards Technology (NIST). Through vo M o
the verification of previous examples (McGrattan et al. 2016), s= (8)
vF MF
the large eddy simulation (LES) model was proven to calculate
well the smoke behaviors. As a result, the method has where YF, Yo are the mass fraction of combustion substance
been extensively employed in fire research (Roh et al. 2009; and oxygen, respectively; vF, vo are the reaction coefficient of
Luo et al. 2014b; Yuan et al. 2015), including our work in combustion substance and oxygen, respectively; and Mo and
this paper. In the FDS model, the governing equations are MF are the relative molecular mass of oxygen and combustion
as following: substance, respectively. The superscript I represents the mass
The continuity equation: fraction at fuel source, and ¥ represents the oxygen mass
fraction in the initial ambient.
¶ρ
+  ⋅ ρu = 0 (1) The radiation transfer equation of non-scattering grey
¶t
gas is solved by the finite volume method.
The momentum equation:
s ⋅ I λ ( x , s ) = κ ( x , λ )[ I b ( x ) - I λ ( x , s ) ] (9)
¶u
ρ( + (  ⋅ u )u)+ p = ρg + f + ⋅ τ (2) where Iλ(x, s) is the radiation intensity at wavelength λ,
¶t
κ(x, λ) is the absorption coefficient, and Ib(x) is the source
The energy equation: term of Planck function.
¶ Dp
( ρh ) +  ⋅ ρhu = -  ⋅ qr +  ⋅ kT + å ⋅ hl ρDl Yl 2.2 Physical model
¶t Dt l

(3)
The physical model in the research is an underground
where ρ designates the air density, t and u are the time and double-island subway station, with a self-symmetric structure
velocity, respectively. p is the pressure, f is the external force, for the whole platform floor. As shown in Figure 1(a), there
and τ stands viscous force. h is the specific enthalpy, qr is is a public station hall on the first floor, with the dimensions
the radiative heat flux, k is the heat conductivity coefficient, of 120 m (L) × 44 m (W) × 6 m (H), and a double-island
Dl and Yl are the diffusion coefficient and mass fraction of platform on the second floor, each island platform with the
the element l respectively. dimensions of 120 m (L) × 14 m (W) × 5 m (H). Two stairs
The transient fluid motion can be decomposed into connecting the platform and hall lie on each island platform,
large-scale motion and sub-scale motion. The large-scale which are surrounded by ceiling screen with 1.5 m height.
motion is directly solved, and the sub-scale motion should be Four tunnels are located on both sides of the two platforms,
solved by the Smagorinsky sub-grid model (McGrattan et al. each tunnel with the dimensions of 4 m (W) × 5 m (H), and
2016). According to the analysis, the viscosity is modeled as: the middle two tunnels are separated partly by vertical wall.
Two rows of full-sealed platform screen doors (PSD) are
2 2 1/2
μLES = ρ ( Cs Δ ) (2Sij ⋅ Sij - (  ⋅ u ) )
2
(4) installed on the edge of each platform. Four exits are situated
3
in the four corners of station hall, each with the dimensions
where Cs is the Smagorinsky constant, and Δ is the of 5 m (W) × 6 m (H).
characteristic length of a grid cell. The thermal conductivity Figure 1(b) gives the top view of the platform and tunnel.
and material diffusivity are related to the turbulent viscosity, In each platform, two ventilation ducts are arranged
4 Long et al. / Building Simulation

(a) Schematic diagram of numerical model

(b) Top view of platform and tunnel

(c) Side view of PSD #1 on the platform-A

(d) Side view of PSD #2 on the platform-A


Fig. 1 Different view of the FDS model

longitudinally along the platform. For each tunnel, the over one of them can be taken as an example under the condition
track exhaust system (OTE) with a series of smoke vents is of single fire source. The fire in the middle of platform has
located beneath the ceiling, and the tunnel ventilation fan a wide range of influence after smoke diffusing over a wide
system (TVF) is situated near the both ends of platform. area. And when a fire happens in the end of platform, the
Besides, two fire sources are located at the center and the temperature near fire source will be higher, and the nearby
left end of platform-A. Figures 1 (c) and (d) show the labelled stair cannot be used as the evacuation paths to station hall.
numbers of PSD in sequence and the Under Platform The two typical fire locations are more harmful and
Exhaust system (UPE) with a range of ventilation openings representative (Yang and Cao 2006).
on the platform-A. The platform fire load includes moving load and fixed
load, and the former is mainly the luggage fire. It is generally
2.3 Fires scenario recommended to take 2 MW – 2.5 MW (Huang 2016), and
Li (2015) suggested taking 3 MW as the maximum fire
Since the structure of the two platforms is exactly the same, source power of the moving load. As for the fixed load,
Long et al. / Building Simulation 5

