04 Installation

5 Installation

CAUTION
Failure to lift the converter in the correct manner can result in bodily injury and/or property
damage.
The device must always be lifted by properly trained personnel using the appropriate equipment
(i.e. protective gloves, etc.).
To preclude the risk of deformation damage to the housings of converters with rated DC current
of 720A or higher, the lifting lugs used to raise them must not be subjected to any horizontal
forces.
The user is responsible for installing the converter, motor, transformer as well as other
equipment according to safety regulations (e.g. DIN, VDE), as well as all other relevant national
or local regulations regarding cable dimensioning and protection, grounding, isolating switch,
overcurrent protection, etc.

The converter must be installed in accordance with the relevant safety regulations (e.g. DIN,
VDE), as well as all other relevant national and local regulations. It must be ensured that the
grounding, cable dimensioning and appropriate short-circuit protection have been implemented
to guarantee operational safety and reliability.

Installation of SIMOREG devices in cabinets in accordance with UL 508 C standards


When the drive is provided in a panel (enclosure), the panel is ventilated and designated "Type 1".
The minimum size panel (enclosure) to be used with the drive is 600 mm length, 600 mm width,
2200 mm height.

Possible lifting method for converters with rated DC current of 1500A to 3000A

Siemens AG 6RX1700-0AD76 5-1


SIMOREG DC Master Operating Instructions
Installation 01.04

Cubicle mounting of converters with rated DC current of 1500A to 3000A

a s

• These converters are supplied with 2 fixing angles a. These can be bolted to the SIMOREG
unit by means of the supplied M6 hexagon-head screws (3 per angle) to assist cubicle mounting.
• The unit can then be supported by 2 further angles s (not included in scope of supply) in the
control cubicle.
• The converters must be bolted to the cubicle rear panel in 4 places.

WARNING
A clearance of at least 100 mm must be left above and below the converter in order to ensure
an unrestricted cooling air intake and outlet.
The converter may overheat if this clearance is not provided!

5-2 Siemens AG 6RX1700-0AD76


SIMOREG DC Master Operating Instructions
5.1
01.04

5.1.1

for M6
239
227 265
17.5
60 230

100 1)

Siemens AG 6RX1700-0AD76
XF1 XF2
s
V8

V7

SIMOREG DC Master Operating Instructions


366

385

350
V1+V4 V3+V6 V5+V2
Converters: 3AC 400V and 460V, 30A, 1Q

X300

T2 T3
Dimension diagrams for standard devices

12.5
10

63.5 15
10101010
70 112.5
Tightening torque for customer connections: 1U1 1V1 1W1
1U1, 1V1, 1W1, 1C1, 1D1 = 1,5 Nm 1D1 1C1
= 25 Nm

100 1)
1) Minimum clearance for air circulation
An adequate cooling air supply must be provided

5-3
Installation
5-4
5.1.2
Installation

for M6

283 265
17.5
271.5 230

100 1)
XF1 XF2

s
V8

V7

R100

V1+V4 V3+V6 V5+V2


366

385

350
X300
Converters: 3AC 400V and 575V, 60A to 280A, 1Q

T2 T3
12.5
10

108 15 48.5 37 48.5 37 48.5


Max. conductor size for cables with cable eye
129 1U1 1D1 1V1 1C1 1W1
in accordance with DIN 46234: 2 x 95 mm2
for M8
Tightening torque for customer connections:

100 1)
1U1, 1V1, 1W1, 1C1, 1D1 = 13 Nm Fan in devices ≥ 210A only
= 25 Nm

1) Minimum clearance for air circulation


An adequate cooling air supply must be provided

SIMOREG DC Master Operating Instructions


01.04

Siemens AG 6RX1700-0AD76
268
19 230
01.04

5.1.3

318 179.7
306.5 123.7 for M8

100 1)
XF1 XF2

s V8
V7

Siemens AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
V1+V4 V3+V6 V5+V2
R100

X300

625
602

585
T2 T3
Converters: 3AC 400V and 575V, 400A, 1Q

for M10

1U1 1D1 1V1 1C1 1W1


133

4U1
4V1
4W1
10

10

for M10 39 47.5 47.5 47.5 47.5


35 120 Max. conductor size for cables with cable eye in accordance with DIN 46234:
1) Minimum clearance for air circulation 160 1U1, 1V1, 1W1 = 2 x 150 mm2
An adequate cooling air supply must be provided

