70k03 and 04-E (Description)
70k03 and 04-E (Description)
04 Description
3 Description
3.1 Applications
Series 6RA70 SIMOREG DC MASTER converters are fully digital, compact units for three-phase
supply which supply the armature and field of variable-speed DC drives with rated armature
currents of between 15A and 3000A. The compact converters can be connected in parallel to
supply currents of up to 12000A. The field circuit can be supplied with currents of up to 85A (current
levels depend on the armature rated current).
3.2 Design
Series 6RA70 SIMOREG DC MASTER converters are characterized by their compact, space-
saving construction. Their compact design makes them particularly easy to service and maintain
since individual components are readily accessible. The electronics box contains the basic
electronic circuitry as well as any supplementary boards.
All SIMOREG DC MASTER units are equipped with a PMU simple operator panel mounted in the
converter door. The panel consists of a five-digit, seven-segment display, three LEDs as status
indicators and three parameterization keys. The PMU also features connector X300 with a USS
interface in accordance with the RS232 or RS485 standard.
The panel provides all the facilities for making adjustments or settings and displaying measured
values required to start up the converter.
The OP1S optional converter operator panel can be mounted either in the converter door or
externally, e.g. in the cubicle door. For this purpose, it can be connected up by means of a 5 m long
cable. Cables of up to 200 m in length can be used if a separate 5 V supply is available. The OP1S
is connected to the SIMOREG via connector X300. The OP1S can be installed as an economic
alternative to control cubicle measuring instruments which display physical measured quantities.
The OP1S features an LCD with 4 x 16 characters for displaying parameter names in plaintext.
German, English, French, Spanish and Italian can be selected as the display languages.
The OP1S can store parameter sets for easy downloading to other devices.
The converter can also be parameterized on a standard PC with appropriate software connected to
the serial interface on the basic unit. This PC interface is used during start-up, for maintenance
during shutdown and for diagnosis in operation. Furthermore, converter software upgrades can be
loaded via this interface for storage in a Flash memory.
On single-quadrant converters, the armature is supplied via a fully controlled three-phase bridge
B6C and, on four-quadrant devices, via two fully controlled three-phase bridges in circulating-
current-free, inverse-parallel connection (B6)A(B6)C.
The field is supplied via a single-phase, branch-pair half-controlled 2-pulse bridge connection
B2HZ.
The frequencies of the armature and field supply voltages may be different (in a range from 45 to
65 Hz). Operation in the extended frequency range between 23 Hz and 110 Hz is available on
request. The armature circuit supply phase sequence is insignificant.
For converters with 15A to 850A (1200A at 400V supply voltage) rated DC current, the power
section for armature and field is constructed of isolated thyristor modules. The heat sink is thus
electrically isolated. On devices with a higher rated DC current, the power section for the armature
circuit is constructed of disk thyristors and heat sinks (thyristor assemblies) at voltage potential. The
housing and terminal covers on power connections provide protection against accidental contact for
operators working in the vicinity. All connecting terminals are accessible from the front.
The power section cooling system is monitored by means of temperature sensors.
DC I
IDC I continuous (IdN)
(P067=1) 100%
15min
DC II
IDC II for 15 min and 1.5 x IDC II for 60 s
150%
(P067=2) 100%
15min
DC III
IDC III for 15 min and 1.5 x IDC III for 120 s
150%
(P067=3) 100%
15min
DC IV
IDC IV for 15 min and 2 x IDC IV for 10 s
200%
(P067=4) 100%
NOTICE
If you set a value of > 1 in P067, you must ensure that the "Dynamic overload capability of power
module“ is enabled, i.e. a value of > 0 must be set in parameter P075.
The SIMOREG DC Master does not monitor for compliance with the criteria of the load class set
in parameter P067. If permitted by the power module, the unit can operate for overload periods
in excess of those defined by the load class. The actual permissible overload period for the
installed power module is always longer than the overload period defined for the load class. The
SIMOREG DC Master does monitor the actual permissible overload period for the power
module. See Section 9.15.