Chen and Zhang (2007) carried out the subway commodity Forney 2008).
physical fire experiment, and the maximum load obtained
Q
was 2.58 MW. In the study, the maximum heat release rate D* = ( )2 / 5 (11)
(HRR) was taken as 3 MW for the consideration of more ρ¥CpT¥ g
dangerous fire scenario in the double-island platform.
In the previous research, different grid sizes were used
T-square fire is currently widely used to describe the fire
under different fire HRRs based on the D*/δx criterion. As
developing process. As shown in Eq. (10), it can be divided
shown in Table 1, the grid size near the fire source was
into four types according to the developing rate, including
approximately 0.1D*. In current study, the HRR of fire
slow, medium, fast and extremely fast. The platform fire is
source was 3MW. According to Eq. (11), the value of D*
generally caused by the ignition of passenger luggage or some
was 1.45 m, and the grid size near fire source should be
paper products, so it can be considered as a rapid growth
0.09–0.36 m. As for the mesh size in other region away
fire, and the value of α is 0.04689 (Li et al. 2012).
from the fire source location, it was suggested to take twice
Q = αt 2 (10) of the mesh size near fire (Liu et al. 2019). To determine the
most appropriate mesh size, we gradually had encrypted
The fuel used in the FDS model is Polyurethane composed from the coarse mesh until the calculation results were little
of Carbon, Hydrogen, Oxygen, Nitrogen. The CO Yield different. The comparison of five kinds of mesh sizes was
(Yco) and Soot Yield (Ys) are adopted as 0.024 and 0.113 shown in Table 2, and their effects on temperature at 1.8 m
respectively. height were presented in Figure 2. It could be found that
the temperature decreased with the mesh size refining from
2.4 Mesh refinement and boundary conditions 0.5 m to 0.2 m and the CPU time was in acceptance thresholds.
Nevertheless, the noticeable increase in calculation time
During using LES model for numerical calculations, mesh did not further lower the prediction value with the mesh
distribution in the calculation region is a critical factor for size reducing from 0.2 m to 0.125 m. Accordingly, it was
the accuracy of simulation results. On the one hand, in order advisable that the grid size near fire source and in other
to accurately describe the variation of physical quantities, places were set as 0.2 m and 0.4 m respectively.
the grid size is required to be small enough, because sparse For the material descriptions and parameters setting in
grid may result in unreasonable calculation results; on the the FDS model, the floor and tunnel surfaces were set as
other hand, it is necessary to take into account computer “CONCRETE”, of which the specific heat and conductivity
resources, and dense grid may bring about a long calculation were 1.04 kJ/(kg·K) and 1.8 W/(m·K). The vents of platform,
time. In the FDS User Guide, the characteristic diameter lobby and OTE system were set as “Exhaust”, “Supply” and
D* was expressed as shown in Eq. (11), where the value “Exhaust” respectively. The exhaust volume of ventilation
of D*/δx was better in the range of 4–16 (McGrattan and fan system was specified as 44 m3/s in each platform and

Table 1 Related study on grid size in metro stations


Grid size (m)
References HRR(MW) D*(m) Near fire source In other places
Zhong et al. (2010) 1.5 1.10 0.1×0.1×0.1 0.2×0.2×0.2
Li (2015) 2 1.26 0.12×0.12×0.1 0.5×0.5×0.3
Zhao et al. (2016) 2 1.26 0.2×0.2×0.2 0.2×0.2×0.2
Wang et al. (2018) 2.5 1.35 0.167×0.167×0.167 0.333×0.333×0.333

Table 2 Results of grid dependence analysis


Grid size (m)
Near fire source In other place Total number of cells CPU time(h)
Test 1 0.5×0.5×0.5 1.0×1.0×1.0 32,900 0.19
Test 2 0.25×0.25×0.25 0.5×0.5×0.5 263,200 3.10
Test 3 0.2×0.2×0.2 0.4×0.4×0.4 598,500 11.30
Test 4 0.15×0.15×0.15 0.3×0.3×0.3 1520,000 30.83
Test 5 0.125×0.125×0.125 0.25×0.25×0.25 2105,600 45.25
6 Long et al. / Building Simulation

and position of opening PSD had an influence on the control


effect. Above all, 18 simulation cases were carried out and
presented in Table 4, where exhaust system in the platform,
supply system in the lobby and OTE system were activated
by default.