100 1)
1C1, 1D1 = 2 x 185 mm2
Tightening torque for customer connections:
1U1, 1V1, 1W1, 1C1, 1D1 = 25 Nm
= 50 Nm

5-5
Installation
268

5-6
19 230
318 179.7 5.1.4
306.5 123.7 for M8

100 1)
Installation

XF1 XF2

s V8
V7

V1+V4 V3+V6 V5+V2


R100

X300

625
602

585
T2 T3
Converters: 3AC 400V and 575V, 600A, 1Q

for M10

1U1 1D1 1V1 1C1 1W1


133

4U1
4V1
4W1

10
10

for M10 39 47.5 47.5 47.5 47.5


35 120 Max. conductor size for cables with cable eye in accordance with DIN 46234:
1) Minimum clearance for air circulation 160 1U1, 1V1, 1W1 = 2 x 150 mm2
An adequate cooling air supply must be provided

100 1)
1C1, 1D1 = 2 x 185 mm2
Tightening torque for customer connections:
1U1, 1V1, 1W1, 1C1, 1D1 = 25 Nm
= 50 Nm

SIMOREG DC Master Operating Instructions


01.04

Siemens AG 6RX1700-0AD76
268 350
01.04

5.1.5

19 230 for M8 150


Lifting lug Ø20

100 1)

Siemens AG 6RX1700-0AD76
XF1 XF2

V8
V7

SIMOREG DC Master Operating Instructions


T2
T3

V1+V4

700
677
V3+V6
660

V5+V2

510
X300

for M12
1U1 1V1 1W1
Converters: 3AC 400V, 575V, and 690V, 720A to 850A, 1Q

85
1D1 1C1

55
10
10
12

33 30 139 for M10 Max. conductor size for cables with cable eye
76 30 192 in accordance with DIN 46234: 4 x 150 mm2
119 30 275 40
100 1)

162 30 Tightening torque for customer connections:


205 30 1U1, 1V1, 1W1, 1C1, 1D1 = 44 Nm
= 50 Nm

1) Minimum clearance for air circulation


An adequate cooling air supply must be provided

5-7
Installation
5-8
for M10 5.1.6
410 310
45 320 194 Lifting lug Ø20
Installation

150

100 1)
XF1
XF2

s
4U1
V7 4V1
V8 4W1

R100

780
765
740
F4 F6 F2

717
R100
V1 V3 V5
+ V4 + +
V4 V6 V2 X300

F1 F3 F5

T2 T3

1U1 1D1 1V1 1C1 1W1

140

20
15
10
56 30 for M12
155 30 30 30 30 Max. conductor size for cables with cable eye
122 30 220
in accordance with DIN 46234: 4 x 150 mm2
100 1)

188 30 350
254 30 362
Tightening torque for customer connections:
320 30
for M12 1U1, 1V1, 1W1, 1C1, 1D1 = 44 Nm
394
= 60 Nm
406
Converters: 3AC 400V, 460V, 575V, 690V, and 830V, 900A to 1200A, 1Q

1) Minimum clearance for circulation


An adequate cooling air supply must be provided

SIMOREG DC Master Operating Instructions


01.04

Siemens AG 6RX1700-0AD76
Front view without doors View of rear thyristor level
01.04

5.1.7

500
450
304
45 360 for M10
260

160 1)
1Q

Lifting lug Ø22


XF1
XF2
4U1
4V1
4W1

Siemens AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
F111 F131 F151 F141 F161 F121
F112 F132 F152 F142 F162 F122

T2 T3 T2 T3

880

855

840
V11 V13 V15 V21 V23 V25

for M12
1U1 1V1 1W1
1C1 1D1
35

30
30

10

171 40 63 40 for M12


2) 40 47
63,5 for M12 205 40
313 40
Customer terminals Cable duct
158 347 40

150 1)
235 1) Minimum clearance for air circulation Max. conductor size for cables with cable eye in accordance with DIN 46234:
433 An adequate cooling air supply must be provided 1U1, 1V1, 1W1 = 4 x 240 mm2
1C1, 1D1 = 8 x 240 mm2
2) Remove transport cover by undoing 6 M6
hexagon head screws before start-up Tightening torque for customer connections:
1U1, 1V1, 1W1, 1C1, 1D1 = 44 Nm
Converters: 3AC 400V, 575V, 690V, and 830V, 1500A to 2000A, 575V/2200A

