Design Analysis PB:: I. Total Load

You might also like

You are on page 1of 1

DESIGN ANALYSIS PB:

I. TOTAL LOAD
LIGHTING LOAD = 5,100
CONVINIENCE LOAD = 5,000
SMALL APPLIANCE LOAD = 1,500
11,600

II. APPLICATION of DEMAND FACTOR


FIRST 3,000 VA @ 100% D.F. = 3,000
REMAINDER @ 35% D.F. = 3,010
6,010

III. OTHER LOADS


ONE (1) RANGE - 2,400
ONE (1) ACU - 2,600
5,000

TOTAL COMPUTED LOAD = 11,010

SERVICE ENTRANCE
IFL = ((11,010 )+(.25 x 2,600))/230 = 50.7A

USE : 2 – 22.0mm2 THHN Cu. Wires in 32mm DIA. PVC CONDUIT


1 – 8.0mm2 THW Cu. Wire FOR GROUND

SERVICE EQUIPMENT PROTECTION:


IFL = (6,010 + 2,400 + 250% (2,600))/230 = 64.83A

USE : ONE 70 AT/AF , 1P, 240V MOLDED CASE CIRCUIT BREAKER, 10KAIC, BOLT ON