2.6 Validation of FDS model

Several reduced-scale model experiments were conducted


to verify the effectiveness and feasibility of the PDS model
built up before. The reduced-scale model kept 1:10 ratio
relative to the actual station, whose structure was similar to
that of the numerical model displayed in Figure 1. According
to the Froude similarity criterion (Shi et al. 2009) shown in
Fig. 2 Temperature at 1.8 m height with different mesh sizes Table 5, parameters in the reduced-scale model experiments
could be converted into those in the full-scale fire scenarios.
33 m3/s in every OTE system. Besides, the supply volume in The model included a public station hall with the dimensions
station hall was set as 88 m3/s, and air volume in each TVF of 12 m (L) × 4.4 m (W) × 0.6 m (H), two island platforms
was 60 m3/s. The four exits in the station hall and both ends and four tunnels. Each platform was 12 m long, 1.4 m wide
of each tunnel were set as “OPEN” boundary. Besides, the and 0.5 m high, and each tunnel was 12 m long, 0.4 m wide
initial ambient temperature and pressure were 293 K and and 0.5 m high. The floors of the 1:10 scale model were
101 kPa. The simulation time was set as 360 s due to the made of steel with 2 mm thickness, and the PSD and one
evacuation requirement in metro fire accident (NFPA 2014). end wall were made of tempered glass for convenience to
observe. Under the condition of natural ventilation and
2.5 TVF operation mode and simulation cases closing all PSD, a 10 cm × 10 cm methanol pool fire was set
in the center and the left end of platform separately, which
In the case of platform fire, it’s better to open exhaust was shown in Table 6. The fire scenario in the 1:10 scale
system in the platform and supply system in the station hall, model was displayed in Figure 3. During the experiment,
meanwhile jointing tunnel ventilation system to control mass loss rate of methanol was measured by electronic
smoke throughout PSD. It has been reported that UPE could balance. And then the heat release rate per second could
just slightly effect the process of smoke exhaust (Zhong et be calculated by Eq. (12), which would be imported to the
al. 2012), so only the OTE was required to be opened. For PDS model.
the platform-A fire, the tunnel structures at both sides are Q =  ´ m ´ ΔH (12)
asymmetric, hence presenting a different airflow distribution.
When opening the PSD near tunnel-1, TVF1 and TVF2 where Q is the heat release rate of fire source, m is the mass
need to be operated. In addition, the TVF in tunnel-2 and loss rate (g/s), H is the heat of combustion and adopted
tunnel-3 need co-work during opening the PSD near tunnel-2. as 22.7 kJ/g (Lide 2001).  is the combustion efficiency,
As shown in Table 3, there were 9 operation modes for the and its value can be taken as 1 owing to methanol burning
TVF to restrict fire-induced smoke. Moreover, the number completely.

Table 3 Operation modes of TVF


No. Modes TVF1 TVF2 TVF3&TVF5 TVF4&TVF6
1 Exhaust Exhaust — —
2 Exhaust at both ends — — Exhaust Exhaust
3 Exhaust Exhaust Exhaust Exhaust
4 Exhaust Supply — —
Exhaust at the left end;
5 — — Exhaust Supply
Supply at the right end
6 Exhaust Supply Exhaust Supply
7 Supply Exhaust — —
Supply at the left end;
8 — — Supply Exhaust
Exhaust at the right end
9 Supply Exhaust Supply Exhaust
Long et al. / Building Simulation 7

Table 4 FDS simulation cases


Cases Fire source TVF Modes PSD #1 PSD #2 End doors
1 1 1 Open 1–24 — —
2 1 1 Open 10–15 — —
3 1 2 — Open 34–39 —
4 1 3 Open 10–15 Open 34–39 —
5 1 3 — — Open 1–4
6 1 4 Open 10–15 — —
7 1 4 Open 1–24 — —
8 1 5 — Open 25–48 —
9 1 6 Open 1–24 Open 25–48 —
10 1 6 — — Open 1–4
11 2 1 Open 1–6 — —
12 2 1 Open 1–3,20–22 — —
13 2 2 — — Open 1,3
14 2 3 — — Open 1–4
15 2 4 Open 1–24 — —
16 2 7 Open 1–24 — —
17 2 8 — Open 25–48 —
18 2 9 Open 1–24 Open 25–48 —

Table 5 Froude similarity criterion (Shi et al. 2009)


Geometry Temperature Time Fire power Velocity Flow

xm = 10xf Tm = Tf t m = 10t f Qm = 10 Qf5/2


Vm = 10Vf qm = 105/2qf
Note: x, T, t, Q, V, q are the geometry, temperature, time, fire power, velocity, flow, respectively. The subscripts m and f represent the parameters of the full-scale station and reduced-scale
model, respectively.