= 60 Nm

5-9
Installation
5-10
Front view without doors View of rear thyristor level 5.1.8
500
450
260
Installation

45 360 for M10

160 1)
125
XF1,XF2
Lifting lug Ø22

4U1
4V1
4W1
3AC 950V / 2200A 1Q

F111 F131 F151 F141 F161 F121


F112 F132 F152 F142 F162 F122

880
855

840
T2
T3
V11 V13 V15 V21 V23 V25

for M12
1C1 1D1 1U1 1V1 1W1
(1D1) (1C1)
3)

30
30

10

171 40 47 40 40 47
2) 10
for M12 48 35 35 for M12
58,5 313 40
Cable duct 190 35 35
Customer terminals 155

150 1)
1) Minimum clearance for air circulation, customer 332 35 35
240
Converters: 3AC 400V / 3000A, 3AC 575V / 2800A, 3AC 690V / 2600A,

connection and replacaement of fan. An adequate


433
418 cooling air supply must be provided Customer terminals Tightening torque for customer connections:
1U1, 1V1, 1W1: copper bus 2x100x10 for M12x50 1U1, 1V1, 1W1, 1C1, 1D1 = 44 Nm
2) Remove transport cover by undoing 6 M6
1C1, 1D1: copper bus 2x80x10 for M12x50 = 60 Nm
hexagon head screws before start-up
: copper bus 120x10 for M12x40
3) Insulation of mains terminals U1, V1, W1

SIMOREG DC Master Operating Instructions


01.04

Siemens AG 6RX1700-0AD76
01.04

5.1.9

for M6
239
227 265
17.5
60 230

100 1)

Siemens AG 6RX1700-0AD76
XF1 XF2

s
V8

V7

SIMOREG DC Master Operating Instructions


366

385
V1 V3 V5

350
V4 V6 V2

X300
Converters: 3AC 400V and 460V, 15A to 30A, 4Q

T2 T3
12.5
10

63.5 15
10101010
70 112.5
Tightening torque for customer connections:
1U1 1V1 1W1
1U1, 1V1, 1W1, 1C1, 1D1 = 1,5 Nm
= 25 Nm 1D1 1C1

100 1)
(1C1) (1D1)

1) Minimum clearance for air circulation


An adequate cooling air supply must be provided

5-11
Installation
5-12
Installation

for M6

283 265
17.5
271.5 230

100 1)
XF1 XF2

s
V8

V7

V1 V3 V5
366

385

350
R100

V4 V6 V2
X300
5.1.10 Converters: 3AC 400V and 575V, 60A to 280A, 4Q

T2 T3
12.5
10

108 15 48.5 37 48.5 37 48.5


Max. conductor size for cables with cable eye
129 1U1 1D1 1V1 1C1 1W1
in accordance with DIN 46234: 2 x 95 mm2
(1C1) (1D1)
for M8
Tightening torque for customer connections:

100 1)
1U1, 1V1, 1W1, 1C1, 1D1 = 13 Nm Fan in devices ≥ 210A only
= 25 Nm

1) Minimum clearance for air circulation


An adequate cooling air supply must be provided

SIMOREG DC Master Operating Instructions


01.04

Siemens AG 6RX1700-0AD76
268
19 230
01.04

318 179.7
306.5 123.7 for M8

100 1)
XF1 XF2

s V8
V7

Siemens AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
V1 V3 V5

V4 V6 V2
R100
X300

625
602

585
T2 T3

for M10
5.1.11 Converters: 3AC 400V and 575V, 400A to 600A, 4Q

1U1 1D1 1V1 1C1 1W1


(1C1) (1D1)
133

4U1
4V1
10 4W1
10

for M10 39 47.5 47.5 47.5 47.5


35 120 Max. conductor size for cables with cable eye in accordance with DIN 46234:
1) Minimum clearance for air circulation 160
An adequate cooling air supply must be provided 1U1, 1V1, 1W1 = 2 x 150 mm2

100 1)
1C1, 1D1 = 2 x 185 mm2
Tightening torque for customer connections:
1U1, 1V1, 1W1, 1C1, 1D1 = 25 Nm
= 50 Nm