Load cycles
US rating
Recommended Tu DC I DC II DC III DC IV
Tu=45°C
SIMOREG DC Master continuous 15min 60sec 15min 120 sec 15min 10sec 15min 60sec
100% 150% 100% 150% 100% 200% 100% 150%
°C A A A A A A A A A
400V, 1Q
460V, 1Q
575V, 1Q
Load cycles
US rating
Recommended Tu DC I DC II DC III DC IV
Tu=45°C
SIMOREG DC Master continuous 15min 60sec 15min 120 sec 15min 10sec 15min 60sec
100% 150% 100% 150% 100% 200% 100% 150%
°C A A A A A A A A A
690V, 1Q
6RA7086-6KS22 40 720 553.1 829.7 527.9 791.9 515.8 1031.6 525.9 788.9
6RA7088-6KS22 40 950 700.1 1050.2 677.1 1015.7 624.4 1248.8 668.1 1002.2
6RA7093-4KS22 40 1500 1156.9 1735.4 1118.2 1677.3 1047.0 2094.0 1101.9 1652.9
6RA7095-4KS22 40 2000 1589.3 2384.0 1522.2 2283.3 1505.5 3011.0 1503.9 2255.9
6RA7097-4KS22 40 2600 1992.7 2989.1 1906.3 2859.4 1887.2 3774.4 1876.9 2815.3
830V, 1Q
6RA7088-6LS22 40 900 663.8 995.7 642.0 963.0 592.1 1184.2 633.5 950.3
6RA7093-4LS22 40 1500 1156.9 1735.4 1118.2 1677.3 1047.0 2094.0 1101.9 1652.9
6RA7095-4LS22 40 1900 1485.4 2228.1 1421.6 2132.4 1396.9 2793.8 1414.2 2121.3
950V, 1Q
6RA7096-4MS22 40 2200 1674.3 2511.4 1603.3 2404.9 1570.7 3141.4 1588.1 2382.1
Load cycles
US rating
Recommended Tu DC I DC II DC III DC IV
Tu=45°C
SIMOREG DC Master continuous 15min 60sec 15min 120 sec 15min 10sec 15min 60sec
100% 150% 100% 150% 100% 200% 100% 150%
°C A A A A A A A A A
400V, 4Q
Load cycles
US rating
Recommended Tu DC I DC II DC III DC IV
Tu=45°C
SIMOREG DC Master continuous 15min 60sec 15min 120 sec 15min 10sec 15min 60sec
100% 150% 100% 150% 100% 200% 100% 150%
°C A A A A A A A A A
460V, 4Q
575V, 4Q
690V, 4Q
6RA7086-6KV62 40 760 598.7 898.1 575.4 863.1 532.9 1065.8 569.3 854.0
6RA7090-6KV62 40 1000 737.3 1106.0 715.2 1072.8 639.5 1279.0 702.3 1053.5
6RA7093-4KV62 40 1500 1171.6 1757.4 1140.1 1710.2 1036.6 2073.2 1116.2 1674.3
6RA7095-4KV62 40 2000 1477.7 2216.6 1435.3 2153.0 1326.7 2653.4 1404.6 2106.9
6RA7097-4KV62 40 2600 1992.7 2989.1 1906.3 2859.4 1887.2 3774.4 1876.9 2815.3
830V, 4Q
6RA7088-6LV62 40 950 700.8 1051.2 679.8 1019.7 607.8 1215.6 667.6 1001.4
6RA7093-4LV62 40 1500 1171.6 1757.4 1140.1 1710.2 1036.6 2073.2 1116.2 1674.3
6RA7095-4LV62 40 1900 1485.4 2228.1 1421.6 2132.4 1396.9 2793.8 1414.2 2121.3
950V, 4Q
6RA7096-4MV62 40 2200 1674.3 2511.4 1603.3 2404.9 1570.7 3141.4 1588.1 2382.1
18 25 28 31
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Weight (approx.) kg 11 14 16 16
75 78 81 85
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V DC 24V internal 3AC 400 (±15%) 50Hz
3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Weight (approx.) kg 16 17 30
87 91 93 95
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 3AC 400 (±15%) 50Hz 3AC 400 (±10%) 50Hz 3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and digital
setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
18 25 28 31
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Weight (approx.) kg 11 15 17 17
75 78 82 85
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
50Hz 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Weight (approx.) kg 17 18 32
87 91
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 1AC 230 (±10%) 1AC 230 (±10%)
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Weight (approx.) kg 42 80
25 31 75 81 85
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Weight (approx.) kg 14 16 30
87 90 93 95 96
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 3AC 400 (±15%) 50Hz 3AC 400 (±10%) 50Hz 3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and digital
setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
86 88 93 95
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 3AC 400 (±15%) 50Hz 3AC 400 (±10%) 50Hz 3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and digital
setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
88 93 95
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 3AC 400 (±10%) 50Hz 3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
13 18 25 28 31
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Weight (approx.) kg 11 11 14 14 16
75 78 81 85
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V DC 24V internal 3AC 400 (±15%) 50Hz
3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Weight (approx.) kg 16 17 30
87 91 93 95
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 3AC 400 (±15%) 50Hz 3AC 400 (±10%) 50Hz 3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and digital
setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
18 25 28 31
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Weight (approx.) kg 11 15 15 17
75 78 82 85
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
50Hz 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Weight (approx.) kg 17 18 32
87 91
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 1AC 230 (±10%) 1AC 230 (±10%)
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Weight (approx.) kg 47 85
25 31 75 81 85
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Weight (approx.) kg 14 16 30
87 90 93 95 96
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 3AC 400 (±15%) 50Hz 3AC 400 (±10%) 50Hz 3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and digital
setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
86 90 93 95
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 3AC 400 (±15%) 50Hz 3AC 400 (±10%) 50Hz 3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and digital
setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
88 93 95
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 3AC 400 (±10%) 50Hz 3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 3AC 400 (±10%) 50Hz 3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 3AC 400 (±10%) 50Hz 3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 3AC 400 (±10%) 50Hz 3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
Rated supply voltage electronics V 2AC 380 (– 25%) to 460 (+15%); In=1A or
power supply 1AC 190 (– 25%) to 230 (+15%); In=2A
(– 35% for 1min)
Rated supply voltage fan V 3AC 400 (±10%) 50Hz 3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 3AC 460 (±10%) 60Hz
Control stability ∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog
setpoint 5)
1) The armature/field supply voltage can be lower than the rated armature/field voltage (setting in
parameter P078, input voltages down to 85V are permissible for converters with rated supply
voltage of 400V). The output voltage is reduced accordingly.