Table 6 Experiments tests in the 1:10 scale model


Test Fire source Pool size Heat release rate Equivalent full-scale heat Ambient
number location (cm×cm) (kW) release rate (MW) temperature (°C)
1 Fire in the left end 22
10×10 4.54 1.44
2 Fire in the center 23

The average heat release rate was estimated and comparison between the experimental and numerical results
transformed as 1.44 MW, and the mesh size in simulation was illustrated in Figure 4, where the time was the converted
was set as 0.2 m near the fire source location. When a
fire occurred in the center or the left end of platform, a

Fig. 4 Comparison of ceiling temperature under different fire


Fig. 3 Fire scenario in the 1:10 scale model scenarios
8 Long et al. / Building Simulation

value in the full-scale scenario. Even though the temperature it is reasonable to only consider visibility and temperature
above fire fluctuated greatly in numerical simulation, the distributions on the platform-A.
difference was little in ceiling temperature variation between Under the condition of TVF at both ends in exhaust
the experiment and simulation under two fire scenarios. mode for cases 1–5, Figure 5 gives the contours of visibility
Therefore, it’s reasonable to employ the current FDS model and temperature at 1.8 m height above platform floor at
and investigate the optimal ventilation modes during fires the time of 360 s. From the results of case 1 and case 2, the
in the double-island platform. former brings about the higher visibility in the middle of
platform but the lower visibility and higher temperature on
3 Results and Discussion the both ends, and the latter is the opposite. So it’s better to
open 6 screen doors near the fire source (labelled as PSD
3.1 Fire in the center of the platform 10–15), which can be attributed to the larger suction force
concentrating on the fewer PSD in comparison with opening
In case of a fire occurring in the center of platform, the PSD1–24. To further research the influences of TVF mode
fire-induced smoke will spread to both ends simultaneously 2 and mode 3, it can be seen that the results of cases 2–4 are
under symmetrical constructions and stable ventilation basically the same while only opening PSD near the fire
conditions. Passengers need to be away from the fire and source location, which shows that it’s not necessary to open
escape through the stair#1 and stair#2 on the both ends, and PSD next to tunnel-2 during TVF at both ends in exhaust
the evacuation process is required to be completed within mode. This is because the flow field inside the platform
6 minutes according the Code for Design of Metro (GB hasn’t been changed after increasing exhaust volume in
50157-2013 2013). Therefore, it’s crucial to pay attention to tunnels. To be specific, it is obvious from Table 7 that the
the fire safety parameters at simulation time of 360 s on total flow volume throughout PSD is essentially the same,
the both ends of the platform. Visibility and temperature and excess flow has been distributed into the OTE system
profiles could reflect fire risk and assess evacuation conditions, and open boundary on both ends of tunnels. In case 5,
which were employed widely to analyze ventilation effect opening four end doors promotes the longitudinal spread
(Domingo et al. 2011; Liang et al. 2017). During a fire in the of smoke to both ends but cannot discharge smoke effectively,
platform-A, since the PSD in the platform-B keep closed, leading to smoke accumulation and subsidence in the
there will be free of smoke in the platform-B. Accordingly, middle of platform. In summary of cases 1–5, the visibility

Fig. 5 Visibility and temperature contours at 1.8 m height at 360 s (cases 1–5)
Long et al. / Building Simulation 9