5-13
Installation
268 350

5-14
19 230 for M8 150
Lifting lug Ø20

100 1)
Installation

XF1 XF2
V1
V3
V5 V8
V7

T2
T3

V4

700
677
V6
V2 660

510
X300

for M12
1U1 1V1 1W1
5.1.12 Converters: 3AC 400V, 575V, and 690V, 760A to 850A, 4Q

85
85
1D1 1C1

55
(1C1) (1D1)

10
12

33 30 139 for M10 Max. conductor size for cables with cable eye
76 30 192
119 30 275 40 in accordance with DIN 46234: 4 x 150 mm2
100 1)

162 30
Tightening torque for customer connections:
205 30
1U1, 1V1, 1W1, 1C1, 1D1 = 44 Nm
= 50 Nm

1) Minimum clearance for air circulation


An adequate cooling air supply must be provided

SIMOREG DC Master Operating Instructions


01.04

Siemens AG 6RX1700-0AD76
01.04

for M10
410 310
45 320 194 Lifting lug Ø20
150

100 1)
XF1
XF2

s
4U1
4V1
V7 4W1
V8

Siemens AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
V1 V3 V5

F1 F3 F5
R100

780
767
740
R100 717

X300

F4 F6 F2

V4 V6 V2

T2 T3
1D1 1C1
(1C1) (1D1) 1U1

1U1 1V1 1W1 140

20
15
10
66 for M12
155 30 30 30 30 max. conductor size for cables with cable eye
122 30 350 in accordance with DIN 46234: 4 x 150 mm2
100 1)

198 362
254 30
Tightening torque for customer connections:
330
for M12 1U1, 1V1, 1W1, 1C1, 1D1 = 44 Nm
394
= 60 Nm
406
5.1.13 Converters: 3AC 400V, 460V, 575V, 690V, and 830V, 950A to 1200A, 4Q

1) Minimum clearance for air circulation


An adequate cooling air supply must be provided

5-15
Installation
5-16
Front view without doors View of rear thyristor level
500
450
Installation

304
45 360 for M10
4Q
260

160 1)
Lifting lug Ø22
XF1
XF2
4U1
4V1
4W1

F111 F131 F151 F141 F161 F121


F112 F132 F152 F142 F162 F122

T2 T3 T2 T3

880
855

840
V24 V26 V22 V14 V16 V12

V11 V13 V15 V21 V23 V25

1C1 1D1 1U1 1V1 1W1


(1D1) (1C1)
35

30
30

10

171 40 63 40 for M12


2) 40 47
63.5 for M12 205 40 for M12
313 40
Customer terminals Cable duct 347 40
158

150 1)
235 1) Minimum clearance for air circulation Max. conductor size for cables with cable eye in accordance with DIN 46234:
433 An adequate cooling air supply must be provided 1U1, 1V1, 1W1 = 4 x 240 mm2
1C1, 1D1 = 8 x 240 mm2
2) Transportblech durch lösen von 6 Sechskantschrauben M6
vor Inbetriebnahme entfernen! Tightening torque for customer connections:
1U1, 1V1, 1W1, 1C1, 1D1 = 44 Nm
5.1.14 Converters: 3AC 400V, 575V, 690V, and 830V, 1500A to 2000A, 575V/2200A

= 60 Nm

SIMOREG DC Master Operating Instructions


01.04

Siemens AG 6RX1700-0AD76
01.04

Front view without doors View of rear thyristor level


500
450
260
45 360 for M10

160 1)
125
XF1,XF2
Lifting lug Ø22

4U1
4V1
4W1

Siemens AG 6RX1700-0AD76
3AC 950V / 2200A 4Q

SIMOREG DC Master Operating Instructions


F111 F131 F151 F141 F161 F121
F112 F132 F152 F142 F162 F122

880
855

840
V24 V26 V22 V14 V16 V12

T2
T3
V11 V13 V15 V21 V23 V25
880

for M12
1C1 1D1 1U1 1V1 1W1
(1D1) (1C1)
3)

30
30

10

171 40 47 40 40 47
2) 10
for M12 Cable duct 48 35 35 for M12
58,5 313 40
Customer terminals 190 35 35
155