The specified output DC voltage can be guaranteed up to an undervoltage corresponding to
95% of line voltage (rated supply voltage armature/field).
3) Load factor K1 (direct current) as a function of coolant temperature (see P077 Section 11).
K1 > 1 permitted only if K1 * K2 ≤ 1.
Total derating factor K = K1 * K2 (K2 see below)
a) In spite of derating, converters of ≥400 A with forced air cooling may be operated at an
ambient or coolant temperature of 50°C only if the rated supply voltage of the converter fan
is safely within the limited tolerance range of 400V + 10% –15%.
b) Not permissible when T400 or OP1S is used.
Curve b1: Reduction factor of load values (DC current) at installation altitudes above 1000 m
5) Conditions
The control stability (closed-loop PI control) is referred to the rated motor speed and applies
when the SIMOREG converter is warm. The following conditions are applicable:
- Temperature changes of ±10 K
- Line voltage changes corresponding to +10% / – 5% of the rated input voltage
- Temperature coefficient of temperature-compensated tacho-generators 0.15‰ per 10 K
(applies only to analog tacho-generator)
- Constant setpoint (14-bit resolution)
10) Operation in the extended frequency range between 23 Hz and 110 Hz is available on request.
3.6 Certification
The products referred to in this document are manufactured and operated in accordance with
DIN ISO 9001 (Certificate Register No.: 257-0).
3.7 Abbreviations
ADB Adapter Board, carrier for miniature-format supplementary boards
CAN Field bus specification of user organization CiA (CAN in Automation)
(Controller Area Network)
CB Supplementary Communication Board
CBC Supplementary board for CAN Bus link
(Communication Board CAN Bus)
CBD Supplementary board for DeviceNet link
(Communication Board DeviceNet)
CBP2 Supplementary board for PROFIBUS link
(Communication Board PROFIBUS)
COB Communication Object for CAN Bus communication
CUD1 Electronics board C98043-A7001 of SIMOREG DC Master
(Control Unit / Direct Current)
CUD2 Terminal expansion board C98043-A7006 for CUD1
DeviceNet Field bus specification of ODVA (Open DeviceNet Vendor Association)
DP Distributed Peripherals
EB1 Supplementary board with additional inputs/outputs (Expansion Board 1)
EB2 Supplementary board with additional inputs/outputs (Expansion Board 2)
GSD file Device master data file defining the communication features of the PROFIBUS
communication board
ID Identifier for CAN Bus communication
IND Parameter Index
LBA Connection module for mounting supplementary modules
(Local Bus Adapter)
LWL Fiber-optic cable
MSAC_C1 Designation of a transmission channel for PROFIBUS
(Master Slave Acyclic / Class 1)
MSCY_C1 Designation of a transmission channel for PROFIBUS
(Master Slave Cyclic / Class 1)
OP1S Optional device operating panel with plaintext display and internal memory for
parameter sets (Operator Panel 1 / Store)
PKE Parameter identifier
PKW Reference to parameter (parameter identifier value)
PMU Simple operator panel of SIMOREG DC Master (Parameterization Unit)
PNU Parameter number
PPO Definition of number of parameter and process data words for PROFIBUS
communication (Parameter Process Data Object)
PROFIBUS Field bus specification of PROFIBUS user organization (Process Field Bus)
PWE Parameter value
4 Shipment, unpacking
SIMOREG converters are packed in the production works according to the relevant ordering data. A
product packing label is attached to the box.
Protect the package against severe jolts and shocks during shipment, e.g. when setting it down.
Carefully observe the information on the packaging relating to transportation, storage and proper
handling.
The SIMOREG device can be installed after it has been unpacked and the shipment checked for
completeness and/or damage.
The packaging materials consist of cardboard and corrugated paper and can be disposed of
according to locally applicable waste disposal regulations.
If you discover that the converter has been damaged during shipment, please inform your shipping
agent immediately.