Table 7 Volume flow of PSD in cases 2–4 height for cases 6–10. It can be obtained from case 7 that
Exhaust volume flow in the stable stage (m3/s) the fire-induced smoke is prevented from spreading to the
Case 2 Case 3 Case 4 left end while opening PSD1–24. This is because in the
PSD10 0.35 0.16 initial stage of the fire, the pressure in the left end of the
PSD11 1.18 1.03
platform is constantly reduced due to the exhaust fan nearby.
PSD12 0.76 0.46
Subsequently, the airflow from the right supply fan can
easily enter the platform once reaching PSD on the left,
PSD13 1.36 0.90
resisting smoke spreading towards the left end. That can be
PSD14 0.90 0.60
illustrated in Figure 7(a), where PSD1–6 keep exhausting
PSD15 1.11 0.72
owing to the left fan at the very start and turn to supply
PSD34 0.36 0.19
afterwards. Furthermore, exhaust and supply volume of PSD1
PSD35 1.20 0.44
are the largest and the smallest respectively among PSD1–6,
PSD36 0.64 0.08 and those of PSD6 are just the opposite. From the Figure 7(b),
PSD37 1.30 0.45 supply vents are converted into exhaust vents for PSD10,
PSD38 1.09 0.28 12, 16 in the middle of platform, and the smoke emission
PSD39 1.12 0.38 in PSD12 near the fire source is relatively small. It could be
Sum total 5.66 5.71 5.69 observed in Figure 7(c) that airflows fluctuate greatly near
PSD20, 22, 24 on the right end of platform, which are mainly
in the both terminal areas is below 10 m, obstructing the in the discharging state resulting from the accumulation of
safe evacuation of personnel (Hao 2012). Hence, it is not smoke. Due to the small amount of exhaust volume in the
recommended to operate TVF exhaust mode at both ends middle, only opening PSD10–15 will nearly lose the supply
for controlling the fire-induced smoke. vents and fail to control smoke by comparing case 6 with
During investigating the effect of TVF in the mode of case 7, which indicates that it ought to open PSD1–24
exhausting on one end and supplying on the other end, under TVF mode 4. For case 8 and case 9, the conditions
owing to fire in the center and the symmetrical structure of of visibility and temperature in the left area perform better,
platform, it’s reasonable to take the mode of exhausting at owing to their greater airflow resistance than case 7, which
the left end and supplying at the right for example. Figure 6 can be reflected in Table 8. Since the air intake plays a
presents the visibility and temperature contours at 1.8 m crucial role in controlling smoke spread, the 12 PSD on the

Fig. 6 Visibility and temperature contours at 1.8 m height at 360 s (cases 6–10)
10 Long et al. / Building Simulation

Fig. 7 Volume flow of PSD in case 7

Table 8 Volume flow of PSD in cases 7–9


Volume flow in the stable stage (m3/s) Volume flow in the stable stage (m3/s)
Case 7 Case 9 Case 8 Case 9
PSD1 +1.55 +1.08 PSD25 +2.25 +0.96
PSD2 +2.31 +0.89 PSD26 +1.85 +0.53
PSD3 +2.42 F PSD27 +1.54 +0.65
PSD4 +3.22 F PSD28 +1.97 F
PSD5 +3.51 +2.00 PSD29 +3.71 F
PSD6 +5.20 +3.93 PSD30 +4.86 +4.24
PSD7 +4.94 +3.47 PSD31 +4.85 +4.73
PSD8 +0.21 F PSD32 +2.18 +2.09
PSD9 +0.94 +1.84 PSD33 +3.88 +3.82
PSD10 −0.54 F PSD34 +1.25 +1.01
PSD11 F +1.67 PSD35 +1.82 +1.88
PSD12 −0.57 F PSD36 F +0.59
Note: positive: supply; negative: exhaust; F: fluctuating constantly during 360 s

left half of platform can be used as analysis objects. It is right stair #2. And the temperature in case 9 is higher than
evident that the supply volume flow increases successively that in case 8 at the entrance of stairs on the both ends,
from case 7 to case 9 despite of air fluctuations near some moreover three tunnel traffic operations will be affected in
PSD in case 9. Nevertheless for TVF mode 6 in case 9, case 9. In other words, case 8 is superior to the other two.
excessive resistance in the left leads to serious accumulation From the result of case 10, it’s better not to open end doors
of smoke in the right end area, resulting in worse evacuation during TVF in the mode of exhausting on one end and
conditions on the stair #2. For more accurate comparison supplying on the other end.
of cases 7–9, Figure 8 gives the temperature and visibility Based on the above analyses in the case of a fire at the
curves at 1.8 m height at the entrance of stair #1 and stair center of platform, when the PSD are properly switched,
#2 on the both ends during 360 s. Visibility in case 9 maintains the mode of exhausting on one end and supplying on the
a high level at the left stair #1, but reduces firstly at the other end is superior to exhausting on both ends for TVF.
Long et al. / Building Simulation 11

Fig. 8 Visibility and temperature at 1.8 m height at the stairs on the both ends during 360 s