150 1)
1) Minimum clearance for air circulation, customer 332 35 35
240
5.1.15 Converters: 3AC 400V / 3000A, 3AC 575V / 2800A, 3AC 690V / 2600A,

connection and replacaement of fan. An adequate


433
418 cooling air supply must be provided Customer terminals Tightening torque for customer connections:
1U1, 1V1, 1W1: copper bus 2x100x10 for M12x50 1U1, 1V1, 1W1, 1C1, 1D1 = 44 Nm
2) Remove transport cover by undoing 6 M6
1C1, 1D1: copper bus 2x80x10 for M12x50 = 60 Nm
hexagon head screws before start-up
: copper bus 120x10 for M12x40
3) Insulation of mains terminals U1, V1, W1

5-17
Installation
5.2

5-18
5.2.1
Installation

265
17,5
313 for M6 230
301,5 1U1 1D1 1V1 1C1 1W1
90
63,5 37 48 37 48

100 1)
10
XF1 XF2

385
366

350
Converters: 3AC 460V, 60A to 125A, 1Q
connections on the top of the device

X300
12,5
10

Max. conductor size for cables with cable eye


in accordance with DIN 46234: 2 x 95 mm2 138 15 48,5 37 48 37 48 for M8
159 1U1 1D1 1V1 1C1 1W1
Tightening torque for customer connections:

100
1)
1U1, 1V1, 1W1, 1C1, 1D1 = 13 Nm
= 25 Nm
Dimension diagrams of the devices with additional cable

1) Minimum clearance for air circulation


An adequate cooling air supply must be provided

SIMOREG DC Master Operating Instructions


01.04

Siemens AG 6RX1700-0AD76
01.04

5.2.2

265
17,5
313 for M6 230
301,5 1U1 1D1 1V1 1C1 1W1
90
63,5 37 48 37 48

100 1)
17.5
10

Siemens AG 6RX1700-0AD76
XF1 XF2

SIMOREG DC Master Operating Instructions


385
366

350
Converters: 3AC 460V, 210A to 280A, 1Q

X300
12,5
12.5
10

Max. conductor size for cables with cable eye


in accordance with DIN 46234: 2 x 95 mm2 138 15 48,5 37 48 37 48 for M8
159 1U1 1D1 1V1 1C1 1W1

100
Tightening torque for customer connections:

1)
1U1, 1V1, 1W1, 1C1, 1D1 = 13 Nm
= 25 Nm

1) Minimum clearance for air circulation


An adequate cooling air supply must be provided

5-19
Installation
268
19 230
318

5-20
306,5 1U1 1D1 1V1 1C1 1W1 5.2.3
155
139 39 47,5 47,5 47,5 47,5
for M8
Installation

100 1)
21
s XF1 XF2

X300

625
602

604

585
Converters: 3AC 460V, 450A to 600A, 1Q

1U1 1D1 1V1 1C1 1W1


for M10
133
10

10
for M10 39 47,5 47,5 47,5 47,5
35 125 Max. conductor size for cables with cable eye in accordance with DIN 46234:
1) Minimum clearance for air circulation 164 1U1, 1V1, 1W1 = 2 x 150 mm2

100 1)
An adequate cooling air supply must be provided 1C1, 1D1 = 2 x 185 mm2
Tightening torque for customer connections:
1U1, 1V1, 1W1, 1C1, 1D1 = 25 Nm
= 50 Nm

SIMOREG DC Master Operating Instructions


01.04

Siemens AG 6RX1700-0AD76
205 30
355 162 30
01.04

5.2.4

192 119 30
Lifting lug Ø20 147 76 30
130 for M8 33 30

100 1)
30
1D1 1C1
1U1 1V1 1W1

Siemens AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
700
677

660
651
Converters: 3AC 460V, 850A, 1Q

X300
1U1 1V1 1W1
for M12
30

1D1 1C1
111

A
12

360 19 230 10
Max. conductor size for cables with cable eye 268
in accordance with DIN 46234: 4 x 150 mm2

100 1)
View A
Tightening torque for customer connections:
1U1, 1V1, 1W1, 1C1, 1D1 = 44 Nm
= 50 Nm

1) Minimum clearance for air circulation


An adequate cooling air supply must be provided
12

275 40
for M10

5-21
Installation
5-22
5.2.5
Installation

265
17,5
313 for M6 230
301,5 1U1 1D1 1V1 1C1 1W1
(1C1) (1D1)
90
63,5 37 48 37 48