Especially for the double-island platform with full-sealed This is because the stair #2 supplies air from hall to platform
PSD, the optimal operation mode of TVF is exhausting on during fire, and two streams of air interact after opening
one end and supply on the other end of tunnel-2 and tunnel-3, the three PSD nearby, leading to smoke chaos and visibility
meanwhile coordinating with opening all full-sealed PSD reduction. When only opening two end doors on the left in
next to the tunnel-2. The mode could enhance the capacity case 13, the right area owns better visibility in comparison
for preventing extensive smoke movement and provide the with opening four end doors in case 14.
safe environment conditions for passengers evacuation. Figure 10 shows the visibility and temperature contours
at 1.8 m height at 360s for cases 15–18 under TVF in the
3.2 Fire in the left end of the platform mode of exhausting on one end and supplying on the other
end. Since fire source is located at the left end of platform,
Fire source locations have an influence on the optimal we couldn’t arbitrarily specify TVF on one end as exhaust
ventilation mode. Restricted by the end wall (Ji et al. 2011), mode like fire in the center. The exhaust or supply mode
fire occurring in the left area gives rise to higher smoke of TVF on the right end has a great influence on smoke
temperature than fire in the center. It’s necessary to further confinement. In the case of left fan exhausting and right
research the operation mode of TVF and full-sealed PSD fan supplying, it can be concluded from case 15 that the
during a fire happening in the left end. In this scenario, the fire-induced smoke cannot be restricted effectively due to
stair #2 on the right end becomes the main evacuation air inlets on the left region of platform. By comparing case
route, so it is highlighted that safety parameters at the right 15 and case 16, it’s better to operate left TVF in supply mode
region need to be focused on. and right TVF in exhaust mode during a fire happening on
Figure 9 presents the visibility and temperature contours the left end. This can be explained by the fact that when
at 1.8 m height at 360s for cases 11–14 during TVF at both one end of platform gets close to the exhaust TVF, there will
ends exhausting. Obviously, the temperatures on the right be air inlets and hinder smoke spreading to this end during
region in different scenarios are pretty much the same. the fire stable stage, which is consistent with the results in
However, temperature and visibility might be inconsistent Section 3.1. For cases 16–18, the visibility and temperature
as safety state index under fire conditions (Zhu et al. 2016). profiles demonstrate that case 18 can achieve better smoke
The results of case 11 demonstrate that opening PSD1–6 control effect. Additionally, Figure 11 gives the comparison
near fire could provide relatively safe condition in the right of the above 8 ventilation modes, and it can be found that
end. The comparison of case 11 and case 12 indicates that it the visibility at the stair #2 always stays unchanged during
should not open PSD20–22 near the stair #2 on the right. 360 s in case 18. The observation is similarly attributed to
12 Long et al. / Building Simulation

Fig. 9 Visibility and temperature contours at 1.8 m height at 360 s (cases 11–14)

Fig. 10 Visibility and temperature contours at 1.8 m height at 360 s (cases 15–18)