100 1)
10

XF1 XF2

385
366

350
Converters: 3AC 460V, 60A to 125A, 4Q

X300
12,5
10

Max. conductor size for cables with cable eye


138 15 48,5 37 48 37 48 for M8
in accordance with DIN 46234: 2 x 95 mm2
159 1U1 1D1 1V1 1C1 1W1
(1C1) (1D1)

100
Tightening torque for customer connections:

1)
1U1, 1V1, 1W1, 1C1, 1D1 = 13 Nm
= 25 Nm

1) Minimum clearance for air circulation


An adequate cooling air supply must be provided

SIMOREG DC Master Operating Instructions


01.04

Siemens AG 6RX1700-0AD76
01.04

5.2.6

265
17,5
313 for M6 230
301,5 1U1 1D1 1V1 1C1 1W1
(1C1) (1D1)
90
63,5 37 48 37 48

100 1)
17.5
10

Siemens AG 6RX1700-0AD76
XF1 XF2

SIMOREG DC Master Operating Instructions


385
366

350
Converters: 3AC 460V, 210A to 280A, 4Q

X300
12,5
12.5
10

Max. conductor size for cables with cable eye


in accordance with DIN 46234: 2 x 95 mm2 138 15 48,5 37 48 37 48 for M8
159 1U1 1D1 1V1 1C1 1W1
Tightening torque for customer connections: (1C1) (1D1)

100
1)
1U1, 1V1, 1W1, 1C1, 1D1 = 13 Nm
= 25 Nm

1) Minimum clearance for air circulation


An adequate cooling air supply must be provided

5-23
Installation
268
19 230
318

5-24
306,5 1U1 1D1 1V1 1C1 1W1 5.2.7
(1C1) (1D1)
155
139 39 47,5 47,5 47,5 47,5
for M8
Installation

100 1)
21
s XF1 XF2

X300

625
602

604

585
Converters: 3AC 460V, 450A to 600A, 4Q

1U1 1D1 1V1 1C1 1W1


(1C1) (1D1) for M10
133
10

10
for M10 39 47,5 47,5 47,5 47,5
35 125 Max. conductor size for cables with cable eye in accordance with DIN 46234:
1) Minimum clearance for air circulation
164 1U1, 1V1, 1W1 = 2 x 150 mm2
An adequate cooling air supply must be provided

100 1)
1C1, 1D1 = 2 x 185 mm2
Tightening torque for customer connections:
1U1, 1V1, 1W1, 1C1, 1D1 = 25 Nm
= 50 Nm

SIMOREG DC Master Operating Instructions


01.04

Siemens AG 6RX1700-0AD76
205 30
162 30
01.04

355
5.2.8

192 119 30
Lifting lug Ø20 147 76 30
for M8
130 33 30

100 1)
30
1D1 1C1
(1C1) (1D1)
1U1 1V1 1W1

Siemens AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
700
677

660
651
Converters: 3AC 460V, 850A, 4Q

X300
1U1 1V1 1W1
for M12
30

1D1 1C1
(1C1) (1D1)
111

A
12

360
19 230 10
Max. conductor size for cables with cable eye
in accordance with DIN 46234: 4 x 150 mm2 268

100 1)
View A
Tightening torque for customer connections:
1U1, 1V1, 1W1, 1C1, 1D1 = 44 Nm
= 50 Nm

1) Minimum clearance for air circulation


An adequate cooling air supply must be provided
12

275 40
for M10

5-25
Installation
Installation 01.04

5.3 Mounting options

5.3.1 Terminal expansion board CUD2

CUD2 4

1
CUD1
3

• Remove electronics board CUD1 from the electronics box by undoing the two fixing screws a.
• Attach the 3 hexagon-head bolts supplied at position s on the CUD1 electronics board with the
screws and fixing elements d supplied and insert the two plug connectors f.
The two plug connectors must be positioned such that the short pin ends are inserted in the
socket connectors of the CUD1 and the long pin ends in the socket connectors of the CUD2.
• Position board CUD2 in such a way that the two plug connectors f are properly contacted.
• Secure board CUD2 in position using the supplied screws and retaining elements g.
• Insert electronics board CUD1 into electronics box and tighten up the two fixing screws a again
as instructed.

5-26 Siemens AG 6RX1700-0AD76


SIMOREG DC Master Operating Instructions
01.04 Installation

5.3.2 Optional supplementary boards

WARNING
Safe operation is dependent upon proper installation and start-up by qualified personnel under
observance of all warnings contained in these operating instructions.
Boards must always be replaced by properly qualified personnel.
Boards must not be inserted or removed when the power supply is connected.
Failure to observe this warning can result in death, severe physical injury or substantial property
damage.