Fig. 11 Visibility at 1.8 m height at the stair #2 during 360 s


Long et al. / Building Simulation 13

the larger supply volume like fire source located in the center. Acknowledgements
However, the difference between the two fire scenarios is that
the safety of both stair #1 and stair #2 need be considered in This work was supported by the National Natural Science
case of fire in the center, and the stair #2 on the right should Foundation of China (51674152, 71790613, 51906123), the
be a key focus in case of fire in the left end. Accordingly, National Outstanding Youth Science Foundation (51425404).
activating all PSD and TVF on the both sides will be the
optimal choice when a fire happens in the left end of the References
platform.
Chen F, Chien SW, Jang HM, Chang WJ (2003). Stack effects on smoke
4 Conclusions propagation in subway stations. Continuum Mechanics and
Thermodynamics, 15: 425–440.
Numerical simulations about fire safety were carried out in Chen P, Zhang Z (2007). Experimental study on fire in shops in subway
a double-island platform, and the fire source was set in the stations. Journal of Xihua University (Natural Science Edition),
center and the left end respectively. Under the condition of 2007(4): 9–10. (in Chinese)
activating the exhaust system in the platform, the supply Cheng L, Ueng T, Liu C (2001). Simulation of ventilation and fire in
the underground facilities. Fire Safety Journal, 36: 597–619.
system in the lobby and the OTE system, the optimal
China Urban Rail Transit Association (2020). Annual statistics and
ventilation modes during the two fire scenarios were
analysis report on urban rail traffic in 2019. (in Chinese)
researched by coordinating the TVF system and PSD system.
Ding W, Shi CL, Zhong M, Hou Z, Zhang L (2016). Platform screen
The numerical model was constructed in FDS software,
doors (PSD) model and its implied relation to the subway station
whose mesh size and boundary conditions were validated
fire. Journal of Safety and Environment, 2016(3): 75–79. (in
after comparing the smoke temperature beneath the ceiling
Chinese)
between simulation and reduced-scale model experiment. Domingo J, Barbero R, Iranzo A, Cuadra D, Servert J, et al. (2011).
Main conclusions of the study are as follows. Analysis and optimization of ventilation systems for an
(1) When a fire happens in the center, opening the PSD or underground transport interchange building under regular
end doors cannot well guarantee the safe evacuation and emergency scenarios. Tunnelling and Underground Space
environment near stairs entrance during TVF in the Technology, 26: 179–188.
mode of exhaust on both ends. It’s better to operate Gao R, Li A, Hao X, Lei W, Deng B (2012a). Prediction of the spread
TVF on one end exhausting and the other end supplying. of smoke in a huge transit terminal subway station under six
Under the circumstance, there are air inlets on one end different fire scenarios. Tunnelling and Underground Space
near the exhaust fan in the stable stage, causing resistance Technology, 31: 128–138.
to the smoke flow and pushing smoke towards the other Gao R, Li A, Hao X, Lei W, Zhao Y, et al. (2012b). Fire-induced
end. After the analysis of volume flow through PSD, with smoke control via hybrid ventilation in a huge transit terminal
the increase in the number of TVF and PSD opened, the subway station. Energy and Buildings, 45: 280–289.
greater the smoke resistance effect. However, excessive GB 50157-2013 (2013). Code for Design of Metro. Ministry of
resistance will lead to an unsafe evacuation environment Housing and Urban-Rural Development of China. (in Chinese)
near the other end. Since the stair#1 and stair#2 on Hao XP (2012). Fire smoke flow and mechanical smoke exhaust mode
both ends should be used as escape routes, the optimal in subway station. Master Thesis, Xi’an University of Architecture
operation mode is to open all the PSD near tunnel-2 and Technology, China. (in Chinese)
Hu L, Wu L, Lu K, Zhang X, Liu S, et al. (2014). Optimization of
and activate TVF in the tunnel-2 and tunnel-3.
emergency ventilation mode for a train on fire stopping beside
(2) When a fire occurs in the left end, activating PSD near
platform of a metro station. Building Simulation, 7: 137–146.
the fire source and TVF exhaust at both ends can provide
Huang RW (2016). Application of air curtain to prevent smoke in
relatively safe condition for stair#2 on the right end.
subway station. Master Thesis, Chongqing University, China. (in
While the mode of the left TVF exhausting and the
Chinese)
right supplying is even inferior to the condition of TVF Ingason H, Li YZ, Lönnermark A (2015). Tunnel Fire Dynamics. New
exhausting at both ends, because air inlets cannot York: Springer.
be formed on the right end to hinder smoke flow. In Ji J, Zhong W, Li KY, Shen XB, Zhang Y, et al. (2011). A simplified
comparison with the former two modes, operating TVF calculation method on maximum smoke temperature under the
supply on the left end and exhaust on the right exhibits ceiling in subway station fires. Tunnelling and Underground Space
better performance. Furthermore, the optimal operation Technology, 26: 490–496.
mode is to open all PSD and TVF on the both sides of Kang K (2007). A smoke model and its application for smoke
the platform on account of confining smoke in the left management in an underground mass transit station. Fire Safety
end and ensuring the safety of the right end. Journal, 42: 218–231.
14 Long et al. / Building Simulation