CAUTION
The boards contain ElectroStatic Discharge Sensitive Devices (ESDS). Before touching a
board, make sure that your own body has been electrostatically discharged. The easiest way to
do this is to touch a conductive, earthed object (e.g. bare metal part of cubicle) immediately
beforehand.

5.3.2.1 Local bus adapter (LBA) for mounting optional supplementary boards
Optional supplementary boards can be installed only in conjunction with the LBA option. If an LBA is
not already fitted in the SIMOREG converter, one must be installed in the electronics box to
accommodate the optional board.

How to install an LBA local bus adapter in the electronics box:

♦ Undo the two fixing screws on the CUD1


board and pull board out by special handles.
♦ Push LBA bus extension into electronics
box (see picture on right for position) until it
engages.
♦ Insert CUD1 board in left-hand board
location again and tighten fixing screws in
handles.

Location 2 (Options)
Location 3 (Options)
Location 1 (CUD1)

5.3.2.2 Mounting of optional supplementary boards


Supplementary boards are inserted in the slots 1 3 2
of the electronics box. Option LBA (local bus Arrangement of
adapter) is required to fit supplementary boards. board locations 1 to 3
The designations of the board locations or slots F D and slots D to G in
are shown in the adjacent diagram. electronics box
CUDx

G E

Siemens AG 6RX1700-0AD76 5-27


SIMOREG DC Master Operating Instructions
Installation 01.04

Supplementary boards may be inserted in any slot subject to the following restrictions:

NOTICE
♦ Slot 3 must not be used until slot 2 is already occupied.
♦ A technology board must always be installed in board location 2 of the electronics box.
♦ If a technology board is used in conjunction with one communication board, then the
communication board must be fitted in slot G (miniature-format boards, for example CBP2
and CBC) or slot 3 (large-format board SCB1).
A type T400 technology module can also be used with two communication boards of type
CBC, CBD or CBP2 (see Section 7.7.1, Procedure for starting up technology boards).
♦ It is not possible to operate boards EB1, EB2, SLB and SBP in conjunction with a technology
board.
♦ The data of large-format boards are always output under slot E or slot G, i.e. the software
version of a technology board, for example, is displayed in r060.003.
♦ In addition to the LBA, miniature-format boards (for example CBP2 and CBC) also require an
ADB (adapter board, support board). Due to their very compact physical dimensions, these
boards must be inserted in an ADB before they can be installed in the electronics box.
♦ A total of two supplementary boards of the same type can be used (e.g. 2 EB1s), but only 1
SBP and 1 SLB may be installed.

The diagram below shows which locations or slots can be used for the supplementary boards you
wish to install and which board combinations are possible:

no
Use TB?
TB = T100, T300 or T400
yes
no
Use SCB1?

no
TB on its own? yes

yes
no
SCB1 on its own?

yes
Only one of the following One of the miniature-format A maximum total of 4 boards
boards can be used in boards CBC, CBD, CBP2, can be installed, these may
addition to the TB: EB1, EB2, SLB or SBP can include no more than two of
CBC, CBD, CBP2, be installed in addition to SCB1. the miniature-format boards
SCB1 CBC, CBD, CBP2, EB1 and
TB in location 2 and SCB1 can be installed in EB2 or one of the miniature-
CBC, CBD, CBP2 in slot G either location 2 or lacation 3. format boards SLB or SBP.
with ADB in location 3 or The ADB required for the other A maximum of two miniature-
SCB1 in location 3. board(s) is then inserted in the format boards may be inserted
Exception: T400 with two other location in each case. in the ADB.
communication modules Location 3 may not be used
(see Section 7.7.1, unless a board has already
Procedure for starting up been inserted in lacation 2.
technology boards)
TB in slot 2 SCB1 in lacation 2

Required: LBA Required: LBA and ADB Required: LBA Required: LBA and ADB Required: LBA and ADBs
(for CBx only) (for miniature-format boards (depending on number of
only) miniature-format boards)

For information about starting up supplementary boards, please refer to Section 7.7 "Starting up
optional supplementary boards".

5-28 Siemens AG 6RX1700-0AD76