Li YF, Shi BW, Li JM, Fan HM, Du XL (2009). Analysis of the Roh JS, Ryou HS, Park WH, Jang YJ (2009). CFD simulation and
influence of safety gates on station smoke exhaust. In: Proceedings assessment of life safety in a subway train fire. Tunnelling and
of China Urban Underground Space Development Summit Forum. Underground Space Technology, 24: 447–453.
(in Chinese) Roh JS, Ryou HS, Yoon SW (2010). The effect of PSD on life safety in
Li Y, Lin X, Feng X, Wang C, Li J (2012). Life safety evacuation for subway station fire. Journal of Mechanical Science and Technology,
cross interchange subway station fire. Procedia Engineering, 45: 24: 937–942.
741–747. Shi CL, Zhong MH, Tu XW, et al. (2009). Fire Experiment and
Li YF (2015). Fire Safety Technology of Large Metro Transfer Station. Numerical Analysis of Deep Underground Metro Station. Beijing:
Beijing: Science Press. (in Chinese) Science Press. (in Chinese)
Li J, Shi CL, Chen CK, Xu X (2016). Study on switch modes of fully Tsukahara M, Koshiba Y, Ohtani H (2011). Effectiveness of downward
enclosed platform screen doors during fire in underground railway evacuation in a large-scale subway fire using Fire Dynamics
island-type platform. Journal of Safety Science and Technology, Simulator. Tunnelling and Underground Space Technology, 26:
2016(11): 114–119. (in Chinese) 573–581.
Li D, Zhu G (2018). Effect of platform screen doors on mechanical Wang W, He T, Huang W, Shen R, Wang Q (2018). Optimization
smoke exhaust in subway station fire. Procedia Engineering, 211: of switch modes of fully enclosed platform screen doors during
343–352. emergency platform fires in underground metro station. Tunnelling
Liang Q, Li Y, Li J, Xu H, Li K (2017). Numerical studies on the and Underground Space Technology, 81: 277–288.
smoke control by water mist screens with transverse ventilation Wu W, You S (2009). Analysis to ventilation effectiveness in subway
in tunnel fires. Tunnelling and Underground Space Technology, fire environment. In: Proceedings of the 4th IEEE Conference on
64: 177–183. Industrial Electronics and Applications (ICIEA) Xi’an, China.
Lide DR (2001). Handbook of Chemistry and Physics. Boca Raton, FL, Yang Y, Cao LY (2006). Discussion on subway fire scenario design.
USA: CRC Press. Journal of Natural Disasters, 4: 125–129. (in Chinese)
Liu C, Zhong M, Tian X, Zhang P, Li S (2019). Study on emergency Yuan JP, Liao YJ, Zhou SD, Tang Z, Fang Z (2015). Smoke extraction
ventilation for train fire environment in metro interchange tunnel. model of station hall fire in large subway transfer station.
Building and Environment, 147: 267–283. Engineering Journal of Wuhan University, 2015(6): 805–808. (in
Luo N, Li A, Gao R, Tian Z, Hu Z (2014a). Smoke confinement utilizing Chinese)
the USME ventilation mode for subway station fire. Safety Science, Zhang Y (2014). Numerical analysis of smoke exhaust system design
70: 202–210. of metro double-island station. Fire Technology & Products
Luo N, Li A, Gao R, Song T, Zhang W, Hu Z (2014b). Performance Information, 2014(4): 15–19. (in Chinese)
of smoke elimination and confinement with modified hybrid Zhao D, Jiang J, Zhou R, Tong Y, Wu F, Shi L (2016). Numerical study
ventilation for subway station. Tunnelling and Underground Space on the optimisation of smoke ventilation mode for interchange
Technology, 43: 140–147. subway station fire. International Journal of Ventilation, 15: 79–93.
McGrattan K, Forney GP (2008). Fire Dynamics Simulator (Version Zhong W (2007). Study on smoke flow characteristics and control
5), User’s Guide. NIST Special Publication 1019. methods in subway station fire. PhD Thesis, University of Science
McGrattan K, Hostikka S, McDermott R, et al. (2016). Fire Dynamics and Technology of China, China. (in Chinese)
Simulator Technical Reference Guide, Volume 3: Validation. Zhong W, Ji J, Yang JP, Huo R, Wang H (2010). Experimental and
NIST Special Publication 1019, Sixth Edition. simulation study on the influence of smoke vent arrangement on
Meng N, Hu L, Wu L, Yang L, Zhu S, Chen L, Tang W (2014). smoke control effect in subway station. Engineering Mechanics,
Numerical study on the optimization of smoke ventilation mode 27(3): 163–168. (in Chinese)
at the conjunction area between tunnel track and platform in Zhong MH, Shi CL, Luo YP, et al. (2012). Progress in research on
emergency of a train fire at subway station. Tunnelling and complex subway fire smoke control technology. In: Proceedings
Underground Space Technology, 40: 151–159. of the 20th Cross-Strait and Hong Kong and Macao Occupational
NFPA (2014). Standard for Fixed Guide Way Transit and Passenger Safety and Health Symposium and China Occupational Safety
Rail Systems. Quincy, MA, USA: National Fire Protection and Health Association 2012 Academic Annual meeting.
Association. Zhou Y, Bu R, Xu Z, Chen H, Gong J (2018). Numerical simulation of
Park WH, Kim DH, Chang HC (2006). Numerical predictions of smoke control effectiveness with different exhaust modes in a
smoke movement in a subway station under ventilation. Tunnelling large subway station. Procedia Engineering, 211: 1065–1074.
and Underground Space Technology, 21: 304. Zhu H, Shen Y, Yan Z, Guo Q, Guo Q (2016). A numerical study on
Rie DH, Hwang MW, Kim SJ, Yoon SW, Ko JW, et al. (2006). A study the feasibility and efficiency of point smoke extraction strategies
of optimal vent mode for the smoke control of subway station fire. in large cross-section shield tunnel fires using CFD modeling.
Tunnelling and Underground Space Technology, 21: 300–301. Journal of Loss Prevention in the Process Industries, 44: 158–170.

You might also like